engineering guide

FH Fan-Coil Units
Low-Profile, Horizontal
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal

Table of contents

Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3


Construction Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Standard And Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Coils, Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Fan Performance Curves (Psc Motors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Motor, Fan And Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Notes:
• Johnson Controls offers Web-Select®, the industry’s first web-based rating and selection program for com-
plete unit, coil and sound selection. See your representative for more information.
• Some drawings are not shown in this catalog.
• All data herein is subject to change without notice.
•  Drawings not for installation purposes; refer to IOM manual.
• ETL Report Number 539840.

2 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)

features and benefits

High Performance CONVENIENT INSTALLATION

Johnson Controls FH Series horizontal low profile fan All FH Series fan coil units are shipped completely
coil units are designed to maximize flexibility of selec- assembled, reducing field installation time and labor.
tion and installation. All units are thoroughly inspected and tested prior to
shipment, eliminating potential problems at startup.
The units are also designed to exceed the stringent Motor wiring is brought to a junction box on the outside
quality standards of the institutional market, while of the unit casing, reducing electrical hook-up time.
remaining cost competitive in the light commercial seg-
ment of the market. Plenum units are field reversible for either rear or bot-
tom return without special adapters, tools or additional
Johnson Controls horizontal fan coil units set the new parts.
standards for quality, flexibility, and competitive pricing.
All FH Series fan coil units have the option of a hinged
DESIGN FLEXIBILITY cover electrical enclosure in the bottom of the unit. The
expansive compartment allows for easy access to all
The extensive variety of standard options available on electrical components, terminal blocks and wiring.
the FH Series units are where you find the versatility to
fit any HVAC system designer’s needs. Factory furnished valve packages assure proper fit,
operation and performance.
Options include: rear or bottom ducted return, foil faced
or elastomeric closed cell foam insulation, solid or tele- For fast track jobs, the FH Series fan coil is available
scoping bottom panels for unit recessing, single wall on Quick Ship with 5, 10 or 15 day lead times.
stainless steel drain pans, electric heat with single point
power connection. All electric heat units are listed with QUALITY PRODUCT
ETL as an assembly and carry the cETL label.
Concealed Model FH Series fan coil units are built from
All units comply with the latest edition of AHRI Standard galvanized steel. Exposed Model FHX cabinetry is
440 for testing and rating fan coil units, are certified, powder coated galvannealed steel.
and display the AHRI symbol.
Standard insulation is 1/2 inch thick fiberglass, complying
High Efficiency motors, fan relays, disconnects and with UL 181 and NFPA 90A. Optional foil faced or elas-
fusing mean easier coordination between mechanical tomeric closed cell foam insulation may be specified.
and electrical trades.
All units, with or without electric heat, are cETL listed
Coil options allow for three or four row chilled water or and labeled. All wiring is in compliance with NEC, assur-
DX cooling coils. One or two row hot water or standard ing safety and quality for the owner.
steam coils may be placed in the preheat or reheat
position. FH Series fan coil units have a removable fan assembly.
The entire fan assembly can be removed from the unit
Silent solid state relays are available for fan and electric and serviced easily on a workbench.
heat control in sound sensitive environments.

Johnson Controls 3
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal

construction features

MODEL fhp
FH Series fan coils have many standard and optional features which are unique to the industry
(see page 6 for a complete listing).

1/2" thick fiberglass insulation


(standard), or foil faced or Galvanized steel casing withstanding
elastomeric closed cell foam
insulation (optional)
1 1/2" duct collar allows quick field
connection of duct work

ETL and AHRI 440


listed and labeled

Integral filter rack with 1"


filter and integral rear
ducted (shown) or
bottom return on
all plenum units

Permanently lubricated, Chilled water or DX cooling


three tap, PSC fan motors coils up to 4 rows
Optional hinged cover
designed for quiet and Optional electrical enclosure
efficient operation secondary drain Hot water heating coils or
allows easy bottom
Optional electronically connection for steam coils up to 2 rows
access to all electrical
comutated (brushless DC) added security can be mounted in the pre-
components
motor (not shown) heat or reheat position
Single point power Bottom access to both
connection on all units entering and leaving sides
with electric heat Single wall galvanized or of all coils for cleaning
stainless steel (optional)
drain pans are double Maximum 6 total rows
Removable fan board for complete sloped to drain connec-
bottom or rear access and servicing of coil combined
tions

Optional electric Drain pans can be


resistance heat is ETL easily removed for
listed as an assembly cleaning, and reversed
for safety compliance for opposite side drain
connections
Entire electric heat assembly can be removed
from the bottom for servicing

Model fhx Model FHF


Horizontal Exposed Cabinet Horizontal Free Return

4 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)

construction features

Models fhf/fhp/fhx

DRAIN PAN
ELECTRICAL ENCLOSURE Standard drain pans are externally insulated, single wall
The bottom hinged electrical enclosure provides access galvanized steel with an option for stainless steel. Drain
to a spacious electrical compartment. This compartment pans are available with secondary drain connection.
houses all electric heat and control components. On concealed models, the FH Series drain pan is eas-
Terminal strips are furnished for simple power and ily removable for cleaning or reversing connections.
control wiring connections. Multiple knockouts allow
wiring entries from either side of the compartment.

TELESCOPING BOTTOM PANEL


The telescoping bottom panel allows for fully recessing
the unit while permitting service access into the ceiling
plenum. The architectural ceiling panel is finished with
a durable powder coat paint.

