FES-Electrical Safety Module-2
FES-Electrical Safety Module-2
FES-Electrical Safety Module-2
Module 2
Modul 2
2 INTRODUCTION......................................................................................................................... 7
3 RESCUES................................................................................................................................... 8
5 ACKNOWLEDGEMENTS......................................................................................................... 73
Competencies
Kompetensi
Description
Deskripsi
The purpose of this manual is to provide Fire Fighters with the necessary knowledge and skill as
well as guidance on the electrical hazards that may be encountered in emergency situations as
well as their day-to-day duties.
Tujuan dari buku manual ini adalah untuk memberikan Petugas pemadam kebakaran pengetahuan
dan keahlian serta panduan yang dibutuhkan mengenai bahaya listrik yang mungkin dihadapi
dalam keadaan darurat dan dalam tugas sehari-hari mereka.
darurat
• Potential electrical hazards in workplace are recognised (e.g. risk
of electric shock and fault currents) and the hazard is eliminated.
Mengenali potensi bahaya listrik di tempat kerja (misalnya
bahaya sengatan listrik dan arus yang salah) dan menghilangkan
bahaya tersebut.
• The ability to use fire extinguishers to put out range of fires which
can occur in workplace is demonstrated.
Mendemonstrasikan kemampuan untuk menggunakan alat
pemadam kebakaran untuk memadamkan api yang dapat muncul
di tempat kerja.
2 INTRODUCTION / PENDAHULUAN
Apabila seseorang menyentuh dua kabel bertegangan atau menyentuh satu kabel
bertegangan dan tanah di saat yang sama, dia akan menjadi bagian dari aliran arus listrik,
dan dapat terbunuh atau cedera. Dalam konteks ini, yang dimaksud dengan “tanah”
termasuk semua struktur yang dapat menyalurkan listrik (sengaja atau tidak sengaja), dan
struktur itu sendiri berhubungan dengan tanah atau bahan penyalur listrik sebagai
pengganti tanah.
3 RESCUES / PENYELAMATAN
3.1 Removing Persons from Electrical Contact / Memindahkan Orang dari Kontak Listrik
terjadi apabila orang yang di dalam kendaraan mencoba keluar dan menyentuh tanah dan
bagian kendaraan pada saat yang bersamaan.
Provided that there is no hazard to the vehicle e.g., fire, leaking hazardous load, etc., they
should stay in the vehicle until a Utilities Department official confirms the line to be safe.
(See Figure 4.4)
Jika tidak ada bahaya terhadap kendaraan itu, misalnya kebakaran, muatan berbahaya
yang bocor, dll, mereka harus tetap berada di kendaraan sampai petugas Utilities
Department menyatakan kabel tersebut telah aman. (Lihat Gambar 4.4)
If it is necessary for the driver or passenger(s) to leave a vehicle they should jump well
clear of the vehicle ensuring that they do NOT touch the vehicle and ground at the same
time and land with both feet together. (See Figure 4.5)
Apabila pengendara atau penumpang harus meninggalkan kendaraan, mereka harus
melompat jauh dari kendaraan untuk memastikan TIDAK menyentuh kendaraan dan tanah
pada saat bersamaan, lalu mendarat dengan kedua kaki disatukan. (Lihat Gambar 4.5)
They should then either jump away with both feet together or hop away with only one foot in
contact with the ground at the same time. This is to avoid the danger of receiving a shock
through the feet in the area where a voltage gradient in the ground is present because of
direct, or indirect, contact between an overhead line and the ground.
Mereka kemudian harus melompat dengan kedua kaki disatukan atau melompat hanya
dengan satu kaki yang berhubungan dengan tanah pada saat yang bersamaan. Hal ini
untuk menghindari bahaya terkena sengatan melalui kaki di area yang memiliki perbedaan
tegangan di tanah, akibat adanya hubungan langsung atau tidak langsung antara kabel
tinggi dengan tanah.
Power lines found lying on the ground, even those apparently for low voltage, should NOT
be approached until it has either been confirmed by an 'Authorised Person' that it safe to do
so, or unless rescue from a line which has been positively identified as LOW VOLTAGE is
involved.
Kabel listrik yang terletak di tanah, bahkan yang untuk tegangan rendah, JANGAN didekati
sampai telah ditegaskan oleh ‘Pihak Berwenang’ bahwa aman untuk melakukannya, atau
kecuali termasuk penyelamatan dari kabel yang telah secara pasti diketahui sebagai
TEGANGAN RENDAH.
Low voltage lines can be identified as:
Kabel bertegangan rendah dapat diketahui sebagai:
(i) lines going into domestic premises.
kabel yang digunakan untuk area rumah tangga.
(ii) generally, low voltage lines are on wooden poles and uninsulated.
Umumnya, kabel bertegangan rendah terdapat pada tiang kayu dan tidak
terinsulasi.
However, it MUST be remembered that many wooden poles carry High Voltage
lines. All poles carrying High Voltage lines SHOULD carry an appropriate warning
sign (see Figure 4.6).
Namun, HARUS diingat bahwa banyak tiang kayu membawa kabel Bertegangan
Tinggi. Semua tiang yang membawa kabel Bertegangan Tinggi HARUS mempunyai
tanda peringatan yang sesuai (lihat Gambar 4.6).
DO NOT take the lack of a warning sign on a single pole as sufficient evidence that
it is a low voltage line. Other nearby wooden poles should also be checked for
warning signs.
JANGAN menganggap tiadanya tanda peringatan pada satu tiang sebagai bukti
bahwa ini kabel bertegangan rendah. Tiang kayu terdekat lainnya juga harus
diperiksa tanda peringatannya.
(iii) conductors are in vertical formation. (usually between 2-6 conductors).
konduktor berada dalam formasi vertikal. (biasanya antara 2-6 konduktor).
If the overhead line has been identified as low voltage, rescue of a person who it is
reasonably thought to be alive can be undertaken provided that the procedures set
out in 4.5(a) above are complied with. Overhead low voltage lines SHOULD NOT be
moved as it can cause arcing, which may bum a person if the conductor is touching
them or ignite any petrol vapours in the area.
Apabila kabel tinggi telah diketahui sebagai tegangan rendah, penyelamatan
seseorang yang diduga masih hidup dapat dilakukan dengan mengikuti prosedur
yang tertera dalam 4.5(a) di atas. Kabel tinggi bertegangan rendah TIDAK BOLEH
digerakkan karena dapat menyebabkan bunga api, yang dapat membakar
seseorang apabila konduktornya disentuh atau membakar uap bensin di area
tersebut.
3.4 How to deal with fallen wires / Cara menangani dengan kabel yang jatuh
Electrical distribution wires may be broken by storms, or as the result of vehicles striking
power poles.
