AEFAC - General
AEFAC - General
AEFAC - TN05
SITE TESTING
GUIDELINES
VOL 1: GENERAL
Ver. 1.1
January 2020
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
Preface
This Technical Note is Volume 1 of a suite of AEFAC Technical Notes dedicated to
providing best practice recommendations for site testing of post-installed fasteners.
The recommendations are intended to assist design engineers formulate appropriate
site testing procedures and to assist field testers conducting on site testing. It is
assumed that the tester is suitably experienced and competent at testing fasteners.
The full series of the “Site Testing Guidelines” Technical Notes is as follows:
• Volume 1: General
• Volume 2: Proof tests
• Volume 3: Ultimate tests
• Volume 4: Testing in masonry
It is a requirement that Volume 1 be used in conjunction with the other volumes as
necessary.
These guidelines have been based on recommendations made in BS 8539:2012 [1]
and by the Construction Fixings Association [2].
Note: Site testing only show the short-term performance of fasteners for the
temperature and environmental conditions present during the tests. The performance
and suitability of the product shall be reviewed and checked from the issued ETA for the
exposure conditions such as temperature and environmental effects to the fastener
during its lifetime.
1. Scope
The test methods outlined in these Technical Notes relate to quasi-static loading
procedures for product-specific evaluation performed on site. These Technical Notes
apply for post-installed fasteners only. The advice provided in this document is of a
general nature and is consistent with international guidelines ([1], [2]). This guidance
document should not be considered a substitute for manufacturer’s installation
instructions or technical advice from the fastener manufacturer/supplier.
Incorrect or incomplete site testing practice may result in a failure to diagnose
deficient installation or the correct performance of a fastener, leading to catastrophic
outcomes.
These Technical Notes do not cover the tests in shear direction, as they are limited by
material strength of base material and fastener, and less sensitive to installation. In
addition, compressive actions are normally transferred from the fixture into the
substrate with little or no effect on the fastener. Thus, the compressive actions are
2
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
excluded in the Technical Notes. This document provides advice primarily on the
tensile resistance of fasteners for applying Proof or Ultimate Loads in tensile
direction
This document provides technical advice on site testing techniques to verify the
performance of fasteners and does not address all safety-precautions needing to be
followed during site testing of fasteners to concrete and masonry. Advice should be
sought from the relevant safety authority such as WorkCover Authority and the site
manager for advice on the use of Personal Protective Equipment (PPE) during testing.
Note: As a minimum PPE for the tester should include a helmet, eye protection, gloves
(if handling chemical fasteners), dust mask (if exposed to dust in a confined space),
hearing protection, and equipment to restrain the test setup during testing (if
necessary).
2. Notation
fy = Characteristic yield strength of steel (fastener)
FOS = Factor of Safety
As = Cross sectional area of steel (fastener) in tension
hef = effective embedment depth of fastener
proof load test factor depending on the percentage of fasteners tested
κP,test =
in a discrete area
ks = statistical sampling factor
Np = load applied to fixing for a proof load test
maximum allowable load applied to fixing for a proof load test
Np, max =
without damaging fastening
maximum load applied to fixture during testing to determine
Ntest =
allowable resistance based on the simplified method
NRd = design resistance of the fastening
NRk = characteristic resistance of a fastening
NR,all = allowable resistance of the fastening
characteristic resistance of the fastening published in the approval
NRk,ETA =
document (ETA)
characteristic ultimate load determined from tests on prequalified
NRk1 =
products
3
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
3. Terminology
The following terminology and definitions are adopted in this document. Additional
terminology and definitions may be found in the AEFAC Fastener Dictionary [3].
4
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
Allowable resistance: maximum working load derived from tests performed on site
when the proposed fastener is to be used in a base material approved by the
manufacturer but for which there is no recommended resistance.
Characteristic resistance: resistance derived as the 5% fractile (95% of fasteners
exceed the characteristic resistance with 90% confidence level) of mean ultimate
resistance. This is determined from tests or empirical calculations based on modes of
failure.
Confined test: a test performed on an installed fastener such that the positioning of
reaction points of the test rig inhibits the formation of concrete-related modes of
failure.