FILTERS
One inch throwaway filters are tight fitting to prevent air
bypass. Filters are easily removable from the bottom
through the access panel or plenum.

COILS
All fan coils are available in 2 or 4 pipe configurations.
The heating coil may be placed in the reheat or preheat
position. On concealed models, heating and cooling
coils are available with right, left or opposite side FAN DECK
connections. The fan assembly is easily removed without
disconnecting the ductwork for service access to motors
and blowers at, or away from the unit.

Johnson Controls 5
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal

standard and Optional features

Standard Features

Construction Electrical
All Units • cETL listed for safety compliance
• AHRI 440 certified and labeled • Electrical junction box for field wiring terminations
• Galvanized steel construction • Unit rated for 5kAIC short circuit current rating
• 1/2" thick fiberglass insulation (SCCR)
• 1 1/2" duct discharge collar
• Four point hanger mounting brackets (hanger rod Electric Heat
holes provided on exposed units) • ETL listed as an assembly for safety compliance
Plenum units • Integral electric heat assembly with removable
• Integral filter rack with 1" throwaway filter elements for easy service
• Integral rear ducted return - field reversible to bot- • Automatic reset primary and back-up secondary
tom return thermal limits
Exposed units • Single point power connection
• Stamped louver supply and return air grilles • Bottom hinged electrical enclosure
• Durable powder coat paint
• 18 gauge bottom panel construction optional features

Coils Construction
• Cooling - 3 or 4 row chilled water or DX, heat All units
pump compatible • Foil faced fiberglass insulation
• Heating - 1 or 2 row hot water or steam – reheat or • Elastomeric closed cell foam insulation
preheat position Plenum units
• 6 total rows of cooling and heating coils maximum • Bottom return
• High efficiency aluminum fin surface for optimizing • 1" pleated filters (MERV 6)
heat transfer, pressure drop and carryover • Spare 1" throwaway filters
• Left or right hand, same or opposite side • Telescoping Bottom Panels
Exposed units
connections
• 1" pleated filters (MERV 6)
• Access to entering and leaving air sides for
• Double deflection discharge grille
cleaning
• Ducted supply and/or return
• Removable for service
• Manual air vents Coils
• Automatic air vents
Drain Pans
• Stainless steel coil casings
• Single wall, galvanized steel, externally insulated –
fire retardant and antimicrobial Drain Pans
• Double sloped to drain connection • Stainless steel construction with external insulation
• Removable, field reversible • 5/8" O.D. secondary drain connection
• 7/8" O.D. primary drain connection • Auxiliary drip pans, galvanized or stainless steel
Fan Assemblies Fan Assemblies
• Forwardly curved, DWDI centrifugal type • 208-230, 220 & 277 volt, single phase, three tap
• 115 volt, single phase, three tap PSC motors PSC motors
• Quick disconnect motor connections
• Removable fan/motor deck for service Electrical
• Electronically commutated motor
Verification of Equipment Efficiencies • Bottom hinged cover electrical enclosure
• Fan coil units that are not certified to AHRI-440 • SCR fan speed controller (high speed only)
shall furnish ratings that are verified by an indepen- • Fan relay packages
dent laboratory test report (per ASHRAE 90.1) • Silent solid state fan relays

6 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)

• Toggle disconnect switch two position electric motorized valves


• Condensate overflow switch (drain pan) • Isolation ball valves with memory stop
• Main fusing • Fixed and adjustable flow control devices
• Unit and remote mounted 3-speed fan switches • Unions and P/T ports
(unit mounted three speed switch is mounted within • Floating point modulating control valves
the control enclosure) • High pressure close-off actuators
(1/2" = 50 PSIG; 3/4" = 25 PSIG)
Electric Heat
• Manual reset secondary thermal limits Thermostats
• Door interlocking disconnect switches • Remote mounted analog, digital display or
• Main fusing programmable
• Silent relay/contactors • 2 and 4 pipe control sequences
• Automatic and manual changeover
Piping Packages • Integral three speed fan switches
• Factory assembled – shipped loose for field instal-
lation
• 1/2" and 3/4", 2 way and 3 way normally closed,

Johnson Controls 7
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal

COILS, PHYSICAL DATA

Coils
Johnson Controls offers hot water, chilled water, direct expansion (DX), and standard steam coils for specific appli-
cation with all FH Series Fan Coil Units. Strict on-site inspection before, during, and after installation guarantees
the highest quality and performance available.

STANDARD FEATURES OPTIONAL FEATURES


•  Cooling - 3 or 4 row chilled water or DX •  Automatic air vents
•  Heating - 1 or 2 row hot water or steam •  Stainless steel coil casings
•  6 total rows of cooling and heating coils maximum • DX coils are heat pump compatible
• High efficiency aluminum fin surface for optimizing heat trans-
fer, pressure drop and carryover
• Left or right hand, same or opposite side connections
•  Manual air vents

Johnson Controls offers Web-Select™, the industry’s first web-based fan coil rating and selection program for
complete unit, coil and sound selection. See your representative for more information.