Kabel listrik mungkin rusak karena badai, atau akibat kendaraan menabrak tiang listrik.
If, during your work, you
come across abnormal
situations such as sagging,
broken, or fallen wires, do
not expose yourself to
needless risks while trying to
eliminate the danger. Always
assume that the wires are
energized and capable of
killing people. You should
telephone the electricity
Utilities Department
immediately. Qualified
personnel will be sent to
remedy the situation.
Apabila selama pekerjaan
Anda menemui keadaan
yang abnormal seperti kabel
yang jatuh, rusak, atau menggantung, jangan mengambil risiko yang tidak ada gunanya
saat berusaha menghilangkan bahaya tersebut. Selalu anggap bahwa kabel tersebut
bermuatan, dan mampu membunuh orang. Anda harus segera menghubungi Utilities
Department bagian listrik. Personil yang memenuhi syarat akan dikirim untuk memperbaiki
keadaan.
3.4.1 Action to be taken on arriving at the scene / Tindakan yang dilakukan saat tiba di
tempat kejadian
1. Before getting out of your vehicle, make sure you are :, parked well away from the
fallen wires. If it is night time, use a flashlight to examine the surroundings carefully
from the car or truck window. If you are parked over or near the fallen wires, move
your vehicle well out of harm's way. (See illustration #5.)
Sebelum keluar dari kendaraan Anda, pastikan Anda telah memarkir kendaraan Anda
jauh dari kabel yang jatuh. Apabila di malam hari, gunakan lampu senter untuk
memeriksa keadaan sekitar secara hati-hati dari jendela mobil atau truk. Apabila
Anda parkir pada atau di dekat kabel yang jatuh, pindahkan kendaraan Anda
menjauh dari bahaya. (Lihat ilustrasi #5.)
4. Keep people away from the broken or sagging wires or other electrically-charged objects.
Live wires in contact with objects on the ground may burn through, and one end may then
curl up or roll along the ground causing injury. (See illustration #8)
Jauhkan orang-orang dari kabel yang rusak, menggantung atau benda beraliran listrik lainnya.
Kabel yang bermuatan dan mengenai benda di tanah dapat membakarnya, dan salah satu
ujungnya dapat melekuk atau menggulung di tanah dan menyebabkan cedera.(lihat ilustrasi #8.)
Apabila sebuah
kabel jatuh di pagar
logam atau benda
logam lainnya, listrik mungkin tersalurkan ke bagian lain. Sebenarnya, tanah itu sendiri
dapat dialiri listrik sampai pada tingkat yang berbahaya di dekat kabel yang jatuh. (Lihatlah
penjelasan dalam potensi injakan atau sentuhan.)
3.4.2 How to aid victims trapped in a vehicle by a fallen Iive wire / Bagaimana membantu
korban yang terjebak dalam kendaraan karena kejatuhan kabel yang bermuatan
listrik
The following instructions are intended only as a guide to emergency personnel.
Instruksi berikut hanya dimaksudkan sebagai panduan bagi personil keadaan darurat.
Wherever possible, electricity supply personnel will handle these situations. However, if
they are not on the scene, you may be guided by the actions recommended for these
emergency situations:
Sedapat mungkin, petugas listrik yang harus menangani keadaan ini. Namun, apabila
mereka tidak ada di tempat kejadian, Anda mungkin dapat dipandu melakukan tindakan
yang disarankan dalam keadaan darurat seperti ini:
A fallen wire lies under a vehicle, with Do not touch any part of the vehicle. (You
one or more people inside. could be killed even if you are wearing
rubber gloves
Jangan menyentuh bagian kendaraan
Kabel jatuh di bawah kendaraan,
apapun. (Anda dapat terbunuh meskipun
dengan ada satu atau beberapa
Anda mengenakan sarung tangan karet)
orang di dalamnya.
If the driver is unhurt and can move Instruct the driver to move the car clear of
his vehicle. (See illustration #9) the wire, and clear of any pools of water,
which may be energized by the live wire.
Make sure you are not in a position to be
Apabila pengemudi tidak terluka dan injured in case the wire springs up after
dapat menggerakkan kendaraannya. being released when the vehicle moves.
(Lihat ilustrasi #9) Also make sure no other emergency
personnel or onlookers are standing in a
dangerous location.
Perintahkan pengendara untuk menjauhkan
mobilnya dari kabel, dan menjauh dari
genangan air, yang mungkin teraliri listrik
oleh kabel yang bermuatan. Pastikan Anda
tidak dalam posisi dapat terluka, jikalau
kabel tersebut terlontar setelah kendaraan
bergerak. Juga pastikan tidak ada penonton
atau petugas lain yang berdiri di lokasi
berbahaya.
Action to be taken by
A fallen wire lies across a vehicle with one or You can do nothing to assist the driver until the
more people inside. circuit has been switch off. Stay at least 8
metres clear of the wire and any part of the
Kabel yang jatuh melintang pada kendaraan
vehicle. Only use extinguishers suitable for
dengan satu atau beberapa orang di dalamnya
fighting an electrical fore. Keep bystanders
• If the driver is seriously injured and/or: away.
Apabila pengendara cedera berat Anda tidak dapat melakukan apa-apa untuk
dan/atau: membantu pengemudi sampai aliran listrik
dimatikan. Beradalah setidaknya 8 meter dari
- The vehicle is on fire
kabel dan dari bagian kendaraan. Hanya
Kendaraan terbakar gunakan alat pemadam yang sesuai untuk
- The vehicle cannot be moved mengatasi electrical fore. Jauhkan orang yang
clear. (See illustration #11) menonton.
Damage to poles may cause additional tension on wires as shown in illustration #13. In this
situation the wire may be damaged and could still break-keep well clear.
Kerusakan pada tiang dapat menyebabkan tegangan tambahan pada kabel seperti yang
ditunjukkan pada ilustrasi #13. Dalam keadaan seperti ini kabel dapat rusak dan putus-
tetaplah berada di tempat yang aman.
3.5.1 How to aid a victim in contact with a live wire/ Bagaimana membantu korban yang
terkena kabel bermuatan listrik
A fallen wire lies across a You can do nothing to the victim until advised by
victim on the ground. (See electricity personnel that the circuit has been
illustration #14) switched off. Do not touch the victim directly. Even
approved rubber gloves may not give protection for
the voltage involved.
Kabel yang jatuh di atas
Anda tidak dapat melakukan apa-apa sampai
korban di tanah. (Lihat
diberitahu oleh petugas listrik bahwa aliran listrik
ilustrasi #14)
telah dimatikan. Jangan menyentuh korban secara
langsung. Bahkan sarung tangan karet yang
dianjurkan mungkin tidak dapat memberikan
perlindungan terhadap tegangan seperti ini.
