0% found this document useful (0 votes)
64 views23 pages

AEFAC - General

This technical document provides guidelines for site testing of post-installed fasteners. It discusses volume 1 of the site testing guidelines, which covers general information intended to assist engineers and testers. The document defines important terminology, outlines the scope of site testing covered, and provides notation for parameters used in testing calculations. It also lists the volumes that make up the full site testing guidelines series.

Uploaded by

Anonymous YW5mvp
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
64 views23 pages

AEFAC - General

This technical document provides guidelines for site testing of post-installed fasteners. It discusses volume 1 of the site testing guidelines, which covers general information intended to assist engineers and testers. The document defines important terminology, outlines the scope of site testing covered, and provides notation for parameters used in testing calculations. It also lists the volumes that make up the full site testing guidelines series.

Uploaded by

Anonymous YW5mvp
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 23

TECHNICAL NOTE

AEFAC - TN05
SITE TESTING
GUIDELINES
VOL 1: GENERAL

Ver. 1.1
January 2020


www.aefac.org.au
TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

Preface
This Technical Note is Volume 1 of a suite of AEFAC Technical Notes dedicated to
providing best practice recommendations for site testing of post-installed fasteners.
The recommendations are intended to assist design engineers formulate appropriate
site testing procedures and to assist field testers conducting on site testing. It is
assumed that the tester is suitably experienced and competent at testing fasteners.
The full series of the “Site Testing Guidelines” Technical Notes is as follows:
• Volume 1: General
• Volume 2: Proof tests
• Volume 3: Ultimate tests
• Volume 4: Testing in masonry
It is a requirement that Volume 1 be used in conjunction with the other volumes as
necessary.
These guidelines have been based on recommendations made in BS 8539:2012 [1]
and by the Construction Fixings Association [2].
Note: Site testing only show the short-term performance of fasteners for the
temperature and environmental conditions present during the tests. The performance
and suitability of the product shall be reviewed and checked from the issued ETA for the
exposure conditions such as temperature and environmental effects to the fastener
during its lifetime.

1. Scope
The test methods outlined in these Technical Notes relate to quasi-static loading
procedures for product-specific evaluation performed on site. These Technical Notes
apply for post-installed fasteners only. The advice provided in this document is of a
general nature and is consistent with international guidelines ([1], [2]). This guidance
document should not be considered a substitute for manufacturer’s installation
instructions or technical advice from the fastener manufacturer/supplier.
Incorrect or incomplete site testing practice may result in a failure to diagnose
deficient installation or the correct performance of a fastener, leading to catastrophic
outcomes.
These Technical Notes do not cover the tests in shear direction, as they are limited by
material strength of base material and fastener, and less sensitive to installation. In
addition, compressive actions are normally transferred from the fixture into the
substrate with little or no effect on the fastener. Thus, the compressive actions are

2
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

excluded in the Technical Notes. This document provides advice primarily on the
tensile resistance of fasteners for applying Proof or Ultimate Loads in tensile
direction
This document provides technical advice on site testing techniques to verify the
performance of fasteners and does not address all safety-precautions needing to be
followed during site testing of fasteners to concrete and masonry. Advice should be
sought from the relevant safety authority such as WorkCover Authority and the site
manager for advice on the use of Personal Protective Equipment (PPE) during testing.
Note: As a minimum PPE for the tester should include a helmet, eye protection, gloves
(if handling chemical fasteners), dust mask (if exposed to dust in a confined space),
hearing protection, and equipment to restrain the test setup during testing (if
necessary).

