Eone W Series Grinder Pump Installation Instructions

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

W-SERIES

TYPICAL
INSTALLATION
INSTRUCTIONS
& WARRANTY
INFORMATION
SIMPLEX, DUPLEX, TRIPLEX &
QUADPLEX STATIONS

1
Environment One Grinder Pump Feature Identification
1. Grinder Pump Basin – High density polyethylene (HDPE)

2. Accessway Cover – Station lid with integral vent (non-traffic rated)

3. Electrical Quick Disconnect (EQD) – Electrical lead from pump core terminates here (NEMA
6P).

4. Power and Alarm Lead – Circuits to be installed in accordance with local codes.

5. Alarm Panel – Rainproof (NEMA 4X) enclosure. Equipped with circuit breakers. Locate accord-
ing to local codes.

6. Alarm Device – Every installation is to have an alarm device to alert the homeowner of a po-
tential malfunction. Visual devices should be placed in conspicuous locations.

7. Inlet – Standard configuration 4-inch PVC socket (4.5 inches ID). For solvent cementing DWV
pipe.

8. Settling Loop – Coil wire to protect against soil settling.

9. Gravity Service Line – Standard configuration 4-inch DWV (4.5 inches OD). Supplied by oth-
ers.

10. Discharge Outlet – Standard configuration 1 ¼-inch solvent weld

11. Discharge Line – 1 ¼-inch nominal pipe size. Supplied by others.

12. Concrete Anchor – See Charts 1 and 2 for correct ballast weight. Supplied by others.

13. Bedding Material – 6-inch minimum depth, rounded aggregate (gravel). Supplied by others.

14. Finished Grade – Grade line should be below the cover and slope away from the accessway.

15. Conduit – 1 ¼-inch PVC to burial depth required by local code. Supplied by others.

16. Rebar – Required to lift tank after pre-cast ballast has been attached (4 places, evenly spaced
around tank). Supplied by others.

17. Grinder Pump Basin – Fiberglass

18. Station Lid – Fiberglass (non-traffic rated)

19. Station Vent – Mushroom vent

20. Inlet – Standard configuration EPDM grommet (4.5” ID). For 4.5” OD DWV pipe.

2
SEAL
CONDUIT PER
NEC SECTION
300.5 & 300.7

FAILURE TO
COMPLY WITH
INSTALLATION SEAL
CONDUIT PER
NEC SECTION

INSTRUCTIONS 300.5 & 300.7

WILL VOID
WARRANTY

Figure 1

3
TYPICAL MULTI-
PUMP STATIONS:
DUPLEX,
TRIPLEX &
QUADPLEX
Simplex 1 Simplex Panel
Duplex 1 Duplex Panel
Triplex 1 Simplex Panel, 1 Duplex Panel
Quadplex 2 Duplex Panels