3.5.2 How to aid a victim in contact with electricity / Bagaimana membantu korban yang
terkena listrik
Unless you are certain that the victim is in contact with low (household) voltage level
you must not attempt to aid the victim until electricity Utilities Department personnel have
switched off the circuit. To do otherwise may well result in the rescuer becoming a second
victim.
Kecuali Anda yakin bahwa korban terkena listrik tingkat tegangan rendah (rumah
tangga) Anda tidak boleh berusaha membantu korban sampai petugas listrik dari Utilities
Department telah mematikan aliran arus. Melakukan hal lain malah dapat menyebabkan
penyelamat menjadi korban kedua.
If you are sure the contact is at a low voltage, the victim must be removed from the contact
as quickly as possible. Seconds are vital. To remove the contact:
Apabila Anda yakin kontak listrik tersebut pada tegangan rendah, korban harus
dipindahkan dari kontak tersebut secepat mungkin. Setiap detik sangatlah penting. Untuk
menghilangkan kontak tersebut:
(First preference) switch off the circuit, pull plug from socket.
(Pilihan pertama) matikan aliran arus, tarik steker dari stopkontak.
(Second preference) drag the victim clear making certain that you do not
contact the victim’s skin. The victim’s own dry clothing
(Pilihan kedua)
or belt, your own dry clothing, a towel, dry piece of
wood or rope etc will provide sufficient insulation. If the
victim’s clothing is providing theinsulation, be alert for
metal buttons or studs or belt buckles which may be in
contact with the victim’s skin.
Tarik korban menjauh, tapi pastikan bahwa Anda tidak
menyentuh kulit korban. Pakaian atau sabuk korban
yang kering, pakaian Anda yang kering, handuk,
benda dari kayu atau tali yang kering dll. akan
memberikan insulasi yang cukup. Apabila pakaian
korban memberikan insulasi tersebut, waspadalah
pada kancing logam atau gesper sabuk yang mungkin
menyentuh kulit korban.
While you render first aid to the victim keep onlookers clear. If practical, have someone go
to the mine switchboard to switch off all electricity supply to the premises. Call the electricity
Utilities Department.
Saat Anda memberikan pertolongan pertama pada korban, jauhkan para penonton. Apabila
memungkinkan, suruh seseorang ke pusat pengendali listrik (main switchboard) untuk
mematikan semua pasokan listrik ke tempat tersebut. Hubungi Utilities Department bagian
listrik.
3.6 How to deal with problems related to kiosks / Bagaimana menangani masalah yang
berhubungan dengan kotak listrik
Kiosks are metal or fibre-glass boxes, installed at ground/level, which house equipment
associated with underground electrical installations.
Kotak listrik adalah kotak logam atau fibre-glass, yang dipasang di tanah, tempat
menghubungkan perlengkapan rumah dengan instalasi listrik bawah tanah.
• A kiosk shows evidence of Call electricity authority, giving the location and any
being tampered with, such as identification, which is stencilled on the side of the
hack saw marks or severe kiosk.
dents. Hubungi petugas listrik, beritahu lokasinya dan
Kotak listrik yang setiap identifikasi yang tertera di sisi kotak listrik.
menunjukkan bukti
pengrusakan, seperti bekas
gergaji besi atau lekukan
yang dalam.
• A kiosk is damaged in a Do not touch the kiosk or any vehicle that may be
vehicle accident and driver is touching the kiosk. Treat it as an energized object,
unable to move the car clear. capable of killing. Warn occupants of car to stay
(see illustration #15). put. Call electricity authority and warn by-standers
away. Electricity Utilities Department will ensure
proper isolation and earthing of the kiosk, and will
Kotak listrik rusak dalam supervise removal of the vehicle after everything is
kecelakaan mobil dan safe.
pengendara tidak dapat
Jangan menyentuh kotak listrik atau bagian
menjauhkan mobil. (lihat
kendaraan yang mungkin menyentuh kotak listrik.
ilustrasi #15).
Perlakukan seperti benda yang beraliran listrik,
yang dapat membunuh. Peringatkan penumpang
mobil untuk tetap di tempat. Utilities Department
bagian Listrik akan memastikan insulasi yang tepat
dan melakukan grounding ke tanah, dan akan
mengawasi pemindahan kendaraan setelah
semuanya aman.
3.7 How to deal with electric wires when fighting fires in houses or other buildings /
Cara menangani kabel listrik ketika memadamkan kebakaran pada rumah atau
bangunan lain
Electric service is usually supplied at homes at 240 volts. Voltage to industrial plants and
commercial buildings may be 240 or 415 volts, but can be 11,000 volts or higher in large
industrial installations.
Pada rumah tinggal, listrik biasanya diberikan pada tegangan sebesar 240 volt. Tegangan
untuk pabrik industri dan bangunan perdagangan mungkin sebesar 240 atau 415 volt,
tetapi pada industri yang besar tegangannya sebesar 11.000 volt atau lebih.
• You are called to a house or Unless you are equipped with your own
building fire, where electric portable emergency lights, leave power and
lights continue to operate. light on as long as possible. With lights left on,
(see illustration #16). you will be able to work more effectively and
the building can be evacuated more rapidly. In
FES Training System Competency Module Approved By Date Published
3.7.1 Opening the building main switch / Membuka switch atau saklar utama bangunan
In some fire situations, it may be necessary to open a power switch. This is one time when
your insulated rubber gloves and protectors may help.
Pada beberapa kebakaran, mungkin harus membuka saklar tenaga listrik. Saat inilah
pelindung dan sarung tangan karet insulasi Anda dapat membantu.
Opening switches under normal conditions is not hazardous. However, the fire may
introduce a fault condition which may overload the switch at the moment of operation.
Membuka saklar pada keadaan normal tidaklah berbahaya. Namun, kebakaran mungkin
menyebabkan kerusakan yang dapat membebani saklar tersebut secara berlebihan pada
saat pengoperasian.
To minimize the problem, do the following:
Untuk meminimalkan masalah tersebut, lakukan hal berikut:
(a) Stand to one side of the switch.
Berdiri pada salah satu sisi saklar tersebut.
(b) Turn your eyes away while operating the switch.
Palingkan muka Anda sambil mengoperasikan saklar tersebut.
3.7.2 Entering flooded or wet buildings / Memasuki bangunan yang penuh air atau basah
The electrical hazards are increased when flooding and wet conditions exist in buildings.
Any open wires (even low voltage) can be lethal if you place yourself between the live wire
and the wet ground surroundings.
Bahaya listrik meningkat ketika bangunan penuh dengan air dan basah. Setiap kabel yang
lepas (bahkan tegangan rendah) dapat mematikan apabila Anda menempatkan diri Anda di
antara kabel yang bermuatan dan keadaan tanah sekitar yang basah.
