Tuttle and Bailey Administration
Tuttle and Bailey Administration
tuttleandbailey.com/techcorner/bulletins/basics.asp
Introduction
This technical article addresses many of the topics regarding space air diffusion as it
relates to the use of Tuttle & Bailey air outlets (supply registers and diffusers) and air inlets
(return grilles and louvers). Basic principles of human comfort, space air diffusion,
selection and location of air outlets and inlets, and sound are all discussed in sufficient
detail for the purpose of educating customers.
1/8
The focus of this article will be on the the occupied zone temperature for
parameters that are influenced by air outlets ventilation. The supply air jet is delivered
(supply registers and diffusers) and air inlets by the air outlet and mixes with room air
(return grilles and louvers), specifically by entrainment (induction), which helps
space temperature, local air velocity, and to reduce the jet velocity and equalize
acoustic quality. the supply air temperature as it enters
the occupied zone. The mixing system is
Be aware that there are instances where the predominant method of space air
human comfort may not be the primary focus diffusion in the United States and is
of the HVAC system, such as industrial widely used with variable air volume
facilities, animal rooms, or clean rooms. (VAV) systems. Tuttle & Bailey ceiling
diffusers, high and low sidewall supply
Space Air Diffusion grilles, and floor registers provide
Where human comfort is the primary excellent mixing air patterns, which
concern, the purpose of space air diffusion is ensures that the cold or warm supply air
to introduce conditioned air into a building is sufficiently tempered before entering
space without making the occupants feel the occupied zone. See Figure 1.
uncomfortable. This can be accomplished by
designing the space with the correct number,
type, and location of air outlets and air inlets.
According to ASHRAE Standard 55-92
Thermal Environmental Conditions for
Human Occupants, the comfort limits for an
occupied space (relative to space air
diffusion) are:
and air outlet face velocities are relatively air distribution plenum underneath the
low (less than 100 fpm), resulting in floor. Underfloor systems are often found
acceptable occupied zone conditions. Air in computer rooms or spaces where
outlets are usually located low on the office layotus are frequently changed.
sidewall, resulting in a flow of conditioned air The topics discussed below are primarily
across the floor. The air then naturally rises directed toward mixing systems but
as it absorbs heat from plumes. Heat and much of the information can be applied
contaminants from the occupied zone are to the other systems as well.
removed from the space through air inlets
2/8
located in the ceiling or high sidewall. Also, a Evaluating Comfort
stratification zone with little or no air motion As mentioned previously, certain
is developed just above the occupied zone. parameters can be controlled to ensure a
Displacement ventilation systems are relatively comfortable environment. The
popular in Scandinavia, where cooling loads question is how does one evaluate the
are rather low. See Figure 2. sytem to make sure that the actual
parameters are within the allowable
range? Standard methods exist to
evaluate these parameters in real or
simulated spaces to determine if the
conditions are being met. The first
evaluation concept is called the effective
draft temperature - , which uses the
local air temperature and velocity in a
single equation to determine a relative
feeling of coolness. The equation is:
3/8
temperatures slightly below room 2. ADPI is based on effective draft
temperature (above 63° F). the difference is temperature and air velocity only.
that the occupant often has local control of Relative humidity and the
the airflow rate and direction of the air jet remaining comfort parameters
through the use of special air outlets (similar should be evaluated in accordance
to those found in automobiles and with ASHRAE Standard 55.
commercial airplanes). Air outlets are 3. ADPI is not to be used as a rating
typically located in the floor, furniture, or method for a single air outlet. It is
workstations. Air inlets (returns) are usually to be used only for the evaluation
located in the ceiling because the air has a of comfort in a space that utilizes a
natural tendency to rise similar to the SYSTEM of air outlets.
displacement ventilation system. Localized
ventilation systems are also used in raised Air Distribution and Diffusion
floor applications where air is supplied Properties of Air Outlets and Air Inlets
throughout an Air outlets possess certain basic
characteristics that allow for the
introduction of air into a space whether it
is a mixing system or any of the other
systems. As air is conveyed through an
air outlet or air inlet, the following
characteristics are important factors in
achieving the desired space air diffusion:
1. The speed of the air (face velocity) Face Velocity (Vk) - The average
leaving the air outlet or entering the air velocity of air entering an air inlet or
inlet. leaving an air outlet. Face velocity is
2. The direction of the air emanating from usually measured at pre-defined
an air outlet (1-way pattern, 2-way locations on the face or can be
pattern, 3-way pattern, 4-way pattern, calculated from the total pressure of the
radial pattern, etc.) device according to the following
3. The effective area of an air outlet or air equation. The common unit of measure
inlet. is feet per minute (fpm).
