Papper-3 A
Papper-3 A
Papper-3 A
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
In a 22 kV feeder, if the voltage is raised from 22 kV to 66 kV for the same loading conditions,
1 the voltage drop in the same feeder system would be lowered to
6 Where transformer loading is known, the actual transformer loss at a given load can be
computed as:
_______________________ 1
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
a) high torque starting or where smooth acceleration over a broad speed range is required.
b) low torque starting or where steady acceleration over a narrow speed range is required.
c) normal torque starting or where high acceleration over a broad speed range is required.
d) low torque starting or where smooth acceleration over a broad speed range is required.
8 A 3-phase, 415 volts, 50 Hz, 100 kW, 6 pole squirrel cage induction motor with a rated slip of
2% will have a full load rotor speed of
(a) 1470 rpm (b) 980 rpm (c) 1020 rpm (d) none of the above
a) I2R loss of stator b) I2R loss of rotor c) friction and windage loss d) all of the above
10 Rewinding can affect which of the following factors that contribute to deterioration in motor
efficiency:
11 If measured Line Current of a 3 phase induction motor is 25.98 A, what will be the Phase
Current?
a) 15 A b) 45 A c) 8.96 A d) 30 A
13
The basic function of air dryer in a compressed air system is to
a) remove remaining traces of moisture after the aftercooler
b ) store and smoothen pulsating air output
c) reduce the temperature of the air before it enters the next state to increase efficiency
d) prevent dust from entering compressor
14
Select the correct statement for reciprocating air compressors:
a) for every 4oC drop in the inlet air temperature, the increase in energy consumption is by 1%.
b) for every 4 oC rise in the inlet air temperature, the decrease in energy consumption is by 1%
c) for every 4 oC rise in the inlet air temperature, the increase in energy consumption is by 1%
d) the energy consumption remains same irrespective of inlet air temperature
_______________________ 2
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
15
Which of the following parameters is not required for evaluating volumetric efficiency of the
compressor?
a) FAD b) Cylinder bore diameter c) Stroke length d) Power input
16
Which of the following will not occur if a reciprocating compressor is operated at a lower
discharge pressure?
a) lower power consumption
b) less load on the piston rods and hence reduced maintenance costs
c) lower leakage losses
d) lower free air delivery than rated
17 Which type of energy efficient dryer can be opted if a user in a plant requires compressed air
at a dew point of -40°C ?
a)"Range" is the difference between the cooling tower water inlet and outlet temperature.
b) "Approach" is the difference between the cooling tower outlet cold water temperature and
ambient wet bulb temperature.
d)'Range' is a better indicator of cooling tower performance.
e) Cooling capacity is the heat rejected in kCal/hr or TR
22 Identify the correct statement:
23 Two energy auditors made following statements regarding Vapour compressor Refrigeration
system and what will be your judgement?
_______________________ 3
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
a) suction heads b) discharge heads c) closed valve heads d) none of the above
29 Input power to the motor driving a pump is 20 kW. The motor efficiency is 0.9 and pump
efficiency is 0.7. The power transmitted to the water is
_______________________ 4
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
a) 8 b) 5.33 c) 4 d) 2
35 Cycles of Concentration (C.O.C) of a cooling tower will depend on
a) That the window allows 70 % of the sun's heat to pass through into interior of the buildings
b) That the window allows 30 % of the sun's heat to pass through into the building
interior
c) That 70 % of the sun's heat is incident on the window
d) That the window reflects back to exterior a minimum of 30 % of the sun's heat
a) more than the induction motor b) less than the induction motor
c) zero d) load dependent
_______________________ 5
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
43 In BEE Star labeled distribution transformers, which of following losses are defined?
a) harmonics occur as spikes at intervals which are multiples of the supply frequency
b) harmonics are multiples of the fundamental frequency
c) induction motors are the major sources of harmonics
d) transformers operating near saturation level create harmonics
_______________________ 6
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
S-2 A pump is delivering 64 m3/hr of water with a discharge head of 26 metres. The water is drawn
from a sump where water level is 3 metres below the pump centerline. The power drawn by
the motor is 8.89 kW at 88% motor efficiency. Find out the pump efficiency
Ans Hydraulic power Ph = Q (m3/s) xTotal head, hd - hs (m) x r (kg/m3) x g (m/s2) / 1000
= 5.0576 kW
= 7.8232 kW
= 5.0576 / 7.8232
= 64.65 %
How do the Time-Of-Day (TOD) metering and billing benefit the utilities as well as consumers?
S-3
ToD meter records demand, time, and energy and the ToD tariff are set in such a way that
Ans
higher rates at peak load periods and lower rates at off-peak load periods. The billing as per
ToD tariff benefits the consumers to avail maximum power and energy at off-peak hours at
lowest tariff ; and the higher peak period tariff dis-incentivise for increased drawl at peak
period. This results effective maximum demand reduction to the utility, and in turn savings in
peak time power procurement at higher rate as well as maximising the load factor for resulting
better financials to the utility.
Explain briefly the difference between static and dynamic head of a centrifugal pumping
S-4
system.
Static head is simply the difference in height of the supply and destination reservoirs and it is
independent of flow.
Dynamic head is the friction loss, on the liquid being moved, in pipes, valves and equipment in
the system. The friction losses are proportional to the square of the flow rate.
_______________________ 7
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
S-5
Compute AT & C (Aggregate Technical and Commercial) Losses for the following data:
S-6
A DG set is operating at 700 kW load with 450OC exhaust gas temperature. The DG set
generates 7.8 kg of exhaust gas/ kWh generated. The specific heat of gas at 430oC is 0.25
kCal/ kgOC. A heat recovery boiler is installed after which the exhaust temperature drops to
220OC. How much steam will be generated at 3 kg/ cm2 with enthalpy of 650.57 kcal/ kg.
Assume boiler feed water temperature as 65oC.
Ans
= 700 kWh x 7.8 kg gas generated/ kWh output x 0.25 kCal/ kg oC x (450oC-220 oC) =3,13,950
kCal/hr
S-7
An energy audit of a fan was carried out. It was observed that the fan was delivering 18,500
Nm3/hr of air with static pressure rise of 45 mm WC. The power measurement of the 3-phase
induction motor coupled with the fan recorded 2.9 kW/ phase on an average. The motor
operating efficiency was assessed as 88% from the motor performance curves. What would
be the fan static efficiency?
Ans
Q = 18,500 Nm3 / hr.= 5.13888 m3/sec ,
SP = 45 mmWC,
ηSt = ?,
_______________________ 8
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
= 5.13888 x 45
102 x 7.656
= 0.296
= 29.6%
S-8
List down any 5 energy conservation opportunities in compressed air system
Ans
§ Ensure air intake to compressor is not warm and humid by locating compressors
in well-ventilated area or by drawing cold air from outside. Every 40C rise in air
inlet temperature will increase power consumption by 1 percent.
§ Keep compressor valves in good condition by removing and inspecting once every
six months. Worn-out valves can reduce compressor efficiency by as much as 50
percent.
§ Install manometers across the filter and monitor the pressure drop as a guide to
replacement of element.
§ Consider the use of regenerative air dryers, which uses the heat of compressed
air to remove moisture.
§ Compressor free air delivery test (FAD) must be done periodically to check the
present operating capacity against its design capacity and corrective steps must
be taken if required.
_______________________ 9
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
L-1
a) In a cooling tower, the cooling water circulation rate is 1200 m3/hr. The water enters the
cooling tower at 38oC. The ambient wet bulb temperature is 26oC. The cooling tower operates
with an approach of 4oC. If the blowdown rate of the cooling tower is 1 % of the circulation
rate, calculate the evaporation loss and COC.
b) A medium scale industry has a load of 450 kVA. It has installed two transformers of 500
kVA each. The no load loss and full load copper loss are 760 W and 5400 W respectively.
From the energy efficiency point of view the management wants to take a decision on whether
to operate a single transformer on full load or two transformers equally sharing the load. What
is your recommendation ? Why?
Ans
a) Leaving cold water temperature = 26 + 4 = 30oC
Evaporation Loss (m3/hr) = 0.00085 x 1.8 x circulation rate (m3/hr) x (T1 –T2)
= 14.69 m3/hr
Blowdown = 12 m3/hr
Blowdown = Evaporation loss / (COC – 1)
12 = 14.69 / (COC – 1)
COC = 2.224
b)
1 x 500 kVA
Two transformers are better because the losses are the least.