Extreme caution is called for in this situation. The only safe way is to shut off the power
before you enter the building.
Anda harus sangat berhati-hati dalam keadaan seperti ini. Satu-satunya cara yang aman
adalah mematikan tenaga listrik sebelum Anda memasuki bangunan.
Pada semua kasus yang melibatkan peralatan listrik, hal pertama yang perlu dilakukan
adalah memastikan bahwa peralatan tersebut telah terisolasi dari listrik dan aman untuk
didekati. Pada instalasi yang besar, hal ini akan dilakukan oleh ‘Pihak Berwenang’ dari
Utilities Department atau, pada instalasi yang lebih kecil, oleh petugas di tempat yang
bersangkutan.
WARNING
Electrical or associated equipment should NOT be
touched or even approached unless it is confirmed to be
isolated and safe.
PERINGATAN
Perlengkapan listrik atau yang berhubungan dengannya
JANGAN disentuh atau didekati kecuali telah dipastikan
terisolasi dan aman.
FES Training System Competency Module Approved By Date Published
Seperti dalam semua keadaan darurat, pertimbangan utama haruslah bahaya terhadap
nyawa orang, baik yang terlibat ataupun yang kemungkinan besar terlibat. Apabila
evakuasi telah dilakukan maka segera lakukan pengecekan absensi. Apabila evakuasi
belum dilakukan maka pertimbangan haruslah diberikan untuk perlunya evakuasi sebagian
atau penuh, tergantung pada skala dan lokasi insiden.
rendah di dalam ruang turbin untuk penggunaan pemadaman kebakaran umum dan
saluran air tambahan biasanya akan tersedia di luar bangunan.
The pumps supplying water mains within the power station site starts automatically as
required by the PT INCO INDONESIA insurance assessor.
Pompa yang memasok saluran air di dalam stasiun pembangkit tenaga listrik berjalan
secara otomatis, seperti yang diharuskan oleh penilai asuransi PT INCO INDONESIA.
The use of water in some areas of a generating station may not be safe, and areas where
water may be used should have been decided beforehand in consultation with the Utilities
Department Engineer.
Penggunaan air di beberapa bagian stasiun pembangkit listrik mungkin tidak aman, dan
area-area di mana air boleh digunakan harus diputuskan sebelumnya dalam konsultasi
dengan Ahli Teknik Utilities Department.
Keadaan mungkin menjadi lebih buruk karena ada kemungkinan penundaan operasi
pemadaman kebakaran, karena memerlukan waktu untuk memastikan isolasi transformer
yang rusak dan menghubungkannya ke tanah (grounding).
Whilst awaiting an assurance that isolation of the transformer has been carried out steps
should be taken to protect surrounding property and water and foam supplies gathered and
made ready.
Sementara menunggu jaminan bahwa isolasi transformer telah dilakukan, harus diambil
langkah-langkah untuk melindungi barang di area sekitar, serta mempersiapkan pasokan
busa dan air.
If the transformer is not separately bunded, burning oil could flow around others in the
group, or 'bank', and rapidly involve them also. In such circumstances it will be essential to
lay and maintain a foam blanket over the affected area as soon as possible. Bearing in
mind the possibility of an explosion this should be done from as far away as practicable and
taking advantage of available protection if possible.
Apabila transformer tidak diberi penahan secara terpisah, minyak yang terbakar dapat
mengalir di sekitar yang lain di dalam kelompok, atau ‘menumpuk’, dan dengan cepat juga
membakarnya. Pada keadaan tersebut, harus membuat lapisan busa pada area yang
terkena, secepat mungkin. Pikirkan kemungkinan ledakan, sehingga hal ini harus dilakukan
dari jarak sejauh mungkin, dan sedapat mungkin manfaatkan perlindungan yang ada.
The transformer oil cooler banks, if they are free standing, may collapse, and the porcelain
insulators may shatter if they come in contact with fire or water jets. If porcelain bushings
or insulators do shatter, hot pieces of porcelain, which may be razor sharp, can be
thrown over considerable distances.
Tanggul pendingin minyak transformer, apabila tanggul tersebut berdiri bebas, dapat rubuh,
dan insulator porselin dapat pecah apabila terkena api atau aliran jet air. Apabila insulator
atau tabung porselin pecah, pecahan porselin yang panas dan mungkin setajam
pisau, dapat terlontar ke jarak yang jauh.
Seperti dengan transformer, apabila terjadi arus pendek maka switchgear berisi
minyak dapat meledak dengan hebat dan menyebarkan minyak yang terbakar ke
jarak yang jauh. Hal ini harus diingat ketika menempatkan personil dan perlengkapan
pemadaman kebakaran.
Fire fighters should be aware of this leaching process and, until expert monitoring
shows otherwise, regard oil filled transformer or oil filled switchgear as dangerous
and requiring full protection procedure including the wearing of breathing apparatus.
(It can be safely assumed that transformers and switchgear belonging PT INCO do not
contain PCB's or are retro filled. It is only in industrial and commercial premises, that
equipment which still contains PCB's and/or has been retro-filled may be found.)
Petugas pemadam kebakaran harus sadar akan proses pelepasan ini dan sampai
pengawasan ahli menunjukkan sebaliknya, harus menganggap transformer berisi
minyak atau switchgear berisi minyak adalah benda berbahaya dan memerlukan
prosedur perlindungan penuh termasuk penggunaan alat bantu pernapasan. (Dapat
dengan aman menganggap bahwa transformer dan switchgear milik PT INCO tidak
mengandung PCB’s atau telah diisi retro. Hanya di tempat industri dan perdagangan,
perlengkapan yang masih memuat PCB’s dan/atau diisi retro masih dapat ditemukan.)
Heating or burning of PCB's greatly increases the hazards as the production of highly toxic
gases and smoke can occur which could result in soil and surface contamination. At such
incidents, there- fore, as well as protecting firefighters with full protective clothing and
breathing apparatus, consideration should also be given to evacuating the area covered, or
likely to be covered, by the resulting smoke/gas cloud.
PCB's yang panas atau terbakar dapat meningkatkan bahaya karena menghasilkan asap
dan gas sangat beracun yang dapat menyebabkan pencemaran tanah dan permukaan.
Oleh karena itu, dalam insiden seperti ini, selain melindungi petugas pemadam dengan
pakaian pelindung lengkap dan alat bantu pernapasan, pertimbangkan juga untuk
mengevakuasi area yang terkena, atau kemungkinan besar terkena, oleh gumpalan
gas/asap yang dihasilkan.
Strict precautions should be taken to ensure that any spillage does not enter sewage
systems or water courses. All spillage, including water used for decontamination purposes,
should be contained for specialist disposal as PCB's are not biodegradable.
