PANDUAN INSTALLASI

DDW COMPACT AIR HANDLING UNIT

Horizontal unit
Model: DDW020C ~ DDW450C
Airflow rate: 2000m3/h ~ 45000m3/h

Vertical unit
Model: DDW040C ~ DDW450C
Airflow rate: 4000m3/h ~ 45000m3/h
Sebelum menggunakan Air handling unit anda, bacalah buku panduan ini dengan
seksama dan simpan untuk referensi di masa yang akan datang.

Daftar isi

1. TINDAKAN PENCEGAHAN KESELAMATAN ······································································· hal. 2


2. PENGENALAN SINGKAT·········································································································· hal. 3
3. KONSTRUKSI SIPIL ··················································································································· hal. 5
4. INSTALASI ·································································································································· hal. 6
5. PARAMETER TABEL DDW - C AHU ································ ···························································· hal. 8
6. OPERASIONAL ·························································································································· hal.19
7 PEMELIHARAAN DAN PERBAIKAN ································ ···························································· hal.19
8. PEMECAHAN MASALAH ········································································································ hal.21
9. GARANSI SERVIS-SETELAH PENJUALAN ·········································································· hal.23

TINDAKAN PENCEGAHAN KESELAMATAN


Sebelum menginstal air handling unit, bacalah dan ikuti petunjuk pencegahan keselamatan
dengan seksama.

Peringatan
 Pemasangan dan pemeliharaan harus dilakukan oleh orang yang ahli, mengerti dengan peraturan dan
nn
kode lokal, dan berpengalaman dengan jenis alat ini.
 Semua pemasangan kabel di lapangan harus mengikuti regulasi yang ada.
 Pastikan nilai voltase di unit sesuai dengan yang ada di plat nama sebelum memulai pemasangan kabel
sesuai diagram pengkabelan.
 Unit harus di pasangkan ke “ground” untuk mencegah kemungkinan bahaya karena kegagalan insulasi.
 Pastikan unit dalam keadaan mati ketika sedang memasang atau memperbaiki unit.

Daikin adalah merek dagang terdaftar dari Daikin Group. Semua hak cipta dilindungi di seluruh dunia.
© 2016 Daikin

Ilustrasi buletin merupakan tampilan umum produk Daikin pada saat publikasi dan kami melindungi hak
cipta untuk perubahan & pembuatan desain setiap saat tanpa pemberitahuan.

2
Pengenalan Singkat
Panduan ini telah disiapkan sebagai petunjuk pemasangan dan pemeliharaan Daikin
air-handling unit. Daikin memproduksi produk yang berkualitas yang efektif memenuhi
kebutuhan anda. Walaupun demikian, prosedur pemasangan dan pemeliharaan yang benar harus
diikuti untuk menghasilkan kapasitas dan lifetime unit yang maksimal.

Tata Nama:
DDW 450 C E A E L A A-- 0 A F E

Kode Model (1) (14) Kode penjualan export


Kode Air flow (2) (13) Opsi power supply
Nama series (3) (12) Tipe Mixing section+Supply section
Tipe Struktur (4) (11) Tipe control
Tipe Coil (5) (10) Tipe Fan Motor
External total pressure (6) (9) Tipe Filter
Pipa Koneksi (7) (8) Material Drain Pan

Penjelasan:
(1) Kode Model: DDW Air Handling Unit.
(2) Kode airflow rate 450 artinya 45,000 m³/ h (airflow rate = kode airflow rate * 100 m³/ h).
(3) Desain serial Number: C Series
(4) Tipe Struktur + penggunaan fitur:
A: 25mm panel horizontal fresh air;
B: 25mm panel horizontal return air;
C: 25mm panel vertical fresh air;
D: 25mm panel vertical return air;
E: 50mm panel horizontal fresh air;
F: 50mm panel horizontal return air;
(5) Koil pendingin:
A: 2C B: 3C
C: 4C D: 5C
E: 6C
Notes: NomorCoil Rows, C Cooling coil,
(6) ETP
B C D E F G H J K
100 125 150 175 200 225 250 275 300
L M N P Q R S T
350 400 450 500 550 600 650 700
Dimana:
Standar ETP untuk model unit DDW020-070 adalah 150, 225, 300 Pa,
Standar ETP untuk model unit DDW080-150 adalah 225, 300, 400 Pa,
Standar ETP untuk model unit DDW180-250 adalah 300, 400, 500 Pa,
Standar ETP untuk model unit DDW270-450 adalah 400, 500 Pa,
(7) Pipa Koneksi: L koneksi koil kiri, R koneksi koil kanan.
(8) Material drain pan + material alumunium foil + pilihan wet film:
A- Galvanized steel plate + normal alumunium,
B- Galvanized steel plate + hydrophilic alumunium,
C- Stainless steel plate + normal alumunium,

3
D- Stainless steel plate + hydrophilic alumunium,
E- Galvanized steel plate + normal alumunium + 50mm wet film humidifier,
F- Galvanized steel plate + hydrophilic alumunium + 50mm wet film humidifier,
G- Stainless steel plate + normal alumunium + 50mm wet film humidifier.
H- Galvanized steel plate + hydrophilic alumunium + 50mm wet film humidifier,
J- Galvanized steel plate + normal alumunium + 100mm wet film humidifier,
K- Galvanized steel plate + hydrophilic alumunium + 100mm wet film humidifier,
L- Stainless steel plate + normal alumunium + 100mm wet film humidifier.
M- Stainless steel plate + hydrophilic alumunium + 100mm wet film humidifier.
(9) Tipe Filter (Nylon mesh, G3/ G4 plate filter, F5/F6/F7 bag filter);
A- Nylon mesh
B- G3
C- G4
D- G3+F5
E- G3+F6
F- G3+F7
G- G4+F5
H- G4+F6
J- G4+F7
K- G4+electronic purifying filter
L- None
(10) Tipe Fan Motor
(11) - --- Frekuensi motor konstan
V--- Inverter motor
(12) 0. No control
1. Local starting cabinet
2. Remote starting cabinet
3. Local control cabinet
4. Remote control cabinet
5. Inverter starting cabinet
6. Inverter control cabinet
(13) Tipe dari Mixing section + supply fan section:
A- Tanpa mixing section + flange horizontal air discharge
B- Tanpa mixing section + flange top air discharge
C- Mixing section (top + front flange) + flange horizontal air discharge
D- Mixing section (top + front flange) + flange top air discharge
E- Mixing section (top + front damper) + flange horizontal air discharge
F- Mixing section (top + front damper) + flange top air discharge
(14) Opsi Power supply: F 380v/3N-/50Hz
(15) Kode penjualan export.

4
 Untuk melihat koneksi unit kiri atau kanan orientasinya: anda harus melihat dari airflow direction jika pipa
koil berada di sebelah kiri, maka unit koneksinya adalah kiri, dan sebaliknya untuk orientasi kanan.

