FH Fan-Coil Units Low-Profile, Horizontal: Engineering Guide
FH Fan-Coil Units Low-Profile, Horizontal: Engineering Guide
FH Fan-Coil Units Low-Profile, Horizontal: Engineering Guide
FH Fan-Coil Units
Low-Profile, Horizontal
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal
Table of contents
Notes:
• Johnson Controls offers Web-Select®, the industry’s first web-based rating and selection program for com-
plete unit, coil and sound selection. See your representative for more information.
• Some drawings are not shown in this catalog.
• All data herein is subject to change without notice.
• Drawings not for installation purposes; refer to IOM manual.
• ETL Report Number 539840.
2 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)
Johnson Controls FH Series horizontal low profile fan All FH Series fan coil units are shipped completely
coil units are designed to maximize flexibility of selec- assembled, reducing field installation time and labor.
tion and installation. All units are thoroughly inspected and tested prior to
shipment, eliminating potential problems at startup.
The units are also designed to exceed the stringent Motor wiring is brought to a junction box on the outside
quality standards of the institutional market, while of the unit casing, reducing electrical hook-up time.
remaining cost competitive in the light commercial seg-
ment of the market. Plenum units are field reversible for either rear or bot-
tom return without special adapters, tools or additional
Johnson Controls horizontal fan coil units set the new parts.
standards for quality, flexibility, and competitive pricing.
All FH Series fan coil units have the option of a hinged
DESIGN FLEXIBILITY cover electrical enclosure in the bottom of the unit. The
expansive compartment allows for easy access to all
The extensive variety of standard options available on electrical components, terminal blocks and wiring.
the FH Series units are where you find the versatility to
fit any HVAC system designer’s needs. Factory furnished valve packages assure proper fit,
operation and performance.
Options include: rear or bottom ducted return, foil faced
or elastomeric closed cell foam insulation, solid or tele- For fast track jobs, the FH Series fan coil is available
scoping bottom panels for unit recessing, single wall on Quick Ship with 5, 10 or 15 day lead times.
stainless steel drain pans, electric heat with single point
power connection. All electric heat units are listed with QUALITY PRODUCT
ETL as an assembly and carry the cETL label.
Concealed Model FH Series fan coil units are built from
All units comply with the latest edition of AHRI Standard galvanized steel. Exposed Model FHX cabinetry is
440 for testing and rating fan coil units, are certified, powder coated galvannealed steel.
and display the AHRI symbol.
Standard insulation is 1/2 inch thick fiberglass, complying
High Efficiency motors, fan relays, disconnects and with UL 181 and NFPA 90A. Optional foil faced or elas-
fusing mean easier coordination between mechanical tomeric closed cell foam insulation may be specified.
and electrical trades.
All units, with or without electric heat, are cETL listed
Coil options allow for three or four row chilled water or and labeled. All wiring is in compliance with NEC, assur-
DX cooling coils. One or two row hot water or standard ing safety and quality for the owner.
steam coils may be placed in the preheat or reheat
position. FH Series fan coil units have a removable fan assembly.
The entire fan assembly can be removed from the unit
Silent solid state relays are available for fan and electric and serviced easily on a workbench.
heat control in sound sensitive environments.
Johnson Controls 3
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal
construction features
MODEL fhp
FH Series fan coils have many standard and optional features which are unique to the industry
(see page 6 for a complete listing).
4 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)
construction features
Models fhf/fhp/fhx
DRAIN PAN
ELECTRICAL ENCLOSURE Standard drain pans are externally insulated, single wall
The bottom hinged electrical enclosure provides access galvanized steel with an option for stainless steel. Drain
to a spacious electrical compartment. This compartment pans are available with secondary drain connection.
houses all electric heat and control components. On concealed models, the FH Series drain pan is eas-
Terminal strips are furnished for simple power and ily removable for cleaning or reversing connections.
control wiring connections. Multiple knockouts allow
wiring entries from either side of the compartment.
FILTERS
One inch throwaway filters are tight fitting to prevent air
bypass. Filters are easily removable from the bottom
through the access panel or plenum.
COILS
All fan coils are available in 2 or 4 pipe configurations.
The heating coil may be placed in the reheat or preheat
position. On concealed models, heating and cooling
coils are available with right, left or opposite side FAN DECK
connections. The fan assembly is easily removed without
disconnecting the ductwork for service access to motors
and blowers at, or away from the unit.