Tindakan pencegahan tegas harus dilakukan untuk memastikan tidak ada tumpahan yang
memasuki sistem pembuangan atau saluran air. Semua tumpahan, termasuk air yang
digunakan untuk proses dekontaminasi, harus dibungkus khusus karena PCB's tidak dapat
diuraikan secara alami.
The appropriate authority should be notified where there is any likelihood of products from a
fire, which involves PCB's, entering water courses.
Pihak berwenang yang sesuai harus diberitahu jika ada kemungkinan hasil dari kebakaran,
yang melibatkan PCB's, memasuki saluran air.
If PCB's are spilled or leaked, the Officer-in-Charge of the incident should request the Local
Authority to arrange disposal of the PCB's and any material which they may have
contaminated.
Apabila PCB's tumpah atau bocor, Petugas atau Officer yang bertangung jawab atas
insiden tersebut harus meminta Pihak Berwenang setempat untuk mengatur pembuangan
PCB's dan setiap bahan yang mungkin telah tercemar olehnya.
4.5 Fires On or Near Overhead Power Lines / Kebakaran Pada atau Di Dekat Kabel Listrik
Tinggi
Apart from transformers and switchgear, or apparatus containing oil, there is little fire risk
involved where transmission and distribution is carried out by means of overhead lines,
although where the lines are carried on wood pole supports, and the route lies across
scrub, heathland or similar country, there is some slight risk of scrub fires setting the wood
pole supports alight and bringing the cables down.
Selain transformer dan switchgear, atau peralatan yang berisi minyak, risiko kebakaran
hanya keci jika transmisi dan penyaluran dilakukan dengan menggunakan kabel tinggi,
walaupun jika kabel tersebut disangga di tiang kayu dan jalurnya terbentang melewati
semak-semak, padang rumput atau daerah yang seperti itu, akan ada sedikit risiko
kebakaran semak dapat membakar tiang kayu dan menjatuhkan kabel-kabelnya.
Fires, especially those involving smoke with a large carbon content, e.g., rubber tyres,
certain types of plastic, forest and heath fires etc., beneath or near overhead transmission
lines, may cause ionisation of the surrounding air and allow arcing to take place (see 5.2(d)
above). In addition heat from large fires in the vicinity of overhead transmission lines may
cause the lines to stretch and sag. If there is any doubt about the safety of the lines then
the Utilities Department should be notified.
Api, khususnya yang melibatkan asap dengan kandungan karbon yang banyak, misalnya
ban karet, jenis plastik tertentu, kebakaran semak dan hutan dll, di bawah atau di dekat
kabel transmisi tinggi, dapat menyebabkan ionisasi udara sekitar dan terjadi bunga api
(lihat 5.2(d) di atas). Selain itu, hawa panas dari kebakaran besar di sekitar kabel transmisi
tinggi dapat menyebabkan kabel tersebut meregang dan menggantung. Apabila ragu
mengenai keamanan kabel tersebut maka Utilities Department harus diberitahu.
There are two further major hazards to be considered when using hose near to overhead
power lines:
Terdapat dua bahaya besar yang harus dipertimbangkan ketika menggunakan selang air di
dekat kabel listrik tinggi:
(i) A high pressure jet playing on an overhead line with horizontal conductors may
cause the conductors to clash and produce arcing. This could lead to a breakage of
the conductor resulting in live conductors falling to the ground; and
Pancaran jet bertekanan tinggi ke kabel tinggi dengan konduktor horisontal dapat
menyebabkan konduktor saling bertabrakan dan menghasilkan bunga api. Hal ini
dapat mengakibatkan kerusakan konduktor, sehingga konduktor bermuatan listrik
itu dapat jatuh ke tanah; dan
(ii) A water jet playing directly on to overhead conductors can result in earth leakage
currents through the water jet stream to ground. This may cause the branch to
become live with potentially fatal consequences.
Pancaran air secara langsung ke konduktor tinggi dapat menyebabkan kebocoran
arus ke tanah melalui aliran pancaran air ke tanah. Hal ini dapat menyebabkan
cabang selang menjadi bermuatan listrik, dengan akibat yang berpotensi fatal.
There are many factors governing the amount of earth leakage current flowing down
a jet stream, but it is not practicable to take all of them into account when fighting a
fire.
Terdapat banyak faktor yang mempengaruhi jumlah kebocoran arus ke tanah yang
melewati aliran pancaran, tetapi tidak mungkin untuk mengingat semuanya ketika
memadamkan kebakaran.
Therefore, to minimise the risk of danger from these hazards:
Oleh karena itu, untuk meminimalkan risiko bahaya ini:
It should be understood that there are no statutory rights of entry to substations for fire
incidents.
Harus dipahami bahwa menurut undang-undang tidak ada hak untuk memasuki gardu
dalam insiden kebakaran.
Should a person be seen lying on top of a transformer, switch, or, anywhere else above
ground level, they must NOT be touched until word is received from an 'Authorised
Person' of the Utilities Department that it is safe for rescue work to be carried out.
Apabila terlihat seseorang terbaring di atas transformer, switch, atau di tempat lain di atas
tanah, mereka JANGAN disentuh sampai telah mendapat pemberitahuan dari 'Orang
yang Berwenang' dari Utilities Department bahwa keadaan telah aman untuk
melakukan penyelamatan.
Care should be taken when attempting to move injured people, even if they are lying on the
ground away from a live power line as either the surrounding ground or the person could
have a residual charge of several thousand volts.
Berhati-hatilah ketika mencoba memindahkan orang yang terluka, bahkan apabila mereka
terbaring di atas tanah jauh dari kabel listrik yang bermuatan, karena orang atau tanah di
sekitar itu bisa saja mengandung muatan listrik sisa sebesar beberapa ribu volt.
Petugas pemadam kebakaran harus melindungi setiap benda di dekat kotak listrik di jalan
itu, dan menunggu kedatangan wakil dari Utilities Department, yang seharusnya telah
diberitahu.
All personnel, and the public, should be warned to keep away from adjacent street boxes,
whether above or below ground, in case further explosions take place.
Semua personil dan masyarakat, harus diperingatkan untuk menjauh dari kotak jalan yang
berdekatan, baik di atas atau di bawah tanah, seandainya terjadi ledakan lanjutan i.
Underground cable or link boxes (Figure 2.22) and feeder pillars are generally located
sufficiently far from a building for any risk of fire spread to be unlikely but of course such an
eventuality should not be discounted.
Kotak penghubung atau kabel bawah tanah (Gambar 2.22) dan pilar feeder biasanya
ditempatkan cukup jauh dari bangunan karena meski bahaya penyebaran kebakarannya
keci, tetapi tentu saja kemungkinan tersebut tidak dapat diabaikan.