Diagram untuk menentukan orientasi kiri atau kanan

Tindakan Pencegahan Keselamatan


a) Personil konstruksi harus terdidik untuk pengetahuan tentang tiga tingkat keselamatan,
memakai helem pengaman di proyek, memakai sabuk pengaman di ketinggian 2 m atau lebih,
memakai sepatu pelindung.
b) Hati-hati ketika menggunakan peralatan listrik, hanya teknisi yang boleh menyambung dan
melepas kabel atau menggunakan panel listrik.
c) Operator Coating harus memakai perlengkapan pakaian pelindung dan memastikan ventilasi
di proyek. Api terbuka dilarang berada di area konstruksi.
d) Konstruksi sipil diperlukan. Jangan membuang material bekas konstruksi sembarangan.

Konstruksi Sipil
a) Material yang sudah selesai di proyek ditumpuk pada posisi khusus dan lindungi material dari
kelembaban, hujan dan salju jika di tumpuk di tempat terbuka.
b) Selama beroperasi serentak di ruangan yang sama, semua pekerja kontruksi harus saling
menghormati, bekerja dengan baik dan koperatif.
c) Lindungi produk yang sudah selesai dengan benar setelah masing-masing sub item konstruksi
selesai, sehingga mengurangi kerugian yang tidak perlu.
d) Jangan mengubah posisi fasilitas instalasi pemadam kebakaran selama beroperasi. Semua
peralatan pemadam kebakaran dan pipa-pipa harus dilindungi dengan benar.
e) Bangun sistem konstruksi sipil yang baik dan berikan wilayah untuk sanitasi dengan orang
khusus yang bertanggung jawab.
f) Bersihkan limbah konstruksi tepat waktu.
g) Pimpinan tim konstruksi bertanggung jawab untuk konstruksi sipil di area kerja. Personil
kontruksi harus melakukan pembersihan untuk memastikan proyek konstruksi rapi setelah
bangunan selesai.

5
Instalasi
Catatan:
a) Sambungan kabel harus benar mengikuti regulasi dan peraturan industri.
b) Suplai Listrik : Toleransi voltase ±10%.
c) Grounding dan insulasi yang baik adalah suatu keharusan
d) Periksa apakah sambungan kabel di pasang dengan kuat atau tidak
e) Desain untuk sistem pendingin air dan sistem suplai udara sesuai dengan standar industri

 Posisi Unit
Jarak ruang kosong ke dinding untuk memasang kabel dan pemeliharaan unit harus cukup
seperti di tunjukan gambar 1 dan 2 ( satuan dalam mm )

500
500
500

00
10
500
10
00

Gambar 1 Gambar 2

 Pengangkatan dan Transportasi


a) Untuk menghindari kerusakan komponen, unit saat di gantung pada posisi horizontal. Unit dan
paking di produksi di pabrik dengan di beri lubang. Ketika unit di angkat, lubang yang di
gunakan untuk mengangkat unit akan menahan berat unit. Lihat gambar no. 3 untuk
pengangkatan unit.

3
2

Gambar 3

6
b) Ketika unit di gantung di langit-langit, Struktur bangunan harus cukup kuat menahan beban
unit yang di gantung. Pastikan unit adalah horizontal dan aman sebelum unit di jalankan.
Berat unit ketika di jalankan adalah 120 % dari berat bersih unit.
c) Ketika unit di pasang di lantai, pastikan lantai cukup kuat dan posisi unit horizontal. Ketinggian
lantai memungkinkan untuk di pasang sistem U trap, Unit harus di kencangkan dengan baut.

 Penyimpanan Unit
Jika unit di taruh di luar, pastikan unit tidak akan rusak terkena kotoran, hujan, salju dan
binatang-binatang. Plastik pembungkus unit harus sempurna.

 Pengaturan dudukan
1. Pastikan bahwa unit adalah horizontal.
Jika lantai tidak rata, akan menyebabkan kebocoran air dan bisa mengganggu keseimbangan
dinamis unit atau kerusakan bearing dan getaran.
2. Bentuk U pada pipa air kondensasi di perlukan,lihat gambar no.4

DRAIN PIPE

H tidak lebih dari tekanan negatif dari unit + 20mm,1mmH2O=9.8Pa


Gambar 4

 Koneksi Kabel
Koneksi kabel harus sesuai dengan regulasi dan peraturan setempat, di samping itu perlu di
perhatikan:
a) Sebelum menyambung kabel, cek suplai listrik apakah sesuai permintaan.
b) Setiap unit harus di suplai dengan sumber listrik yang dipisah dengan pengaman arus sendiri.
c) Lebih jelasnya seperti di tunjukan gambar no.5.

MOTOR POWER≤3kW 3kW<MOTOR POWER<11kW MOTOR POWER≥11kW

Gambar 5

7
T abel parameter DDW Horizontal AHU
Unit model
DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW
020C 030C 040C 050C 060C 070C 080C 100C 120C 150C 180C 200C 220C 250C 270C 300C 330C 360C 400C 450C
Nominal airflow rate (m3/h) 2000 3000 4000 5000 6000 7000 8000 10000 12000 15000 18000 20000 22000 25000 27000 30000 33000 36000 40000 45000

Ⅰ 150 150 150 150 150 150 225 225 225 225 300 300 300 300 400 400 400 400 400 400

ETP(Pa) Ⅱ 225 225 225 225 225 225 300 300 300 300 400 400 400 400 500 500 500 500 500 500