Johnson Controls 5
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal
Standard Features
Construction Electrical
All Units • cETL listed for safety compliance
• AHRI 440 certified and labeled • Electrical junction box for field wiring terminations
• Galvanized steel construction • Unit rated for 5kAIC short circuit current rating
• 1/2" thick fiberglass insulation (SCCR)
• 1 1/2" duct discharge collar
• Four point hanger mounting brackets (hanger rod Electric Heat
holes provided on exposed units) • ETL listed as an assembly for safety compliance
Plenum units • Integral electric heat assembly with removable
• Integral filter rack with 1" throwaway filter elements for easy service
• Integral rear ducted return - field reversible to bot- • Automatic reset primary and back-up secondary
tom return thermal limits
Exposed units • Single point power connection
• Stamped louver supply and return air grilles • Bottom hinged electrical enclosure
• Durable powder coat paint
• 18 gauge bottom panel construction optional features
Coils Construction
• Cooling - 3 or 4 row chilled water or DX, heat All units
pump compatible • Foil faced fiberglass insulation
• Heating - 1 or 2 row hot water or steam – reheat or • Elastomeric closed cell foam insulation
preheat position Plenum units
• 6 total rows of cooling and heating coils maximum • Bottom return
• High efficiency aluminum fin surface for optimizing • 1" pleated filters (MERV 6)
heat transfer, pressure drop and carryover • Spare 1" throwaway filters
• Left or right hand, same or opposite side • Telescoping Bottom Panels
Exposed units
connections
• 1" pleated filters (MERV 6)
• Access to entering and leaving air sides for
• Double deflection discharge grille
cleaning
• Ducted supply and/or return
• Removable for service
• Manual air vents Coils
• Automatic air vents
Drain Pans
• Stainless steel coil casings
• Single wall, galvanized steel, externally insulated –
fire retardant and antimicrobial Drain Pans
• Double sloped to drain connection • Stainless steel construction with external insulation
• Removable, field reversible • 5/8" O.D. secondary drain connection
• 7/8" O.D. primary drain connection • Auxiliary drip pans, galvanized or stainless steel
Fan Assemblies Fan Assemblies
• Forwardly curved, DWDI centrifugal type • 208-230, 220 & 277 volt, single phase, three tap
• 115 volt, single phase, three tap PSC motors PSC motors
• Quick disconnect motor connections
• Removable fan/motor deck for service Electrical
• Electronically commutated motor
Verification of Equipment Efficiencies • Bottom hinged cover electrical enclosure
• Fan coil units that are not certified to AHRI-440 • SCR fan speed controller (high speed only)
shall furnish ratings that are verified by an indepen- • Fan relay packages
dent laboratory test report (per ASHRAE 90.1) • Silent solid state fan relays
6 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)
Johnson Controls 7
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal
Coils
Johnson Controls offers hot water, chilled water, direct expansion (DX), and standard steam coils for specific appli-
cation with all FH Series Fan Coil Units. Strict on-site inspection before, during, and after installation guarantees
the highest quality and performance available.
Johnson Controls offers Web-Select™, the industry’s first web-based fan coil rating and selection program for
complete unit, coil and sound selection. See your representative for more information.
8 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)
physical data
Johnson Controls 9
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal
physical data
HEATING CAPACITY
NOMINAL 1 ROW 2 ROW
UNIT TYPE UNIT SIZE
CFM QS (MBH) GPM WPD QS (MBH) GPM WPD
20 250 8.6 0.4 0.2 15.7 0.8 0.9
25 400 15.0 0.6 0.6 21.0 1.1 3.1
FHP 30 500 16.1 0.8 0.6 29.2 1.5 3.2
FHF 40 750 23.6 1.2 1.5 40.5 2.1 1.6
50 1000 28.7 1.5 0.7 53.7 2.7 2.9
60 1400 36.1 1.9 1.1 66.9 3.4 4.7
20 250 7.9 0.4 0.3 14.0 0.8 1.5
25 350 10.8 0.6 0.5 19.3 1.0 2.6
30 450 13.5 0.7 0.9 24.0 1.3 4.8
FHX
40 650 20.4 1.1 2.0 34.0 1.8 1.7
50 850 22.5 1.2 0.7 40.7 2.1 3.1
60 1200 30.9 1.6 1.2 55.4 2.9 5.5
NOTE: Based on 70°F DB EAT, 180°F EWT, 40°F temperature drop, high fan speed.
