Electrical Code
Electrical Code
1. As may be defined and provided in the rules and regulations, owners, administrators or
occupants of buildings, structures and their premises or facilities and other responsible persons
shall be required to comply a fire safety inspection shall be conducted by the Chief, BFP or his
duly authorized representative as prerequisite to the grants of permits and/or licenses by local
governments and other government agencies concerned.
2. The following are declared as prohibited act and omission: m. Use of jumpers or tampering
with electrical wiring or overloading the electrical system beyond its designated capacity or such
other practices that would tend to undermine the fire safety features of the electrical system.
3.Service drop shall have sufficient ampacity to carry the load without a temperature rise
detrimental to the covering or insulation of the conductors and shall have adequate mechanical
strength. The conductors shall not be smaller than 8 mm2copper, 14 mm2 aluminum or copper-
clad aluminum.
4. In dry locations, where not exposed to physical damage, conductors shall be permitted to be
separately enclosed in flexible nonmetallic tubing. The tubing shall be in continuous lengths
not exceeding 4 500 mm and secured to the surface by straps at intervals not exceeding 1 400
mm.
5. Conductors entering or leaving locations subject to dampness, wetness, or corrosive vapors
shall have drip loops formed on them and shall then pass upward and inward from the outside of
the buildings, or from the damp, wet, or corrosive location, through noncombustible,
nonabsorbent insulating tubes.
6. Raceways are channels designed for holding wires, cables or bus-bars, which are either made
of metal or insulating materials. The common types of raceways in household wiring are the a)
conduits, b) connectors, and c) others.
7. A ground is an electrical connection which may either be intentional or accidental between an
electric circuit or equipment and the earth, or to some conducting body that serves in place of the
earth. The purpose of grounding a circuit is to fix permanently a zero voltage point in the system.
The grounded line of a circuit should not be broken nor fused to maintain a solid and
uninterrupted connection to the ground.
8. Wiring method shall be insulated conductors installed in conduit, except where specifically
indicated or specified otherwise, or required by the PEC to be installed otherwise. An insulated
equipment grounding conductor shall be provided in all feeder and branch circuits, including
lighting circuits. Provide insulated, green-colored conductor for grounding conductors installed
in conduit or raceways.
9. Provide boxes in the wiring or raceway systems wherever required for pulling of wires,
making connections, and mounting of devices of fixtures. Boxes for metallic raceways shall be
of the cast-metal hub type when located in normally wet locations, when surface mounted on
outside of exterior surfaces, when installed exposed up to 2.10 m above interior floors and
walkways.
10. Mount panelboards, circuit breakers, and disconnecting switches so that the height of the
operating handle at its highest position will not exceed 1.8 m from the floor. Mounting lighting
switches, receptacles and other devices as indicated. Measure mounting heights of wiring devices
and outlets to the center of device or outlet.
PLUMBING CODE
1. All premises intended for human use or habitation shall be provided with a supply of pure and
wholesome water, neither connected to unsafe water supply nor subject to backflow or back-
siphonage.
2. Plumbing fixtures, devices and appurtenances shall be supplied with water in sufficient
volume and pressure adequate to function satisfactorily and without undue
noise.
3. Each family dwelling unit shall have at least one water closet, one kitchen type sink, a lavatory
and a bathtub or shower to meet the basic requirements of sanitation and personal hygiene.
4. The drainage system shall be designed, constructed and maintained to safeguard against
fouling, deposit of solids, clogging and with adequate cleanouts so arranged that the pipes may
be readily cleaned.
5. Substance which will clog the pipes, produce explosive mixtures, destroy the pipes or their
joints or interfere unduly with the sewage-disposal process shall not be allowed to enter the
building drainage system.
6. Proper protection shall be provided to prevent contamination of food, water, sterile goods and
similar materials by backflow of sewage. When necessary, the fixture, device or appliance shall
be connected indirectly with the building drainage system.
7. If there is no sewer system in the area, suitable provision shall be made for the disposal of
building sewage by some accepted method of sewage treatment and disposal, such as a septic
tank.
8. Where a plumbing drainage system may be subject to backflow of sewage, suitable provision
shall be made to prevent its overflow in the building.
9. Plumbing shall be installed with due regard to the preservation of the strength of structural
members and the prevention of damage to walls and other surfaces through fixture usage.
10. Sewage or other waste from plumbing systems, which may be deleterious to surface or sub-
surface waters shall not be discharged into the ground or into any waterway, unless first rendered
innocuous through subjection to some acceptable form of treatment.