Ⅲ 300 300 300 300 300 300 400 400 400 400 500 500 500 500 - - - - - -
4-row
11.6 18.1 23.4 29.2 34.8 44.0 49.0 60.7 71.8 92.9 106.6 121.5 137.1 155.2 165.1 189.7 207.8 226.8 237.7 265.5
(return air condition)
4-row
Nominal cooling 28.0 40.4 52.3 70.8 85.4 90.0 106.0 136.6 164.0 208.3 245.0 269.6 299.7 341.8 361.5 419.8 460.5 488.8 519.2 576.2
(fresh air condition)
capacity
6-row
(kW) 15.6 21.7 30.0 39.8 45.1 53.4 60.6 78.0 93.6 115.7 140.5 159.6 177.4 203.8 207.5 236.4 259.8 280.1 296.3 329.5
(return air condition)
6-row
34.5 53.6 65.6 87.8 104.6 120.9 136.5 169.9 201.6 257.6 309.2 345.3 383.8 438.5 463.3 520.6 566.3 607.6 631.4 702.5
(fresh air condition)
4-row
21.7 33.9 42.6 56.6 66.0 80.2 94.2 123.3 147.9 188.8 221.9 246.6 274.1 308.1 332.8 377.9 411.2 443.8 498.4 554.7
(return air condition)
4-row
Nominal heating 26.1 39.2 50.1 68.8 80.6 91.8 106.1 145.2 174.2 222.6 267.0 296.6 329.7 368.8 383.6 435.5 473.9 517.1 580.7 646.4
(fresh air condition)
capacity
6-row
(kW) 25.0 38.5 48.9 66.5 76.4 90.4 106.2 145.2 173.4 218.7 262.4 291.6 322.1 362.8 386.5 437.4 476.8 517.9 580.5 650.2
(return air condition)
6-row
29.8 46.3 56.7 77.8 92.2 113.7 131.1 168.7 202.4 257.5 309.1 343.4 379.6 429.3 463.7 522.2 569.3 618.2 693.2 772.8
(fresh air condition)
4-row
0.55 0.86 1.11 1.39 1.66 2.09 2.33 2.89 3.42 4.42 5.07 5.78 6.53 7.39 7.86 9.03 9.90 10.80 11.32 12.64
(return air condition)
4-row
1.33 1.92 2.49 3.37 4.06 4.29 5.05 6.51 7.81 9.92 11.67 12.84 14.27 16.28 17.21 19.99 21.93 23.28 24.72 27.44
Nominal cooling (fresh air condition)
water flow (I/s) 6-row
0.74 1.03 1.43 1.89 2.15 2.54 2.89 3.71 4.46 5.51 6.69 7.60 8.45 9.70 9.88 11.26 12.37 13.34 14.11 15.69
(return air condition)
6-row
1.64 2.55 3.12 4.18 4.98 5.76 6.50 8.09 9.60 12.27 14.72 16.44 18.28 20.88 22.06 24.79 26.97 28.93 30.07 33.45
(fresh air condition)
4-row
Cooling coil 0.52 0.81 1.01 1.35 1.57 1.91 2.24 2.94 3.52 4.50 5.28 5.87 6.53 7.34 7.92 9.00 9.79 10.57 11.87 13.21
(return air condition)
4-row
0.62 0.93 1.19 1.64 1.92 2.19 2.53 3.46 4.15 5.30 6.36 7.06 7.85 8.78 9.13 10.37 11.28 12.31 13.83 15.39
Nominal heating (fresh air condition)
water flow (I/s) 6-row
0.60 0.92 1.16 1.58 1.82 2.15 2.53 3.46 4.13 5.21 6.25 6.94 7.67 8.64 9.20 10.41 11.35 12.33 13.82 15.48
(return air condition)
6-row
0.71 1.10 1.35 1.85 2.20 2.71 3.12 4.02 4.82 6.13 7.36 8.18 9.04 10.22 11.04 12.43 13.55 14.72 16.50 18.40
(fresh air condition)
4-row
18.9 42.5 39.7 13.4 12.7 19.3 29.0 42.7 36.3 50.2 21.7 28.6 32.7 30.9 35.6 46.9 50.1 54.3 61.5 66.3
(return air condition)
4-row
44.4 35.4 29.9 58.1 63.4 15.6 22.8 57.9 52.4 61.8 67.4 71.7 75.3 70.2 37.7 48.9 55.6 60.9 75.6 87.7
Nominal cooling (fresh air condition)
wate WPD (kPa) 6-row
49.9 14.0 30.8 52.6 27.8 39.7 54.8 59.2 62.0 35.9 49.1 64.6 71.8 70.6 29.0 37.6 40.8 43.8 51.6 56.9
(return air condition)
6-row
30.2 67.0 24.6 34.3 50.2 61.4 82.8 39.0 37.1 52.1 68.2 72.5 76.2 79.4 81.7 90.5 92.3 94.3 103.5 109.3
(fresh air condition)
Type Copper pipe embedded with new corrugated aluminum fin

FPI 12

Working pressure (MPa) 1.6


R2 R2 R2-1/2
Water pipe diameter R1-1/2 R1-1/2 R2 R2 R2 R2-1/2 R2-1/2 R3 R3 R3 R3 R3 R3 R3 R3 R3 R3
(R2-1/2) (R2-1/2) (R3)
Drainage pipe diameter R1-1/4

Model/ Material Efficient centrifugal forerake multi-blade fan/galvanized steel plate

Fan Drive mode V-belt drive

Air discharge direction Horizontal air discharge or Top air discharge

Power supply 380V/3N~/50Hz

Type 3-phase asynchronous motor with insulation level F and protection level IP55
0.55 1.1 15
Motor 0.55 0.75 1.1 1.5 2.2 2.2 3 4 5.5 5.5 5.5 7.5 11 11 11 15 15
(0.75) (1.5) (18.5)
0.75 1.1 7.5
Power (kW) 0.55 0.75 1.5 1.5 2.2 3 3 4 5.5 7.5 7.5 11 15 15 15 15 18.5
(1.1) (1.5) (11)
1.5 7.5
0.55 0.75 1.1 1.5 1.5 3 3 4 5.5 7.5 7.5 11 - - - - - -
(2.2) (11)
Type Nylon filter
Filter
Thickness (mm) 8 21
Double layer panel with thickness of 25mm/50mm, outer plate as color plate.and inner plate as aluminum zinc plate, filled with thermal insulation polyurethane high-
Cabinet Type
pressure foaming material.
Length (mm) 955 955 955 1075 1075 1125 1125 1255 1275 1145 1275 1275 1275 1275 1275 1315 1555 1555 1625 1625
Dimension of
25mm panel Width (mm) 900 1050 1080 1250 1320 1500 1680 1690 1690 1920 2100 2280 2400 2400 2470 2760 2760 2760 2920 2920
cabinet(mm)*
Height (mm) 520 520 680 680 730 750 750 880 990 1120 1180 1180 1250 1370 1370 1440 1500 1560 1690 1820

Length (mm) 1005 1005 1025 1125 1125 1185 1185 1315 1315 1195 1315 1315 1315 1315 1315 1365 1605 1605 1675 1675
Dimension of
50mm panel Width (mm) 950 1100 1130 1300 1370 1550 1730 1740 1740 1970 2150 2330 2450 2450 2520 2810 2810 2810 2970 2970
cabinet(mm)*
Height (mm) 570 570 730 730 780 800 800 930 1040 1170 1230 1230 1300 1420 1420 1490 1550 1610 1740 1870

4-row 126 137 156 181 194 232 251 304 339 414 497 515 560 626 628 707 789 804 897 959
Unit weight of
25mm panel(kg)
6-row 130 142 163 189 203 244 266 320 358 443 529 550 645 666 670 757 841 859 959 1026

4-row 146 158 179 206 220 261 282 343 379 450 544 565 618 686 688 773 860 876 974 1039
Unit weight of
50mm panel(kg)
6-row 150 163 186 214 229 273 297 359 398 479 576 600 703 726 730 823 912 931 1036 1106