10 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)
electric heat
Johnson Controls offers electric heating coils for specific application with all FH Series Fan Coil units. This allows
the flexibility to provide an unrivaled amount of electric heat options in one complete package.
Johnson Controls 11
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal
1. Fan curves on the following pages depict actual performance of each motor tap without any additional fan balance adjust-
ment. Actual capacities which fall below each curve can be obtained by adding an adjustment device. Units should not be
run prior to installation of downstream ductwork; otherwise, damage to the motor may result.
2. Johnson Controls Fan Coil Units are equipped with permanent split-capacitor (PSC) motors with three taps (High, Medium
and Low) which provides variable horsepower outputs. Most often, size selections are conservative and actual CFM require-
ments and/or external static pressure requirements are lower than those specified. In this case, the unit fan motor can be
run at low or medium tap, substantially reducing the operating cost of the unit.
3. All fan curves are for 115/1/60 motors and include pressure losses for cabinet, electric heater, and 3 or 4 row coil. Plenum
units include a clean 1" throwaway filter. For other coil configurations, adjust performance curves based on pressure losses
for the coils using Web-Select®.
4. See page 14 for fan motor electrical data.
5. For additional high static pressure applications and rating points, contact factory.
Size 20 Size 25
Model FHP (Plenum)
Model FHP (Plenum)
0.40 0.80
0.35 0.70
HIGH
0.50
ESP (IN. W.G.)
MED
0.20 0.40
0.15 0.30
LOW
0.10 0.20
0.05 0.10
0.00 0.00
0 50 100 150 200 250 300 0 50 100 150 200 250 300 350 400 450 500
3 ROW COIL 3 ROW COIL
SCFM SCFM
4 ROW COIL
4 ROW COIL
MED HIGH
0.30 0.60
LOW
ESP (IN. W.G.)
0.50
ESP (IN. W.G.)
0.25
MED
0.20 0.40
0.15 0.30
LOW
0.10 0.20
0.05 0.10
0.00 0.00
0 50 100 150 200 250 300 350 400 0 50 100 150 200 250 300 350 400 450 500
0.35 0.60
HIGH
0.30
0.50 MED
0.25
ESP (IN. W.G.)
0.40
0.20 LOW
0.30
0.15
0.20
0.10
0.10
0.05
HIGH
LOW MED
0.00 0.00
0 50 100 150 200 250 300 0 50 100 150 200 250 300 350
3 ROW COIL SCFM 3 ROW COIL
SCFM 4 ROW COIL 4 ROW COIL
12 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)
Size 30 Size 40
0.35 0.80
HIGH
0.30 0.70 HIGH
MED
0.60
0.25
MED
LOW
0.50
0.20
0.40
0.15
0.30
0.10
0.20
LOW
0.05 0.10
0.00 0.00
0 50 100 150 200 250 300 350 400 450 500 550 600 0 100 200 300 400 500 600 700 800 900
0.40 0.90
0.35 0.80
HIGH HIGH
0.70
0.30
MED
0.60
ESP (IN. W.G.)
0.25
ESP (IN. W.G.)
MED
LOW 0.50
0.20
0.40
0.15
0.30
0.10
0.20
0.05 LOW
0.10
0.00 0.00
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 0 100 200 300 400 500 600 700 800 900
0.35 0.70
0.30 0.60
0.25 0.50
ESP (IN. W.G.)
0.20 0.40
0.15 0.30
0.10 0.20
HIGH
0.05 MED 0.10 MED HIGH
LOW
LOW
0.00 0.00
0 50 100 150 200 250 300 350 400 450 500 0 50 100 150 200The thick
250 line
300 350 3 row
400coil 450 500 550 600 650 700
indicates
3 ROW COIL 3 ROW COIL
SCFM 4 ROW COIL SCFM
4 ROW COIL
Johnson Controls 13
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal
Size 50 Size 60
0.70 0.80
HIGH
0.70
0.60 MED
0.60
0.50
0.50
0.40
HIGH 0.40 LOW
0.30
0.30
MED
0.20
0.20
LOW
0.10 0.10
0.00 0.00
0 200 400 600 800 1000 1200 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
SCFM 3 ROW COIL SCFM 3 ROW COIL
4 ROW COIL 4 ROW COIL
0.90 HIGH
0.80
HIGH
0.80
0.70
0.60
ESP (IN. W.G.)