2. Notation
fy = Characteristic yield strength of steel (fastener)
FOS = Factor of Safety
As = Cross sectional area of steel (fastener) in tension
hef = effective embedment depth of fastener
proof load test factor depending on the percentage of fasteners tested
κP,test =
in a discrete area
ks = statistical sampling factor
Np = load applied to fixing for a proof load test
maximum allowable load applied to fixing for a proof load test
Np, max =
without damaging fastening
maximum load applied to fixture during testing to determine
Ntest =
allowable resistance based on the simplified method
NRd = design resistance of the fastening
NRk = characteristic resistance of a fastening
NR,all = allowable resistance of the fastening
characteristic resistance of the fastening published in the approval
NRk,ETA =
document (ETA)
characteristic ultimate load determined from tests on prequalified
NRk1 =
products

3
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

characteristic ultimate load determined from simplified tests in the


NRk2 =
masonry
NSk = Characteristic action applied to fastener
Nu = ultimate strength of a fastening
Nu,ave = average ultimate strength of a sample of fastenings
Nu,low = lowest ultimate strength from a sample population of fastenings
N1mm = load at 1 mm displacement for a single fastener
average load at 1 mm displacement for a sample population of
N1mm,ave =
fasteners
S* = design load
standard deviation of the ultimate strength of a sample population of
s =
fasteners
v = coefficient of variation of the ultimate loads determined from testing
product specific influencing factor provided in the approval
β = document (ETA) based on performance measures determined from
testing and evaluation in a given substrate
γF = partial safety factor for action, typically 1.4 for general case
partial safety factor for material published in the approval document
γM =
(ETA)
factor used to determine the allowable strength of a fixture based on
κave =
average ultimate loads determined from testing
factor used to determine the allowable strength of a fixture based on
κlow =
the lowest ultimate load determined from testing
factor used to establish the test load for the simplified approach for
κtest =
determining the allowable resistance
φ = capacity reduction factor
capacity reduction factor for material resistance, inversely related to
φM = the partial safety factor for material strength (γM) published in the
approval document (ETA)

3. Terminology
The following terminology and definitions are adopted in this document. Additional
terminology and definitions may be found in the AEFAC Fastener Dictionary [3].

4
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

Allowable resistance: maximum working load derived from tests performed on site
when the proposed fastener is to be used in a base material approved by the
manufacturer but for which there is no recommended resistance.
Characteristic resistance: resistance derived as the 5% fractile (95% of fasteners
exceed the characteristic resistance with 90% confidence level) of mean ultimate
resistance. This is determined from tests or empirical calculations based on modes of
failure.
Confined test: a test performed on an installed fastener such that the positioning of
reaction points of the test rig inhibits the formation of concrete-related modes of
failure.
Design resistance: resistance derived from the characteristic resistance by the
application of capacity reduction factor
Fastener: a type of device that is post-installed into hardened concrete or cast into
concrete.
Fastening: an assembly comprising fastener(s) to secure a fixture to the concrete base
material.
Fixture: the element that is being secured to the base material via fasteners.
Manufacturer’s recommended load: maximum working load recommended by a
manufacturer, typically the characteristic resistance divided by partial safety factor
for material and action [NRk /(γM × γF)]
Preliminary test: test carried out on site to determine the allowable resistance in the
case where no characteristic resistance or recommended resistance is available.
Proof tests: a test performed on a completely installed fastener and is intended to
validate correct installation.
Responsible engineer: the person responsible for overseeing the test regime for the
fasteners and to ensure that the site testing of fasteners provides the information
required for the project.
Safe Working Load: See “Working Load Limit”
Tester: the person with the responsibility to conduct the on-site fastener testing to an
agreed regime and to report information collected during testing.
Unconfined test: a test performed on an installed fastener such that the positioning of
reaction points of the test rig does not inhibit the formation of any modes of failure.

5
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

Ultimate load test: A test performed on a fastener whose installation is complete and
is intended to aid in establishing the suitability of the fastener in a particular base
material.
Working Load Limit (WLL): the maximum load that can be applied without the
strength and stability requirements being exceeded. Also known as safe working load,
allowable working load, maximum rated load, and permissible working load.