8
Nomenklatur untuk unit standar
DDW 450 C E C D L A A - 0 A F
A:25mm panel horizontal fresh air B:25mm panel horizontal return air
C:25mm panel vertical fresh air D:25mm panel vertical return air A:No mixing section + flange horizontal air discharge
E:50mm panel horizontal fresh air F:50mm panel horizontal return air B:No mixing section + flange top air discharge
Notes: The vertical unit with top air discharge is the standard unit
Coil rows: C (4 rows), E (6 rows)
L:Connected from left
ETP: D (150), G (225), K (300), M (400), P (500) R:Connected from right

Tabel Parameter DDW Vertical AHU


DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW DDW
Unit model
040C 050C 060C 070C 080C 100C 120C 150C 180C 200C 220C 250C 270C 300C 330C 360C 400C 450C
3
Nominal airflow rate (m /h) 4000 5000 6000 7000 8000 10000 12000 15000 18000 20000 22000 25000 27000 30000 33000 36000 40000 45000
Ⅰ 150 150 150 150 225 225 225 225 300 300 300 300 400 400 400 400 400 400
ETP(Pa) Ⅱ 225 225 225 225 300 300 300 300 400 400 400 400 500 500 500 500 500 500
Ⅲ 300 300 300 300 400 400 400 400 500 500 500 500 - - - - - -
4-row
23.4 29.2 34.8 44.0 49.0 60.7 71.8 92.9 106.6 121.5 137.1 155.2 165.1 189.7 207.8 226.8 237.7 265.5
(return air condition)
4-row
Nominal cooling 52.3 70.8 85.4 90.0 106.0 136.6 164.0 208.3 245.0 269.6 299.7 341.8 361.5 419.8 460.5 488.8 519.2 576.2
(fresh air condition)
capacity
6-row
(kW) 30.0 39.8 45.1 53.4 60.6 78.0 93.6 115.7 140.5 159.6 177.4 203.8 207.5 236.4 259.8 280.1 296.3 329.5
(return air condition)
6-row
65.6 87.8 104.6 120.9 136.5 169.9 201.6 257.6 309.2 345.3 383.8 438.5 463.3 520.6 566.3 607.6 631.4 702.5
(fresh air condition)
4-row
42.6 56.6 66.0 80.2 94.2 123.3 147.9 188.8 221.9 246.6 274.1 308.1 332.8 377.9 411.2 443.8 498.4 554.7
(return air condition)
4-row
Nominal heating 50.1 68.8 80.6 91.8 106.1 145.2 174.2 222.6 267.0 296.6 329.7 368.8 383.6 435.5 473.9 517.1 580.7 646.4
(fresh air condition)
capacity
6-row
(kW) 48.9 66.5 76.4 90.4 106.2 145.2 173.4 218.7 262.4 291.6 322.1 362.8 386.5 437.4 476.8 517.9 580.5 650.2
(return air condition)
6-row
56.7 77.8 92.2 113.7 131.1 168.7 202.4 257.5 309.1 343.4 379.6 429.3 463.7 522.2 569.3 618.2 693.2 772.8
(fresh air condition)
4-row
1.11 1.39 1.66 2.09 2.33 2.89 3.42 4.42 5.07 5.78 6.53 7.39 7.86 9.03 9.90 10.80 11.32 12.64
(return air condition)
4-row
Nominal cooling (fresh air condition) 2.49 3.37 4.06 4.29 5.05 6.51 7.81 9.92 11.67 12.84 14.27 16.28 17.21 19.99 21.93 23.28 24.72 27.44
water flow (l/s) 6-row
1.43 1.89 2.15 2.54 2.89 3.71 4.46 5.51 6.69 7.60 8.45 9.70 9.88 11.26 12.37 13.34 14.11 15.69
(return air condition)
6-row
3.12 4.18 4.98 5.76 6.50 8.09 9.60 12.27 14.72 16.44 18.28 20.88 22.06 24.79 26.97 28.93 30.07 33.45
(fresh air condition)
Cooling coil 4-row
1.01 1.35 1.57 1.91 2.24 2.94 3.52 4.50 5.28 5.87 6.53 7.34 7.92 9.00 9.79 10.57 11.87 13.21
(return air condition)
4-row
Nominal heating (fresh air condition) 1.19 1.64 1.92 2.19 2.53 3.46 4.15 5.30 6.36 7.06 7.85 8.78 9.13 10.37 11.28 12.31 13.83 15.39
water flow (l/s) 6-row
1.16 1.58 1.82 2.15 2.53 3.46 4.13 5.21 6.25 6.94 7.67 8.64 9.20 10.41 11.35 12.33 13.82 15.48
(return air condition)
6-row
1.35 1.85 2.20 2.71 3.12 4.02 4.82 6.13 7.36 8.18 9.04 10.22 11.04 12.43 13.55 14.72 16.50 18.40
(fresh air condition)
4-row
39.7 13.4 12.7 19.3 29.0 42.7 36.3 50.2 21.7 28.6 32.7 30.9 35.6 46.9 50.1 54.3 61.5 66.3
(return air condition)
4-row
Nominal cooling (fresh air condition) 29.9 58.1 63.4 15.6 22.8 57.9 52.4 61.8 67.4 71.7 75.3 70.2 37.7 48.9 55.6 60.9 75.6 87.7
water WPD (kPa) 6-row
30.8 52.6 27.8 39.7 54.8 59.2 62.0 35.9 49.1 64.6 71.8 70.6 29.0 37.6 40.8 43.8 51.6 56.9
(return air condition)
6-row
24.6 34.3 50.2 61.4 82.8 39.0 37.1 52.1 68.2 72.5 76.2 79.4 81.7 90.5 92.3 94.3 103.5 109.3
(fresh air condition)
Type Copper pipe embedded with new corrugated aluminum fin
FPI 12
Working pressure (MPa) 1.6
R2 R2 R2-
Water pipe diameter R2 R2 R2 R2-1/2 R2-1/2 R3 R3 R3 R3 R3 R3 R3 R3 R3 R3
(R2-1/2) (R2-1/2) 1/2(R3)
Drainage pipe diameter R1-1/4
Model/ Material Efficient centrifugal forerake multi-blade fan/galvanized steel plate
Fan Drive mode V-belt drive
Air discharge direction Top air discharge
Power supply 380V/3N~/50Hz
Type 3-phase asynchronous motor with insulation level F and protection level IP55
1.1 15
0.75 1.1 1.5 2.2 2.2 3 4 5.5 5.5 5.5 7.5 11 11 11 15 15
Motor (1.5) (18.5)
0.75 1.1 7.5
Power (kW) 1.5 1.5 2.2 3 3 4 5.5 7.5 7.5 11 15 15 15 15 18.5
(1.1) (1.5) (11)
1.5 7.5
1.1 1.5 1.5 3 3 4 5.5 7.5 7.5 11 - - - - - -
(2.2) (11)
Type Nylon filter
Filter
Thickness (mm) 8 21
Double layer panel with thickness of 25mm, outer plate as color plate and inner plate as aluminum zinc plate,filled with thermal insulation polyurethane high-pressure
Cabinet Type
foaming material.
Length (mm) 650 650 650 750 750 900 900 900 900 900 900 900 900 900 1100 1100 1170 1170
Dimension of
25mm panel Width (mm) 1080 1250 1320 1500 1680 1690 1690 1920 2100 2280 2400 2400 2470 2760 2760 2760 2920 2920
cabinet(mm)*
Height (mm) 1170 1240 1290 1370 1370 1620 1750 1760 1940 1940 2010 2130 2130 2200 2340 2400 2610 2685
Unit weight of 4-row 174 199 211 287 317 379 429 489 568 592 638 706 709 803 892 908 1013 1074
25mm panel(kg) 6-row 181 207 220 305 332 395 448 518 600 627 723 746 751 853 944 963 1075 1141