MODEL FHX MODEL FHP


COIL
UNIT
FACE RETURN AIR SUPPLY AIR FILTER
NOMINAL FILTER
FILTER
NOMINAL FILTER
SIZE GRILLE GRILLE FACE FACE
AREA SIZES SIZES
FREE AREA FREE AREA AREA AREA
1.11 30 x 8.5 x 1 1.18 20 x 8.5 x 1
20 0.47 (.04) 0.40 (.04) 1.77 (.16)
[0.1] (762 x 216 x 25) (.11) (508 x 216 x 25)
1.44 (2) 20 x 8.5 x 1 1.54 26 x 8.5 x 1
25 0.58 (.05) 0.50 (.05) 2.36 (.22)
[0.13] (508 x 216 x 25) (.14) (660 x 216 x 25)
1.67 (2) 20 x 8.5 x 1 1.77 30 x 8.5 x 1
30 0.68 (.06) 0.56 (.05) 2.36 (.22)
[0.15] (508 x 216 x 25) (.16) (762 x 216 x 25)
2.22 (1) 20, (1) 30 x 8.5 x 1 2.36 (2) 20 x 8.5 x 1
40 0.81 (.08) 0.80 (.07) 2.95 (.27)
[0.21] (508, 762 x 216 x 25) (.22) (508 x 216 x 25)
2.78 (2) 30 x 8.5 x 1 2.95 (1) 20, (1) 30 x 8.5 x 1
50 1.01 (.09) 0.96 (.09) 3.54 (.33)
[0.26] (762 x 216 x 25) (.27) (508, 762 x 216 x 25)
3.33 (2) 20, (1) 30 x 8.5 x 1 3.54 (2) 30 x 8.5 x 1
60 1.15 (.11) 1.20 (.11) 4.13 (.38)
[0.31] (508, 762 x 216 x 25) (.33) (762 x 216 x 25)
NOTES:
1. Face and free areas are in square feet (square meters).
2. Filter sizes are in inches (millimeters).
3. Return Air Grille Free Area applies to FHX and Telescoping Bottom Panel return grilles.
4. Supply Air Grille Free Area applies to FHX supply grille and minimum free area allowable for a supply grille supplied by
others.

8 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)

physical data

AhRI Standard Ratings


COOLING
COIL AIRFLOW WATER POWER
CAPACITY
MODEL / SIZE CFM INPUT
(Dry Flow) QT QS Flow Rate WPD (WATTS)
Rows FPI
(BTUH) (BTUH) (GPM) ft-wg
FHF 20 3 10 330 10060 7380 2.0 5.8 57
FHF 25 3 10 448 14580 10410 2.9 11.4 125
FHF 30 3 10 772 19500 15030 3.9 7.2 165
FHF 40 3 10 793 23230 17060 4.6 11.2 261
FHF 50 3 10 1196 31640 23930 6.4 10.6 472
FHF 60 3 10 1443 35570 27740 7.0 5.0 522
FHF 20 4 10 309 12970 8870 2.6 11.1 57
FHF 25 4 10 432 16360 11550 3.3 6.4 125
FHF 30 4 10 712 24130 17560 4.8 12.0 165
FHF 40 4 10 775 28980 20520 5.8 9.9 261
FHF 50 4 10 1157 38130 28040 7.5 9.6 472
FHF 60 4 10 1353 43970 32830 8.7 4.5 522
FHP 20 3 10 265 8470 6160 1.7 4.3 57
FHP 25 3 10 415 13810 9810 2.8 10.8 125
FHP 30 3 10 621 16950 12820 3.4 5.7 165
FHP 40 3 10 768 22720 16650 4.5 10.7 261
FHP 50 3 10 1069 29480 22060 5.9 9.0 472
FHP 60 3 10 1325 34010 26230 6.8 4.7 522
FHP 20 4 10 253 10980 7450 2.2 8.7 57
FHP 25 4 10 404 15630 10970 3.1 6.0 125
FHP 30 4 10 604 21870 15600 4.4 10.2 165
FHP 40 4 10 744 28330 19950 5.7 9.7 261
FHP 50 4 10 1022 35510 25680 7.1 8.8 472
FHP 60 4 10 1258 41980 31070 8.4 4.1 522
FHX 20 3 10 265 8470 6160 1.7 4.3 57
FHX 25 3 10 415 13810 9810 2.8 10.8 125
FHX 30 3 10 621 16950 12820 3.4 5.7 165
FHX 40 3 10 768 22720 16650 4.5 10.7 261
FHX 50 3 10 1069 29480 22060 9.04 4.4 472
FHX 60 3 10 1325 34010 26230 4.69 3.4 522
FHX 20 4 10 253 10980 7450 2.2 8.7 57
FHX 25 4 10 404 15630 10970 3.1 6.0 125
FHX 30 4 10 604 21870 15600 4.4 10.2 165
FHX 40 4 10 744 28330 19950 5.7 9.7 261
FHX 50 4 10 1022 35510 25680 8.75 4.2 472
FHX 60 4 10 1258 41980 31070 4.13 3.1 522
NOTE: Based on 80°F DB and 67°F WB EAT, 45°F EWT, 10°F temperature rise, high fan speed. Motor type is PSC and
motor voltage is 115/1/60. Airflow under dry coil conditions. Models FHX tested at 0.0" external static pressure. Models FHF
and FHP tested at 0.05" external static pressure.