_______________________ 10
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
L-2
Fill in the blanks for the following
4. In a centrifugal pump if the liquid to be pumped has density twice that of water, then
the horse power required (as compared to that while pumping water) will be______
times
5. The friction loss in a pipe carrying a fluid is proportional to the fifth power of
_________
6. A 10 MVA generator has power factor 0.866 lagging. The reactive power produced will
be ______ MVAR
7. Totally-enclosed, fan cooled (TEFC) motors are______ efficient than Screen –
protected, drip-proof (SPDP) induction motors
8. Low speed Squirrel cage induction motors are normally ______efficient than high
speed squirrel cage induction motors
9. Harmonics in electricity supply are multiples of the ________frequency
10. For the same rating, slip ring induction motors are normally _________efficient than
squirrel cage induction motors
Ans
1. Synchronous
2. 4
3. volute or diffuser
4. 2
5. pipe diameter
6. 5
7. more
8. less
9 fundamental
10 less
3
L-3 a) Calculate the free air delivery (FAD) in m /min of a compressor for the following observed
data:
3
Receiver capacity: 0.25 m
2
Initial pressure: 1 kg/cm (g)
2
Final pressure: 7 kg/cm (g)
o
Initial temperature: 32 C
o
Final temperature: 52 C
3
Additional holdup volume: 0.05 m
Compressor pump up time: 2.1 minutes
b) Identify the following statements as applicable to Vapor Compression Refrigeration System
_______________________ 11
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
The measured values of a water cooled 20 TR package air conditioning plant are given
L-4
below:
Average air velocity across suction side filter: 2.5 m/s
Cross Sectional area of suction: 2.4 m2
Inlet air : Dry Bulb:20 deg. C, Wet Bulb: 14 deg. C; Enthalpy: 9.37 k Cal per kg
Outlet air: Dry Bulb: 12.7 deg. C, Wet Bulb: 11.3 deg. C; Enthalpy: 7.45 k Cal per kg
Specific volume of Air: 0.85 m3/kg
Power drawn: by Compressor : 18.42 k W
by Pump : 2.1 k W
by Evaporator Fan : 1.25 k W
_______________________ 12
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
L-5
a) How do you calculate the velocity of air/gas in a duct using the average differential
pressure and density of the air/gas?
i. Find out Iron Loss plus Friction Loss plus Windage Loss
ii. Stator Copper Loss at name plate ratings(full load), considering stator temperature
=120 °C
iii. No load power factor of the motor
Ans
a) Ans:
Velocity V, m/s = CP x (2 x 9.81 p x y)1/2
y
measurement at number of points over the entire cross section of the duct.
= Density at air/ gas at test condition
b) Let Iron Loss plus Friction Loss plus Windage Loss be Pi+fw
Stator Copper Loss, Pst, 30°C = 3X (17/ 3)2X0.24 = 69.36 Watt
Pi+fw = Pnl - Pst= 955 – 69.36 = 885 .64
Ans (i) two most important electrical parameters, which are to be monitored for safe
operation of Diesel Generator set are KVA and kW
_______________________ 13
Bureau of Energy Efficiency
Click Here & Upgrade
Expanded Features
PDF Unlimited Pages
Documents
Complete Paper 3 –Set A Key
Slip
Load = *100%
Ss − Sr
Where:
Load = Output power as a % of rated power
Slip = Synchronous speed - Measured speed in rpm
Ss = Synchronous speed in rpm at the operating frequency
Sr = Nameplate full-load speed
Slip also varies inversely with respect to the motor terminal voltage squared. A voltage
correction factor can, also, be inserted into the slip load equation. The voltage
compensated load can be calculated as shown
Where:
Load = Output power as a % of rated power
Slip = Synchronous speed - Measured speed in rpm
Ss = Synchronous speed in rpm
Sr = Nameplate full-load speed
V = RMS voltage, mean line to line of 3 phases
Vr = Nameplate rated voltage
_______________________ 14
Bureau of Energy Efficiency
Paper 3 –Set A KEY
Date: 25.08.2013 Timings: 0930 – 1230 HRS Duration: 3 HRS Max. Marks: 150
1. The gross efficiency of a coal based power generating unit with a gross heat rate of
2490 kcal/kWh is
a) kWh per square meter per year b) kWh per square meter
c) kW per square meter d) kWh per year
_______________________ 1
Bureau of Energy Efficiency
Paper 3 –Set A KEY
6. If the maximum demand is 3500 kVA at 0.88 p.f., the maximum demand will reduce
by______ kVA if PF is improved to 0.98 :
a) 8 b) 6 c) 4 d) 2
9. A 7.5 kW, 415 V, 14.5 A, 1460 RPM rated 3 phase induction motor with full load
efficiency of 90%, draws 9.1 A and 4.6 kW of input power. The percentage loading of
the motor is about
10. The power input to a rotor of three phase induction motor is 42.3 kW. If the induction
motor is operating at a slip of 1.30 % the total mechanical power developed will be :
_______________________ 2
Bureau of Energy Efficiency
Paper 3 –Set A KEY
15. Reduction in the delivery pressure of an air compressor working at 7 bar, by 1 bar would
reduce the power consumption by
a) for every 5.5oC drop in the inlet air temperature, the increase in energy
consumption is by 2%
b) for every 4oC rise in the inlet air temperature, the increase in energy
consumption is by 1%
c) for every 4oC rise in the inlet air temperature, the decrease in energy
consumption is by 1%
d) the energy consumption remains same irrespective of inlet air temperature
17. The Free Air Delivery of a reciprocating air compressor is directly proportional to
_______________________ 3
Bureau of Energy Efficiency
Paper 3 –Set A KEY
24. The driving force for refrigeration in a vapour absorption refrigeration system is
a) tube axial fan b) vane axial fan c) propeller fan d) all of the above
28. The parameter used by ASME to classify fans, blowers and compressors is
_______________________ 4
Bureau of Energy Efficiency
Paper 3 –Set A KEY
35. A water pump is delivering 20 m3/hr at ambient conditions. The impeller diameter is
trimmed by 10%. This will reduce the pump discharge by
a) M = E + B + D b) M = E + B - D c) M = E - B + D d) M = E - B - D
39. If the wet bulb temperature of air is 380C, then its relative humidity in % is
_______________________ 5
Bureau of Energy Efficiency
Paper 3 –Set A KEY
46. Which of the following with respect to turbocharger in a Diesel engine is true?
S-1 A 15 kW, 415 V, 4 pole, 50 Hz, 3 Phase squirrel cage induction motor has a full load
efficiency of 92% and power factor of 0.89. Find the following if the motor operates at full
load rated values.
a) input power in kW
b) current drawn by the motor
c) RPM at a full load slip of 0.8%
_______________________ 6
Bureau of Energy Efficiency
Paper 3 –Set A KEY
pressure is 2.60 kg/cm2. The flow rate of water is 1.5 m3 /min. Find out the pump
efficiency if the actual power drawn by the pump motor is 14 kW at a motor operating
efficiency of 0.88.
Discharge Head = 2.60 kg/cm2
Ans
= 26 metre head.
Ans
42 2 33 2
I THD x 100
300 300
Velocity m/s
Cp x √2 x 9.81 x ∆p x γ / γ
0.9 x √2 x 9.81 x 4
_______________________ 7
Bureau of Energy Efficiency
Paper 3 –Set A KEY
25.6 m/s
x 1.135 / 1.135
S-5 List five measures to reduce energy consumption in lighting system for buildings,
industry and street lighting
Reduce excessive illumination levels to standard levels using switching, delamping, etc.
Ans
(Know the electrical effects before doing delamping.)
Aggressively control lighting with clock timers, delay timers, photocells, and/or
occupancy sensors.
Install efficient alternatives to incandescent lighting, mercury vapor lighting, etc.
Efficiency (lumens/watt) of various technologies range from best to worst approximately
as follows: low pressure sodium, high pressure sodium, metal halide, fluorescent,
mercury vapor, incandescent.
Select ballasts and lamps carefully with high power factor and long-term efficiency in
mind.
Upgrade obsolete fluorescent systems to Compact fluorescents and electronic ballasts
Consider lowering the fixtures to enable using less of them.
Consider daylighting, skylights, etc.
Consider painting the walls a lighter color and using less lighting fixtures or lower
wattages.
Use task lighting and reduce background illumination.
Re-evaluate exterior lighting strategy, type, and control. Control it aggressively.
Change exit signs from incandescent to LED.
(Need not copy and write the following statements in the Answer book; only write against
the statements A, B, C, D etc. whether it is applicable to VCR or VAR )
_______________________ 8
Bureau of Energy Efficiency
Paper 3 –Set A KEY
I. VCR
J. VCR
S-7 List any five factors that affect the rate of evaporation of water in cooling towers
Ans
Cooling tower capacity (TR) = (flow rate x density x sp.heat x diff. temp)/ 3024
= (2X60) x 1000 x 1.0 x (43-35)/ 3024
= 317.5TR
L-1 An efficiency assessment test was carried out for a standard 4 pole squirrel cage
induction motor in a chemical plant. The motor specifications are as under:
Motor rated specification: 3 phase delta connected,37 kW, 415 Volt, 63 Amps, 1475 rpm,
The following data was collected during the no- load test on the motor:
_______________________ 9
Bureau of Energy Efficiency
Paper 3 –Set A KEY
(iv) Full load slip and rotor input assuming rotor losses are slip times rotor input.
