ENGINEERING DATA
Split Type Air Conditioners
Split Type Air Conditioners
- Cooling Only -
FTKC-N Series
FTKC-N Series
EDMT041428
Split Type
Air Conditioners
FTKC-N Series
FTKC25NVM RKC25NVM
FTKC35NVM RKC35NVM
Cooling Only
FTKC50NVM RKC50NVM
FTKC60NVM RKC60NVM
1. Power Supply ..........................................................................................2
2. Functions.................................................................................................3
3. Specifications ..........................................................................................4
4. Dimensions .............................................................................................6
4.1 Indoor Unit................................................................................................6
4.2 Outdoor Unit .............................................................................................7
5. Wiring Diagrams......................................................................................8
5.1 Indoor Unit................................................................................................8
5.2 Outdoor Unit .............................................................................................9
6. Piping Diagrams....................................................................................10
6.1 Indoor Unit..............................................................................................10
6.2 Outdoor Unit ...........................................................................................11
7. Capacity Tables ....................................................................................13
7.1 Cooling Only...........................................................................................13
7.2 Capacity Correction Factor by the Length of Refrigerant Piping
(Reference) ............................................................................................15
8. Operation Limit......................................................................................16
9. Sound Level ..........................................................................................17
9.1 Measuring Location ................................................................................17
9.2 Indoor Unit..............................................................................................17
9.3 Outdoor Unit ...........................................................................................18
10.Electric Characteristics..........................................................................19
11.Installation Manual ................................................................................20
11.1 25/35 Class ............................................................................................20
11.2 50/60 Class ............................................................................................30
12.Operation Manual..................................................................................40
13.Optional Accessories ............................................................................65
13.1 Option List ..............................................................................................65
13.2 <KPW937B4> Air Direction Adjustment Grille........................................66
13.3 <KPW945A4> Air Direction Adjustment Grille........................................67
1. Power Supply
Indoor Unit Outdoor Unit Power Supply
FTKC25NVM RKC25NVM
FTKC35NVM RKC35NVM 1 phase, 220 - 230 - 240 V, 50 Hz
FTKC50NVM RKC50NVM 1 phase, 220 - 230 V, 60 Hz
FTKC60NVM RKC60NVM
2. Functions
FTKC25/35NVM
FTKC50/60NVM
FTKC25/35NVM
FTKC50/60NVM
RKC25/35NVM
RKC50/60NVM
RKC25/35NVM
RKC50/60NVM
Category Functions Category Functions
Basic Inverter (with inverter power control) z z Health & Air-purifying filter — —
Function Clean
Operation limit for cooling (°CDB) 19.4 19.4 Photocatalytic deodorising filter — —
~ 46 ~ 46
Air-purifying filter with photocatalytic
Operation limit for heating (°CWB) — — deodorising function — —
3. Specifications
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V
Indoor Unit FTKC25NVM FTKC35NVM
Model
Outdoor Unit RKC25NVM RKC35NVM
kW 2.5 (1.2 ~ 3.4) 3.5 (1.3 ~ 4.1)
Capacity Btu/h 8,500 (4,100 ~ 11,600) 11,900 (4,400 ~ 14,000)
Rated (Min. ~ Max.)