4
This is a sewage handling levels. The amount of concrete slope of the inlet pipe (per na-
pump and must be vented in required varies for each unit tional and local code require-
accordance with local plumbing (see station detail sheet for the ments) must be accounted
codes. Do not install the unit in correct ballast weight). for when determining the inlet
locations classified as hazard- The unit should be leveled location. The supply cable path
ous in accordance with the and filled with water to the and cord grip location should
National Electric Code, ANSI/ bottom of the inlet; doing so be considered when selecting
NFPA 70. All piping and electri- prevents the unit from shift- the inlet location (see Section
cal systems must be in compli- ing when pouring the cement. 11 and Figure 5).
ance with applicable local and The cement must be manually If the site conditions require
state codes. vibrated to eliminate any voids. concrete tank ballast to prevent
1. Remove Packing Material If pouring the cement to a level flotation, ensure that the vol-
Give the User Instructions to higher than the inlet piping is ume of concrete used complies
the homeowner. Hardware sup- necessary, place an 8-inch with the site Engineer’s recom-
plied with the unit, if required, sleeve over the inlet prior to mendation. Concrete ballast,
will be used during installation. pouring the cement. if required, should be cast in
2. Tank Installation (HDPE 3. Tank Installation (Fiber- place around the tank in the
tank) The tank is supplied with glass tank) Improper handling excavation. Do not pour the
a standard 4-inch PVC DWV of the fiberglass tank may concrete ballast above the
(4.5 inches inside dia.) inlet for result in damage and, ultimate- marked inlet pipe location.
connecting the incoming sewer ly, failure of the station. Care If the ballast must be poured
drain. Other inlet types and should be taken during lifting above this level, proceed with
sizes are optional (caution 4” and placement to prevent im- installation of the inlet piping
DR-35 pipe is of smaller diam- pacting or otherwise damaging (see Section 5) before pour-
eter and won’t create a water the tank. A non-marring sling ing the concrete. The inlet pipe
tight joint with the standard should be used when lifting the must be sleeved with an 8”
grommet). Confirm that you tank by the fiberglass surfaces. tube prior to pouring. The tank
have the correct inlet before Ensure that lifting sling is rated should be filled with water, to a
continuing with installation. If a for the load being lifted. Lifting level above the specified bal-
concrete ballast is attached to chains or cables should never last height to prevent shifting
the tank, lift only by the lifting be placed in direct contact with during the concrete pour.
eyes embedded in concrete. the fiberglass tank surfaces. Alternatively, precast con-
Do not drop, roll or lay the Place the unit on a 6-inch bed crete, around the tank bottom,
tank on its side. Doing so may of gravel, naturally rounded ag- may be used for ballast (Fig.
damage the unit and void the gregate, clean and free-flowing, 1). Do not pour ballast above
warranty. with particle size not less than the intended inlet location. If
Excavate a hole to a depth so 1/8 inch or more than ¾ inch in this ballast method is used, lift-
the removable cover extends diameter in the excavated hole. ing hooks must be anchored in
2 inches above the finished Orient the installed discharge the concrete to support subse-
grade line; the grade should fitting, as required, to align it quent handling of the tank. The
slope away from the unit. The with the existing or proposed lifting hooks must be adequate
diameter of the hole must be discharge piping path. to support the combined weight
large enough to allow a con- Determine and mark the 4” of the tank and concrete bal-
crete anchor. Place the unit on DWV inlet pipe location on the last, and should be sized and
a 6-inch bed of gravel, naturally fiberglass tank wall. The inlet installed in accordance with the
rounded aggregate, clean and pipe location corresponds with site engineer’s recommenda-
free-flowing, with particle size the actual or projected point tion.
not less than 1/8 inch or more where the 4” building sewer line Place the ballasted tank in
than ¾ inch in diameter. The intersects the tank wall. The the excavated hole using the
concrete anchor is required to center of the inlet pipe must lifting hooks. Do not lift the
keep the unit from floating as be a minimum of 30 inches tank by any of the fiberglass
a result of high groundwater from bottom of the tank. The surfaces if precast ballast is
5
utilized. ments of the inlet pipe must be Apply a film of pipe soap or
4. Discharge The use of in accordance with all national dish soap to the outside sur-
1-1/4” PVC pressure pipe and local plumbing codes. The face of the inlet pipe end and
Schedule 40 and polyethylene pump is a sewage-handling the inside of the grommet. In-
pipe SDR 11 or SIDR 7 are pump and requires ventilation sert the pipe end into the grom-
recommended. If polyethylene for proper and safe operation. met and push the inlet pipe
is chosen, use compression An HDPE station is supplied into the fiberglass tank until the