0.50
0.50
0.40
0.40 LOW
0.30
0.30
LOW
0.20
0.20
0.10 0.10
0.00 0.00
0 200 400 600 800 1000 1200 1400 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700
SCFM 3 ROW COIL SCFM 3 ROW COIL
4 ROW COIL 4 ROW COIL
0.80
0.70
0.70
0.60
0.60
0.50
ESP (IN. W.G.)
0.50
0.40
0.40
0.30
0.30 HIGH
HIGH
0.20
0.20
MED
MED
LOW 0.10
0.10
LOW
0.00 0.00
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 0 100 200 300 400 500 600 700 800 900 1000 1100 1200
3 ROW COIL 3 ROW COIL
SCFM 4 ROW COIL SCFM 4 ROW COIL
14 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)
HORIZONTAL EXPOSED
MOTOR 115 VOLTS 208-230 VOLTS 277 VOLTS
UNIT FAN # OF
H.P. WATTS 3-PHASE 3-PHASE 3-PHASE
SIZE SPEED FANS FLA FLA FLA
(QTY.) NEUTRAL NEUTRAL NEUTRAL
20 High (1) 1/4 1 25 0.70 1.00 0.60 0.90 0.60 0.90
25 High (1) 1/4 1 40 1.00 1.50 0.70 1.00 0.70 1.00
30 High (1) 1/4 2 44 1.00 1.50 0.80 1.20 0.80 1.20
40 High (1) 1/4 2 79 1.90 2.70 1.40 2.00 1.40 2.00
50 High (2) 1/4 3 92 2.40 3.40 1.80 2.60 1.80 2.60
60 High (2) 1/4 4 148 3.60 5.20 2.80 4.00 2.80 4.00
NOTES:
1. Watts as shown are for a Plenum / Exposed unit with .05" ESP, 4 row coil, 115/1/60, 12 FPI, and throwaway filters
2. Motors nameplated for 208-230/1/60. Data is at 230 volts
3. Motor HP as noted is a nominal rating
4. Data as supplied is for reference only. For project specific operational points see seletion tool report out.
Johnson Controls 15
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal
sound data
sound data
TOTAL SOUND POWER LEVEL
UNIT SIZE FAN SPEED SCFM OCTAVE BAND / CENTER FREQUENCY (HZ)
2/125 3/250 4/500 5/1000 6/2000 7/4000 8/8000
High 282 55 59 53 50 46 38 36
20 Medium 216 50 52 47 44 38 31 32
Low 175 47 48 43 39 32 27 31
High 420 58 62 57 54 51 44 39
25 Medium 286 53 53 49 45 41 34 29
Low 180 48 42 38 36 33 27 27
High 522 60 60 57 56 50 44 40
30 Medium 458 57 55 54 52 46 40 36
Low 269 48 44 43 39 32 27 31
High 810 65 68 64 60 55 51 47
40 Medium 565 59 59 57 51 46 40 35
Low 300 51 46 41 36 28 27 30
High 1050 61 66 68 62 56 52 49
50 Medium 840 56 61 63 55 49 44 40
Low 490 48 53 59 46 39 33 32
High 1400 67 72 70 68 59 54 51
60 Medium 1050 61 65 67 57 52 47 42
Low 500 50 56 48 40 33 28 31
NOTES:
1. Sound data tested in accordance with AHRI 350-2000.
2. Sound levels are expressed in decibels, dB RE: 1 x 10-12 watts.
3. Total sound power level data based on Model FHP with fan CFM at corresponding motor tap with 115/1/60 volt motor, 3 or
4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses.
16 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)
dimensional data
Johnson Controls 17
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal
dimensional data
18 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)
Johnson Controls 19
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal
dimensional data
20 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)
guide specifications
General
Furnish and install Johnson Controls Model FH Unit mounting shall be by hanger brackets provided at
Horizontal Concealed Direct Drive Fan Coil Units where four locations.
indicated on the plans and in the specifications. Units
shall be completely factory assembled, tested and PAINTED Finish
shipped as one piece. All units shall be capable of
meeting or exceeding the scheduled capacities for cool- All painted cabinet exterior panels shall be finished with
ing, heating and air delivery. All unit dimensions for each a heat cured anodic acrylic powder paint of the standard
model and size shall be considered maximums. Units factory color.
shall be ETL listed in compliance with UL/ANSI Standard
1995, and be certified as complying with the latest edi- Sound
tion of AHRI Standard 440.