kcal/h 2,150 (1,030 ~ 2,920) 3,010 (1,120 ~ 3,530)
Moisture Removal L/h 1.2 1.9
Running Current (Rated) A 3.4 - 3.3 - 3.1 / 3.4 - 3.3 4.6 - 4.4 - 4.2 / 4.6 - 4.4
Power Consumption (Rated) W 700 990
Power Factor (Rated) % 93.6 - 92.3 - 94.1 / 93.6 - 92.3 97.8 - 97.8 - 98.2 / 97.8 - 97.8
COP (Rated) W/W 3.57 3.54
Liquid mm φ 6.4 φ 6.4
Piping φ 9.5 φ 9.5
Connections Gas mm
Drain mm φ 16.0 φ 16.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length m 15 15
Max. Interunit Height Difference m 12 12
Chargeless m 10 10
Amount of Additional Charge of g/m 20 20
Refrigerant
Indoor Unit FTKC25NVM FTKC35NVM
Front Panel Colour Shiny Pure White Shiny Pure White
H 9.0 (318) 9.2 (324)
M m³/min 6.7 (237) 6.9 (244)
Airflow Rate (cfm)
L 4.4 (155) 4.6 (162)
SL 3.5 (124) 3.6 (127)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 16 16
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards
Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof
Running Current (Rated) A 0.19 - 0.18 - 0.17 / 0.19 - 0.18 0.27 - 0.26 - 0.24 / 0.27 - 0.26
Power Consumption (Rated) W 39 57
Power Factor (Rated) % 93.3 - 94.2 - 95.6 / 93.3 - 94.2 96.0 - 95.3 - 99.0 / 96.0 - 95.3
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) mm 283 × 770 × 203 283 × 770 × 203
Packaged Dimensions (H × W × D) mm 263 × 840 × 344 263 × 840 × 344
Weight (Mass) kg 8 8
Gross Weight (Gross Mass) kg 10 10
Sound
Pressure H / M / L / SL dB(A) 38 / 33 / 25 / 22 39 / 34 / 26 / 23
Level
Outdoor Unit RKC25NVM RKC35NVM
Casing Colour Ivory White Ivory White
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Compressor Model 1YC25BXD 1YC25BXD
Motor Output W 860 860
Refrigerant Type FW68DA FW68DA
Oil Charge L 0.350 0.350
Type R-32 R-32
Refrigerant
Charge kg 0.5 0.7
Airflow Rate H m³/min 27.1 (957) 27.1 (957)
(cfm)
Type Propeller Propeller
Fan
Motor Output W 20 20
Running Current (Rated) A 3.21 - 3.12 - 2.93 / 3.21 - 3.12 4.33 - 4.14 - 3.96 / 4.33 - 4.14
Power Consumption (Rated) W 661 933
Power Factor (Rated) % 93.6 - 92.1 - 94.0 / 93.6 - 92.1 97.9 - 98.0 - 98.2 / 97.9 - 98.0
Starting Current A 2.5 2.5
Dimensions (H × W × D) mm 550 × 658 × 275 550 × 658 × 275
Packaged Dimensions (H × W × D) mm 616 × 788 × 359 616 × 788 × 359
Weight (Mass) kg 28 32
Gross Weight (Gross Mass) kg 32 34
Sound
Pressure H dB(A) 47 - 48 - 48 / 49 - 50 49 - 49 - 50 / 49 - 50
Level
Drawing No. 3D089138A 3D089139A
Note: The data are based on the conditions shown in the table below.
Cooling Piping Length Conversion Formulae
Note: The data are based on the conditions shown in the table below.
Cooling Piping Length Conversion Formulae
4. Dimensions
4.1 Indoor Unit
FTKC25/35NVM
PERFORMANCE)
REAR
(SPACE FOR
770
30MIN.