In the case of a small fire, it may only be necessary to isolate circuits near the fire, and this
should be done by the plant engineer.
Pada kasus kebakaran kecil, mungkin hanya perlu untuk mengisolasi aliran arus di dekat
api, dan hal ini harus dilakukan oleh ahli teknik pabrik tersebut.
4.10 Fires Involving Storage Batteries / Kebakaran yang Melibatkan Baterai Aki
The traditional type of storage batteries are usually of the lead-acid or nickel-iron type and
will be found in many Utilities Department and commercial premises and are also used in
motor vehicles. Newer types of batteries, especially for use in vehicles are in the research
stage and use sub- stances such as sodium sulphur, sodium nickel chloride. Other
substances which are now used in batteries are zinc and lithium.
Jenis tradisional dari baterai aki biasanya jenis timah hitam atau nikel besi dan akan
ditemukan pada banyak Utilities Department dan tempat perdagangan, dan juga digunakan
di kendaraan motor. Jenis aki yang lebih baru, khususnya untuk digunakan pada
kendaraan masih dalam tahap penelitian dan menggunakan bahan seperti sodium sulfur,
sodium nikel klorida. Bahan lain yang saat ini digunakan dalam baterai aki adalah zinc dan
litium.
4.10.1 Lead Acid/Nickel Iron Batteries / Baterai Timah Hitam/ Nikel Besi
When correctly installed and maintained, these batteries present little fire risk, but the
unsuitable conditions under which they are sometimes recharged can frequently lead to a
fire.
Jika dipasang dan dipelihara dengan benar, baterai aki ini berisiko kebakaran yang kecil,
tetapi dalam keadaan yang tidak benar, dan di mana aki tersebut kadangkala diisi ulang,
seringkali dapat mengakibatkan kebakaran.
Hydrogen is released during the charging process and concentration levels of only 4% are
sufficient to create an explosive atmosphere. If a source of ignition is introduced into a
battery charging area, and the conditions are suitable, there is a risk of an explosion.
Hidrogen dilepaskan selama proses pengisian, dan tingkat kepekatan sebesar 4% saja
sudah cukup untuk membuat lingkungan yang dapat meledak. Apabila sumber pengapian
masuk ke area pengisian aki, dan keadaannya sesuai, terdapat bahaya ledakan.
If batteries are involved in fire then the products of combustion will contain droplets of
electrolyte (dilute sulphuric acid) which is both corrosive and poisonous.
Apabila ada aki yang terlibat dalam kebakaran maka hasil pembakaran akan mengandung
tetesan elektrolit (asam belerang cair) yang bersifat korosif dan beracun.
Salt water should NOT be used on fires in which lead-acid type batteries are involved since,
under certain conditions, free chlorine may be generated.
Air garam TIDAK BOLEH digunakan pada kebakaran yang melibatkan aki jenis timah hitam
karena pada keadaan tertentu, dapat menghasilkan klorin bebas.
Because of the possibility of the presence of corrosive and poisonous electrolyte and/or
chlorine when dealing with fires involving lead acid batteries the use of breathing apparatus
and protective clothing should be considered. Nickel-iron batteries which use alkaline
electrolyte are free of this danger.
Karena kemungkinan adanya klorin dan/atau elektrolit yang korosif dan beracun ketika
menangani kebakaran yang melibatkan aki timah hitam, maka penggunaan alat bantu
pernapasan dan pakaian pelindung harus dipertimbangkan. Aki nikel-besi yang
menggunakan elektrolit alkali tidak memiliki bahaya ini.
If a fire has been caused by a short circuit, the circuit should be broken, if possible, by
opening the switch or disconnecting the leads, otherwise the conditions which caused the
fire will persist until the battery is fully discharged. The fire should, preferably, be tackled
with a hose-reel fog or spray, not because of the risk of shock, but because needless
damage may be caused if a high pressure jet is allowed to strike the cells. Water should be
kept away from cells which are not involved in the fire, because it will adversely affect the
electrolyte. Any electrolyte which has been released by the failure of a cell should be
diluted with a stream of water.
Apabila kebakaran disebabkan oleh arus pendek, maka apabila mungkin aliran arus harus
diputus, dengan membuka switch atau memutuskan sambungannya, kalau tidak keadaan
yang menyebabkan kebakaran akan tetap berlangsung sampai aki habis. Kebakaran
tersebut, lebih baik dipadamkan dengan semprotan spray atau kabut dari rol selang, bukan
karena bahaya sengatan listrik, tetapi karena dapat menyebabkan bahaya yang tidak perlu
apabila pancaran ket bertekanan tinggi diarahkan ke sel-selnya. Air harus dijauhkan dari
sel yang tidak terlibat dalam kebakaran, karena dapat merusak elektrolit. Setiap elektrolit
yang telah lepas karena kerusakan sel harus dibasahi dengan aliran air.
4.10.4 Fires involving Uninterruptible Power Supplies (UPS) / Kebakaran yang melibatkan
Uninterruptible Power Supplies (UPS)
An Uninterruptible Power Supply (UPS) is a, device that cleans up mains power and also
provides back-up power from its battery to a computer or other electrical equipment e.g.,
telecommunications or medical equipment, during a power blackout.
Uninterruptible Power Supply (UPS/Pasokan Listrik Tanpa Henti) merupakan alat yang
membersihkan saluran listrik utama dan juga memberikan tenaga cadangan dari baterainya
ke komputer atau perlengkapan elektronik lainnya, seperti perlengkapan telekomunikasi
atau medis, selama listrik mati.
There are two main types of UPS.
Terdapat dua jenis utama UPS.
One type is used for individual pieces of electrical/electronic equipment and are commonly
found associated with computers, especially personal computers. They vary in size
considerably. 'Desk top models', which typically have a power output of about 150/300 VA,
are approximately the size of a large shoe box or, for 'slim line models', the size of an
attache case. Standing floor models vary in ", size from a small suitcase to models the size
of a small refrigerator with, typically, power outputs of between 5-20 kVA.
Satu jenis digunakan untuk perlengkapan listrik/elektronik dan biasa ditemukan
berhubungan dengan komputer, khususnya komputer personal. UPS ini mempunyai ukuran
yang sangat beragam. ‘Model desk top’, yang biasanya mempunyai keluaran tenaga
sekitar 150/300 VA, kira-kira berukuran sebesar kotak sepatu yang besar, atau untuk
‘model slim line’, sebesar ukuran tas kantor. Model yang berdiri di lantai beragam dalam
ukuran incinya, berukuran dari koper kecil sampai seukuran kulkas kecil, dengan keluaran
tenaga umumnya sekitar 5-20 kVA.