Johnson Controls 9
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal

physical data

HEATING CAPACITY
NOMINAL 1 ROW 2 ROW
UNIT TYPE UNIT SIZE
CFM QS (MBH) GPM WPD QS (MBH) GPM WPD
20 250 8.6 0.4 0.2 15.7 0.8 0.9
25 400 15.0 0.6 0.6 21.0 1.1 3.1
FHP 30 500 16.1 0.8 0.6 29.2 1.5 3.2
FHF 40 750 23.6 1.2 1.5 40.5 2.1 1.6
50 1000 28.7 1.5 0.7 53.7 2.7 2.9
60 1400 36.1 1.9 1.1 66.9 3.4 4.7
20 250 7.9 0.4 0.3 14.0 0.8 1.5
25 350 10.8 0.6 0.5 19.3 1.0 2.6
30 450 13.5 0.7 0.9 24.0 1.3 4.8
FHX
40 650 20.4 1.1 2.0 34.0 1.8 1.7
50 850 22.5 1.2 0.7 40.7 2.1 3.1
60 1200 30.9 1.6 1.2 55.4 2.9 5.5
NOTE: Based on 70°F DB EAT, 180°F EWT, 40°F temperature drop, high fan speed.

UNIT WEIGHT DATA


UNIT SIZE
COMPONENT
20 25 30 40 50 60
FHF BASE UNIT 40 (18) 51 (23) 59 (27) 69 (31) 91 (41) 111 (50)
FHP BASE UNIT 45 (20) 56 (25) 65 (30) 80 (36) 103 (47) 123 (56)
FHX BASE UNIT 119 (54) 138 (63) 155 (70) 181 (82) 220 (100) 257 (117)
1 ROW - DRY 7 [3] 8 [4] 9 [4] 10 [5] 12 [5] 14 [6]
1 ROW - WET 8 [4] 10 [4] 10 [5] 12 [5] 14 [6] 16 [7]
2 ROW - DRY 9 [4] 11 [5] 12 [5] 14 [6] 17 [8] 20 [9]
2 ROW - WET 12 [5] 13 [6] 14 [7] 17 [8] 21 [10] 25 [11]
COIL 3 ROW - DRY 12 [5] 14 [6] 15 [7] 19 [9] 23 [10] 26 [12]
ROWS 3 ROW - WET 14 [6] 17 [8] 19 [9] 24 [11] 28 [13] 33 [15]
4 ROW - DRY 14 [6] 16 [7] 18 [8] 23 [10] 28 [13] 33 [15]
4 ROW - WET 17 [8] 20 [9] 23 [11] 29 [13] 35 [16] 41 [19]
5 ROW - DRY 16 [7] 19 [8] 21 [9] 25 [12] 31 [14] 35 [16]
5 ROW - WET 21 [9] 24 [11] 27 [12] 32 [14] 38 [17] 44 [20]
NOTE: Unit weight data is in pounds (kilograms).

10 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)

electric heat
Johnson Controls offers electric heating coils for specific application with all FH Series Fan Coil units. This allows
the flexibility to provide an unrivaled amount of electric heat options in one complete package.

Standard Features useful formulas


• ETL listed as an assembly kW* = CFM x ∆T x 1.085**
for safety compliance 3413
• Single point power connection 1Ø AMPs = kW x 1000
• Mounted in preheat position Volts
• Automatic reset primary and back-up * 1kW = 3413 BTU/H
secondary thermal limits ** Capacity at sea level
• Internal wiring rated at 105°C Altitude Considerations:
• Integral electric heat assembly with Reduce by 0.034 for each 1000 ft. of altitude
removable element for easy service above sea level.
• Stainless steel terminals and hardware Example: 5000 ft./1000 ft. = 5
optional features 5 x 0.034 = 0.17
• Silent solid state relays 1.085 - 0.17 = 0.915
• Manual reset secondary limits
• Door interlocking disconnect switch
• Main fusing (Branch fusing for EH>48 amps)
ELECTRICAL CALCULATIONS INFORMATION
1. Contact your local Johnson Controls sales office.
2. Non-Fused Door Interlock Disconnect Switch shall be sized according to MCA.
3. Fused Door Interlock Disconnect Switch and Main Fusing shall be sized according to MOP.
Electric Heat Selection Chart (AMPs)
MBH 5.1 6.8 10.2 13.7 17.1 20.5 25.6 27.3 34.1
UNIT
KW 1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 10.0
SIZE
VOLTS AMPS
115 13.0 17.4 26.1
208 7.2 9.6 14.4
20
230 6.5 8.7 13.0
277 5.4 7.2 10.8
115 13.0 17.4 26.1
208 7.2 9.6 14.4
25
230 6.5 8.7 13.0
277 5.4 7.2 10.8
115 13.0 17.4 26.1 34.8 43.5
208 7.2 9.6 14.4 19.2 24.0 28.8
30
230 6.5 8.7 13.1 17.4 21.7 26.1
277 5.4 7.2 10.8 14.4 18.1 21.7
115 17.4 26.1 34.8 43.5
208 9.6 14.4 19.2 24.0 28.8 33.7
40
230 8.7 13.1 17.4 21.7 26.1 30.4
277 7.2 10.8 14.4 18.1 21.7 25.3
115 26.1 34.8 43.5
208 14.4 19.2 24.0 28.8 33.7 38.5
50
230 13.1 17.4 21.7 26.1 30.4 34.8
277 10.8 14.4 18.1 21.7 25.3 28.9
115 26.1 34.8 43.5
208 14.4 19.2 24.0 28.8 33.7 38.5
60
230 13.1 17.4 21.7 26.1 30.4 34.8 43.5
277 10.8 14.4 18.1 21.7 25.3 28.9 36.1
NOTES:
1. Shaded areas of the electric heat selection chart indicate kW and voltage options not available.
2. Available voltages are single phase, 60 hertz.
3. Size heater for Leaving Air Temperature (LAT) less than 104°F.
4. Silent, solid state heater relay is available for sound sensitive environments.
5. Ask your Johnson Controls representative about continuously modulating electric heat using SSR and special control
options.