9
Dimensi DDW horizontal unit (25mm panel)
Horizontal air discharge
J 24.5

24
LQ
T
N
F D
B Hoisting hole4-̋31
M
M+60

Air vent
40
Chilled water outlet pipe
H

K
C
E
Chilled water inlet pipe

G
I

Condensate water drainage pipe A 50


53.3

50
Top air discharge J 24.5
24
LQ
T
N

B Hoisting hole4-̋31
M
M+60

Air vent G
F D E
Chilled water outlet pipe
40
H

K
C

Chilled water inlet pipe


I

Condensate water drainage pipe A 50


53.3

50

Unit: mm
Return air inlet Hoisting hole
Ukuran unit ukuran kabinet ukuran suplai udara keluar ukuran pipa
size size
G G H H I I Q Q L L
Unit model A B C D E F (Horizontal air-out) (Top air-out)
T J K M N
(4R) (6R) (4R) (6R) (4R) (6R) (4R) (6R)
DDW020C 955 900 520 232 262 178 362 430 294 294 123 123 135 141 66 110 355 853 445 1020 904
DDW030C 955 1050 520 298 262 218 362 430 294 294 123 123 135 141 66 110 355 1003 445 1170 904
DDW040C 955 1080 680 331 289 209 423 507 434 434 129 129 135 141 66 110 355 1033 605 1200 904
DDW050C 1075 1250 680 309 341 289 441 582 434 434 129 129 135 141 66 110 405 1203 605 1370 1024
DDW060C 1075 1320 730 395 341 288 474 568 485 485 129 129 135 141 66 110 405 1273 655 1440 1024
DDW070C 1125 1500 750 373 404 363 504 678 485 469 129 137 135 141 66 110 405 1453 675 1620 1074
DDW080C 1125 1680 750 373 404 543 504 678 485 469 129 137 135 141 66 110 405 1633 675 1800 1074
DDW100C 1255 1690 880 430 478 442 577 810 609 609 137 137 154 141 110 138 405 1643 805 1810 1204
DDW120C 1275 1690 990 557 478 392 650 803 736 736 137 137 154 141 110 138 405 1643 915 1810 1224

10
Dimensi DDW horizontal unit (25mm panel)
Horizontal air discharge J 24.5

24
LQ
T
N
F S D S
B Hoisting hole4-̋31
M
M+60

Air vent 40
Chilled water
outlet pipe
H

K
C
Chilled water

E
G
inlet pipe
I

Condensate water
A W
53.3

63
drainage pipe

Top air discharge J 24.5


24
LQ
T
N

B
M Hoisting hole4-̋31
M+60

G
F S D S Air vent
E
Chilled water
outlet pipe
40
H

K
C

Chilled water
inlet pipe
I

Condensate water
A W
53.3

63

drainage pipe

Unit: mm
Hoisting hole
Ukuran unit ukuran kabinet ukuran suplai udara keluar ukuran pipa Return air inlet size
size
G G H H I I Q Q L L
Unit model A B C D S E F T J K W M N
(Horizontal air-out) (Top air-out) (4R) (6R) (4R) (6R) (4R) (6R) (4R) (6R)
DDW150C 1145 1920 1120 294 373 404 204 572 675 863 850 137 143 154 141 110 138 405 1873 1045 50 2040 1094
DDW180C 1275 2100 1180 343 430 478 172 650 796 913 913 143 143 154 141 110 138 405 2053 1105 50 2220 1224
DDW200C 1275 2280 1180 343 430 478 252 650 806 913 913 143 143 154 141 110 138 405 2233 1105 50 2400 1224
DDW220C 1275 2400 1250 458 557 478 114 650 806 977 977 143 143 154 141 110 138 405 2353 1175 50 2520 1224
DDW250C 1275 2400 1370 458 557 478 114 650 806 1104 1104 143 143 154 141 110 138 405 2353 1295 50 2520 1224

11
Dimensi DDW horizontal unit (25mm panel)
Horizontal air discharge J 24.5

LQ
T
F S D S
B

Air vent 40
Chilled water
outlet pipe
H

C
E
Chilled water

G
inlet pipe
I

Condensate water
A W
53.3

63
drainage pipe

Top air discharge J 24.5


LQ
T

G
F S D S Air vent
E
Chilled water
outlet pipe
40
H

Chilled water
inlet pipe
I

Condensate water
A W
53.3

63

drainage pipe

Unit: mm

Ukuran unit Ukuran kabinet ukuran suplai udara keluar Ukuran pipa Return air inlet size

G G H H I I Q Q L L
Unit model A B C D S E F (Horizontal air-out) (Top air-out) (4R)
T J K W
(6R) (4R) (6R) (4R) (6R) (4R) (6R)
DDW270C 1275 2470 1370 458 557 478 122 650 806 1104 1104 143 143 154 141 110 138 405 2423 1295 50
DDW300C 1315 2760 1440 458 557 478 267 650 794 1167 1167 143 143 154 141 110 138 455 2713 1365 90
DDW330C 1555 2760 1500 450 569 569 290 749 887 1231 1231 143 143 154 141 110 138 455 2713 1425 90
DDW360C 1555 2760 1560 450 569 569 290 749 887 1294 1294 143 143 154 141 110 138 455 2713 1485 90
DDW400C 1625 2920 1690 500 638 638 261 818 981 1421 1421 143 143 154 141 110 138 455 2873 1615 90
DDW450C 1625 2920 1820 500 638 638 261 818 981 1548 1548 143 143 154 141 110 138 455 2873 1745 90