(v) Motor input assuming that stray losses are 0.5% of the motor rated output
power.
(vi) Motor full load efficiency
Ans
Let Iron plus friction and windage loss, Pi + fw
No load power, Pnl = 1152 Watts
Stator Copper loss, P st-300C (Pst.cu)
= 3 (17 / 3)2 0.260
= 75.13Watts
Pi + fw = Pnl – Pst.cu
= 1152 – 75.13
= 1076.87 W
Poutput
Efficiency = 100
Pinput
_______________________ 10
Bureau of Energy Efficiency
Paper 3 –Set A KEY
= 91.87 %
1. Cavitation may occur in a pump when the local static pressure in a fluid reaches a
level below the _________pressure of the liquid at the actual temperature.
3. The system resistance of a fan system is proportional to the ______of flow rate or
velocity
4. If the dry bulb temp.is 30 0C and the wet bulb temp. is 30 0C, then the % relative
humidity will be _______
5. Slip ring induction motors are comparatively ________efficient than of the squirrel
cage motors of same ratings.
6. In a pumping system with a horizontal discharge, the suction static head is 3 m and
the friction head is 21 m. The total head developed by the pump will be ___________
7. The lowest theoretical temperature to which water can be cooled in a cooling tower is
the _________ of atmospheric air
9. It is acceptable to run pumps in parallel provided their__ _______ heads are similar
10. When heat load, range and wet bulb temperature are held constant, the cooling
tower size is ________proportional to the approach.
Ans
1. Vapour
2. Water
3. Square
4. 100%
5. Less
6. 18 m
7. Wet bulb temperature
8. Lux
9. Closed valve heads
10. Inversely
L-3 The cooling water circuit of a process industry is depicted in the figure below. Cooling
water is pumped to three heat exchangers via pipes A,B and C where flow is throttled
depending upon the requirement. The diameter of pipes and measured velocities with
non-contact ultrasonic flow meter in each pipe are indicated in the figure.
_______________________ 11
Bureau of Energy Efficiency
Paper 3 –Set A KEY
Ans
Flow in pipe A 22/7 x (0.1)2/4 x 1.5
0.011786 m3/s
0.014143 m3/s
0.062857 m3/s
0.088786 m3/s
Total flow
Total head 34 m – 2 m = 32 m
27.9 kW
Pump efficiency 61 %
L4
a) The size of an engine room to be ventilated is 30 m x 20 m x 5 m. The number of air
changes per hour is designed to be 20. If the static pressure rise across the ventilator
fan is 15 mm WC and fan efficiency is 70 % find out the motor power drawn at a
motor efficiency of 90%.
_______________________ 12
Bureau of Energy Efficiency
Paper 3 –Set A KEY
b) A seal air fan for a coal mill is operating with suction damper in 25 % open condition.
The power drawn at 50 Hz by fan motor is 120 kW. A VFD is to be installed eliminating
the damper operation. It is found that the damper can be completely opened and the
fan motor can be operated at 33 Hz. Calculated the power drawn by the fan motor at
33 Hz, assuming that motor and fan efficiency remains constant.
b) Further a leakage test was carried out in the same compressed air system and with
the same compressor as in problem a) above and following were the observations:
- Compressor was on load for 03 minutes
- Compressor was unloaded for 13 minutes
- Compressor was drawing 145 kW during load
Calculate the following:
i. % leakage in compressed air system
ii. Leakage quantity
iii. Specific power consumption
iv. Power lost due to leakage
Ans
a)
P2 P1 V 273 t1
Q =
P0 t
273 t 2
Time = 65 sec=1.0833 secs
_______________________ 13
Bureau of Energy Efficiency
Paper 3 –Set A KEY
(i) In a throttle valve-controlled pumping system with oversized pump list any five
options to improve energy efficiency? (Note: Name only options, no explanation
required)
(ii) Define one ‘Ton of Refrigeration (TR)’. How do you calculate TR across the Air
Handling Units?
(iii) List five energy conservation opportunities in fan system.
Ans
i) Trim impeller, replace with smaller impeller, install variable speed drive, change pulley if it is
belt driven, change to two speed drive, and lower rpm drive
ii) A ton of refrigeration is defined as the quantity of heat to be removed in order to form one
ton of ice in 24 hours when the initial temperature of water is 0 °C. This is equivalent to 50.4
Kcal/min or 3024 Kcal/h in metric system
Refrigeration load in TR is assessed as ;
_______________________ 14
Bureau of Energy Efficiency
Paper 3 –Set A KEY
Q ρ h in h out
TR
3024
Where Q is the air flow in CMH
is density of air kg/m3
h in is enthalpy of inlet air kCal/kg
h out is enthalpy of outlet air kCal/kg
_______________________ 15
Bureau of Energy Efficiency
Paper 3 – Set A Key
Name: ___________________
Date: 06.02.2011 Timings: 0930-1230 HRS Duration: 3 HRS Max. Marks: 150
General instructions:
o Please check that this question paper contains 17 printed pages
o Please check that this question paper contains 64 questions
o The question paper is divided into three sections
o All questions in all three sections are compulsory
o All parts of a question should be answered at one place
a) lower the heat rate of a power generating unit, higher is the generation efficiency.
b) one kilo Watt hour of electrical energy being equivalent to 3600 kilo Joules of thermal energy
c) ‘Heat Rate’ is directly proportional to the efficiency of power generation.
d) design ‘Heat Rate’ of a 210 MW thermal generating unit is higher than that of a 110 MW thermal
generating unit.
2. If power factor is improved from PF1 to PF2 then the reduction in distribution losses in an electric
network is proportional to :
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
5. Busbar Voltages at the main electrical panel were balanced but at the following Motor Control
Circuit (MCC), fitted with PF Correction capacitors, the voltages were unbalanced by about 3%.
The possible reason for this could be
a) rated input of the motor b) maximum input power which the motor can draw
c) rated output of the motor d) maximum instantaneous input power of the motor
9. A 7.5 kW, 415 V, 14.0 A, 1480 RPM, three phase rated squirrel cage induction motor, after
decoupling from the driven equipment, was found to be drawing 3.5 A at no load. The current
drawn by the motor at no load is high because of
a) very high supply frequency at the time of no load test b) faulty ammeter reading
c) very poor power factor as the load is almost inductive d) loose motor terminal connections
10. A six pole induction motor operating at 49.6 Hz, with 980 RPM actual speed , will have operating %
slip of
a) 3 kW b) 12 kW c) 18 kW d) 25 kW
12. Eff1 (as per IS 12615:2004) induction motor is
a) required PF capacitor kVAr at induction motor terminal increases with decrease in speed of the
motor
b) PF capacitor improves power factor from the point of installation back to the load side.
c) induction motor efficiency increases with increase in its rated capacity
d) The largest potential for electricity savings with variable speed drives is generally in variable
torque applications
14. The adsorption material used in an adsorption air dryer is
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
a) static head b) dynamic head c)suction head d) net positive suction head available
27. In a pumping system the static head is 10 m and the dynamic head is 15 m. If the pump speed is
doubled, then the total head will be
a) "Voltage" fluctuations in lighting circuit can be minimized by isolating from the power feeders.
b) reduction of voltage related problems, which in turn increases the efficiency of the lighting
system.
c) with proper control device “over voltage” that might occur during lean load or off-peak can be
avoided, in turn less energy consumption and improved lamp life can be achieved
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
a) will double the flow b) will double the fan static pressure
c) will increase flow by more than two times d) will not double the flow
30. The COP of a vapour compression refrigeration system is 3.0. If the compressor motor output is
9.555 kW, the tonnage (TR) of the refrigeration system is
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
41. A fan is operating at 970 RPM developing a flow of 3000 Nm3/hr. at a static pressure of 650
mmWC. If the speed is reduced to 700 RPM, the static pressure (mmWC) developed will be
a) voltage and ampere b) kVA and ampere c) power factor and voltage d) kW and kVA
47. Which of the following is not a climate zone as per ECBC classification?
a) Metal halide lamp can be considered as a variant of high pressure mercury vapour lamp
(HPMV)
b) Efficacy of fluorescent tube light (FTL) remains constant throughout its operational life
c) HPSV lamps differ from mercury and metal-halide lamps in that they do not contain starting
electrodes
d) LPSV lamps are the most efficacious light sources, but they produce the poorest quality light of
all the lamp types
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
FOR
ENERGY MANAGERS & ENERGY AUDITORS
Date: 06.02.2011 Timings: 0930-1230 HRS Duration: 3 HRS Max. Marks: 150
General instructions:
o All questions are compulsory
o All parts of a question should be answered at one place
S-1 Compute AT & C (Aggregate Technical and Commercial) losses for the following
data:
Annual
Description
Data
Input energy = (import - export), MU 10
Energy billed (metered), MU 6
Energy billed (Un-metered), MU 1
Amount billed (Rs. lakhs ) 400
Gross amount collected (Rs. lakhs) 410
Arrears collected (Rs. lakhs) 40
Ans:
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
S-2 Match the following load-shape objectives of any Demand Side Management (DSM)
programme of a utility.