Johnson Controls 11
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal

FAN PERFORMANCE CURVES (psc motors)

1. Fan curves on the following pages depict actual performance of each motor tap without any additional fan balance adjust-
ment. Actual capacities which fall below each curve can be obtained by adding an adjustment device. Units should not be
run prior to installation of downstream ductwork; otherwise, damage to the motor may result.
2. Johnson Controls Fan Coil Units are equipped with permanent split-capacitor (PSC) motors with three taps (High, Medium
and Low) which provides variable horsepower outputs. Most often, size selections are conservative and actual CFM require-
ments and/or external static pressure requirements are lower than those specified. In this case, the unit fan motor can be
run at low or medium tap, substantially reducing the operating cost of the unit.
3. All fan curves are for 115/1/60 motors and include pressure losses for cabinet, electric heater, and 3 or 4 row coil. Plenum
units include a clean 1" throwaway filter. For other coil configurations, adjust performance curves based on pressure losses
for the coils using Web-Select®.
4. See page 14 for fan motor electrical data.
5. For additional high static pressure applications and rating points, contact factory.

Size 20 Size 25
Model FHP (Plenum)
Model FHP (Plenum)
0.40 0.80

0.35 0.70
HIGH

0.30 MED 0.60


HIGH
LOW
0.25
ESP (IN. W.G.)

0.50
ESP (IN. W.G.)
MED
0.20 0.40

0.15 0.30

LOW
0.10 0.20

0.05 0.10

0.00 0.00
0 50 100 150 200 250 300 0 50 100 150 200 250 300 350 400 450 500
3 ROW COIL 3 ROW COIL
SCFM SCFM
4 ROW COIL
4 ROW COIL

Model FHF (Free Return) Model FHF (Free Return)


0.40 0.80

0.35 HIGH 0.70

MED HIGH
0.30 0.60
LOW
ESP (IN. W.G.)

0.50
ESP (IN. W.G.)

0.25

MED
0.20 0.40

0.15 0.30
LOW

0.10 0.20

0.05 0.10

0.00 0.00
0 50 100 150 200 250 300 350 400 0 50 100 150 200 250 300 350 400 450 500

SCFM 3 ROW COIL SCFM 3 ROW COIL


4 ROW COIL
4 ROW COIL

Model FHX (Exposed Cabinet) Model FHX (Exposed Cabinet)


0.40 0.70

0.35 0.60
HIGH

0.30
0.50 MED

0.25
ESP (IN. W.G.)

ESP (IN. W.G.)

0.40

0.20 LOW
0.30
0.15

0.20
0.10

0.10
0.05
HIGH
LOW MED
0.00 0.00
0 50 100 150 200 250 300 0 50 100 150 200 250 300 350
3 ROW COIL SCFM 3 ROW COIL
SCFM 4 ROW COIL 4 ROW COIL

12 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)

Size 30 Size 40

Model FHP (Plenum) Model FHP (Plenum)

0.35 0.80

HIGH
0.30 0.70 HIGH
MED
0.60
0.25
MED
LOW

ESP (IN. W.G.)


ESP (IN. W.G.)

0.50
0.20
0.40
0.15
0.30

0.10
0.20

LOW
0.05 0.10

0.00 0.00
0 50 100 150 200 250 300 350 400 450 500 550 600 0 100 200 300 400 500 600 700 800 900

SCFM 3 ROW COIL SCFM 3 ROW COIL


4 ROW COIL 4 ROW COIL

Model FHF (Free Return) Model FHF (Free Return)

0.40 0.90

0.35 0.80
HIGH HIGH
0.70
0.30
MED
0.60
ESP (IN. W.G.)

0.25
ESP (IN. W.G.)

MED

LOW 0.50
0.20
0.40
0.15
0.30

0.10
0.20

0.05 LOW
0.10

0.00 0.00
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 0 100 200 300 400 500 600 700 800 900

SCFM 3 ROW COIL SCFM 3 ROW COIL


4 ROW COIL 4 ROW COIL

Model FHX (Exposed Cabinet) Model FHX (Exposed Cabinet)


0.40 0.80

0.35 0.70

0.30 0.60

0.25 0.50
ESP (IN. W.G.)

ESP (IN. W.G.)

0.20 0.40

0.15 0.30

0.10 0.20

HIGH
0.05 MED 0.10 MED HIGH
LOW
LOW
0.00 0.00
0 50 100 150 200 250 300 350 400 450 500 0 50 100 150 200The thick
250 line
300 350 3 row
400coil 450 500 550 600 650 700
indicates
3 ROW COIL 3 ROW COIL
SCFM 4 ROW COIL SCFM
4 ROW COIL

Johnson Controls 13
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal

FAN PERFORMANCE CURVES (psc motors)

Size 50 Size 60

Model FHP (Plenum) Model FHP (Plenum)


0.80 0.90

0.70 0.80
HIGH

0.70
0.60 MED

0.60
0.50

ESP (IN. W.G.)


ESP (IN. W.G.)