type fittings to provide a with 4-inch PVC socket (4.5 3-1/2” mark lines up with the
smooth inner passage. inches ID) for solvent cement- grommet outside edge. Inspect
E/One requires that an ing DWV pipe. the grommet flange on the
E/One Uni-Lateral assembly A fiberglass station is sup- outside of the tank. The flange
(E/One part number plied with a standard grommet should be flush against the
NB0184PXX or NC0193GXX) to accept a 4” DWV (4.5” out- tank wall and completely visible
or E/One Redundant Check side diameter) sewer inlet pipe. when the pipe and grommet
Valve (E/One part number The grommet is self-sealing are installed properly.
PC0051GXX) be installed in and does not require the use of 6. Vent Installation A fiber-
the pipe lateral outside the additional sealant or adhesives. glass station is supplied with a
home between the pump Other grommet sizes are avail- 2” mushroom vent to be in-
discharge and the street main able upon request. Verify that stalled in the station cover.
on all installations. Never use the grommet supplied with the Locate the 3” hole in the sta-
a ball-type valve as a check station will accommodate the tion cover. A vent hole may be
valve. E/One recommends selected inlet piping. Using a added to a station cover in the
the valve be installed as close 5” hole saw, drill through the field if it is not existing, using a
to the public right-of-way as fiberglass tank wall at the 3” diameter hole saw. Consult
possible. Check local codes for marked inlet location. Install the factory before installing a
applicable requirements. the supplied inlet grommet in vent hole in an existing sta-
CAUTION: Redundant check the 5” hole. tion cover.
valves on station laterals and Place a mark on the inlet Install the rubber grommet
anti-siphon/check valve assem- pipe 3-1/2” in from the end that in the hole in the station. The
blies on grinder pump cores will enter the fiberglass tank. A flange on the grommet should
should not be used as system bevel should be ground or filed sit flush with the station cover.
isolation valves during line on the pipe end to aid in instal- Apply soap to the end of the
tests. lation through the grommet. nipple on the vent assembly.
5. Inlet Installation The Clean the grommet and pipe Align the nipple on the vent
type, size and venting require- surfaces to remove any debris. assembly with the grommet in
the station cover and press the
vent assembly down into the
grommet until the vent housing
bottoms on the grommet.
7. Backfill Requirements
Proper backfill is essential to
the long-term reliability of any
underground structure. Several
methods of backfill are avail-
able and each yields favorable
results when done properly.
Clean, compact, native soil
that is free from rocks, roots or
organic material may be used if
compacted in lifts not to exceed
one foot. It must be compact-
Figure 2 ed to a final Proctor density
6
between 85 and 90 percent. Your panel may differ from the one shown below. Wire your panel
Heavy, non-compactible clays per the wiring decal on the inside of the enclosure door.
are not acceptable backfill for
this or any underground struc-
ture such as inlet or discharge
lines.
Class 1 or Class 2 backfill
material as defined by ASTM
2321 may also be used.
Crushed stone and gravel
backfill materials offer an
advantage since they typically
reach a compaction level of 90
to 95 percent standard density
with minimal compaction.
Another option is flowable fill
(i.e., low slump concrete). This
is particularly attractive when
installing grinder pump stations
in augered holes where tight
clearances make it difficult to
assure proper backfilling and
compaction with dry materials.
Flowable fills should not be
dropped more than four feet
from the discharge nozzle to
the bottom of the hole since
this can cause separation of
the constituent materials.
8. Electrical Connection
(supply panel to alarm panel)
Before proceeding verify that Figure 3 – 120V Simplex
the service voltage is the same
as the motor voltage shown 9. Electrical Connection stalled per national and local
on the name plate. An alarm (pump to panel) codes. Conduit must enter
device is to be installed in a The cable provided for con- panel from bottom and be
conspicuous location where nection between the station sealed per NEC section 300.5
it can be readily seen by the and alarm panel is a six-con- & 300.7.
home owner. An alarm device ductor tray cable that meets 10. Installing E/One supply
is required on every installa- NEC requirements for direct cable with EQD (HDPE)
tion. There shall be no excep- burial as long as a minimum a. Open the lid of the station,
tions. of 24 inches of cover is main- locate the cable and the feed-
Wiring of supply panel and tained. Those portions of cable thru connector on the wall
alarm panel shall be per figures that have less than 24 inches of the tank. Loosen the nut
3 and 4, alarm panel wiring of cover must be contained on the connector and pull
diagrams and local codes. A within suitable conduit. This in- the supply cable out through
dedicated 30-amp breaker with cludes the vertical section that the connector until it hits the
ground and separate neutral is drops to a 24-inch depth at the crimped on stop feature on the
required before all alarm pan- station and the length exiting cable, approximately 24” from