LEFT RIGHT
INCLUDING
MOUNTING PLATE
283
SIGNAL RECEIVER
TERMINAL BLOCK
OPERATION LAMP
WITH EARTH
TIMER LAMP TERMINAL
INDOOR UNIT ON/OFF SWITCH (INSIDE)
BOTTOM FLAPS
GAS PIPE φ9.5 CuT DRAIN HOSE
ROOM TEMP. THERMISTOR (THE LENGTH OF PIPE OUTSIDE
(INSIDE) (CONNECTING PART
THE UNIT : ABOUT 350) I.D. φ14
LIQUID PIPE φ6.4 CuT O.D. φ16
(THE LENGTH OF PIPE OUTSIDE THE HOSE LENGTH OF OUTSIDE
THE UNIT : ABOUT 400) THE UNIT IS ABOUT 450)
16
PLATE
6
58 18 BLADE ANGLE
UP/DOWN (AUTOMATIC)
172
DAIKIN
283
41.3
COOLING DRY
5˚ 5˚
163
41.3
FAN WALL HOLE FOR EMBEDDED PIPING
RIGHT/LEFT (MANUAL)
φ65 HOLE
WALL HOLE
5˚
STANDARD LOCATIONS OF WALL HOLES φ65 HOLE
WIRELESS REMOTE CONTROLLER 45˚
45˚ 45˚ 3D089148
(ARC433A88)
FTKC50/60NVM
PERFORMANCE)
REAR REAR
LEFT RIGHT
(SPACE FOR
MIN.30
( INSTALLATION
INCLUDING
PLATE )
239
237
MIN.50 MIN.50
MODEL NAME (SPACE FOR (SPACE FOR
PLATE MAINTENANCE) REQUIRED SPACE MAINTENANCE)
290
COOLING DRY
14.5
155.5
10˚ 5˚
290
(163)
52
40˚ 10˚ 5˚
35˚
40˚ 35˚
FAN
VERTICAL BLADE (MANUAL)
52
RKC25/35NVM
150
4-HOLES FOR ANCHOR BOLTS
WITH DRAIN JOINT) (M8 OR M10)
470 96
379
11
100
150
40
50 50
300
50
297
50
100
HANDLE BRAND NAME LABEL MANUFACTURE'S LABEL
275 13.5 12 658 50 8 OUTDOOR AIR THERMISTOR
LIQUID
STOP VALVE
WIRING (φ6.4 CuT)
INLET
550
SERVICE
PORT
168
108
155
GAS STOP VALVE
(φ9.5 CuT)
INDICATION LABEL (INDONESIA)
FOR INDONESIA MODEL ONLY IN CASE OF REMOVING
STOP VALVE COVER
3D089153
RKC50/60NVM
DRAIN OUTLET MINIMUM SPACE FOR AIR PASSAGE WALL HEIGHT ON AIR OUTLET SIDE
100
(I.D.φ15.9 HOSE FOR CONNECTION) =LESS THAN 1200
825 78
325
100
124 580
350
2
36
50 50
50
350
350
330
300
100
350
IN CASE OF REMOVING
STOP VALVE COVER
10
25
89 64
3D083536B
5. Wiring Diagrams
5.1 Indoor Unit
FTKC25/35NVM
PCB2 PCB1
S27 S26
1 BLK 9 FIELD WIRING.
BLK
LED1 H1P BLK TRANSMISSION GRN/YLW
BLK CIRCUIT
LED2 H2P BLK FG 3
BLK GRN
BLK 2
BLK RECTIFIER H3
+ RED 3 OUTDOOR
9 BLK 1 V1 MR10 1
H2
WHT 2
H1
S1W BLK 1 CAUTION
F1U NOTE THAT OPERATION WILL
t˚ 3.15A X1M RESTART AUTOMATICALLY IF
+ THE MAIN POWER SUPPLY IS
R1T TURNED OFF AND THEN BACK
SIGNAL IPM200 ON AGAIN.
RECEIVER
1 2 1 5 1 6 9 12 1 S403 10
S32 S6 S200
BLK INDOOR
BLK
BLK
BLK
BLK
BLK
BLK
BLK
YLW
BLK BLK
WHT
BLK BLK
ORG
RED
BLU
BLK
FTKC50/60NVM
1
PCB3 PCB1
S49 S46 FU1 X1M 2
1 BLK 1 F1U H1
LED1 BLK 1
BLK 3 OUTDOOR
H1P 3.15A
BLK ~ WHT 2
BLK C102 V1
LED2 RED 3
BLK MR10 H2
H2P GRN
BLK
BLK FIELD WIRING.
LED3
H3P BLK C101 GRN/YLW
TRANSMISSION H3
9 BLK 9
CIRCUIT CAUTION
SW1 FG NOTE THAT OPERATION WILL RESTART
S21 AUTOMATICALLY IF THE MAIN POWER SUPPLY
t˚ IS TURNED OFF AND THEN BACK ON AGAIN.