4. General
Site testing may be performed for one of two reasons:
(i) Validate correct installation (proof tests), or
(ii) Identify the characteristic strength of a fastener in a given substrate (ultimate
tests).
The performance of fasteners in concrete is typically known, thus ultimate tests
generally are not warranted in concrete substrates. However, given the complexity of
masonry substrates, technical data is generally limited such that site testing is
frequently employed to determine the ultimate strength of a fixing for use in masonry
substrates.
Site testing for proof tests and ultimate tests requires that the fasteners being tested
are installed in accordance with the manufacturer’s installation instructions, as well
as any supplementary requirements stipulated by the responsible engineer.
Note: It is the responsibility of the tester to prepare a report of results from the tests
undertaken. Interpretation of the test results from site testing is undertaken by the
responsible engineer, including identifying causes of any failures, any modifications to
the test regime and the modification to the specification of fasteners (if required).
This Guidance Note provides advice primarily on the tensile resistance of fasteners
since the shear strength is less sensitive to installation and is generally governed by
material strength if sufficient edge distance is present. Shear strength may therefore
be readily determined by calculating the shear capacity of the fastener component or
substrate. However, when the required edge distance is less than the manufacturer’s
published edge distance, technical assistance from the manufacturer should be
sought to determine an appropriate shear test program. Shear testing may also be
required to determine the performance of a fastener in low strength masonry. Tensile
testing is necessary since the tensile performance of fasteners is dependent on the
suitability of the fastener in the substrate, proper design and correct installation.
Fastener products having a European Technical Approval/Assessment (ETA) publish
their performance for a given substrate type, together with other parameters defining

6
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

their performance [4, 10]. This information may then be used with design provisions
such as those in AS 5216 [5] to calculate the expected strength. When a product does
have an ETA, the design engineer may request site tests to be performed to verify that
the product has been installed correctly.
Note: If site shear tests are deemed necessary, technical advice should be sought from
the supplier of the fastener product to develop a suitable test procedure.

5. Type of test: proof test vs ultimate test


The engineer responsible for requesting the site tests determines the nature of the
tests which may fall into one of two categories outlined below. Therefore, while the
tester performs the test in a prescribed manner, the tester’s role does not include
identification of suitable test loads, interpretation of results or calculating allowable
loads based on the outcomes of testing [7]. These responsibilities belong to the
engineer specifying the test.

5.1. Proof tests

5.1.1. General
The objective of proof tests is to validate installation on a sample population of
fasteners by loading the installed fasteners to a prescribed test load (proof load) that
is a fraction of the fastener’s capacity. The magnitude of the test load depends on the
fastener application and material. Proof tests should be conducted on a sample of the
fasteners installed for the project. A proof load does not result in the fixture
experiencing failure and is not used to determine the allowable strength of the
fastener in a given substrate.
Proof tests are generally short term in nature and are therefore not suitable for
investigating creep behaviour. While the nature of the proof tests provides a modest
safety margin, they are not appropriate for investigating the suitability of a fastener
in a given substrate.
Proof tests may only be carried out after the manufacturer’s recommended curing
time for the chemical fasteners.
Note: The requirement for proof tests to verify correct installation of safety-critical
fasteners may not be required if the fastener has been prequalified according to the
relevant EAD/ETAG, and the installer is under supervision and is appropriately trained
either via the AEFAC Installer Certification Program and/or training provided by the
product supplier. The requirement for proof testing is determined by the responsible
engineer.

7
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

5.1.2. Proof test sequence


The requirement of a proof test is to load each fastener to the proof load identified by
the design engineer to demonstrate that the fastener has been installed correctly.
Upon achieving the proof load, the test may be terminated. Further guidance may be
found in Volume 2.

5.2. Ultimate tests

5.2.1. General
The objective of ultimate tests is to determine the allowable strength of the fastening.
If ultimate tests are required, they should be performed prior to completion of the
fastener selection process to ensure that all project requirements are met.
Scenarios where ultimate testing may be performed are as follows:
(i) Manufacturer has a provisional approval for the product to be used in the
substrate but performance data is not available.
(ii) Fastener has an approval (e.g. ETA) for use in masonry but the type,
strength or dimensions of the masonry are outside the scope of the ETA.
(iii) Fastener has an approval (e.g. ETA) but the application is outside the scope
of the ETA, for example edge distance is outside the scope of the ETA.