Peak Clipping
i a
ii
Valley filling b
Load shifting
iii c
Conservation
iv d
Load building
v e
Ans:
i – c; ii – d; iii – b; iv – e; v-a
S-3 The power input to a three phase induction motor is 52 kW. If the induction motor is
operating at a slip of 1.9% and with total stator losses of 1.30 kW, find the total
mechanical power developed.
Ans:
Stator input: 52 kW
Stator losses: 1.30 kW
Stator output: 52-1.30= 50.7kW = Rotor input
Slip= 1.9%
Mechanical Power Out put= ( 1-s)x Rotor Input
= (1- 0.019) x 50.7=0.981x 50.7=49.737 kW
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
S-4 In a Commercial building, five window ACs each of 1.5 TR capacity, were
evaluated for replacement with three star labeled new ACs having Energy Efficiency
Ratio (EER) of 2.50 kW/kW. The measured EER of existing ACs is as follows.
Existing EER
AC No 1 2.05
AC No 2 2.19
AC No 3 2.30
AC No 4 2.40
AC No 5 2.17
Calculate the total kW saving potential if all the existing ACs are replaced with 3 star
labeled ACs of same capacity?
Ans:
Input kW = TR delivered*3.516/EER
Existing kW input
AC No1 2.573
AC No2 2.408
AC No3 2.293
AC No4 2.198
AC No5 2.430
Total 11.902
S-5 The following data of a water pump of a process plant have been collected
Flow: 70 m3/hr, Total head: 24 meters, Power drawn by motor– 7.2 kW, Motor
efficiency – 89%. Determine the pump efficiency
Ans:
Hydraulic power Q (m3/s) x total head (m) x 1000 x 9.81 /1000
(70/3600) x 24 x 1000 x 9.81/1000
Hydraulic power 4.578kW
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
70.65 %
Ans:
The following energy conservation opportunites have been demonstrated for energy
saving in agricultural pumping.
Ans:
Industrial heat pumps are mainly used for:
• Space heating
• Heating of process streams
• Water heating for washing, sanitation and cleaning
• Steam production
• Drying/dehumidification
• Evaporation
• Distillation
• Concentration
S-8 An induced draft-cooling tower is designed for a range of 8 °C. The energy auditor
finds the operating range as 2 °C during the conduct of energy audit. In your opinion
what could be the reasons for this situation
Ans:
1. There may be excess cooling water flow rate
2. There may be reduced heat load from the process
3. Some of the cooling tower cells fan are switched off
4. Approach may be poor because of high humid condition
5. Cooling tower nozzles may be blocked
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
L-1 The contract demand of a process plant is 6000 kVA with the electricity supply utility
company. The average monthly recorded maximum demand of the process plant is
5500 kVA at a power factor of 0.78. The utility bill analysis provides the following tariff
structure.
a) Minimum monthly billing demand is 75% of the contract demand or the actual recorded
maximum demand whichever is higher. No PF improvement incentives are provided.
Find out the optimum limit of power factor capacitor requirement entirely from the
view of reducing maximum demand so that no excess demand charges are paid to
the supply company. Also work out the simple payback period, assuming cost of
power factor capacitor installation along with automatic power factor correction
controller is Rs. 500 per kVAr.
Ans:
Cost of power factor capacitor installation = Rs. 500 per kVAr x 2083 kVAr = 10.4
lakhs
Monthly savings due to MD reduction = 1000 kVA
Yearly savings = 1000 x 400 x 12 = Rs. 48.0 lakhs
Simple payback period = investment cost / yearly savings = 10.4/ 48 = 0.21 years =
2.6 months
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
Ans:
a. increase
b. decrease
c. higher
d. slipring
e. reduced
f. backward-inclined
g. dynamic
h. Solar Reflactance
i. Solar heat gain coefficient
j. illuminance
L-3 A free air delivery test was carried out before conducting a leakage test on a
reciprocating air compressor in an engineering industry and following were the
observations:
Receiver capacity : 12 m3
Initial pressure : 0.2 kg / cm2 (g)
Final pressure : 7.0 kg / cm2 (g)
Additional hold-up volume : 0.3 m3
Atmospheric pressure : 1.026 kg / cm2 (a)
Compressor pump-up time : 4.8 minutes
The following was observed during the conduct of leakage test during the lunch time
when no pneumatic equipment/ control valves were in operation:
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
Ans.
(i)
Compressor output m3/minute :
(P2 − P1 ) × Total Volume
Atm. Pressure × Pump up time
:
(7.0 − 0.2)× 12.3 = 16.9834 m3/minute
1.026 × 4.8
: 1019 m3/hr
power consumption : 95 kW
output : 1019 m3/hr
(ii)
Specific power consumption : 95/1019 = 0.093228 kW/m3/hr
(iii) % Leakage in the system
Load time (T) : 40 secs.
Un load time (t) : 90 secs
T
% leakage in the system : x 100
(T + t)
40
: x100
(40 + 90)
: 30.77%
iv) Leakage quantity : 0.3077x1019
: 313.54 m3/hr
v) Power lost due to leakage : Leakage quantity x specific power
consumption
: 313.54 x 0.093228
: 29.23 kW
L-4 An energy audit was conducted to find out the ton of refrigeration (TR) of an Air
Handling Unit (AHU). The audit observations are as under.
Parameter Values
Evaporator area (m2) 10.0
Inlet velocity (m/s) 1.9
Inlet air DBT (°C) 21.5
RH (%) 75.0
Enthalpy (kJ/kg) 53.0
Out let air DBT (°C) 17.4
RH (%) 90.0
Enthalpy (kJ/kg) 46.4
Density of air (kg/m3) 1.14
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
Ans:
Ans:
Air-Conditioning System
Minimise exfiltration of cool air and infiltration of warm air through leaky windows and
doors by incorporating effective means of weather stripping. Self-closing doors
should also be provided where heavy traffic of people is anticipated.
Ensure human comfort by setting the temperature to between 23oC and 25oC and the
relative humidity between 55% and 65%.
Ensure higher chiller energy efficiency by maintaining the chilled water leaving
temperature at or above 7o C. As a rule of thumb, the efficiency of a centrifugal chiller
increases by about 2¼ % for every 1o C rise in the chilled water leaving temperature.
Ensure that the insulation of the chilled water pipes and ducting system is maintained
in good condition. This helps to prevent heat gain from the surroundings.
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
heat transfer of the condenser tubes and thereby reducing the energy efficiency of
the chiller.
Cooling Towers
Ensure that the cooling towers are clean to allow for maximum heat transfer so that
the temperature of the water returning to the condenser is less than or equal to the
ambient temperature.
Install devices such as frequency converters to vary the fan speed. This will reduce
the energy consumption of the fan motor by as much as 15%.
Maintain the filter in a clean condition. This will improve the heat transfer between air
and chilled water and correspondingly reduce the energy consumption.
Lighting System
A flexible lighting system, which made use of natural lighting for the peripherals of the
room, should be considered so that these peripheral lights can be switched off when
not needed.
Use lamps with high luminous efficacy. For example, replacing incandescent bulbs
with compact fluorescent lamps can reduce electricity consumption by 75% without
any reduction in illumination levels.
The ballast losses of conventional ballast and electronic ballast are 12W and 2W
respectively. Hence, consider the use of electronic ballast for substantial energy
savings in the lighting system.
Optical lamp luminaries made of aluminum, silver or multiple dielectric coatings have
better light distribution characteristics. Use them to reduce electricity consumption by
as much as 50% without compromising on illumination levels.
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
In open plan offices, the air-conditioning and lighting systems can be combined in
such a way that the return air is extracted through the lighting luminaires. This
measure ensures that lesser heat will be directed from the lights into the room.
Clean the lights and fixtures regularly. For best results, dust at least four times a
year.
The higher surface reflectance values of light colors will help to make the most of any
existing lighting system.