12
Dimensi DDW horizontal unit (50mm panel)
Horizontal air discharge

25
LQ
T
N
F D Hoisting hole4-̋31
B
M
M+60

Air vent
40
Chilled water
outlet pipe
H

C
K
E
Chilled water

G
inlet pipe
I

Condensate water
A 50
78.3

50
drainage pipe

Top air discharge


J 24.5
25
LQ
T
N

B Hoisting hole4-̋31
M
M+60

Air vent G
F D E
Chilled water
outlet pipe
H

C
K

Chilled water
inlet pipe
I

Condensate water
A 50
78.3

50

drainage pipe

Unit: mm

Return air inlet Hoisting hole


ukuran unit ukuran kabinet ukuran suplai udara keluar Ukuran pipa
size size
G G H H I I Q Q L L
Unit model A B C D E F (Horizontal air-out) (Top air-out)
T J K M N
(4R) (6R) (4R) (6R) (4R) (6R) (4R) (6R)
DDW020C 1005 950 570 232 262 203 387 466 294 294 148 148 155 161 66 110 370 903 508 1070 950
DDW030C 1005 1100 570 298 262 243 388 467 294 294 148 148 155 161 66 110 370 1053 508 1220 950
DDW040C 1025 1130 730 331 289 234 448 538 434 434 154 154 155 161 66 110 370 1083 668 1250 970
DDW050C 1125 1300 730 309 341 314 466 617 434 434 154 154 155 161 66 110 420 1253 668 1420 1070
DDW060C 1125 1370 780 395 341 313 499 611 485 485 154 154 155 161 66 110 420 1323 718 1490 1070
DDW070C 1185 1550 800 373 404 388 529 723 485 469 154 162 155 161 66 110 420 1503 738 1670 1130
DDW080C 1185 1730 800 373 404 568 529 723 485 469 154 162 155 161 66 110 420 1683 738 1850 1130
DDW100C 1315 1740 930 430 478 467 602 855 609 609 162 162 174 161 110 138 420 1693 868 1860 1260
DDW120C 1315 1740 1040 557 478 417 675 828 736 736 162 162 174 161 110 138 420 1693 978 1860 1260

13
Dimensi DDW horizontal unit (50mm panel)
Horizontal air discharge J 24.5

25
LQ
T
N
F S D S
Hoisting hole4-̋31
B
M
M+60

Air vent 40
Chilled water
outlet pipe
H

C
K
Chilled water
inlet pipe

E
G
Condensate water
drainage pipe
I
78.3

A W

63
Top air discharge J 24.5
25
LQ
T
N

B Hoisting hole4-̋31
M
M+60

F S D S G
Air vent E
Chilled water
outlet pipe
H

C
K

Chilled water
inlet pipe
Condensate water
drainage pipe
I
78.3

A W
63

Unit: mm

Ukuran unit ukuran kabinet ukuran suplai udara keluar Ukuran Pipa ukuran masukan udara return

G G H H I I Q Q L L
Unit model A B C D S E F (Horizontal air-out) (Top air-out) (4R)
T J K W
(6R) (4R) (6R) (4R) (6R) (4R) (6R)
DDW150C 1195 1970 1170 294 373 404 229 597 701 863 850 162 168 174 161 110 138 420 1923 1108 50
DDW180C 1315 2150 1230 343 430 478 197 675 826 913 913 168 168 174 161 110 138 420 2103 1168 50
DDW200C 1315 2330 1230 343 430 478 277 675 832 913 913 168 168 174 161 110 138 420 2283 1168 50
DDW220C 1315 2450 1300 458 557 478 139 675 828 977 977 168 168 174 161 110 138 420 2403 1238 50
DDW250C 1315 2450 1420 458 557 478 139 675 830 1104 1104 168 168 174 161 110 138 420 2403 1358 50

14
Dimensi DDW vertical unit (25mm panel)
Horizontal air discharge
J 24.5

LQ
T
F S D S
B

Air vent 40
Chilled water
outlet pipe

C
K
E
Chilled water

G
inlet pipe
I

Condensate water
78.3

A W

63
drainage pipe

Top air discharge


J 24.5
LQ
T

F S D S G
Air vent
E
Chilled water
outlet pipe
H

C
K

Chilled water
inlet pipe
I

Condensate water
78.3

A W
63

drainage pipe
Unit: mm

Ukuran unit Ukuran kabinet Ukuran suplai udara keluar Ukuran pipa Return air inlet size

G G H H I I Q Q L L
Unit model A B C D S E F (Horizontal air-out) (Top air-out) (4R)
T J K W
(6R) (4R) (6R) (4R) (6R) (4R) (6R)
DDW270C 1315 2520 1420 458 557 478 147 675 830 1104 1104 168 168 174 161 110 138 420 2473 1358 50
DDW300C 1365 2810 1490 458 557 478 292 675 819 1167 1167 168 168 174 161 110 138 470 2763 1428 90
DDW330C 1605 2810 1550 450 569 569 315 774 916 1231 1231 168 168 174 161 110 138 470 2763 1488 90
DDW360C 1605 2810 1610 450 569 569 315 774 916 1294 1294 168 168 174 161 110 138 470 2763 1548 90
DDW400C 1675 2970 1740 500 638 638 286 843 1007 1421 1421 168 168 174 161 110 138 470 2923 1678 90
DDW450C 1675 2970 1870 500 638 638 286 843 1007 1548 1548 168 168 174 161 110 138 470 2923 1808 90

15
Dimensi DDW vertical unit (25mm panel)

J 24.5

L Q

40 G

F D E

Air vent

Chilled water outlet pipe


C
H

Chilled water inlet pipe


I

Condensate water drainage pipe


A 50
53.3

63

Unit: mm

Return air inlet


Ukuran unit Ukuran kabinet Ukuran suplai udara keluar Ukuran pipa
size
H H I I Q Q L L
Unit model A B C D E F G T J K
(4R) (6R) (4R) (6R) (4R) (6R) (4R) (6R)
DDW040C 650 1080 1170 331 289 208 403 434 434 129 129 173 179 66 110 393 1033 605
DDW050C 650 1250 1240 309 341 293 423 434 434 129 129 173 179 66 110 443 1203 605
DDW060C 650 1320 1290 395 341 288 422 485 485 129 129 173 179 66 110 443 1273 655
DDW070C 750 1500 1370 373 404 364 484 485 469 129 137 173 179 66 110 443 1453 675
DDW080C 750 1680 1370 373 404 543 484 485 469 129 137 173 179 66 110 443 1633 675
DDW100C 900 1690 1620 430 478 442 565 609 609 137 137 192 179 110 138 443 1643 805
DDW120C 900 1690 1750 557 478 392 550 736 736 137 137 192 179 110 138 443 1643 915