The test procedure for applications involving products without an ETA is closely
based on recommendations from BS 8539 [1] and the Construction Fixings
Association’s guidance note, “Procedure for Site Testing Construction Fixings” [2].
Ultimate tests are carried out on a sample population of sacrificial fastenings that are
considered to be representative of the intended application. This requires a
representative substrate, the same type of fasteners that will be used in the project
and installation by the same work crew. It may be necessary following testing to make
good any substrate damage incurred by the test population.
Ultimate tests are not required for fasteners in concrete provided the product is
prequalified in accordance with Appendix A of AS 5216 and the application falls
within the scope of the product’s approval. In this case the design data is published in
the prequalification. If the fastener is being installed in masonry that is the same
category for which it has been awarded a prequalification, ultimate tests may still be
required if either the strength of the masonry or the dimensions of the masonry are
less than the minimum requirement of the prequalification. In the case of masonry,
the category of substrate relates to the type or material and type of brick unit (e.g.
solid, perforated, hollow).

8
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

If the intended application is beyond the scope of its prequalification (approval),


ultimate tests may be performed to establish the allowable strength provided the
fastener manufacturer approves the fastening for use in this specific application.
Further guidance is available on the limitations of fasteners installed in concrete
applications in [3] and for chemical fasteners installed in masonry in [6].
Note: Fasteners for ultimate tests are considered sacrificial and should not be used in
the project.

5.2.2. Ultimate test sequence


There are two types of ultimate test that may be performed depending on the
requirements of the project:
• Simplified regime: Each fastener in the sample population is loaded to a test load
(Ntest) determined by the designer prior to the test taking place. Once the desired
load is achieved the load is removed to reduce the likelihood of damaging the
substrate. The allowable strength of the fastener (NR,all) is calculated by
considering the maximum test load, average ultimate strength and the lowest
ultimate strength recorded from tests on the sample population.
• Statistical regime: This regime is destructive and requires each specimen within
the sample population to be tested to failure. The allowable strength of the fastener
(NR,all) is calculated using a statistical method based on the ultimate strength of the
sample population.
Further details of these two regimes are provided in Volume 3.

6. Test Setup

6.1. Test equipment


Test equipment should be inspected prior to commencement of testing to ensure
good working condition. Additional requirements for the test apparatus include:
• The Working Load Limit of all components of the test apparatus (support frame,
tension rods, couplers, etc.) should not be less than the test loads. The Working
Load Limit should include a suitable safety margin to ensure the equipment is not
damaged during testing.
• The specified stroke of hydraulic test equipment should not be exceeded at any
stage during the test.
• The accuracy of the load gauge should be +/- 5% of the load readings. The
equipment should be calibrated at least annually, as well if the equipment is
dropped or repaired. If a calibration requires a conversion from gauge readings to
actual load, the conversion should be provided in the test report. The load gauge

9
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

should be capable of indicating the maximum load achieved during the test that
may be referred to upon completion of the test.
• Calibration should occur in a precision test machine such as one that has NATA
certification.
• The accuracy of displacement measurement should be to within +/- 0.02 mm.

Note: If it is necessary to install fasteners for the purpose of testing the manufacturer’s
installation instructions should be consulted for a list of equipment necessary for correct
fastener installation.

6.2. Configuration of test rig


There are a variety of different sized test setups available for applying loads to fixings,
including those suitable for larger fixings (see Figure 2) and those suitable for smaller
fixings (see Figure 3). The suitability of the test rig should be accounted for when
considering the project requirements.
Selection of an appropriate test rig should consider the nature of the test (proof test
vs. ultimate test) and the type of fastener (e.g. mechanical vs. chemical) since this
affects the potential mode(s) of failure that may be observed. An ultimate test
performed for mechanical or chemical fasteners or a proof test of mechanical
fasteners generally requires an unconfined test setup (refer to Figure 1 (a)) to
demonstrate the decisive mode of failure. A confined test setup (refer to Figure 1(b))
may be utilised for proof test of chemical fasteners to verify the correct bond has been
achieved between the chemical and steel element or the chemical and substrate.
However, it should be noted that a confined test may not detect gross errors related
to incorrect embedment depth of fasteners installed. An unconfined test setup would
be more appropriate for checking potential gross errors in embedment depth during
installation.