Units shall have published sound power level data
Construction tested in accordance with AHRI Standard 350-2000
(non-ducted equipment).
All unit chassis shall be fabricated of heavy gauge
galvanized steel panels. All exterior panels shall be Fan Assembly
insulated with 1/2" thick insulation with a maximum k
value of .24 (BTU - in) / (hr - ft2 - °F) and rated for a Unit fan shall be a dynamically balanced, forwardly
maximum air velocity of 5000 f.p.m. Insulation must curved, DWDI centrifugal type constructed of 18 gauge
meet all requirements of ASTM C1071 (including zinc coated galvanized steel for corrosion resistance.
C665), UL 181 for erosion, and carry a 25/50 rating Motors shall be high efficiency, permanently lubricated
for flame spread/smoke developed per ASTM E-84, sleeve bearing, permanent split-capacitor type with UL
UL 723 and NFPA 90A. and CSA listed automatic reset thermal overload protec-
tion and three separate horsepower taps. Single speed
All concealed units shall have a minimum 1-1/2" duct motors are not acceptable.
collar on the discharge. Plenum and exposed units
shall have a minimum 3/4" duct collar on the return. The fan assembly shall be easily removable for servic-
ing the motor and blower at, or away from the unit. The
All exposed units shall have exterior panels fabri- entire fan assembly shall be able to come out of the
cated of galvannealed steel. The fan and filter bottom unit by removing two screws and unplugging the motor.
access panel shall be attached with quarter turn quick Plenum unit fan assemblies shall be easily serviced
open fasteners to allow for easy removal and access through an access panel provided.
for service.
Option: Provide Electronically Commutated (EC) Motor
Option: Provide foil faced insulation in lieu of standard. capable of operation with low voltage 3 speed thermo-
Foil insulation shall meet or exceed the requirements stat. Motor shall come factory programmed and
stated above, and in addition meet ASTM Standards configured for 3 speed operation. Each speed shall be
C-665 and C-1136 for biological growth in insulation. manually adjustable in the field. All manual speed
Insulation shall be lined with aluminum foil, fiberglass adjustments shall be stored in non-volatile memory.
scrim reinforcement, and 30 pound kraft-paper lami- Motor shall be capable of accepting a 2-10 VDC output
nated together with a flame resistant adhesive. All from BAS. Motor bearings shall be rated for L10-40,000
exposed edges shall be sealed to prevent any fibers hours.
from reaching the air stream.
Option: Provide an electronic (SCR) fan speed control-
Option: Provide Elastomeric Closed Cell Foam Insulation ler as an aid in balancing the fan capacity. The speed
in lieu of standard. Insulation shall conform to UL 181 controller shall have a turn down stop to prevent the
for erosion and NFPA 90A for fire, smoke and melting, possibility of harming the motor bearings, and incorpo-
and comply with a 25/50 Flame Spread and Smoke rate electrical noise suppression to minimize noise on
Developed Index per ASTM E-84 or UL 723. Additionally, the incoming power lines.
insulation shall comply with Antimicrobial Performance
Rating of 0, no observed growth, per ASTM G-21. Option: Devices used to energize and de-energize
Polyethylene insulation is not acceptable. (switch) fan speeds must be totally silent. Magnetic,
mercury, and/or quiet relays and/or contactors are not
acceptable.
Johnson Controls 21
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal
guide specifications
Coils
All cooling and heating coils shall optimize rows and Option: Provide a secondary drain connection on the
fins per inch to meet the specified capacity. Coils shall primary drain pan for condensate overflow.
have seamless copper tubes and shall be mechani-
cally expanded to provide an efficient, permanent bond Filters
between the tube and fin. Fins shall have high effi-
ciency aluminum surface optimized for heat transfer, air All plenum and exposed units shall be furnished with a
pressure drop and carryover.All coils shall be hydro- minimum 1" nominal glass fiber throwaway filter. Filters
statically tested at 450 PSIG air pressure under water, shall be tight fitting to prevent air bypass. Plenum unit
and rated for a maximum of 300 PSIG working pressure filters shall be easily removable from the bottom of the
at 200°F. unit without the need for tools.