0.50
0.40
HIGH 0.40 LOW
0.30
0.30
MED
0.20
0.20
LOW
0.10 0.10

0.00 0.00
0 200 400 600 800 1000 1200 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
SCFM 3 ROW COIL SCFM 3 ROW COIL
4 ROW COIL 4 ROW COIL

Model FHF (Free Return)


Model FHF (Free Return)
1.00 0.90

0.90 HIGH
0.80
HIGH
0.80
0.70

0.70 MED MED


0.60
ESP (IN. W.G.)

0.60
ESP (IN. W.G.)

0.50
0.50
0.40
0.40 LOW

0.30
0.30
LOW
0.20
0.20

0.10 0.10

0.00 0.00
0 200 400 600 800 1000 1200 1400 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700
SCFM 3 ROW COIL SCFM 3 ROW COIL
4 ROW COIL 4 ROW COIL

Model FHX (Exposed Cabinet) Model FHX (Exposed Cabinet)


0.90 0.80

0.80
0.70

0.70
0.60

0.60
0.50
ESP (IN. W.G.)

ESP (IN. W.G.)

0.50

0.40
0.40

0.30
0.30 HIGH
HIGH
0.20
0.20
MED
MED
LOW 0.10
0.10
LOW

0.00 0.00
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 0 100 200 300 400 500 600 700 800 900 1000 1100 1200
3 ROW COIL 3 ROW COIL
SCFM 4 ROW COIL SCFM 4 ROW COIL

14 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)

motor, fan and sound data


PSC MOTOR AND FAN DATA
UNIT FAN MOTOR # OF 115 VOLTS 208-230 VOLTS 277 VOLTS
WATTS
SIZE SPEED H.P. (QTY.) FANS AMPS AMPS AMPS
High (1) 1/30 57 0.8 0.4 0.3
20 Medium (1) 1/50 1 39 0.4 0.3 0.3
Low (1) 1/60 33 0.3 0.3 0.3
High (1) 1/15 125 1.0 0.5 0.45
25 Medium (1) 1/30 1 90 0.9 0.3 0.3
Low (1) 1/60 60 0.5 0.2 0.2
High (1) 1/10 165 1.6 0.7 0.6
30 Meduim (1) 1/30 2 76 0.8 0.3 0.5
Low (1) 1/60 47 0.5 0.2 0.4
High (1) 1/6 261 2.6 0.9 0.85
40 Medium (1) 1/12 2 162 1.5 0.5 0.5
Low (1) 1/40 75 0.6 0.4 0.3
(1) 1/8 215 1.6 0.9 0.68
High
(1) 1/6 257 2.1 0.9 0.85
(1) 1/15 145 1.3 0.6 0.5
50 Medium 3
(1) 1/12 156 1.5 0.5 0.5
(1) 1/40 69 0.8 0.3 0.3
Low
(1) 1/40 75 0.6 0.4 0.3
High (2) 1/6 522 4.2 1.8 1.7
60 Medium (2)1/12 4 324 3.0 1.0 1.0
Low (2) 1/40 150 1.2 0.6 0.6
NOTES:
1. Motor electrical data is nameplated data. Actual data will vary with application. Watts shown are for115V.
2. 230 volt motor is nameplated for 208-230/1/60. Use 230 volt motor data for 208 volt applications.
3. Unit size 30, 208-230 and 277 volt motors are 1/12 HP at high tap.

EC MOTOR AND FAN DATA


HORIZONTAL PLENUM
MOTOR 115 VOLTS 208-230 VOLTS 277 VOLTS
UNIT FAN # OF
H.P. WATTS 3-PHASE 3-PHASE 3-PHASE
SIZE SPEED FANS FLA FLA FLA
(QTY.) NEUTRAL NEUTRAL NEUTRAL
20 High (1) 1/4 1 39 1.00 1.50 0.70 1.00 0.70 1.00
25 High (1) 1/4 1 74 1.70 2.50 1.30 1.90 1.20 1.70
30 High (1) 1/4 2 70 1.70 2.50 1.30 1.90 1.20 1.70
40 High (1) 1/4 2 124 2.80 4.00 2.10 3.00 2.10 3.00
50 High (2) 1/4 3 185 4.00 5.80 3.00 4.40 2.80 4.00
60 High (2) 1/4 4 250 5.20 7.40 4.00 4.80 3.80 5.40

HORIZONTAL EXPOSED
MOTOR 115 VOLTS 208-230 VOLTS 277 VOLTS
UNIT FAN # OF
H.P. WATTS 3-PHASE 3-PHASE 3-PHASE
SIZE SPEED FANS FLA FLA FLA
(QTY.) NEUTRAL NEUTRAL NEUTRAL
20 High (1) 1/4 1 25 0.70 1.00 0.60 0.90 0.60 0.90
25 High (1) 1/4 1 40 1.00 1.50 0.70 1.00 0.70 1.00
30 High (1) 1/4 2 44 1.00 1.50 0.80 1.20 0.80 1.20
40 High (1) 1/4 2 79 1.90 2.70 1.40 2.00 1.40 2.00
50 High (2) 1/4 3 92 2.40 3.40 1.80 2.60 1.80 2.60
60 High (2) 1/4 4 148 3.60 5.20 2.80 4.00 2.80 4.00
NOTES:
1. Watts as shown are for a Plenum / Exposed unit with .05" ESP, 4 row coil, 115/1/60, 12 FPI, and throwaway filters
2. Motors nameplated for 208-230/1/60. Data is at 230 volts
3. Motor HP as noted is a nominal rating
4. Data as supplied is for reference only. For project specific operational points see seletion tool report out.