10
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL


(a) Unconfined test setup. (b) Confined test setup.

Figure 1: Different types of test setup that may be required on site.

6.2.1. Position of legs of test rig


Regardless of the size of the rig, the legs should be adjustable to ensure that direct
tension is applied to the fixing and that shear loads and bending moments are
avoided. Proper adjustment of the legs will ensure correct alignment of the
application of load and proper support of the legs of the test rig.
The proximity of the test apparatus’s legs to the fastener is important and may
influence the results when too close to the fastener by suppressing a mode of failure
(such as concrete cone failure). The recommended minimum spacing between the test
rig leg and the fixing for an unconfined test (refer to Figure 2 and Figure 3) depends
on the type of test as summarised in Table 1.
Table 1: Minimum required distance between fastener and support legs of test rig.

Minimum distance between


Type of test Magnitude of maximum load fastener and support legs of
apparatus
< 1.5 x manufacturer’s
Proof* 0.75hef
recommended load and 0.7 ×
steel yield strength
Ultimate Determined from test 2.0hef
* Note that for proof tests on chemical fasteners to assess the performance of the
interface between the fastener and concrete, the support legs may be very close to the
fastener to simulate a confined test.

11
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

The effective depth (hef) refers to the greatest depth to which load is resisted by the
fixing (fastener engages with the concrete), not the total depth of the fixing or depth
of hole.
If the minimum spacing between the fastener and test rig support leg outlined in
Table 1 cannot be achieved due to restricted access, the engineer requesting the tests
should be notified in the test report.



Figure 2: Hydraulic ram setup for large Figure 3: Hand operated test rig for
fixings with high load. small fixings with lower test loads.

6.2.2. Stability of test rig


The stability of the test rig should not be compromised at any time during the test or
as a result of a failure of the fixture being tested. In the case of overhead tests (such
as on the soffit of a concrete slab) the test rig should be secured so as the test rig and
its parts/components will not fall in the event of failure of the fixing.

6.2.3. Connection of fastener to test equipment


The fastener should be installed in accordance with the manufacturer’s installation
instructions. In the event that the fastener is to be torqued during installation, the
fastener should be installed through an appropriately sized bush and plate assembly
with an appropriate hole clearance and thickness as per the engineer’s specification.
A torque may only be applied to chemical fasteners once manufacturer’s
recommended curing time is complete.
The choice of connection between the fixing and the test rig will depend on the
objective of the test. A simple threaded coupler may be used where a projected thread

12
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

is available, with or without a plate clamped with a nut to simulate clamping (refer to
Figure 5(a) and Figure 5(b), respectively). All necessary precautions should be taken
to ensure the test rig is aligned with the orientation of the fastener so as not to induce
bending during testing that may lead to invalid results.


(a) Torque required to (b) Torque not Figure 4: Pulling frame for clamping
clamp plate. required for fixture effect.
installation.

Figure 5: Couplers attached to pulling rod.

For ultimate load testing the coupler should cover a length of thread equal to at least
1.5 times the diameter of the rod being tested. The choice between the two methods
(with or without a clamped plate) will depend on whether a torque is applied to the
fixture during installation. Displacement-controlled fasteners, some undercut
fasteners and most bonded fasteners do not require an installation torque to operate
correctly. Conversely, installation torque for torque-controlled expansion fasteners is
imperative for their correct operation.
Figure 5 depicts an alternate setup that may be adopted when the clamping effect is
to be monitored during the test. In this setup the plate simulates the fixture and
accurate displacement measurements may be made on the top of the fastener.
Spherical washers may be used to eliminate negative effects of bending.