HA S1 BZ : BUZZER
BZ RTH1 7 RED C101, C102 : CAPACITOR
R1T FG : FRAME GROUND
F1U : FUSE
4 BLU H1P~H3P : PILOT LAMP
BRN MR10 : MAGNETIC RELAY
MS
ORG
M1F : FAN MOTOR
M1S : SWING MOTOR
1 WHT
PCB1~PCB3 : PRINTED CIRCUIT BOARD
S47 S32 S41 M1F R1T, R2T : THERMISTOR
1 3 1 2 15 13 11 9 7 S1~S49 : CONNECTOR
SW1 : OPERATION SWITCH
V1 : VARISTOR
BLK
BLK
BLK
BLK
BLK
YLW
PNK
BLU
: PROTECTIVE EARTH
PCB2 S48
WIRELESS 1 3 t˚
REMOTE INDOOR
R2T M
CONTROLLER SIGNAL
RECEIVER
M1S
3D088910
RKC25/35NVM
3D088772A
RKC50/60NVM
6. Piping Diagrams
6.1 Indoor Unit
FTKC25/35NVM FTKC50/60NVM
INDOOR UNIT
INDOOR UNIT
HEAT EXCHANGER
7.0 CuT
4.8 CuT
(7.9 CuT)
7.0 CuT
THERMISTOR
CROSS FLOW FAN ON HEAT EXCH.
FIELD PIPING
(6.4 CuT)
M FIELD PIPING
CROSS FLOW FAN
REFRIGERANT FLOW
COOLING REFRIGERANT FLOW
COOLING
4D075755A 4D083425C
RKC25NVM
OUTDOOR UNIT
OUTDOOR TEMPERATURE
6.4 CuT HEAT EXCHANGER THERMISTOR
6.4 CuT
7.0 CuT
HEAT EXCHANGER
MOTOR OPERATED
THERMISTOR
VALVE
6.4 CuT 6.4 CuT 6.4 CuT
FAN MUFFLER
6.4 CuT
M MOTOR WITH
FILTER
PROPELLER FAN
STRAINER
4.8 CuT
6.4 CuT
9.5 CuT
FIELD PIPING
LIQUID STOP (6.4 CuT)
VALVE
REFRIGERANT FLOW
DISCHARGE PIPE 9.5 CuT FIELD PIPING
COMPRESSOR COOLING
THERMISTOR (9.5 CuT)
MUFFLER MUFFLER GAS STOP
ACCUMULATOR VALVE
3D089192A
RKC35NVM
OUTDOOR UNIT
7.0 CuT
HEAT EXCHANGER
MOTOR OPERATED
THERMISTOR
VALVE
6.4 CuT6.4 CuT 6.4 CuT
MUFFLER
FAN
M WITH
6.4 CuT
MOTOR
FILTER
PROPELLER FAN
STRAINER
4.8 CuT
7.9 CuT
9.5 CuT
FIELD PIPING
REFRIGERANT FLOW
(6.4 CuT)
LIQUID STOP
COOLING
VALVE
9.5 CuT FIELD PIPING
DISCHARGE PIPE COMPRESSOR
THERMISTOR (9.5 CuT)
MUFFLER MUFFLER GAS STOP
ACCUMULATOR VALVE
3D089185A
RKC50/60NVM
OUTDOOR UNIT
HEAT EXCHANGER
7.0 CuT OUTDOOR TEMPERATURE
THERMISTOR
7.0 CuT
M
7.9 CuT
6.4 CuT
PROPELLER FAN
FIELD PIPING
MUFFLER (6.4 CuT)
LIQUID STOP
DISCHARGE PIPE VALVE
THERMISTOR 12.7 CuT
COMPRESSOR FIELD PIPING
ACCUMULATOR 12.7 CuT (12.7 CuT)
GAS STOP
VALVE
REFRIGERANT FLOW
COOLING
3D090240
7. Capacity Tables
7.1 Cooling Only
FTKC25NVM + RKC25NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 9
BF 0.10
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D089843
FTKC35NVM + RKC35NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 9.2
BF 0.12
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D089844
FTKC50NVM + RKC50NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 14.3
BF 0.07
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the
BF : Bypass factor figures in the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D089845
FTKC60NVM + RKC60NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 15.4
BF 0.08
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the
BF : Bypass factor figures in the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D089846
Cooling (R-32)
(%)
100
Capacity correction factor
90
Range of the
refrigerant
80
additional
charge
5 10 15 (m)
Piping length
(R20651)
Cooling (R-32)
(%)
100
Capacity correction factor
90
80
Range of the refrigerant additional charge
5 10 15 20 25 30 (m)
Piping length
(R20375)
Note: The graphs show the factor when additional refrigerant of the proper quantity is charged.