The other type is linked to a number of pieces of equipment in a room or, in the case of the
very largest types, to all the equipment in a whole building. These vary in size from a
medium sized refrigerator to a large wardrobe and have power outputs of up to 100 kVA for
the largest models. (Figures 5.7 and 5.8)
Jenis lain dihubungkan dengan sejumlah perlengkapan di satu ruangan, atau pada jenis
yang terbesar, dengan semua perlengkapan di seluruh gedung. Ragam ukurannya mulai
dari kulkas berukuran sedang sampai lemari pakaian yang besar dan mempunyai keluaran
tenaga sampai 100 kVA untuk model terbesar. (Gambar 5.7 dan 5.8)
In the case of the larger UPSs which provide back-up for a whole building there should be a
"cut-off” switch for it near the "cut-off” switch for the mains power and thus it should not
pose a problem. However, the smaller individual UPSs can pose a particular hazard as they
will stay "live" until their own individual on/off switches are operated.
Pada kasus UPS yang lebih besar dan memberikan cadangan untuk seluruh gedung harus
ada switch “pemutus hubungan listrik” untuk cadangan tersebut di dekat switch “pemutus
hubungan listrik” untuk tenaga listrik utama, agar UPS tersebut tidak menjadi masalah.
Namun, UPS perseorangan yang lebih kecil dapat mempunyai bahaya khusus karena akan
tetap “hidup” sampai switch on/off-nya sendiri yang dioperasikan.
Firefighters should therefore treat all electrical/ electronic equipment, especially personal
computers, as potentially being "live" and not deliberately direct water upon them or come
into contact with damaged or suspect equipment unless they have been assured that the
item does not have an UPS or that, if it has, it has been turned off.
Oleh karena itu, petugas pemadam kebakaran harus memperlakukan semua perlengkapan
listrik/elektronik, khususnya komputer pribadi, sebagai memiliki kemungkinan “bermuatan
listrik” dan jangan dengan sengaja mengarahkan air pada alat-alat tersebut, atau
bersentuhan dengan perlengkapan yang diduga bermuata atau rusak, kecuali telah
dipastikan bahwa barang tersebut tidak mempunyai UPS atau (apabila punya UPS) telah
dimatikan.
It should be remembered that an UPS system is installed to safeguard the electrical supply
of vital or even life saving equipment and its disconnection could have serious
consequences. If possible, therefore, advice should be sought before such a system is
switched off.
Harus diingat bahwa sistem UPS dipasang untuk mengamankan pasokan listrik ke alat-alat
yang sangat penting atau bahkan menyelamatkan nyawa, dan pemutusannya dapat
mempunyai akibat yang serius. Oleh karena itu, apabila mungkin harus mendapatkan
saran dahulu sebelum sistem tersebut dimatikan.
4.12 How to deal with substation fires / Bagaimana menangani kebakaran gardu listrik
Substations contain large quantities of oil, energized electrical equipment and, in some
cases, cylinders of compressed gas.
Gardu listrik memuat sejumlah besar minyak, perlengkapan listrik yang bermuatan listrik
dan terkadang tabung-tabung gas padat.
On arriving at a substation fire, do not enter the substation.
Saat tiba pada kebakaran gardu listrik, jangan memasuki gardu listrik tersebut.
Fire fighters should hook up and stand ready to protect adjacent properties. Utilities
Department personnel will advise fire fighters after the substation has been made
electrically safe. Firemen can then proceed with conventional fire fighting equipment.
Petugas pemadam kebakaran harus bersiap untuk melindungi barang di sekitarnya.
Personil dari Utilities Department akan memberi saran kepada petugas pemadam
kebakaran setelah gardu listrik telah aman dari listrik. Petugas pemadam kebakaran
kemudian dapat melanjutkan dengan perlengkapan pemadaman kebakaran yang biasa.
Most substations are unattended. However, an automatic signal system should summon a
Utilities Department representative when an emergency develops. If a Utilities Department
representative is not present when the fire fighter arrives, the utility must be contacted to
make sure one has been dispatched.
Sebagian besar gardu listrik tidak dijaga. Namun, sistem sinyal otomatis harus memanggil
wakil dari Utilities Department jika terjadi keadaan darurat. Apabila wakil Utilities
Department tidak hadir ketika petugas pemadam kebakaran tiba, Utilities Department harus
dihubungi untuk memastikan seseorang telah dikirim.
Utilities Department representatives are familiar with the substations they service. They are
trained in the use of the specialized station fire fighting apparatus and can identify the areas
that are electrically safe.
Wakil dari Utilities Department telah mengenal gardu listrik yang mereka kerjakan. Mereka
telah dilatih dalam penggunaan alat-alat pemadaman kebakaran yang khusus, dan dapat
mengenali area yang aman dari listrik.
You have been called to a Do not enter the substation. Keep the danger zone
substation fire. (See clear of onlookers. Do not spray the fire with water
illustration #17). or any other liquid. Await the arrival of the Utilities
Department personnel to shut off the power and to
give you guidance.
Anda dipanggil ke kebakaran
gardu listrik. (Lihat ilustrasi
#17). Jangan memasuki gardu listrik. Jauhkah orang-
orang dari zona berbahaya. Jangan menyemprot
kebakaran dengan air atau cairan lain. Tunggu
kedatangan personil Utilities Department untuk
mematikan tenaga listrik dan untuk memandu
Anda.
4.13 How to deal with unauthorized persons in substations / Bagaimana menangani orang
tak berwenang di gardu listrik
Another dangerous situations arises from people playing around electrical installations and
equipment.
Keadaan berbahaya lainnya terjadi dari orang-orang yang iseng berada di sekitar
perlengkapan dan instalasi listrik.
• People are seen Call them to come to the fence and remain there. Warn
climbing over a fence of the danger. Call for assistance from the Utilities
into a substation Department. (see illustration #19)
Orang-orang terlihat Panggil mereka ke pagar dan tetap di sana. Peringatkan
memanjat pagar ke mengenai bahayanya. Panggil bantuan dari Utilities
dalam gardu listrik Department. (lihat ilustrasi #19)
4.14 How to deal with fires and explosions in underground electrical vaults / Bagaimana
menangani kebakaran dan ledakan pada saluran listrik bawah tanah
In high-density areas of every city, and in many residential subdivisions, electric distribution
wires run through cable tunnels or conduits located under footpaths roadways.
FES Training System Competency Module Approved By Date Published
Pada area yang sangat padat dari setiap kota, dan pada banyak pemukiman, kabel
penyaluran listrik dilakukan melalui saluran atau terowongan kabel yang ditempatkan di
bawah trotoar jalan.
Transformer and switchgear for these circuits are situated underground in concrete vaults,
with access provided to each vault by a manhole.
Transformer dan switchgear untuk sirkuit ini ditempatkan di bawah tanah dalam ruang
beton, dengan sebuah lubang sebagai jalur masuk ke masing-masing saluran.