6.2.4. Displacement measurement


Characteristics important for displacement measurement including the following:

13
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

i) The accuracy of the displacement measurement should not exceed 10% of the
actual reading.
ii) The precision of measurement should be no greater than 5% of the maximum
displacement for the test.
Recording of deformation is at the discretion of the engineer requesting the test and
will generally depend on the type of test (proof or ultimate). The three typical
deformation measurement profiles adopted during site testing are as follows:
i) None: measurement of deformation is typically not warranted for proof tests
where very little (if any) visible deformation occurs. A fastener exhibiting visible
movement up to the proof load will often be deemed a failure. For applications
where serviceability function is critical for the fastener, displacement
measurements should be taken.
ii) First visual: if visible deformation is observed, a suitable method of measurement
such as a dial gauge should be adopted to quantify the relative deformation
between the fastener head and the surface of the substrate.
iii) Detailed: where the intent of the site test is to reproduce the load-deflection
characteristics of the fastener’s performance, it is recommended that
displacement measurements occur at load intervals equal to one-tenth of the
ultimate load expected or at shorter intervals.
Care should be taken when measuring deformation, particularly regarding the chosen
reference point. Deformation measurements on test apparatus are typically global in
nature and include stretching or deformation of various components of the test rig
that are difficult to compensate for. Consequently, it is strongly recommended that
the point of reference is beyond the zone where a concrete cone may form and that is
independent to any part of the test device. Further, measurement should not be made
from any point on the test rig since this will experience deformation during testing.
Where ‘first movement’ requires detection, a simple visual assessment may be made
of a gap opening in the fixture. If the serviceability limit is to be assessed at the
manufacturer’s recommended load, feeler gauges may be used to assess the gap in
the fixture, taking care to ensure the gap measured is representative of fastener
displacement. For safety-critical applications, in either Proof or Ultimate Load Tests,
movement should be monitored to ensure that a serviceability limit is not exceeded
before the Design Load is reached.
In the event that detailed recordings are required a dial gauge or a more sophisticated
electronic data acquisition system should be adopted. When detailed recordings and
a pulling plate assembly are required, direct measurements of the head of the fastener
may be made (refer to Figure 6). Direct measurement provides the most accurate
recording of displacement; however, the measuring equipment may be damaged if

14
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

the fastener fails. To avoid the possibility of damaging the measuring equipment, an
eccentric attachment may be introduced to facilitate measurement of the head of the
fastener as illustrated in Figure 6. If an eccentric displacement measurement is
performed (e.g. on one side of the plate), errors are possible since the fastener may
experience rotation during loading, resulting in an apparent increase or decrease in
the displacement measurement. Care should be taken as this error may go unnoticed
during testing since the tester may not be able to detect bending visually.
The application of a torque during installation of a fastener results in a preload that
will delay displacement until the preload has been overcome by the applied load. The
permissible deformation of the fastening may be governed by serviceability limits
specific to the project that will determine when the test should terminate. The
serviceability limit for deformation should not be reached before achieving the design
load. The expected displacement will also depend on the type of fastener, with an
example being displacement-controlled expansion fasteners which are likely to
experience relatively less displacement prior to failure compared to torque-
controlled expansion fasteners which have a follow-up expansion capability.


(a) Elevation. (b) Plan view.
Figure 6: Example test rig set for detailed displacement measurement (section view).

In the event that detailed deformation measurements are required, the following
procedure should be adopted for the application of load:
1. Recordings of displacement are made at predetermined intervals, such as
1/10th ultimate load or proof load, depending on the type of test being
conducted. Sufficient resolution should be available in the results to identify
the load-displacement curve of the fastener. It is recommended that the loading
regime include measurements when the displacement equals 0.1mm, as well

15
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

as when the design load or manufacturer’s recommended applied load is


achieved. If the fastener is not tightened during installation, the load reading at
0.1 mm displacement may not be relevant.
2. It is recommended that a very small ‘bedding-in’ load (< 100 N or no greater
than 5% of the estimated strength of the fastening) be applied at the beginning
of the test to help correct for any offset present in the displacement measuring
equipment and a recording made of the load and displacement.
3. Upon reaching the end of a load interval, record the load and displacement
readings.
4. Resume loading until the proof load or ultimate load is achieved.
5. Record the maximum load achieved, failure mode observed and any damage
sustained by the structure.
6. Deduct the displacement recorded from the ‘bedding-in’ load from all
displacement measurements and plot the resultant load-displacement
relationship.