Design resistance: resistance derived from the characteristic resistance by the
application of capacity reduction factor
Fastener: a type of device that is post-installed into hardened concrete or cast into
concrete.
Fastening: an assembly comprising fastener(s) to secure a fixture to the concrete base
material.
Fixture: the element that is being secured to the base material via fasteners.
Manufacturer’s recommended load: maximum working load recommended by a
manufacturer, typically the characteristic resistance divided by partial safety factor
for material and action [NRk /(γM × γF)]
Preliminary test: test carried out on site to determine the allowable resistance in the
case where no characteristic resistance or recommended resistance is available.
Proof tests: a test performed on a completely installed fastener and is intended to
validate correct installation.
Responsible engineer: the person responsible for overseeing the test regime for the
fasteners and to ensure that the site testing of fasteners provides the information
required for the project.
Safe Working Load: See “Working Load Limit”
Tester: the person with the responsibility to conduct the on-site fastener testing to an
agreed regime and to report information collected during testing.
Unconfined test: a test performed on an installed fastener such that the positioning of
reaction points of the test rig does not inhibit the formation of any modes of failure.
5
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
Ultimate load test: A test performed on a fastener whose installation is complete and
is intended to aid in establishing the suitability of the fastener in a particular base
material.
Working Load Limit (WLL): the maximum load that can be applied without the
strength and stability requirements being exceeded. Also known as safe working load,
allowable working load, maximum rated load, and permissible working load.
4. General
Site testing may be performed for one of two reasons:
(i) Validate correct installation (proof tests), or
(ii) Identify the characteristic strength of a fastener in a given substrate (ultimate
tests).
The performance of fasteners in concrete is typically known, thus ultimate tests
generally are not warranted in concrete substrates. However, given the complexity of
masonry substrates, technical data is generally limited such that site testing is
frequently employed to determine the ultimate strength of a fixing for use in masonry
substrates.
Site testing for proof tests and ultimate tests requires that the fasteners being tested
are installed in accordance with the manufacturer’s installation instructions, as well
as any supplementary requirements stipulated by the responsible engineer.
Note: It is the responsibility of the tester to prepare a report of results from the tests
undertaken. Interpretation of the test results from site testing is undertaken by the
responsible engineer, including identifying causes of any failures, any modifications to
the test regime and the modification to the specification of fasteners (if required).
This Guidance Note provides advice primarily on the tensile resistance of fasteners
since the shear strength is less sensitive to installation and is generally governed by
material strength if sufficient edge distance is present. Shear strength may therefore
be readily determined by calculating the shear capacity of the fastener component or
substrate. However, when the required edge distance is less than the manufacturer’s
published edge distance, technical assistance from the manufacturer should be
sought to determine an appropriate shear test program. Shear testing may also be
required to determine the performance of a fastener in low strength masonry. Tensile
testing is necessary since the tensile performance of fasteners is dependent on the
suitability of the fastener in the substrate, proper design and correct installation.
Fastener products having a European Technical Approval/Assessment (ETA) publish
their performance for a given substrate type, together with other parameters defining
6
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
their performance [4, 10]. This information may then be used with design provisions
such as those in AS 5216 [5] to calculate the expected strength. When a product does
have an ETA, the design engineer may request site tests to be performed to verify that
the product has been installed correctly.
Note: If site shear tests are deemed necessary, technical advice should be sought from
the supplier of the fastener product to develop a suitable test procedure.
5.1.1. General
The objective of proof tests is to validate installation on a sample population of
fasteners by loading the installed fasteners to a prescribed test load (proof load) that
is a fraction of the fastener’s capacity. The magnitude of the test load depends on the
fastener application and material. Proof tests should be conducted on a sample of the
fasteners installed for the project. A proof load does not result in the fixture
experiencing failure and is not used to determine the allowable strength of the
fastener in a given substrate.
Proof tests are generally short term in nature and are therefore not suitable for
investigating creep behaviour. While the nature of the proof tests provides a modest
safety margin, they are not appropriate for investigating the suitability of a fastener
in a given substrate.