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
and in the treated spaces and stored in the memory of the processor. Equations are
developed for defining the performance of the control elements, the items of plant
and the behavioural characteristics of the systems. These equations are fed into the
micro-processor as algorithms. The deviations from the desired performance are
dealt with by calculations using the equations fed in. This in turn controls the overall
systems. So in effect, mathematical functions replace control modes.
For example, if the room temperature rose in a conditioned space, the correct
position of the valve in the chilled water line feeding the AHU could be calculated and
corrected as necessary, to bring the room temperature back to the set point as
rapidly as possible. Data can be stored to establish trends and anticipation can be
built into the program so that excessive swings in controlled conditions may be
prevented. Based on the operating experience, self-correction can be incorporated to
get the best possible system performance. This implies that, commissioning
inadequacies and possibly even design faults can be corrected, but only to a certain
extent. Only if the systems are properly designed, installed and commissioned,
optimum results can be obtained and the cost of the installation can be justified.
Energy Conservation Building Codes are developed to set minimum energy efficiency
standards for design and construction of commercial and residential buildings, to
encourage energy efficient design or retrofit of buildings so that it does not constrain
the building function, comfort, health, or the productivity of the occupants.
In order to implement ECBC across the country in India, it has been decided to group
the country in five climatic zones as per the weather conditions. The Five Climatic
Zones are:
o Composite (Delhi)
o Hot-Dry (Ahmedabad)
o Warm-Humid (Kolkata)
o Moderate / Temperate (Bangalore)
o Cold (Shillong)
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
L-6 A cooling tower cools 1450 m3/hr of water from 43 ºC to 36.6 ºC at 30 ºC wet bulb
temperature. The cooling tower fan flow air rate is 9,50,000 m3/hr (air density =1.08
kg/m3) and operates at 2.7 cycles of concentration.
a) Range
b) Approach
c) % CT Effectiveness
d) L/G Ratio in kg/kg
e) Cooling Duty Handled in TR
f) Evaporation Losses in m3/hr
g) Blow down requirement in m3/hr
h) Make up water requirement in m3/hr
Ans:
_______________________
Bureau of Energy Efficiency
Paper 3 – Set A Key
1
= 14.198 /(2.7–1) = 8.352
m3/hr
Mark: 1
h) Make up water requirement in m3/hr = Evaporation Loss + Blow
down Loss
= 14.198 + 8.352
= 22.55
_______________________
Bureau of Energy Efficiency
Paper 3 –Set A Key
Name: ___________________
Date: 16.10.2011 Timings: 0930-1230 HRS Duration: 3 HRS Max. Marks: 150
S-1 Briefly explain transformer losses and how the total transformer losses at any load level can be computed.
Ans Transformer losses consist of two parts: No-load loss and Load loss
1. No-load loss (also called core loss) is the power consumed to sustain the magnetic field in the transformer's steel
core. Core loss occurs whenever the transformer is energized; core loss does not vary with load. Core losses are
caused by two factors: hysteresis and eddy current losses. Hysteresis loss is that energy lost by reversing the
magnetic field in the core as the magnetizing AC rises and falls and reverses direction. Eddy current loss is a
result of induced currents circulating in the core.
2. Load loss (also called copper loss) is associated with full-load current flow in the transformer windings. Copper
loss is power lost in the primary and secondary windings of a transformer due to the ohmic resistance of the
windings. Copper loss varies with the square of the load current. (P=I2R).
For a given transformer, the manufacturer can supply values for no-load loss, P NO-LOAD , and load loss, P LOAD . The total
transformer loss, P TOTAL , at any load level can then be calculated from:
P TOTAL = P NO-LOAD + (% Load/100)2 x P LOAD
Where transformer loading is known, the actual transformers loss at given load can be computed as:
2
kVA Load
= No load loss + full load loss
Rated kVA
S-2 A 15 kW, 3 phase, 415 V induction motor draws 25 A and 12 kW input power at 410 V. Calculate the Apparent
and Reactive Power drawn by the motor at the operating load?
Ans Apparent power = 1.7321 x 0.410 x 25 = 17.15 Kva
Active power = 12 kW
Therefore reactive power = sqrt (315.2-144)
= sqrt (171.2) = 13.08 kVAr
_______________________ 1
Bureau of Energy Efficiency
Paper 3 –Set A Key
The findings of performance assessment trials will automatically indicate potential areas for improvement, which could
be one or a more of the following:
A water pump of a process plant is analysed for efficiency and following data is collected:
S-4
Flow - 50 m3/hr, Suction head -3 meters, Discharge head - 27 meter, meters, Power drawn by motor – 7.5 kW,
Motor efficiency – 88%
Distinguish between NPSH available and NPSH required in case of a centrifugal pump ?
S-5
Ans NPSH Required (NPSHR): The minimum pressure required at the suction port of the pump to keep the pump from
cavitating.
NPSHA is a function of pumping system and must be calculated, whereas NPSHR is a function of the pump and must
be provided by the pump manufacturer. NPSHA must be greater than NPSHR for the pump system to operate
without cavitating. Put another way, you must have more suction side pressure available than the pump requires.
S-6 A DG set is operating at 600 kW load with 450OC exhaust gas temperature. The DG set generates 8 kg of
exhaust gas/ kWh generated. The specific heat of gas at 450oC is 0.25 kCal/ kgOC. A heat recovery boiler is
installed after which the exhaust temperature drops to 230OC. How much steam will be generated at 3 kg/ cm2
with enthalpy of 650.57 kCal/ kg. Assume boiler feed water temperature as 80oC.
_______________________ 2
Bureau of Energy Efficiency
Paper 3 –Set A Key
Ans = 600 kWh x 8 kg gas generated/ kWh output x 0.25 kCal/ kg oC x (450oC-230 oC) =2,64,000 kCal/hr
S-7 3
An energy audit of a fan was carried out. It was observed that the fan was delivering 16,000 Nm /hr of air with
static pressure rise of 55 mm WC. The power measurement of the 3-phase induction motor coupled with the
fan recorded 2.1 kW/ phase on an average. The motor operating efficiency was assessed as 86% from the
motor performance curves. What would be the fan static efficiency?.
= 4.444 x 55
102 x 5.418
= 0.4423
= 44.23%
S-8 Discuss in brief any three methods by which energy can be saved in a building air conditioning system
Insulate all cold lines / vessels using economic insulation thickness to minimize heat gains; and choose
appropriate (correct) insulation.
b) Building Envelop
Optimise air conditioning volumes by measures such as use of false ceiling and segregation of critical areas for
air conditioning by air curtains.
Minimise the air conditioning loads by measures such as roof cooling, roof painting, efficient lighting, pre-cooling
of fresh air by air- to-air heat exchangers, variable volume air system, otpimal thermo-static setting of
temperature of air conditioned spaces, sun film applications, etc.
_______________________ 3
Bureau of Energy Efficiency
Paper 3 –Set A Key
L-1 An energy audit of electricity bills of a process plant was conducted. The plant has a contract demand of 5000
kVA with the power supply company. The average maximum demand of the plant is 3850 kVA/month at a
power factor of 0.95. The maximum demand is billed at the rate of Rs.600/kVA/month. The minimum billable
maximum demand is 75 % of the contract demand. An incentive of 0.5 % reduction in energy charges
component of electricity bill are provided for every 0.01 increase in power factor over and above 0.95. The
average energy charge component of the electricity bill per month for the plant is Rs.18 lakhs.
The plant decides to improve the power factor to unity. Determine the power factor capacitor kVAr required,
annual reduction in maximum demand charges and energy charge component. What will be the simple
payback period if the cost of power factor capacitors is Rs.900/kVAr.
3657.5 kW
Kvar required to improve power factor from 0.95 to 1 kW ( tan θ 1 – tan θ 2 )
kW ( tan (cos-θ 1 ) – tan (cos-θ 2 )
3657.5 ( tan (cos-0.95) – tan (cos-1)
3657.5(0.329 - 0)
1203 x 900 kVAr
Cost of capacitors @Rs.900/kVAr Rs.10,82,700
s
_______________________ 4
Bureau of Energy Efficiency
Paper 3 –Set A Key
1. The ratio of solar heat gain that passes through fenestration to the total incident solar radiation that falls on the
fenestration is called ________
2. Presenting the load demand of a consumer against time of the day is known as______ curve
3. The vector sum of active power and reactive power is ____.
4. The ratio of isothermal power to actual measured input power of an air compressor is known as------:
5. The type of main input energy used for refrigeration in vapor absorption refrigeration plants is____
6. One ton of refrigeration is equivalent to ______kW
7. Stray losses in an induction motor generally are proportional to the square of the ________current
8. The capacitor kVAR selected for PF Correction at the induction motor terminals , should not exceed ____ % of
the no-load kVAR of the motor.