6.3. Summary of test equipment


The test equipment typically required will include:
• Loading frame
• Hydraulic cylinder
• Load gauge
• Displacement transducer with suitable mount (if required)
• Coupler or suitable connection to fastener
• Pulling rod
• Spherical washer (optional)

7. Test regime

7.1. Application of load


In all cases the load should be applied progressively, without abrupt changes or a
sharp stepped behaviour if the application of load is via a hand operated pump.
Sudden changes in load may lead to erroneous results and premature failure due to a
sudden spike in load.
The nature of loading will be influenced by the chosen displacement measurement
profile. Load relaxation may occur due to many factors such as pressure release in
test equipment, slip between fastener components, slip between the fastener and wall
of the hole, formation of micro-cracks within the substrate, elastic deformation within

16
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

the fastener system, as well as other factors. Consequently, corresponding load and
displacement measurements should be recorded as close together as possible to
avoid the effects of load relaxation on the results.
The increase in load should occur at a rate such that the peak load is experienced
between one to three minutes from the commencement of the test.
It is highly recommended that the test be witnessed by a representative from the
client or engineer requesting the tests.
Note: Testing fasteners may be dangerous, particularly when testing to ultimate load or
failure. When pulling rods in tension no person should stand in line with the rod. Before
commencing the tests, all necessary precautions such as the wearing of personal
protective equipment should be taken to mitigate the risk of injury to the tester,
witnesses and any bystanders present during testing.
The number of required tests should be assessed on a case-by-case basis by the
engineer requesting the tests. The minimum number of tests is recommended in the
respective Volumes 2 to 4 of this series.

8. Additional requirements for tests

8.1. General
If the fastener manufacturer does not approve their use in the general category of the
substrate, site testing should not be considered a suitable method of demonstrating
satisfactory performance. Some fasteners are not compatible with certain types of
substrate (e.g. expansion fasteners in hollow masonry). Manufacturer’s literature
should always be consulted to determine suitability of a product.
Where the properties of the substrate are known or may be readily identified, design
data is available for the substrate properties, and installation is performed by a
competent individual under appropriate supervision, site testing is generally not
required.
There may be certain special applications whereby industry-specific requirements
may be published for which the fastener manufacturer should be able to provide
guidance.

9. Report of results
A list of the information to be included in the test report is provided in Appendix A.

17
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

10. Summary
This Technical Note provides general recommendations for the site testing of safety-
critical fasteners for the purpose of proof testing and to evaluate ultimate strength.
Recommendations have been provided for proper test setup, including test rig
positioning, connection to the fastener, displacement measurement and application
of load. Provided the substrate properties are known, the fastener has a suitable
prequalification such as an ETA for the substrate, and the fastener is installed as per
manufacturer’s installation instructions by a suitably qualified installer, site testing is
generally not required. However, the responsible engineer may elect to specify site
testing for added confidence in the installation. While proof tests are performed to
verify correct installation, the purpose of ultimate tests is to determine ultimate
strength of the fastening. Appendix B provides a summary of test regimes.
The advice provided is not exhaustive and should be used together with advice
provided in the other volumes of this series as appropriate to the type of testing being
conducted.