4. The distance the air travels away from
an air outlet (throw, spread, and drop).
5. The pressure resistance of an air outlet
or air inlet (static and total pressure). Effective Area (Ak) - The actual
6. The quantity of the air (airflow rate). minimum area of an air outlet or air inlet
through which air is able to pass. The
The above characteristics of an air outlet or following two equations can be used to
air inlet are measured in accordance with calculate the effective area. The
ASHRAE Standard 70-1991 Method of common unit of measure for Ak is square
Testing for Rating the Performance of Air feet (ft²).
Outlets and Inlets and are often found in
manufacturer's literature. These Effective area of an air outlet or air inlet
characteristics are defined as follows: is NOT the same as the free area. Free
area is the geometric opening of an air
4/8
Airflow Rate (Q) - The unit volume
displacement of air per unit time. The
common unit of measure is cubic feet per
minute (cfm).
5/8
amount of air, as well as the sound produced Selection and Location of Air Inlets
by the air outlet or air inlet. The common unit The location and selection of air inlets
of measure is inches of water (in w.c.). depends on the allowable pressure loss
of the device, the location of any
concentrated heating or cooling loads,
and the permissible sound. Air inlets do
not influence the room air motion beyond
one characteristic length of the opening
away from the inlet, so rarely do air inlets
cause unwanted drafts.
6/8
The sound power of air outlets and air inlets 2. Increase the size of the air outlet or
is measured in accordance with ASHRAE air inlet, which decreases the face
Standard 70-1991. The standard requires velocity and pressure loss.
sound power levels to be determined in the However, increasing the size of an
125 to 4000 Hz octave bands at a given air outlet without increasing the
operating condition. The sound power levels airflow will result in shorter throws
can then be reduced to sound pressure and may cause conditioned air to
levels by subtracting the space attenuation drop into the occupied zone.
in accordance with ARI Standard 885-98 3. Balancing dampers should not be
Procedure for Estimating Occupied used in the neck of the air outlet.
Sound Levels in the Application of Air This can add anywhere from 5 to
Terminals and Air Outlets (this standard 16 NC to the sound rating,
can be downloaded free of charge from the depending on the amount of
ARI homepage at www.ari.org). The damper closure. Balancing
resultant sound pressure levels are plotted dampers should be located as far
on a noise criteria (NC) chart to determine upstream from the air outlet as
the actual NC level of the device. possible.
Manufacturers often use a standard 4. The approaching ductwork to the
deduction of 10 dB per octave band for air outlet should be kept as straight
determining published NC ratings. The as possible. Any offset or abrupt
drawback of this method is that the actual bend will add up to 15 NC to the
space rarely has an attenuation value of 10 sound rating. If flexible duct is
dB per octave band. Therefore, the standard used, sharp bends should be
attenuation value is to be used only for prevented at the neck of the air
comparison purposes and the ARI standard outlet.
should be consulted for accurately 5. As a general rule of thumb, the
determing actual space attenuation. Please face velocity of an air outlet should
note that ASHRAE Standard 70 does not not exceed 800 fpm and the face
require the conversion of sound power levels velocity of an air inlet should not
to NC. This is done strictly to give the end exceed 400 fpm.
user a single number sound rating for a
particular device at a given operating
condition.
References
ASHRAE. 1997. Handbook
Fundamentals, Chapter 31. Atlanta:
American Society of Heating,
Refridgerating, and Air-Conditioning
Engineers, Inc.
Ebbing, C.E. and W.E. Blazier. 1998.
Application of Manufacturers' Sound
Data. Atlanta: American Society of
Heating, Refridgerating, and Air-
Conditioning Engineers, Inc.
7/8
8/8