Johnson Controls 15
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal

sound data

sound data
TOTAL SOUND POWER LEVEL
UNIT SIZE FAN SPEED SCFM OCTAVE BAND / CENTER FREQUENCY (HZ)
2/125 3/250 4/500 5/1000 6/2000 7/4000 8/8000
High 282 55 59 53 50 46 38 36
20 Medium 216 50 52 47 44 38 31 32
Low 175 47 48 43 39 32 27 31
High 420 58 62 57 54 51 44 39
25 Medium 286 53 53 49 45 41 34 29
Low 180 48 42 38 36 33 27 27
High 522 60 60 57 56 50 44 40
30 Medium 458 57 55 54 52 46 40 36
Low 269 48 44 43 39 32 27 31
High 810 65 68 64 60 55 51 47
40 Medium 565 59 59 57 51 46 40 35
Low 300 51 46 41 36 28 27 30
High 1050 61 66 68 62 56 52 49
50 Medium 840 56 61 63 55 49 44 40
Low 490 48 53 59 46 39 33 32
High 1400 67 72 70 68 59 54 51
60 Medium 1050 61 65 67 57 52 47 42
Low 500 50 56 48 40 33 28 31
NOTES:
1. Sound data tested in accordance with AHRI 350-2000.
2. Sound levels are expressed in decibels, dB RE: 1 x 10-12 watts.
3. Total sound power level data based on Model FHP with fan CFM at corresponding motor tap with 115/1/60 volt motor, 3 or
4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses.

16 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)

dimensional data

model fHF free return units


Drawings are not to scale and not for submittal or installation purposes.

Johnson Controls 17
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal

dimensional data

model FHP plenum units


Drawings are not to scale and not for submittal or installation purposes.

18 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)

model fhx exposed cabinet units


Drawings are not to scale and not for submittal or installation purposes.

Johnson Controls 19
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal

dimensional data

telescoping bottom panel


Drawings are not to scale and not for submittal or installation purposes.

20 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)

guide specifications

General

Furnish and install Johnson Controls Model FH Unit mounting shall be by hanger brackets provided at
Horizontal Concealed Direct Drive Fan Coil Units where four locations.
indicated on the plans and in the specifications. Units
shall be completely factory assembled, tested and PAINTED Finish
shipped as one piece. All units shall be capable of
meeting or exceeding the scheduled capacities for cool- All painted cabinet exterior panels shall be finished with
ing, heating and air delivery. All unit dimensions for each a heat cured anodic acrylic powder paint of the standard
model and size shall be considered maximums. Units factory color.
shall be ETL listed in compliance with UL/ANSI Standard
1995, and be certified as complying with the latest edi- Sound
tion of AHRI Standard 440.
Units shall have published sound power level data
Construction tested in accordance with AHRI Standard 350-2000
(non-ducted equipment).
All unit chassis shall be fabricated of heavy gauge
galvanized steel panels. All exterior panels shall be Fan Assembly
insulated with 1/2" thick insulation with a maximum k
value of .24 (BTU - in) / (hr - ft2 - °F) and rated for a Unit fan shall be a dynamically balanced, forwardly
maximum air velocity of 5000 f.p.m. Insulation must curved, DWDI centrifugal type constructed of 18 gauge
meet all requirements of ASTM C1071 (including zinc coated galvanized steel for corrosion resistance.
C665), UL 181 for erosion, and carry a 25/50 rating Motors shall be high efficiency, permanently lubricated
for flame spread/smoke developed per ASTM E-84, sleeve bearing, permanent split-capacitor type with UL
UL 723 and NFPA 90A. and CSA listed automatic reset thermal overload protec-
tion and three separate horsepower taps. Single speed
All concealed units shall have a minimum 1-1/2" duct motors are not acceptable.
collar on the discharge. Plenum and exposed units
shall have a minimum 3/4" duct collar on the return. The fan assembly shall be easily removable for servic-
ing the motor and blower at, or away from the unit. The
All exposed units shall have exterior panels fabri- entire fan assembly shall be able to come out of the
cated of galvannealed steel. The fan and filter bottom unit by removing two screws and unplugging the motor.
access panel shall be attached with quarter turn quick Plenum unit fan assemblies shall be easily serviced
open fasteners to allow for easy removal and access through an access panel provided.
for service.
Option: Provide Electronically Commutated (EC) Motor
Option: Provide foil faced insulation in lieu of standard. capable of operation with low voltage 3 speed thermo-
Foil insulation shall meet or exceed the requirements stat. Motor shall come factory programmed and
stated above, and in addition meet ASTM Standards configured for 3 speed operation. Each speed shall be
C-665 and C-1136 for biological growth in insulation. manually adjustable in the field. All manual speed
Insulation shall be lined with aluminum foil, fiberglass adjustments shall be stored in non-volatile memory.
scrim reinforcement, and 30 pound kraft-paper lami- Motor shall be capable of accepting a 2-10 VDC output
nated together with a flame resistant adhesive. All from BAS. Motor bearings shall be rated for L10-40,000
exposed edges shall be sealed to prevent any fibers hours.
from reaching the air stream.
Option: Provide an electronic (SCR) fan speed control-
Option: Provide Elastomeric Closed Cell Foam Insulation ler as an aid in balancing the fan capacity. The speed
in lieu of standard. Insulation shall conform to UL 181 controller shall have a turn down stop to prevent the
for erosion and NFPA 90A for fire, smoke and melting, possibility of harming the motor bearings, and incorpo-
and comply with a 25/50 Flame Spread and Smoke rate electrical noise suppression to minimize noise on
Developed Index per ASTM E-84 or UL 723. Additionally, the incoming power lines.
insulation shall comply with Antimicrobial Performance
Rating of 0, no observed growth, per ASTM G-21. Option: Devices used to energize and de-energize
Polyethylene insulation is not acceptable. (switch) fan speeds must be totally silent. Magnetic,
mercury, and/or quiet relays and/or contactors are not
acceptable.