16
Dimensi DDW vertical unit (25mm panel)

J 24.5

L Q
T
B

40
E
F S D S

Air vent

Chilled water outlet pipe


C

K
H

Chilled water inlet pipe


I

A W

63
Condensate water drainage pipe
53.3

Unit: mm

Ukuran unit Ukuran kabinet Ukuran suplai udara discharge Ukuran pipa Return air inlet size
H H I I Q Q L L
Unit model A B C D S E F G T J K W
(4R) (6R) (4R) (6R) (4R) (6R) (4R) (6R)
DDW150C 900 1920 1760 294 373 404 204 545 863 850 137 143 192 179 110 138 443 1873 1045 50
DDW180C 900 2100 1940 343 430 478 172 572 913 913 143 143 192 179 110 138 443 2053 1105 50
DDW200C 900 2280 1940 343 430 478 252 571 913 913 143 143 192 179 110 138 443 2233 1105 50
DDW220C 900 2400 2010 458 557 478 114 571 977 977 143 143 192 179 110 138 443 2353 1175 50
DDW250C 900 2400 2130 458 557 478 114 571 1104 1104 143 143 192 179 110 138 443 2353 1295 50
DDW270C 900 2470 2130 458 557 478 122 571 1104 1104 143 143 192 179 110 138 443 2423 1295 50
DDW300C 900 2760 2200 458 557 478 267 571 1167 1167 143 143 192 179 110 138 493 2713 1365 90
DDW330C 1100 2760 2340 450 569 569 290 711 1231 1231 143 143 192 179 110 138 493 2713 1425 90
DDW360C 1100 2760 2400 450 569 569 290 711 1294 1294 143 143 192 179 110 138 493 2713 1485 90
DDW400C 1170 2920 2610 500 638 638 261 769 1421 1421 143 143 192 179 110 138 493 2873 1615 90
DDW450C 1170 2920 2685 500 638 638 261 769 1548 1548 143 143 192 179 110 138 493 2873 1745 90

17
T abel day a motor - mak s imal ek s ternal total pres s ure
Unit model DDW020C DDW030C DDW040C DDW050C DDW060C
Nominal airflow rate (m3/h) 2000 3000 4000 5000 6000
Row of coil Motor power (kW) ETP (Pa)
0.55 430 200 130
0.75 590 360 250
1.1 820 550 450 260 200
4-row
1.5 740 650 460 350
2.2 790 750 620
3 870 820
0.55 390 140
0.75 550 310 200
1.1 780 490 400 210 140
6-row
1.5 690 600 410 300
2.2 750 700 570
820 760

Unit model DDW070C DDW080C DDW100C DDW120C DDW150C


Norminal airflow rate (m3/h) 7000 8000 10000 12000 15000
Row of coil Motor power (kW) ETP (Pa)
0.75
1.1 130
1.5 300
2.2 560 350 270 190
4-row cooling coil
3 830 610 460 350 180
4 870 890 690 520 350
5.5 850 750 600
7.5 830 850
0.75
1.1
1.5 240
2.2 510 300 220 140
6-row cooling coil
3 780 560 420 300 130
4 820 840 640 470 310
5.5 800 700 550
780 800

Unit model DDW180C DDW200C DDW220C DDW250C DDW270C


Nominal airflow rate (m3/h) 18000 20000 22000 25000 27000
Row of coil Motor power (kW) ETP (Pa)
3 160
4 290 210 180
5.5 490 380 340 220 170
4-row cooling coil
7.5 720 590 530 410 320
11 780 790 700 580
15 740
3 110
4 250 160 140
5.5 440 340 300 170
6-row cooling coil
7.5 670 550 480 360 270
11 730 740 650 530
690

Unit model DDW300C DDW330C DDW360C DDW400C DDW450C


Nominal airflow rate (m3/h) 30000 33000 36000 40000 45000
Row of coil Motor power (kW) ETP (Pa)
5.5
7.5 190 210
11 440 450 290 320
4-row cooling coil
15 720 730 690 600 400
18.5 850 790 590
22 780
5.5
7.5 160
11 400 400 240 270
6-row cooling coil
15 680 680 640 550 350
18.5 800 750 540
730

18
Operasional
1. Setelah instalasi sistem pemipaan, bersihkan sistem , tutup valve yang ke coil , untuk
menghindari sumbatan kotoran di pipa coil.
2. Setelah pemasangan instalasi unit, cek kondisi putaran kipas, jika tidak ada suara bising,
kemudian sambungkan dengan listrik, dan pastikan arah putaran kipas benar.
3. Sebelum mengisi air, buka akses valve udara, pastikan aliran udara bisa keluar dari valve.
Kemudian tutup valve tersebut.
4. Jika unit berhenti beroperasi, coil perlu di isi air penuh, untuk menghindari kerusakan pada coil.
5. Selama musim dingin suhu di bawah 0o C, Air di coil harus di keluarkan, atau pipa menjadi
rusak karena menjadi es.
6. Interval pencucian、pembersihan harus dilakukan setelah 2-3 tahun di pakai, hal ini di perlukan
untuk membersihkan kotoran yang terdapat di dinding bagian dalam pipa. “Soft water” sangat
di anjurkan jika mungkin di gunakan.
7. Cek secara berkala kondisi filter dari kotoran jika mungkin, direkomendasikan untuk memasang
alat pendeteksi perbedaan tekanan, ketika tekanan turun terlalu besar, kemudian ganti filter
udara dengan yang baru.
8. Setelah berjalan 1 minggu, ini penting untuk pengaturan belt, cek kekencangan belt setiap 3
bulan. (V belt force seperti di tunjukan tabel 12)

Pemeliharaan dan perbaikan


1. Pelaksanaan pemeliharaaan dari rencana jadwal yang baik membantu mengurangi dari
kemungkinan terjadi kerusakan.
2. Debu yang menempel pada filter akan berpengaruh pada volume udara dan performa unit, cek
filter setiap sebulan sekali.
3. Semprot dengan air atau angin untuk membersihkan coil, bersihkan permukaan coil dengan
sikat. Vakum debu yang menutupi unit dengan menggunakan mesin vakum.
4. Di musim dingin, jaga di dalam coil tetap kering, atau kemungkinan karena suhu rendah, coil
akan menjadi rusak.
5. Lakukan pengecekan berikut dengan interval:
1) Setiap 6 bulan, cek kondisi keseluruhan dari fan, bersihkan dari kotoran dan debu.
2) Sering-seringlah mengecek drain pan dan pipa saluran air, jaga coil dan pipa dari kotoran
dan debu.

19
3) Cek bearing; pastikan menumpu poros dengan baik.
4) Bersihkan pipa coil setiap 6 bulan sekali.
5) Cek V belt profil dan motor profil berada di bidang yang sama, Pastikan V belt dan poros
motor bersilangan vertikal, Metode umum adalah 4 poin permeriksaan(Lihat gambar .14)
6) Dilarang untuk menggunakan belt yang berbeda dengan merk berbeda dan baru & lama
untuk di gunakan bersama.
7) Cek, ukur kekencangan V belt.(seperti ditunjukan gambar no .15)

Tabel 12

Gaya untuk mencapai lengkungan pada V Belt :16mm


V Belt Model Gaya (N)
V Wheel Diameter(mm)
Min Max
56-95 13 20
SPZ
100-140 20 25
80-132 25 35
SPA
140-200 35 45
112-224 45 65
SPB
236-315 65 85
224~355 85 115
SPC
375~560 115 150

Catatan:
1. V belt dan pulley diatur dengan benar sebelum meninggalkan pabrik, cek kembali
sebelum dioperasikan.
2. Setelah beropersi 1 minggu, harus di cek kembali.
3. Setelah beroperasi 3 bulan, harus di cek dan di atur kembali.
4. Interval pengecekan harus di lakukan 3 bulan sekali.
Peringatan: V belt yang terlalu longgar atau terlalu kencang dapat menyebabkan suara bising
yang tidak perlu di sistem.