Steam coils shall be standard steam type suitable for Option: Provide unit with 1" pleated filter (MERV 8).
temperatures above 35°F and 15 PSIG maximum work-
ing pressure. Electrical
Option: Coil casing shall be fabricated from Stainless Units shall be furnished with single point power connec-
Steel. tion. Provide an electrical junction box for motor and
other electrical terminations.
All coils shall be provided with a manual air vent fitting
to allow for coil venting. Option: Provide a hinged electrical enclosure in the
bottom of the unit for easy access to all electrical com-
Option: Provide automatic air vents in lieu of manual ponents, terminal blocks and wiring.
air vents.
Electric Heat
Heating coils shall be furnished in the reheat or preheat
position on units with chilled water coils, or in the reheat Furnish an electric resistance heating assembly as an
position for DX coils. integral part of the fan coil unit, with the heating capac-
ity, voltage and kilowatts scheduled. The heater
Drain Pans assembly shall be designed and rated for installation
on the fan coil unit without the use of duct extensions
Primary condensate drain pans shall be single wall, or transitions, and be located in the unit as to not
heavy gauge galvanized steel for corrosion resistance, expose the fan assembly to excessive leaving air tem-
and extend under the entire cooling coil. Drain pans peratures that could affect motor performance.
shall be of one-piece construction and be double sloped
for condensate removal. Drain pans on concealed The heater and unit assembly shall be listed for zero
models shall be field reversible for right or left hand clearance and meet all NEC requirements, and be ETL
connections. listed with the unit as an assembly in compliance with
UL/ANSI Standard 1995.
The drain pan shall be externally insulated with a fire
retardant, closed cell foam insulation. The insulation All heating elements shall be open coil type nichrome
shall carry no more than a 25/50 Flame Spread and wire mounted in ceramic insulators and located in an
Smoke Developed Rating per ASTM E-84 and UL 723 insulated heavy gauge galvanized steel housing. All
and an Antimicrobial Performance Rating of 0, no elements shall terminate in a machine staked stainless
observed growth, per ASTM G-21. steel terminal secured with stainless steel hardware for
corrosion resistance. The element support brackets
Option: Provide a single wall primary drain pan con- shall be spaced no greater than 3-1/2" on center. All
structed entirely of heavy gauge stainless steel for internal wiring shall be rated for 105°C minimum.All
superior corrosion resistance. Stainless steel drain pans heaters shall include overtemperature protection con-
shall be externally insulated and meet or exceed the sisting of an automatic reset primary thermal limit and
requirements stated above. back up secondary thermal limit. All heaters shall be
single stage.
22 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)
Option: Provide a manual reset secondary thermal Option: Provide 3-wire floating point modulating control
limit. valve (fail-in-place) in lieu of standard 2-position control
valve with factory assembled valve piping package.
All units with electric heat shall have a bottom hinged
electrical enclosure for easy access and service to the Option: Provide high pressure close-off actuators for
electrical components and wiring. An incoming line 2-way on/off control valves. Maximum close-off pres-
power distribution block shall be provided and desig- sure is 50 PSIG (1/2") or 25 PSIG (3/4)".
nated to accept single point power wiring capable of
carrying 125% of the calculated load current. Option: Provide either a fixed or adjustable flow control
device for each piping package.
Option: Devices used to energize and de-energize
(switch) electric heat must be totally silent. Magnetic, Option: Provide pressure-temperature ports for each
mercury, and/or quiet relays and/or contactors are not piping package.
acceptable.
Piping package shall be completely factory assembled,
Piping Packages including interconnecting pipe, and shipped separate
from the unit for field installation on the coil, so as to
Provide a standard factory assembled valve piping minimize the risk of freight damage.
package to consist of a 2 or 3 way, on/off, motorized
electric control valve and two ball isolation valves.
Control valves are piped normally closed to the coil.
Maximum entering water temperature on the control
valve is 200°F, and maximum close-off pressure is 40
PSIG (1/2") or 20 PSIG (3/4"). Maximum operating
pressure shall be 300 PSIG.
Johnson Controls 23
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal
NOTES