9. The ratio of luminous flux emitted by a lamp to the power consumed by the lamp is called_________________.
10. In an amorphous core distribution transformer, ______ loss is less than a conventional transformer
L-3 A free air delivery test was carried out before conducting a leakage test on a reciprocating air compressor in
an engineering industry and following were the observations:
3
Receiver capacity : 8.0 m
Initial pressure : 0.1 kg / cm2g
Final pressure : 7.0 kg / cm2g
Additional hold-up volume : 0.3 m3
Atmospheric pressure : 1.026 kg / cm2 abs.
Compressor pump-up time : 3.5 minutes
Further the following observations were made during the conduct of leakage test during the lunch time when
no pneumatic equipment/ control valves were in operation:
_______________________ 5
Bureau of Energy Efficiency
Paper 3 –Set A Key
Ans
(i) Compressor output m3/minute : (P2 − P1 ) × Total Volume
Atm. Pressure × Pumpup time
(ii)
3
output : 956.89 m /hr
power consumption : 92 kW
Specific power consumption : 92/956.89 = 0.09614 kW/m3/hr
L-4 a) In a Thermal Power Station, steam input to a turbine operating on a fully condensing mode is 110
Tonnes/Hr. The heat rejection requirement of the steam turbine condenser is 556 kCals/kg of steam
condensed. The cooling water temperatures at the inlet to and outlet from the turbine condenser were
measured to be 29oC and 38o C respectively. Find out the circulating cooling water flow.
b) An energy audit was conducted to find out the ton of refrigeration (TR) of an Air Handling Unit (AHU). The
audit observations are as under.
Parameter AHU
Evaporator area (m2) 9.5
Inlet velocity (m/s) 1.9
Inlet air DBT (°C) 21.5
RH (%) 75.0
Enthalpy (kJ/kg) 53.0
Out let air DBT (°C) 17.4
RH (%) 90.0
Enthalpy (kJ/kg) 46.4
Density of air (kg/m3) 1.14
_______________________ 6
Bureau of Energy Efficiency
Paper 3 –Set A Key
Ans a)
110 (TPH) x 1000 (kg/T) x 556 = Cooling water flow rate x 1 kCal/kg oC x (38-29) oC
b)
Q × ρ × (h in − h out )
TR =
3024
ρ = 1.14 kg/m3
L-5 a) The efficiency at various stages from power plant to end-use is given below.
b) The energy audit observations at a cooling tower (CT) in a process industry are given below:
Cooling capacity, kCal/hr = heat rejected = CW flow rate in kg per hour X (CW inlet hot water tem. to CT, deg. C-
_______________________ 7
Bureau of Energy Efficiency
Paper 3 –Set A Key
Cooling capacity = 3000X1000X (41 - 31) = 30,000,000 kCal per hour = 30 Million kCal per hour
Ans i) Ideally capacitor voltage rating is to match the supply voltage. If the supply voltage is lower, the reactive kVAr
2 2
produced will be the ratio V /V where V is the actual supply voltage, V is the rated voltage.
1 2 1 2
ii) Impeller trimming refers to the process of machining the diameter of an impeller to reduce the energy added to
the system fluid.
Impeller trimming offers a useful correction to pumps that, through overly conservative design practices or changes in
system loads are oversized for their application. The laws with respect to impeller trimming will be
Flow, Q ∝ D
Head, H ∝ D 2
Power, P ∝ D 3
iii) The equations relating centrifugal machine performance parameters of flow, head and power absorbed, to
speed are known as the Affinity Laws:
Flow, Q ∝ N
Head, H ∝ N 2
Power, P ∝ N 3
Where,
Q = Flow rate
H = Head or resistance
P = Power absorbed
N = Rotating speed
iv) Trigeneration refers to simultaneous generation of steam (heat), power and refrigeration through integrated
systems. . For example in a DG set besides power is generated, Steam is produced with waste exhaust gases and
Chilled water is generated using jacket cooling water. Three different utilities are created using a single fuel as energy
source.
v) Fenestration systems include windows, skylights, ventilators, and doors that are more than one-half glazed. All
openings (including the frames) in the building envelope that let in light. Total area of the fenestration measured using
the rough opening (including glazing, sash and frame). For glass doors where glazed vision area is less than 50% of
the door area, the fenestration area is the glazed vision area; otherwise, it is the door area.
_______________________ 8
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
Name: ___________________
Date: 20.12.2009 Timings: 0930-1230 HRS Duration: 3 HRS Max. Marks: 150
General instructions:
o Please check that this question paper contains 15 printed pages
o Please check that this question paper contains 64 questions
o The question paper is divided into three sections
o All questions in all three sections are compulsory
o All parts of a question should be answered at one place
_______________________ 1
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
c) PF capacitors operating at lower voltage then their rated values have higher operating
kVArs then their rated values
d) the power factor of an induction motor decreases with decrease in percentage motor
loading
4 If the efficiencies of a power plant, transmission and distribution systems are 30%, 95%
& 85% respectively, the cascade efficiency of power generation, and transmission
system is given by
_______________________ 2
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
14 At which of the following discharge pressures, the reciprocating air compressor will
consume maximum power
2 2
a) 3 bar b) 3.5 kg/cm c) 150 psi d) 6 kg/cm
15 Which of the following is not true of air receivers?
21 Backward-inclined fans are known as _____ because change in static pressure does not
overload the motor
a) overloading b) non-overloading
c) radial d) axial
22 The fan characteristic curve is a plot of
_______________________ 3
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
25 For the same flow through which of the following diameter pipes, the pump will work with
maximum pressure
_______________________ 4
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
36 Which method uses infrared, acoustic, ultrasonic or microwave sensors for lighting
control?
a) 29.7 kW b) 37.8 kW
c) 0.36 kW d) none of the above as cooling effect is always measured in TR
41 Which of the following can also act as a heat pump?
_______________________ 5
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
a) slip ring induction motors are normally less efficient than squirrel cage induction
motors
b) high speed squirrel cage induction motors are normally less efficient than low speed
Squirrel cage induction motors
c) the capacitor requirement for PF improvement at induction motor terminal increases
with decrease in rated speed of the induction motor
d) induction motor efficiency increases with increase in its rated capacity
50 Coefficient of Performance (COP) for a refrigeration compressor is given by
a) kW/TR
b) power input to compressor (kW) / cooling effect (kW)
c) cooling effect (kW) / Power input to compressor (kW)
d) none of the above
S-1 a) A 10 kVAr, 415 V rated power factor capacitor was found to be having terminal supply
voltage of 440 V. Calculate the capacity of the power factor capacitor at the operating
supply voltage.
_______________________ 6
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
b) What would be the nearest kVAr compensation required for changing the power factor
of a 500 kW load from 0.9 lead to unity power factor ?
Ans:
a) kCal/kWh
b) decrease
c) dew
d) total and static
e) fifth
(1 Mark each)
S-3 A pump is delivering 40 m3/hr of water with a discharge pressure of 29 metre. The
water is drawn from a sump where water level is 6 metre below the pump centerline.
The power drawn by the motor is 7.5 kW at 89% motor efficiency. Find out the pump
efficiency.
Ans:
Hydraulic power Ph = Q (m3/s) xTotal head, hd - hs (m) x (kg/m3) x g (m/s2) / 1000
= 3.815 kW
(2 Marks)
= 6.675 kW
_______________________ 7
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
(2 Marks)
Pump efficiency = hydraulic power / pump shaft power
= 3.815 /6.675
= 57.15 %
(1 Mark)
S-4 Define one ‘Ton of Refrigeration (TR)’. How do you calculate TR across the Air
Handling Units?
S-5 Estimate the cooling tower capacity (TR) and approach with the following parameters
Ans:
Cooling tower capacity (TR) = (flow rate x density x sp.heat x diff. temp)/ 3024
= 120 x 1000 x 1.0 x (42-36)/ 3024
= 238 TR
(3 Marks)
Approach = 36- 32 = 4oC
(2 Marks)
_______________________ 8
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
S-6 A fan is delivering 20,000 Nm3/hr. of air at static pressure difference of 70 mm WC. If
the fan static efficiency is 55%, find out the shaft power of the fan.
Ans:
Q = 20,000 Nm3 / hr. , Pst = 70 mmWC, St = 55% , P = ?
S-7 a) Briefly explain the difference between a ‘filament lamp’ and a ‘gas discharge lamp’?
b) State any 3 best practices in a lighting system for energy savings?
Ans:
a) Filament lamps like incandescent lamps produce light by virtue of a filament heated
to incandescence by the flow of electric current through it. The light from a gas
discharge lamp is not produced by heating a filament, but by the excitation of gas
contained in either a tubular or elliptical outer bulb.