Gambar. 14: Metode pengecekan vertikal ada 4 point.

Rul er
A B C D

4 - poi nt s met hod

Gambar 14

20
Gambar 15: Pengukuran kekencangan V Belt:

Cen
ter
poi Center point for torture testing
nt
dis
tan
ces

Distance 16mm

Gambar 15

Pemecahan masalah
Kerusakan Posisi Masalah Solusi
Defleksi poros fan Hubungi Distributor
Poros dan Bearing tidak cocok Hubungi Distributor
Kipas kendor Hubungi Distributor
1. Fan Wheel Bearing dan poros lepas Hubungi Distributor
Kipas rusak Hubungi Distributor
Baut kipas kendor Kencangkan bautnya
Kipas kotor Bersihkan
Roda kipas dan poros kendor Atur dan kencangkan belt
V-belt kendor Atur belt
V-belt terlalu kencang Kendorkan V belt
V-belt tidak cocok dengan pulley Pakai V belt yang sama
2. Bagian yang bergerak
Menggunakan lebih dari satu V belt Ganti dengan panjang
dengan panjang berbeda. sama
Berisik V-Belt Rusak Ganti
Baut kendor Kencangkan baut.
Bearing rusak Ganti
Pelumas Kurang Tambahkan pelumas
Bearing Longgar Kencangkan
Pemasangan salah Pasang Ulang
3. Bearing
Bearing kotor di bagian dalam Bersihkan atau Ganti
Bearing Rusak Ganti
Bearing berkarat Ganti atau bersihkan
dengan Cairan asam.
Kotor di housing Bersihkan
4. Housing Housing kendor Hubungi distributor
Housing rusak Hubungi distributor

21
Sambungan kendor Kencangkan sambungan
5. Kelistrikan Suplai listrik AC Hubungi distributor
3 fasa Suplai listrik 3 fasa
Bengkok , perubahan bentuk Ganti poros
6. Poros Tidak seimbang Atur keseimbangan
Poros kendor Kencangkan poros
7. Kecepatan kipas Penampang permukaan terlalu kecil Desain ulang sistem suplai
terlalu tinggi ESP tidak sesuai desain udara
Penampang permukaan terlalu kecil
Desain ulang sistem
Sistem tidak stabil
8. Getaran Berkala Atur sistem
Saluran udara bergetar dengan fan
Atur kecepatan fan
motor
9. Kebisingan Saluran
Kebocoran udara di saluran udara Tambah seal
udara (I)
Desain ulang sistem saluran
Tekukan saluran udara terlalu tajam udara
Ekspansi saluran udara secara dramatis Desain ulang sistem saluran
Saluran udara mengerut secara udara
10. Kebisingan Saluran
dramatis Desain ulang sistem saluran
udara (II)
Kecepatan udara di saluran udara udara
terlalu tinggi Desain ulang sistem saluran
Adaptor getaran terlalu kecil udara
Atur adaptor

Pemecahan Masalah(Lanjutan)
Kerusakan Posisi Masalah Solusi
Pemasangan Wheel salah Hubungi distributor
1. Fan
Putaran terbalik Atur fase motor
Desain Ulang sistem
Aliran udara yang hilang besar
“Duct”
2. Duct sistem Kerapatan saluran udara
Tambahkan seal adhesive
Katup api tertutup
Buka katup api
3. Filter Terlalu kotor, tersumbat Bersihkan filter
Volume 4. Coil Terlalu kotor, macet Cuci coil
aliran udara 5. Hubungan udara Jarak keluaran udara dengan udara masuk
Diberi panel pemisah
kecil terlalu pendek terlalu dekat, tidak ada pemisah.
6. Udara keluar Pindahkan fan
Penghalang di keluaran udara
terhalang Pindahkan penghalang
7. Tidak ada udara Tidak ada belokan udara keluar yang Diharuskan ada udara
keluar diperbolehkan keluaran langsung
Pindahkan penghalang
8. Saluran udara Ada penghalang di saluran udara
Desain ulang saluran
terhalang Design belokan saluran udara
udara

22
Desain ulang sistem
Ukuran saluran udara salah saluran udara
Pintu Servis tidak tertutup Tutup pintu servis
Volume 1. Sistem Aliran udara yang hilang terlalu kecil Desain ulang sistem
aliran udara Tidak terpasang damper dan diffuser Filter Pasang ulang damper dan
besar tidak terpasang diffuser
Pasang ulang filter
2. Saluran Udara Kebocoran Udara balik Tambahkan seal adhesive

Udara 1. Filter Filter Kotor Bersihkan Filter


Ruangan Tambahkan pasokan udara
Pengap 2. Fresh Kekurangan udara segar
segar

GARANSI SERVIS - SETELAH PENJUALAN


1) Ada perbaikan dan pemeliharaan yang harus di tanyakan kepada asisten dari distributor di
daerah asal. Perbaikan dan pemeliharaan yang tidak tepat dapat menyebabkan kebocoran air
dan listrik bahkan bisa menyebabkan bahaya kebakaran.
2) Ketika unit harus dipindahkan atau di pasang ulang, hubungi distributor di wilayah asal.
Instalasi yang tidak benar akan mengakibatkan kebocoran air dan listrik bahkan bencana
kebakaran.
3) Ketika meminta perbaikan , sediakan data detail berikut :
a) Model unit ( Lihat di nameplate);
b) Tanggal pemasangan (lihat di aplikasi garansi);
c) Keterangan kerusakan;
d) Nama, alamat lengkap, Telepon.
4) Perbaikan setelah masa garansi habis, servis akan di kenakan biaya sesuai dengan kasusnya.
5) Pengecekan dan pemeliharaan:
a) Setelah beberapa musim beroperasi, performa unit akan mengalami penurunan di sebabkan
oleh kotoran yang terakumulasi di dalam unit.
b) Di samping pemeliharaan yang dilakukan oleh pemilik, disarankan juga untuk mengontrak
kontraktor perawatan dengan distributor atau pabrikan. Untuk detail servis, silahkan hubungi
distributor.
6) Permintaan: Ada pertanyaan tentang purna jual servis silahkan hubungi distributor.
7) Garansi: Selama waktu garansi masih ada, beberapa servis adalah gratis jika kamu menunjukan
aplikasi garansi.

23