Vigilon Plus Control Panels: Key Features
Vigilon Plus Control Panels: Key Features
Vigilon Plus Control Panels: Key Features
The Compact Plus 2 loop panels and Vigilon Plus 4 loop panels are
available with integrated 24 hour standby and the 6 loop panel has full 72
hr standby capacity. Advanced networking options allow networking of up
to 200 panels in a multi-domain structure with options of copper or optic
fibre connections (Vigilon 4 & 6 Loop Panels only).
Fully compatible with Honeywell Gent’s innovative S-Quad range – a The Vigilon Plus Range of Advanced Fire
combined Multi-Sensor range with speech, sounder and EN54-23 Visual Detection Control Panels is applicable for
Alarm devices in one intelligent unit. buildings of any size.
The Vigilon Plus Repeat control panel provides full display and control of
the system. Connecting to the detection loop, the repeat panel provides
a cost effective solution with minimum requirements for cabling and
installation.
Repeat panels are supplied complete with their own 72 hour power supply
and standby batteries.
K E Y F E AT U R E S
• Integral EN54-4 PSU • PC based • The control panel has • Flexible programming • In the event of a fire or
and battery standby commissioning tools a simple user interface options are available fault, Vigilon’s
for 24 hours (4 loop) allow complex fire with LCD screen at the panel analogue addressable
plans to be configured providing accurate technology will
• Integral EN54-4 PSU • All Vigilon devices
information in an provide a detailed log
for 72 hours with • Advanced loop card connect onto the same
emergency of events
external batteries (6 technology allows for two core loop,
loop) system status • Multiple panel separate sounder or • PC based Graphics
monitoring and networks can be repeater panel wiring user interface (GUI)
• Vigilon’s advanced
diagnostics programmed circuits are not available
sensing technology
seamlessly as one required
and powerful software • Extended event log
system, allowing for
processing in the using flash memory
flexible design and
panel quickly card
system management
identifies real fires
Vigilon Plus Control Panels Technical Specifications
ORDER CODES SPECIFICATION
1 TO 2 LOOP CONTROL PANEL COMPACT-PLUS PANEL TYPE Compact Plus 2 Vigilon Plus 4 Loop Vigilon Plus 6 loop Vigilon Plus
1 TO 4 LOOP CONTROL PANEL VIGPLUS-24 Loop Panel panel Repeat Panel
MAX. NO. OF LOOPS 2 4 6 -
1 TO 4 LOOP CONTROL PANEL – NO PRINTER VIGPLUS-24-NP
LOOP CAPACITY 200 with Alarm 200 with an alarm 200 with an alarm Max 4 per loop
1 TO 6 LOOP CONTROL PANEL VIGPLUS-72
Current 800mA current of up to current of up to
VIGILON LOOP CARD VIG-LPC-EN (Max Alarm current 800mA (Equivalent to 800mA (Equivalent
VIGILON NETWORK CARD (COPPER) VIG-NC across both loops 100 sensor sounders to 100 sensor
(1.2 A) VADs) sounders VADs)
VIGILON NETWORK CARD (MULTIMODE VIG-NC-FO
FIBRE) - (VIG 4,6 LOOP PANEL ONLY) BATTERIES 2 x 12Ah 2 x 21Ah 4 or 8 x 21Ah 1 x 7Ah
SINGLE MODE FIBRE CARD VIG-NC-SMF BATTERY STANDBY 24hrs +30 mins in 24 hours + 30 minutes 72 hours + 30 72 hours
alarm alarm upgradeable to minutes alarm
ADDITIONAL LOOP CARD (2KM) FOR COMPACT-LPC-EN 72 hours
COMPACT-24-N
APPROX. WEIGHT 12 Kg (inc 22 Kg (inc batteries) 10.2 Kg (panel 9Kg (inc
NETWORK CARD FOR VIGILON COMPACT (EN COMPACT-NC batteries) only) batteries)
NETWORKS ONLY)
31 Kg (battery
VIGILON UPGRADE KIT VIG72-UPGR enclosure inc four
FLUSH SURROUND
batteries)
VIG-FLUSH
OPERATING TEMP. 0 - 45ºC 0 - 45ºC 0 - 45ºC 0 - 45ºC
VIGILON PLUS REPEAT PANEL VIGPLUS-RPT
CABLE ENTRY Top and rear knockins
VIGILON PLUS TERMINAL NODE (EN54 VIGPLUS-NODE
VERSION) FOR MULTIPLE IO CARDS AND APPROVALS EN54 Parts 2 & 4 -
FIBRE NETWORKS (SUPPLIED IN BLACK) EN54-2 requires that Vigilon 4 & 6 loop panels are restricted to max. 512 sensors and call points
COMPACT PLUS TERMINAL NODE FOR VIGILON COMPACT-NODE
PANEL NETWORKS (SUPPLIED IN BLACK)
STAINLESS STEEL OPTIONS System Architecture MCP
S-Quad Sensor
Sounder Sprinkler
Interface
Dimensions (mm) Loop Length up Units Door Release or
S-Cubed to 2.5 km Plant Shutdown
2.5km with 2.5mm cable CSA S-Quad Sensor
Alarm 2km with 1.5mm cable CSA
Sounder Sounder
Beam Beam
Transmitter S-Quad Sensor sounder Receiver
B EN54-23 VAD
Loop 1
Fire Station
A C
Secure Secure
Node
Vigilon Fibre Copper Loop 1
A B C Plus Network
Loop 6
Network
Vigilon Plus 406 543 172
Battery Box 421 437 174 Node Node
(only required with VIG1-72 Secure
6 loop panel) Honeywell Fibre Optic Loop 2
4 or 6 loop,
Voice Alarm Serial link Domain Loop 3