(2 Marks)
_______________________ 9
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
S-8 Calculate the free air delivery (FAD) capacity of a compressor in m3/min for the
following observed data:
Ans:
P2 P1 V 273 t1
=
P0 t 273 t 2
(3 Marks)
7 0 (0.5 0.03) 273 32
=
1.026 4.5 273 51
= 0.7564 m3/min
(2 Marks)
L-1 a) A small scale industry has a constant load of 380 kVA. It has installed two
transformers of 500 kVA each. The no load loss and full load copper loss of each 500
kVA transformer is 750 W and 5410 W respectively. From the energy efficiency point
of view the small scale industry management wants to take a decision on whether to
operate a single transformer or two transformers equally sharing the load. What is
your recommendation ?
b) A no load test conducted on a three phase delta connected induction motor gave the
following values:
_______________________ 10
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
Answer a)
1 x 500 kVA
Transformer loss at 380 kVA load No load loss + [kVA load/Rated kVA]2 x
full load loss = 750 + [(380/500)2 x 5410]
= 750 + (0.5776 x 5410)
750 + 3124.8
3874.8 W
Two transformers are better because the losses are the least and there is a
saving of 812.4 watts.
(5 Marks)
Answer b)
L-2 A 15 kW, 415 V, 26 A, 4 pole, 50 Hz, 3 phase rated squirrel cage induction motor has
a full load efficiency and power factor of 90% and 0.89 respectively.
_______________________ 11
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
Ans:
L-3 a) What is the impact of condensing temperature and evaporator temperature on the
Coefficient of Performance (COP) of a refrigeration system?
b) Why is it beneficial to operate induction motors in star mode operating at loads below
50 % of rated capacity?
L-4 A compressed air leakage test was conducted by an energy auditor in an engineering
industry, which normally runs 3 nos. of 500 cfm reciprocating compressors. The
compressed air system is maintained at the normal loading-unloading settings of 6.6
_______________________ 12
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
kg/cm2g and 7.0 kg/ cm2g respectively. The following was observed for a period of 10
minutes trial by running a 500 cfm compressor during an off day:
Subsequently some of the air leakage points were attended and the leakage test was
repeated. The following was observed while maintaining the same loading &
unloading pressure settings and trial period:
The average power drawn during the above 2 trials was observed as 71 kW during
load and 16 kW during unload condition. Calculate the annual cost savings for
4000 hr/ year of compressor operation. Assume energy charge of Rs. 6.00 per kWh.
Ans:
_______________________ 13
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
Answer a):
i) “Range” is the difference between the cooling tower water inlet and outlet
temperature.
ii) “Approach” is the difference between the cooling tower outlet cold water
temperature and ambient wet bulb temperature. Although, both range and
approach should be monitored, the `Approach’ is a better indicator of cooling
tower performance.
iii) Cooling tower effectiveness (in percentage) is the ratio of range, to the ideal
range, i.e., difference between cooling water inlet temperature and ambient wet
bulb temperature, or in other words it is = Range / (Range + Approach).
(6 Marks)
Answer b)
1. There may be excess cooling water flow rate
2. There may be reduced heat load from the process
3. Some of the cooling tower cells fan is switched off
4. Approach may be poor because of high humid condition
5. Nozzles may be blocked
(4 Marks)
L6 In an alkali chemical plant, salt brine flow at the rate of 18 m3/ hr is cooled down from
12 °C to 7 °C using chilled water. The chiller unit compressor motor draws 31 kW
power and total input power to the allied accessories is 16 kW. The operating
efficiency of the motor is 90%. The salt brine density is 1.2 kg/litre and specific heat
capacity is 0.97 kCal/kg °C.
Answer:
_______________________ 14
Bureau of Energy Efficiency
Paper 3 –Set A Solutions
_______________________ 15
Bureau of Energy Efficiency
Paper 3 –Set A Key
Date: 24.05.2009 Timings: 0930-1230 HRS Duration: 3 HRS Max. Marks: 150
General instructions:
o Please check that this question paper contains 8 printed pages
o Please check that this question paper contains 64 questions
o The question paper is divided into three sections
o All questions in all three sections are compulsory
1 All parts of a question should be answered at one place
_______________________ 1
Bureau of Energy Efficiency
Paper 3 –Set A Key
a) 3 kW b) 12 kW c) 18 kW d) 25 kW
5 A pure resistive load in an alternating current (AC) circuit draws only
7 The ratings of the PF correction capacitors at motor terminals for a 37 kW induction motor at
3000 rpm synchronous speed will be---------------------in comparison to the same sized induction
motor at 1500 rpm synchronous speed
8 The largest potential for electricity savings with variable speed drives is generally in
9 A 7.5 kW, 415 V, 15 A, 970 RPM, 3 phase rated induction motor with full load efficiency of
86% draws 7.5 A and 3.23 kW of input power. The percentage loading of the motor is about
11 A two pole induction motor operating at 50 Hz, with 1% slip will run at an actual speed of
_______________________ 2
Bureau of Energy Efficiency
Paper 3 –Set A Key
a) low speed Squirrel cage induction motors are normally less efficient than high speed
Squirrel cage induction motors
b) the capacitor requirement for PF improvement at induction motor terminals
decreases with decrease in rated speed of the induction motors of the same sizes
c) induction motor efficiency increases with increase in its rated capacity
d) totally-enclosed, fan cooled (TEFC) motors are more efficient than Screen–protected, drip-
proof (SPDP) induction motors
a) compressor efficiency will be reduced by about 2 percent for every 250 mm WC pressure
drop across the air inlet filters.
0
b) every 4 C rise in inlet air temperature results in a higher energy consumption by 1 % to
achieve equivalent output
0
c) an increase of 5.5 C in the inlet air temperature to the second stage results in a 2 %
increase in the specific energy consumption.
d) compressed air receiver volume should be 100% of the rated hourly free air output
17 Which of the following is not a part of the vapour compression refrigeration system
2 3
P N1 P N1 P N1
a) 1 = b) 1 = c) 1 = d) none of the above
P2 N 2 P2 N 2 2 P2 N 2 3
_______________________ 3
Bureau of Energy Efficiency
Paper 3 –Set A Key
2
a) fluid flow b) (fluid flow) c) 1 d) 1
2
fluid flow (fluid flow)
24 _____ fans are known as “non-overloading“ because change in static pressure do not overload
the motor
a) "Voltage" fluctuations in lighting circuit can be minimized by isolating from the power
feeders.
b) This will reduce the voltage related problems, which in turn increases the efficiency of the
lighting system.
c) With proper control device “over voltage” that might occur during lean load or off-peak can
be avoided, in turn excess energy consumption and improved lamp life
d) all the above
29 Parallel operation of two identical fans in a ducted system
a) will double the flow b) will double the fan static pressure
c) will not double the flow d) will increase flow by more than two times
30 Normally the guaranteed best approach a cooling tower can achieve is
o o o o
a) 5 C b) 8 C c) 12 C d) 2.8 C
31 Select the wrong statement ---
a) for a given heat rejection duty, a higher range will reduce the circulating water flow rate
b) when the cycle of concentration is left at one, all water left in the cooling tower after
evaporation needs to be removed as blowdown.
c) a better indicators for cooling tower performance is Range
o o
d) a cooling tower size will be greater for 20 C Wet bulb temperature (WBT) than for a 30 C
WBT, for the same circulation, range and approach
32 Which of the following ambient conditions will evaporate minimum amount of water in a cooling
tower
o o o o
a) 35 C DBT and 30 C WBT b) 38 C DBT and 31 C WBT
o o o o
c) 38 C DBT and 37 C WBT d) 35 C DBT and 29 C WBT
_______________________ 4
Bureau of Energy Efficiency
Paper 3 –Set A Key
33 Input power to the motor driving a pump is 30 kW. The motor efficiency is 0.9. The power
transmitted to the water is 16.2 kW. The pump efficiency is
_______________________ 5
Bureau of Energy Efficiency
Paper 3 –Set A Key
_______________________ 6
Bureau of Energy Efficiency
Paper 3 –Set A Key
S-1 Briefly explain transformer losses and how the total transformer losses
at any load level can be computed.
Answer:
Transformer losses consist of two parts: No-load loss and Load loss
1. No-load loss (also called core loss) is the power consumed to sustain the
magnetic field in the transformer's steel core. Core loss occurs whenever the
transformer is energized; core loss does not vary with load. Core losses are
caused by two factors: hysteresis and eddy current losses. Hysteresis loss is
that energy lost by reversing the magnetic field in the core as the magnetizing
AC rises and falls and reverses direction. Eddy current loss is a result of
induced currents circulating in the core.