8. Operation Limit
RKC25/35NVM
50
46
40
Continuous operation
Pull-down period
30
20
19.4
Notes : 10 14 20 23 28 30
The graph is based Indoor temp. (˚CWB)
on the following conditions.
· Equivalent piping length 7.5m
· Level difference 0m
· Air flow rate High
4D073983E
RKC50/60NVM
50
46
40
Outdoor temp. (˚CDB)
Continuous operation
Pull-down period
30
20
19.4
Notes : 10 14 20 23 28 30
The graph is based Indoor temp. (˚CWB)
on the following conditions.
• Equivalent piping length 7.5m
• Level difference 0m
• Air flow rate High
4D083533A
9. Sound Level
9.1 Measuring Location
1m 1m
0.8 m
MICROPHONE
MICROPHONE
50 50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60Hz POWER SOURCE 220-240/220-230V 50/60 Hz
20 20
APPROXIMATE APPROXIMATE NC-20
NC-20
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D089376 63 125 250 500 1000 2000 4000 8000 4D089379
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
FTKC50NVM FTKC60NVM
50 50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60Hz POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD JIS STANDARD
40 40
NC-40 220-240/220-230V 50/60Hz (H) NC-40 220-240/220-230V 50/60Hz (H)
220-240/220-230V 50/60Hz (L) 220-240/220-230V 50/60Hz (L)
30 Cooling 30 Cooling
NC-30 NC-30
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS NC-20 FOR CONTINUOUS NC-20
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D089508 63 125 250 500 1000 2000 4000 8000 4D089509
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
COOLING COOLING
70 OVER ALL (dB) 70 OVER ALL (dB)
NC-70 NC-70
50Hz 60Hz 50Hz 60Hz
SCALE SCALE
220-230-240V 220-230V
60 60
NC-60 A 47-48-48 49-50 NC-60 A 49-49-50 49-50
dB (0dB=0.0002µ bar)
50 50
dB (0dB=0.0002µ bar)
30 30
NC-30 NC-30
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING NC-20
NC-20 FOR CONTINUOUS
FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D089535A 63 125 250 500 1000 2000 4000 8000 4D089392A
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
RKC50NVM RKC60NVM
SCALE SCALE
OCTAVE BAND SOUND PRESSURE LEVEL
dB (0dB=0.0002µ bar)
50 50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60Hz (H) POWER SOURCE 220-240/220-230V 50/60Hz (H)
40 JIS STANDARD 40 JIS STANDARD
NC-40 NC-40
220-240/220-230V 50/60Hz (H) 220-240/220-230V 50/60Hz (H)
30 30
NC-30
NC-30
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING NC-20 THRESHOLD HEARING
FOR CONTINUOUS NC-20
FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D088836A 63 125 250 500 1000 2000 4000 8000 4D088837A
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
Symbols: Notes:
MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.
Indoor temp. 27°CDB / 19°CWB
MFA : Max. fuse amps (A) Outdoor temp. 35°CDB
RHz : Rated operating frequency (Hz) 2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
RLA : Rated load amps (A) 4. Instead of fuse, use circuit breaker.
OFM : Outdoor fan motor 5. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leak
IFM : Indoor fan motor detector capable of handling high harmonics must be used in
W : Fan motor rated output (W) order to prevent malfunctioning of the earth leak detector.)
FLA : Full load amps (A)
3D089021
3P363835-16C
3P363835-17C
3P363834-9B
4P202735-1
3P089958-2C