Proof tests may only be carried out after the manufacturer’s recommended curing
time for the chemical fasteners.
Note: The requirement for proof tests to verify correct installation of safety-critical
fasteners may not be required if the fastener has been prequalified according to the
relevant EAD/ETAG, and the installer is under supervision and is appropriately trained
either via the AEFAC Installer Certification Program and/or training provided by the
product supplier. The requirement for proof testing is determined by the responsible
engineer.
7
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
5.2.1. General
The objective of ultimate tests is to determine the allowable strength of the fastening.
If ultimate tests are required, they should be performed prior to completion of the
fastener selection process to ensure that all project requirements are met.
Scenarios where ultimate testing may be performed are as follows:
(i) Manufacturer has a provisional approval for the product to be used in the
substrate but performance data is not available.
(ii) Fastener has an approval (e.g. ETA) for use in masonry but the type,
strength or dimensions of the masonry are outside the scope of the ETA.
(iii) Fastener has an approval (e.g. ETA) but the application is outside the scope
of the ETA, for example edge distance is outside the scope of the ETA.
The test procedure for applications involving products without an ETA is closely
based on recommendations from BS 8539 [1] and the Construction Fixings
Association’s guidance note, “Procedure for Site Testing Construction Fixings” [2].
Ultimate tests are carried out on a sample population of sacrificial fastenings that are
considered to be representative of the intended application. This requires a
representative substrate, the same type of fasteners that will be used in the project
and installation by the same work crew. It may be necessary following testing to make
good any substrate damage incurred by the test population.
Ultimate tests are not required for fasteners in concrete provided the product is
prequalified in accordance with Appendix A of AS 5216 and the application falls
within the scope of the product’s approval. In this case the design data is published in
the prequalification. If the fastener is being installed in masonry that is the same
category for which it has been awarded a prequalification, ultimate tests may still be
required if either the strength of the masonry or the dimensions of the masonry are
less than the minimum requirement of the prequalification. In the case of masonry,
the category of substrate relates to the type or material and type of brick unit (e.g.
solid, perforated, hollow).
8
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
6. Test Setup
9
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
should be capable of indicating the maximum load achieved during the test that
may be referred to upon completion of the test.
• Calibration should occur in a precision test machine such as one that has NATA
certification.
• The accuracy of displacement measurement should be to within +/- 0.02 mm.
Note: If it is necessary to install fasteners for the purpose of testing the manufacturer’s
installation instructions should be consulted for a list of equipment necessary for correct
fastener installation.
10
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
(a) Unconfined test setup. (b) Confined test setup.
11
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
The effective depth (hef) refers to the greatest depth to which load is resisted by the
fixing (fastener engages with the concrete), not the total depth of the fixing or depth
of hole.
If the minimum spacing between the fastener and test rig support leg outlined in
Table 1 cannot be achieved due to restricted access, the engineer requesting the tests
should be notified in the test report.
Figure 2: Hydraulic ram setup for large Figure 3: Hand operated test rig for
fixings with high load. small fixings with lower test loads.
12
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
is available, with or without a plate clamped with a nut to simulate clamping (refer to
Figure 5(a) and Figure 5(b), respectively). All necessary precautions should be taken
to ensure the test rig is aligned with the orientation of the fastener so as not to induce
bending during testing that may lead to invalid results.
(a) Torque required to (b) Torque not Figure 4: Pulling frame for clamping
clamp plate. required for fixture effect.
installation.
For ultimate load testing the coupler should cover a length of thread equal to at least
1.5 times the diameter of the rod being tested. The choice between the two methods
(with or without a clamped plate) will depend on whether a torque is applied to the
fixture during installation. Displacement-controlled fasteners, some undercut
fasteners and most bonded fasteners do not require an installation torque to operate
correctly. Conversely, installation torque for torque-controlled expansion fasteners is
imperative for their correct operation.
Figure 5 depicts an alternate setup that may be adopted when the clamping effect is
to be monitored during the test. In this setup the plate simulates the fixture and
accurate displacement measurements may be made on the top of the fastener.