11. References
[1] British Standard 8539, “Code of practice for the selection and installation of
post-installed anchors in concrete and masonry”, BSI Standards Limited 2012
[2] Construction Fixings Association, “Procedure for Site Testing Construction
Fixings”, Guidance Note, www.fixingscfa.co.uk
[3] AEFAC Technical Note 07, “AEFAC Fastener Dictionary”, www.aefac.org.au
[4] EAD 330232, “Mechanical fasteners for use in concrete”, EOTA, 2016
[5] AS 5216:2018, “Design of post-installed and cast-in fastenings in concrete”,
Standards Australia
[6] EOTA TR053“ Recommendations for job-site tests of metal injection anchors for
use in masonry”, www.eota.eu, 2016
[7] Construction Fixings Association, “How to test anchors on site in accordance
with BS 8539:2012”, Guidance Note, www.fixingscfa.co.uk
[8] AEFAC Technical Note 01, “Design Concepts for Post-Installed and Cast-In
Fasteners”, www.aefac.org.au
[9] AEFAC Technical Note 02, “Prequalification of Post-Installed and Cast-In
Fasteners”, www.aefac.org.au
[10] EAD 330499, “Bonded fasteners for use in concrete”, EOTA, 2017

18
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

APPENDIX A
TEST REPORT
The following provides a list of minimum information that should be recorded and
reported to the design engineer/specifier. Additional information may be warranted
subject to site-specific considerations.
The purpose of the test report is to identify if all objectives of the test(s) have been
met, as well as any deviations.

A.1 Administration details


• Date of test
• Reason for test
• Name of person requesting test
• Report reference number
• Client’s company name, address, contact name and position
• Site location, contact name and position
• Name and company of tester with job title and/or appropriate qualifications
• Name and companies of witnesses
• Name and company of installer of fasteners

A.2 Anchor/application details


• Name of manufacturer
• Anchor type, size and finish
• Proposed application of fastener
• Design resistance and manufacturer’s recommended resistance in the base
material concerned (for proof tests)

A.3 Test objectives


• Proof tests or ultimate tests
• Required load for proof tests (if applicable)

A.4 Test location


• Detail of the location of each test within the structure with sketch where
appropriate
• Edge distance, centre spacing and structural thickness, if appropriate

19
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

A.5 Base material


• Type and strength at time of test, if known
• Whether solid, hollow or perforated units (masonry)

A.6 Installation details


If the installation is carried out by the tester, the following information should be
reported:
• Nominal hole diameter
• Drill bit cutting diameter, recorded to 0.1 mm
• Drilling method/tools
• Hole depth
• Effective embedment depth
• Hole cleaning method in detail
• Prescribed installation torque and tightening torque applied
• For bonded fasteners (if applicable):
o Ambient temperature when installed
o Manufacturer’s recommended curing time
o Actual curing time allowed

A.7 Test equipment details


• Make, type and load capacity of hydraulic ram/gauge or tester
• Date of last calibration, calibrating authority
• Make and type of movement recorder, dial gauge, etc.
• Loading frame: distance between fastener and closest support
• Make and range of torque wrench

A.8 Test results


The information reported is dependent on the nature of the test undertaken.

A.8.1 Load
• Maximum load
• Condition of fastener and surrounding base material before and after test
• Load at first visible movement

20
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

A.8.2 Movement
If required, the load should be reported at different load increments specified by the
engineer requesting the tests, as well as the maximum load.

A.8.3 Mode of failure


Single or multiple modes of failure observed including the following possible modes:
• Base material: cone failure, spalling, splitting, cracking, blow-out failure, bond
failure (chemical fasteners), combined cone-bond failure (chemical fasteners)
• Steel failure: fracture
• Pull-out/excessive movement

A.8.4 Method statement


A.8.5 Gauge calibration certificate
A.8.6 Test summary
• Statement of whether the test procedure was followed including a summary of any
deviations
• Statement regarding whether or not the test objectives where met

21
www.aefac.org.au

TECHNICAL NOTE:

SITE TESTING GUIDELINES – VOL 1: GENERAL

APPENDIX B:
SUMMARY OF TEST REGIMES


Figure B1: Flowchart of test regimes

22
www.aefac.org.au

Disclaimer: The information provided in this Technical Note is intended for


general guidance only, and in no way replaces the services of design engineers on
particular projects or subjects. AEFAC and its board, constituent members,
representatives or agents will not be liable for any claims or damages whatsoever
resulting from use or reliance on information in this Technical Note.

www.aefac.org.au

You might also like