Underground electrical systems are designed to withstand great stress. However, earth
movement can crack the concrete walls of cable tunnels, as well as adjacent sewer pipes,
natural gas pipes and water mains. Hazardous conditions can result, including
accumulations of explosive and toxic gases, and dangerously-high water levels.
Sistem listrik bawah tanah dirancang untuk menahan tekanan yang besar. Namun, gerakan
tanah dapat memecahkan dinding beton pada terowongan kabel, beserta pipa air, pipa gas
alam dan pipa air yang berdekatan. Keadaan yang berbahaya dapat menyebabkan
pengumpulan gas yang dapat meledak dan beracun, serta ketinggian air yang berbahaya.
Electrical failure of a cable may result in an explosion or fire, which could damage insulation
and energize all metal parts within the vault.
Kerusakan kabel listrik dapat menyebabkan ledakan atau kebakaran, yang dapat merusak
insulasi dan mengaliri listrik semua bagian logam di dalam terowongan.
Emergency service personnel should not enter any electricity Utilities Department manhole
except under one condition. That is, if a victim is found, unconscious, inside an open
manhole, and there are no electricity Utilities Department representatives on hand to effect
a rescue. Suitable breathing apparatus must be worn by any rescuer who enters the vault.
Personil keadaan darurat tidak boleh memasuki lubang listrik dari Utilities Department ini,
kecuali pada satu keadaan. Yaitu, apabila korban ditemukan, tidak sadar, di dalam lubang
yang terbuka, dan tidak ada perwakilan Utilities Department listrik di tempat untuk
membantu penyelamatan. Alat bantu pernapasan yang sesuai harus dikenakan oleh setiap
penyelamat yang memasuki terowongan.
• A victim is lying unconscious at the Do not enter unless you have been
bottom of an open vault. trained in the use of the proper
equipment to safely carry out the
Korban terbaring tidak sadarkan diri di
rescue. The manhole may be filled
dasar terowongan yang terbuka.
with toxic gases generated by burning
oil or the carbonization of insulating
material on the cables. These gases
could kill you or damage your lungs
unless you use proper breathing
equipment.
• You have been called to the scene of 1. Call Utilities Department, gas supply
an explosion in the street. One or more company, water board, etc. indicating
manhole covers have been blown clear the location and number of manholes
of their seatings. (See Illustration #20). involved.
Anda telah dipanggil ke lokasi ledakan Hubungi Utilities Department,
di jalan. Satu atau beberapa penutup perusahaan gas, badan air, dll dan
lubang telah terlempar dari tempatnya. katakan lokasi dan jumlah lubang
(Lihat ilustrasi #20). yang terlibat.
2. Do not approach an open manhole. It
may explode a second time.
Jangan mendekati lubang yang
terbuka. Dapat terjadi ledakan lagi.
3. Keep the public at a safe distance.
Jauhkan orang-orang pada jarak yang
aman.
4. Stop traffic until there is no danger of
another explosion.
Hentikan lalu lintas sampai tidak ada
bahaya ledakan lain.
5. Maintain precautions until conditions
have been evaluated by an expert
representative.
Pertahankan tindakan pencegahan
sampai keadaan telah dinilai oleh
seorang perwakilan yang ahli.
4.15 Electrical equipment which may be mounted on poles / Perlengkapan listrik yang
mungkin ditempatkan pada tiang
4.15.1 Transformer
There are several hazards to be aware of when fighting transformer type fires.
Terdapat beberapa bahaya yang harus disadari ketika memadamkan kebakaran jenis
transformer.
Transformers are devices used to step-up or step-down voltages. They contain, usually,
large volumes of insulating oil which, of course, is combustible and has a flash point of 145
o
C.
Transformer merupakan alat yang digunakan untuk menaikkan atau menurunkan
tegangan. Biasanya Transformer memuat banyak minyak yang terinsulasi yang tentu saja
mudah terbakar, dan mempunyai titik nyala pada 145 oC.
Basically, a transformer consists of an iron-core on which is placed two or three coils of
conductors. By varying the number of turns on the coils, the voltage can be changed.
Pada dasarnya, transformer terdiri dari inti besi diisi dua atau tiga kumparan konduktor.
Dengan mengubah jumlah putaran pada kumparan, tegangannya dapat diubah.
The turns on the coils need to be insulated from each other to withstand the voltages. This
insulation is usually combustible paper.
Putaran pada kumparan perlu saling diinsulasi satu sama lain untuk menahan
tegangannya. Insulasi ini biasanya berupa kertas yang mudah terbakar.
For both cooling and insulating purposes, transformers are placed in large metal tanks.
Further refinements can include pumps, fans, radiators and a large tank at the top of the
main transformer tank called a conservator, which also contains oil.
Untuk tujuan pendingin dan insulasi, transformer ditempatkan pada tangki logam yang
besar. Tambahan lanjutan antara lain pompa, kipas, radiator dan tangki besar di atas
tangki utama transformer yang disebut konservator, yang juga berisi minyak.
Usually it is possible to extinguish transformer fires before all the oil has been consumed,
thereby saving adjacent equipment from damage. No attempt should be made to extinguish
transformer fires until the electricity authority has confirmed that it is safe to do so. Burning
oil at ground level can be extinguished where it presents other dangers.
Biasanya masih mungkin untuk memadamkan kebakaran transformer sebelum semua
minyak habis terpakai, dengan demikian menyelamatkan perlengkapan yang berdekatan
dari kerusakan. Jangan mencoba memadamkan kebakaran transformer sampai petugas
listrik telah menyatakan aman untuk melakukannya. Minyak yang terbakar di tanah dapat
dipadamkan jika menunjukkan bahaya lain.
Transformers have porcelain bushings fixed on the lid or sides. The function of these
bushings is simply to let the high voltage transformer connection pass through the earthed
metal tanks. Typically they contain the same insulating material found in transformers paper
and oil. When subjected to high temperatures the porcelain material can explode. This
could result in flying projectiles and more oil as fuel for the fire. Be aware!
Transformer mempunyai tabung porselin yang dipasang pada penutup atau sampingnya.
Fungsi tabung ini agar hubungan transformer bertegangan tinggi dapat melewati tangki
logam yang telah dihubungkan ke tanah. Biasanya tabung tersebut memuat bahan insulasi
yang sama seperti yang ditemukan di minyak dan kertas transformer. Ketika terkena suhu
yang tinggi bahan porselin dapat meledak. Hal ini dapat menyebabkan proyektil yang
beterbangan dan lebih banyak minyak sebagai bahan bakar kebakaran. Waspadalah!
A typical pole mounted transformer is shown in illustration #21.
Transformer yang ditempatkan pada tiang khusus ditunjukkan pada ilustrasi #21.