Spherical washers may be used to eliminate negative effects of bending.
13
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
i) The accuracy of the displacement measurement should not exceed 10% of the
actual reading.
ii) The precision of measurement should be no greater than 5% of the maximum
displacement for the test.
Recording of deformation is at the discretion of the engineer requesting the test and
will generally depend on the type of test (proof or ultimate). The three typical
deformation measurement profiles adopted during site testing are as follows:
i) None: measurement of deformation is typically not warranted for proof tests
where very little (if any) visible deformation occurs. A fastener exhibiting visible
movement up to the proof load will often be deemed a failure. For applications
where serviceability function is critical for the fastener, displacement
measurements should be taken.
ii) First visual: if visible deformation is observed, a suitable method of measurement
such as a dial gauge should be adopted to quantify the relative deformation
between the fastener head and the surface of the substrate.
iii) Detailed: where the intent of the site test is to reproduce the load-deflection
characteristics of the fastener’s performance, it is recommended that
displacement measurements occur at load intervals equal to one-tenth of the
ultimate load expected or at shorter intervals.
Care should be taken when measuring deformation, particularly regarding the chosen
reference point. Deformation measurements on test apparatus are typically global in
nature and include stretching or deformation of various components of the test rig
that are difficult to compensate for. Consequently, it is strongly recommended that
the point of reference is beyond the zone where a concrete cone may form and that is
independent to any part of the test device. Further, measurement should not be made
from any point on the test rig since this will experience deformation during testing.
Where ‘first movement’ requires detection, a simple visual assessment may be made
of a gap opening in the fixture. If the serviceability limit is to be assessed at the
manufacturer’s recommended load, feeler gauges may be used to assess the gap in
the fixture, taking care to ensure the gap measured is representative of fastener
displacement. For safety-critical applications, in either Proof or Ultimate Load Tests,
movement should be monitored to ensure that a serviceability limit is not exceeded
before the Design Load is reached.
In the event that detailed recordings are required a dial gauge or a more sophisticated
electronic data acquisition system should be adopted. When detailed recordings and
a pulling plate assembly are required, direct measurements of the head of the fastener
may be made (refer to Figure 6). Direct measurement provides the most accurate
recording of displacement; however, the measuring equipment may be damaged if
14
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
the fastener fails. To avoid the possibility of damaging the measuring equipment, an
eccentric attachment may be introduced to facilitate measurement of the head of the
fastener as illustrated in Figure 6. If an eccentric displacement measurement is
performed (e.g. on one side of the plate), errors are possible since the fastener may
experience rotation during loading, resulting in an apparent increase or decrease in
the displacement measurement. Care should be taken as this error may go unnoticed
during testing since the tester may not be able to detect bending visually.
The application of a torque during installation of a fastener results in a preload that
will delay displacement until the preload has been overcome by the applied load. The
permissible deformation of the fastening may be governed by serviceability limits
specific to the project that will determine when the test should terminate. The
serviceability limit for deformation should not be reached before achieving the design
load. The expected displacement will also depend on the type of fastener, with an
example being displacement-controlled expansion fasteners which are likely to
experience relatively less displacement prior to failure compared to torque-
controlled expansion fasteners which have a follow-up expansion capability.
(a) Elevation. (b) Plan view.
Figure 6: Example test rig set for detailed displacement measurement (section view).
In the event that detailed deformation measurements are required, the following
procedure should be adopted for the application of load:
1. Recordings of displacement are made at predetermined intervals, such as
1/10th ultimate load or proof load, depending on the type of test being
conducted. Sufficient resolution should be available in the results to identify
the load-displacement curve of the fastener. It is recommended that the loading
regime include measurements when the displacement equals 0.1mm, as well
15
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
7. Test regime
16
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
the fastener system, as well as other factors. Consequently, corresponding load and
displacement measurements should be recorded as close together as possible to
avoid the effects of load relaxation on the results.
The increase in load should occur at a rate such that the peak load is experienced
between one to three minutes from the commencement of the test.
It is highly recommended that the test be witnessed by a representative from the
client or engineer requesting the tests.