Johnson Controls 21
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal

guide specifications

Coils

All cooling and heating coils shall optimize rows and Option: Provide a secondary drain connection on the
fins per inch to meet the specified capacity. Coils shall primary drain pan for condensate overflow.
have seamless copper tubes and shall be mechani-
cally expanded to provide an efficient, permanent bond Filters
between the tube and fin. Fins shall have high effi-
ciency aluminum surface optimized for heat transfer, air All plenum and exposed units shall be furnished with a
pressure drop and carryover.All coils shall be hydro- minimum 1" nominal glass fiber throwaway filter. Filters
statically tested at 450 PSIG air pressure under water, shall be tight fitting to prevent air bypass. Plenum unit
and rated for a maximum of 300 PSIG working pressure filters shall be easily removable from the bottom of the
at 200°F. unit without the need for tools.

Steam coils shall be standard steam type suitable for Option: Provide unit with 1" pleated filter (MERV 8).
temperatures above 35°F and 15 PSIG maximum work-
ing pressure. Electrical

Option: Coil casing shall be fabricated from Stainless Units shall be furnished with single point power connec-
Steel. tion. Provide an electrical junction box for motor and
other electrical terminations.
All coils shall be provided with a manual air vent fitting
to allow for coil venting. Option: Provide a hinged electrical enclosure in the
bottom of the unit for easy access to all electrical com-
Option: Provide automatic air vents in lieu of manual ponents, terminal blocks and wiring.
air vents.
Electric Heat
Heating coils shall be furnished in the reheat or preheat
position on units with chilled water coils, or in the reheat Furnish an electric resistance heating assembly as an
position for DX coils. integral part of the fan coil unit, with the heating capac-
ity, voltage and kilowatts scheduled. The heater
Drain Pans assembly shall be designed and rated for installation
on the fan coil unit without the use of duct extensions
Primary condensate drain pans shall be single wall, or transitions, and be located in the unit as to not
heavy gauge galvanized steel for corrosion resistance, expose the fan assembly to excessive leaving air tem-
and extend under the entire cooling coil. Drain pans peratures that could affect motor performance.
shall be of one-piece construction and be double sloped
for condensate removal. Drain pans on concealed The heater and unit assembly shall be listed for zero
models shall be field reversible for right or left hand clearance and meet all NEC requirements, and be ETL
connections. listed with the unit as an assembly in compliance with
UL/ANSI Standard 1995.
The drain pan shall be externally insulated with a fire
retardant, closed cell foam insulation. The insulation All heating elements shall be open coil type nichrome
shall carry no more than a 25/50 Flame Spread and wire mounted in ceramic insulators and located in an
Smoke Developed Rating per ASTM E-84 and UL 723 insulated heavy gauge galvanized steel housing. All
and an Antimicrobial Performance Rating of 0, no elements shall terminate in a machine staked stainless
observed growth, per ASTM G-21. steel terminal secured with stainless steel hardware for
corrosion resistance. The element support brackets
Option: Provide a single wall primary drain pan con- shall be spaced no greater than 3-1/2" on center. All
structed entirely of heavy gauge stainless steel for internal wiring shall be rated for 105°C minimum.All
superior corrosion resistance. Stainless steel drain pans heaters shall include overtemperature protection con-
shall be externally insulated and meet or exceed the sisting of an automatic reset primary thermal limit and
requirements stated above. back up secondary thermal limit. All heaters shall be
single stage.

22 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)

Option: Provide a manual reset secondary thermal Option: Provide 3-wire floating point modulating control
limit. valve (fail-in-place) in lieu of standard 2-position control
valve with factory assembled valve piping package.
All units with electric heat shall have a bottom hinged
electrical enclosure for easy access and service to the Option: Provide high pressure close-off actuators for
electrical components and wiring. An incoming line 2-way on/off control valves. Maximum close-off pres-
power distribution block shall be provided and desig- sure is 50 PSIG (1/2") or 25 PSIG (3/4)".
nated to accept single point power wiring capable of
carrying 125% of the calculated load current. Option: Provide either a fixed or adjustable flow control
device for each piping package.
Option: Devices used to energize and de-energize
(switch) electric heat must be totally silent. Magnetic, Option: Provide pressure-temperature ports for each
mercury, and/or quiet relays and/or contactors are not piping package.
acceptable.
Piping package shall be completely factory assembled,
Piping Packages including interconnecting pipe, and shipped separate
from the unit for field installation on the coil, so as to
Provide a standard factory assembled valve piping minimize the risk of freight damage.
package to consist of a 2 or 3 way, on/off, motorized
electric control valve and two ball isolation valves.
Control valves are piped normally closed to the coil.
Maximum entering water temperature on the control
valve is 200°F, and maximum close-off pressure is 40
PSIG (1/2") or 20 PSIG (3/4"). Maximum operating
pressure shall be 300 PSIG.

Johnson Controls 23
FORM 115.26-EG7 (215) FH Fan-Coil Units Low-Profile, Horizontal

NOTES

24 Johnson Controls
FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (215)

NOTES

Johnson Controls 25
Printed on recycled paper

Form: 115.26-EG7 (215) Supersedes: 115.26-EG7 (514)


© 2015 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 Printed in USA
www.johnsoncontrols.com