2. Load loss (also called copper loss) is associated with full-load current flow in
the transformer windings. Copper loss is power lost in the primary and
secondary windings of a transformer due to the ohmic resistance of the
windings. Copper loss varies with the square of the load current. (P=I2R).
For a given transformer, the manufacturer can supply values for no-load loss, PNO-
LOAD, and load loss, PLOAD. The total transformer loss, PTOTAL, at any load level can
then be calculated from:
PTOTAL = PNO-LOAD+ (% Load/100)2 x PLOAD
Where transformer loading is known, the actual transformers loss at given load can
be computed as:
2
kVA Load
No load loss full load loss
Rated kVA
S-2 The power input to a three phase induction motor is 45 kW. If the
induction motor is operating at a slip of 2% and with total stator losses
of 1.80 kW, find the total mechanical power developed.
Solution:
_______________________ 7
Bureau of Energy Efficiency
Paper 3 –Set A Key
Answer:
S-4 A water pump of a process plant is analysed for efficiency and following
data is collected:
Flow: 60 m3/hr, Total head: 30 meters, Power drawn by motor– 7.4 kW,
Motor efficiency – 90%
Answer
S-5 Name any five methods of capacity controls for fans (Note: no
explanation is required)
Answer
_______________________ 8
Bureau of Energy Efficiency
Paper 3 –Set A Key
1. Pulley Change
2. Damper Controls
3. Inlet Guide Vanes
4. Variable Speed Drives
5. Parallel Operation
Answer
= 700 kWh x 8 kg gas generated/ kWh output x 0.25 kCal/ kg oC x (450oC-260
o
C) =2,66,000 kCal/hr
Steam generation = 2,66,000 kCal/hr / (650.57 kCal/kg – 60) = 450 kg/ hr.
S-7 An energy audit of a fan was carried out. It was observed that fan was
delivering 15,000 Nm3/hr of air at static pressure rise of 60 mm WC. The
power measurement of the 3-phase induction motor coupled with the fan
recorded 1.92 kW/ phase on an average. The motor operating efficiency
was assessed as 0.88 from the motor performance curves. What would
be the fan static efficiency ?.
Answer:
= 4.167 x 60
102 x 5.067
=0.484
= 48.4%
S-8 Discuss in brief any three methods by which energy can be saved in an
air conditioning system.
Answer:
_______________________ 9
Bureau of Energy Efficiency
Paper 3 –Set A Key
a) Cold Insulation
Insulate all cold lines / vessels using economic insulation thickness to minimize
heat gains; and choose appropriate (correct) insulation.
b) Building Envelop
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains.
Minimise the air conditioning loads by measures such as roof cooling, roof
painting, efficient lighting, pre-cooling of fresh air by air- to-air heat exchangers,
variable volume air system, otpimal thermo-static setting of temperature of air
conditioned spaces, sun film applications, etc.
_______________________ 10
Bureau of Energy Efficiency
Paper 3 –Set A Key
L-1 An energy audit of electricity bills of a process plant was conducted. The plant
has a contract demand of 3000 kVA with the power supply company. The
average maximum demand of the plant is 2300 kVA/month at a power factor of
0.95. The maximum demand is billed at the rate of Rs.500/kVA/month. The
minimum billable maximum demand is 75 % of the contract demand. An
incentive of 0.5 % reduction in energy charges component of electricity bill are
provided for every 0.01 increase in power factor over and above 0.95. The
average energy charge component of the electricity bill per month for the
company is Rs.11 lakhs.
The plant decides to improve the power factor to unity. Determine the power
factor capacitor kVAr required, annual reduction in maximum demand charges
and energy charge component. What will be the simple payback period if the
cost of power factor capacitors is Rs.800/kVAr.
Answer
2185 kW
Kvar required to improve power factor from 0.95 kW ( tan 1 – tan 2)
to 1
kW ( tan (cos-1) – tan (cos-2)
2185 ( tan (cos- – tan (cos-
2185(0.329 - 0)
719 kVAr
Cost of capacitors @Rs.800/kVAr Rs.5,75,200
_______________________ 11
Bureau of Energy Efficiency
Paper 3 –Set A Key
Rs.27,500/month
Annual reduction Rs.27,500 x 12
Rs.3,30,000
Savings in electricity bill Rs.6,30,000
Investment Rs.5,75,200
Payback period 5,75,200/6,30,000
0.91 years or 11months
1. The intersection point of the pump curve and the system curve is
called_____________
2. Presenting the load demand of a consumer against time of the day is
known as______
3. The vector sum of active power and reactive power is ____.
4. The ratio of isothermal power to actual measured input power of an air
compressor is known as------:
5. The input energy for refrigeration in vapour absorption refrigeration
plants is____
6. The fan which is choosen for moving large flows against relatively low
pressures is_____ curved fan.
7. The system resistance in a fan ducting system refers to ____________
pressure
8. The friction loss, on the liquid being moved, in pipes, valves and
equipment in the system is called ________ head.
9. The ratio of luminous flux emitted by a lamp to the power consumed
by the lamp is called_________________.
10. In an amorphous core distribution transformer, ______ loss is less
than a conventional transformer
ANS:
1 Best efficiency point / pump operating point/ duty point
2. Load curve
3. Apparent Power
4. Isothermal efficiency
5. Thermal energy (or steam or waste heat or gas or any energy related to
thermal energy)
6. Forward Curve
7. Static
8.Dynamic/friction head
9.Luminous efficacy
_______________________ 12
Bureau of Energy Efficiency
Paper 3 –Set A Key
10. No load
L-3 A free air delivery test was carried out before conducting a leakage test on a
reciprocating air compressor in an engineering industry and following were the
observations:
Receiver capacity : 10 m3
Initial pressure : 0.2 kg / cm2g
Final pressure : 7.0 kg / cm2g
3
Additional hold-up volume : 0.2 m
Atmospheric pressure : 1.026 kg / cm2 abs.
Compressor pump-up time : 4.5 minutes
The following was observed during the conduct of leakage test during the lunch time
when no pneumatic equipment/ control valves were in operation:
a) Compressor on load time is 30 seconds and unloading pressure is 7
kg/cm2g
b) Average power drawn by the compressor during loading is 90 kW
c) compressor unload time and loading pressure are 70 seconds and 6.6
kg/cm2 g respectively.
Ans.
(i)
P2 P1 Total Volume
Compressor output m3/minute :
Atm. Pressure Pumpup time
:
7.0 0.2 10.2 = 15.0227 m3/minute
1.026 4.5
: 901.36 m3/hr
power consumption : 90 kW
output : 901.36 m3/hr
(ii)
Specific power consumption : 90/901.36 = 0.099 kW/m3/hr
(iii) % Leakage in the system
Load time (T) : 30 secs.
Un load time (t) : 70 secs
_______________________ 13
Bureau of Energy Efficiency
Paper 3 –Set A Key
T
% leakage in the system : x 100
(T t)
30
: x 100
(30 70)
: 30%
iv) Leakage quantity : 0.30x901.36
: 270.41 m3/hr
v) Power lost due to leakage : Leakage quantity x specific power
consumption
: 270.41 x 0.099
: 26.77 kW
b) An energy audit was conducted to find out the ton of refrigeration (TR) of
an Air Handling Unit (AHU). The audit observations are as under.
Parameter AHU
Evaporator area (m2) 9.0
Inlet velocity (m/s) 1.81
Inlet air DBT (°C) 21.5
RH (%) 75.0
Enthalpy 53.0
(kJ/kg)
Out let air DBT (°C) 17.4
RH (%) 90.0
Enthalpy 46.4
(kJ/kg)
Density of air 1.14
(kg/m3)
_______________________ 14
Bureau of Energy Efficiency
Paper 3 –Set A Key
Answer:
L-5 A Cooling Tower cools 1565 m3/hr of water from 44º C to 37.6º C at 29.3º
C wet bulb temperature. The cooling tower fan flow air rate is 989544
m3/hr (air density =1.08 kg/m3) and operates at 2.7 cycles of
concentration.
Find
a) Range,
b) Approach,
c) % CT Effectiveness
d) L/G Ratio in kg/kg
e) Cooling Duty Handled in TR
f) Evaporation Losses in m3/hr
g) Blow down requirement in m3/hr
h) Make up water requirement/cell in m3/hr
Ans:
_______________________ 15
Bureau of Energy Efficiency
Paper 3 –Set A Key
i) Ideally capacitor voltage rating is to match the supply voltage. If the supply voltage is
2 2
lower, the reactive kVAr produced will be the ratio V /V where V is the actual supply
1 2 1
voltage, V is the rated voltage.
2
_______________________ 16
Bureau of Energy Efficiency