Note: Testing fasteners may be dangerous, particularly when testing to ultimate load or
failure. When pulling rods in tension no person should stand in line with the rod. Before
commencing the tests, all necessary precautions such as the wearing of personal
protective equipment should be taken to mitigate the risk of injury to the tester,
witnesses and any bystanders present during testing.
The number of required tests should be assessed on a case-by-case basis by the
engineer requesting the tests. The minimum number of tests is recommended in the
respective Volumes 2 to 4 of this series.
8.1. General
If the fastener manufacturer does not approve their use in the general category of the
substrate, site testing should not be considered a suitable method of demonstrating
satisfactory performance. Some fasteners are not compatible with certain types of
substrate (e.g. expansion fasteners in hollow masonry). Manufacturer’s literature
should always be consulted to determine suitability of a product.
Where the properties of the substrate are known or may be readily identified, design
data is available for the substrate properties, and installation is performed by a
competent individual under appropriate supervision, site testing is generally not
required.
There may be certain special applications whereby industry-specific requirements
may be published for which the fastener manufacturer should be able to provide
guidance.
9. Report of results
A list of the information to be included in the test report is provided in Appendix A.
17
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
10. Summary
This Technical Note provides general recommendations for the site testing of safety-
critical fasteners for the purpose of proof testing and to evaluate ultimate strength.
Recommendations have been provided for proper test setup, including test rig
positioning, connection to the fastener, displacement measurement and application
of load. Provided the substrate properties are known, the fastener has a suitable
prequalification such as an ETA for the substrate, and the fastener is installed as per
manufacturer’s installation instructions by a suitably qualified installer, site testing is
generally not required. However, the responsible engineer may elect to specify site
testing for added confidence in the installation. While proof tests are performed to
verify correct installation, the purpose of ultimate tests is to determine ultimate
strength of the fastening. Appendix B provides a summary of test regimes.
The advice provided is not exhaustive and should be used together with advice
provided in the other volumes of this series as appropriate to the type of testing being
conducted.
11. References
[1] British Standard 8539, “Code of practice for the selection and installation of
post-installed anchors in concrete and masonry”, BSI Standards Limited 2012
[2] Construction Fixings Association, “Procedure for Site Testing Construction
Fixings”, Guidance Note, www.fixingscfa.co.uk
[3] AEFAC Technical Note 07, “AEFAC Fastener Dictionary”, www.aefac.org.au
[4] EAD 330232, “Mechanical fasteners for use in concrete”, EOTA, 2016
[5] AS 5216:2018, “Design of post-installed and cast-in fastenings in concrete”,
Standards Australia
[6] EOTA TR053“ Recommendations for job-site tests of metal injection anchors for
use in masonry”, www.eota.eu, 2016
[7] Construction Fixings Association, “How to test anchors on site in accordance
with BS 8539:2012”, Guidance Note, www.fixingscfa.co.uk
[8] AEFAC Technical Note 01, “Design Concepts for Post-Installed and Cast-In
Fasteners”, www.aefac.org.au
[9] AEFAC Technical Note 02, “Prequalification of Post-Installed and Cast-In
Fasteners”, www.aefac.org.au
[10] EAD 330499, “Bonded fasteners for use in concrete”, EOTA, 2017
18
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
APPENDIX A
TEST REPORT
The following provides a list of minimum information that should be recorded and
reported to the design engineer/specifier. Additional information may be warranted
subject to site-specific considerations.
The purpose of the test report is to identify if all objectives of the test(s) have been
met, as well as any deviations.
19
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
A.8.1 Load
• Maximum load
• Condition of fastener and surrounding base material before and after test
• Load at first visible movement
20
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
A.8.2 Movement
If required, the load should be reported at different load increments specified by the
engineer requesting the tests, as well as the maximum load.
21
www.aefac.org.au
TECHNICAL NOTE:
SITE TESTING GUIDELINES – VOL 1: GENERAL
APPENDIX B:
SUMMARY OF TEST REGIMES
Figure B1: Flowchart of test regimes
22
www.aefac.org.au
www.aefac.org.au