els. Additionally, a dedicated 40 out of the ground at the control the EQD.
amp breaker is required before panel. **IMPORTANT: All but 24”
a 120V duplex alarm panel. NOTE: Wiring must be in- of the cable must be pulled
7
Your panel may differ from the one shown below. Wire your panel National Electric Code (NEC)
per the wiring decal on the inside of the enclosure door. for direct burial as long as a
minimum of 24” of ground cover
is maintained. Those portions
of the cable with less than 24”
of cover must be housed in a
suitable protective conduit. The
supply cable terminates in a
convenient, electrical quick-dis-
connect (EQD) plug to support
future servicing of the grinder
pump. The supply cable cord
grip provides a leak tight seal
around the power cable as it
enters the tank and will prevent
movement of the supply cable
during burial and subsequent
ground settlement. The cord
grip should be installed in a
position on the tank that will
provide convenient, direct rout-
ing of the supply cable to the
alarm panel. (Exception: On
48” tall tanks the cord grip
should penetrate the tank 18”
below the top of the tank; the
portion of the cable with less
then 24” of soil cover shall be
installed in suitable protec-
Figure 3a – 120V Duplex
tive conduit.)
Locate and mark the loca-
out of the station, and the burial depth. tion of the cord grip on the
portion of the cable between e. Run the cable fiberglass tank wall. Using
the EQD and the molded in underground, in a trench or a 1-1/16” hole saw, drill
cable breather should be tunnel, to the location of the through the tank wall at this
secured in the hook provided to E/One panel. Leave a 6- to location. Install the cord grip
ensure that the pump functions 12-inch loop of cable at each and O-ring seal as shown.
properly. Do not leave the end to allow for shifting and Tighten the cord grip locknut
excess cable in the station. settling. Connections made until snug.
b. Retighten the nut. This at the panel are shown in the Loosen the cord nut and
connection must be tight or panel wiring diagram (Figs. 3 slide the supply cable free end
ground water will enter the and 4). through the cord grip as shown
station. 11. Installing E/One supply in Fig. 5. Continue to slide the
c. Feed the wire through the cable with EQD (Fiberglass) entire cable length through the
length of conduit (contractor A 32’ supply cable and cord cord grip until the metal cable
provided) which will protect it grip are provided with the stop rests against the cord grip
until it is below the 24” burial station for electrical connec- face. Tighten the cord nut until
depth. tion between the station and snug. Failure to tighten the cord
d. Position the conduit the alarm panel. All electrical nut will result in groundwater
vertically below the cable wiring must be in accordance entering the station. Use care
connector along side of the with local codes. The sup- when installing and burying the
station reaching down into the ply cable is rated under the supply cable. If the cable is cut
8
Your panel may differ from the one shown below. Wire your panel or otherwise damaged it may
per the wiring decal on the inside of the enclosure door. result in a pump malfunction.
Run the supply cable under-
ground, ensuring 24”, mini-
mum, of soil coverage, to the
control panel location. Leave
a 6- to 12-inch loop of supply
cable near the station and the
control panel to accommodate
settlement of the soil. A protec-
tive conduit must be utilized
where 24” of soil cover cannot
be maintained.
12. Stand Assembly
Temporarily rest the grinder
pump on its side. Using a block
of wood or similar object, prop
up the lower pump end to allow
installation of the pump stand.
Align the two legs of each
pump stand half with two of the
holes in the pump lower end.
Push the stand legs into the
pump lower end. Using a mal-
let, ensure that the stand legs
bottom into the mounting holes.
Repeat for the other stand half.
Figure 4 – 240V Simplex
Turn the pump upright on the
installed stand.
13. Slide Face Discharge
(Fiberglass Tanks)
Install slide face discharge
receiver to tank’s discharge
hub. The slide face has a 1
¼-inch solvent weld socket. A 1
¼-inch PVC nipple is supplied
if a threaded connection is
necessary. Glue nipple to slide
face with Schedule 80 primer
and glue. Take care not to get
glue on slide face surfaces.
(Fig. 7)
Refer to any documenta-
tion that may have shipped
with your discharge. Attach
the discharge hose to the anti-
siphon check valve. Use pipe
sealer on threads to ensure
PIN FUNCTION 2000S EXTREME
1 MANUAL RUN RED BROWN
2 L1 BLACK RED
3
4
5
L2
GND
WHITE BLACK
GREEN GRN/YEL
ALARM FEED ORANGE YELLOW
leak tightness (Fig. 8). Check
6 ALARM RETURN BLUE BLUE
the O-ring on the slideface
A DEDICATED 30A CIRCUIT BREAKER
adapter for adequate lubrica-
Figure 4a – 240 V Duplex tion (Fig. 10). Attach discharge
9
Figure 6

Figure 5

Power at the station must not drop below 10%


of nameplate voltage. Maximum Recommended
Length:
120 Volt 60’ (min. voltage at pump — 108V)
240 Volt 150’ (min. voltage at pump — 216V) Figure 7
Consult factory for longer lengths

installation tool on male adapt- hung as high as possible in the


er (Figs. 8 and 9). tank. Refer to the “Installation
14. Pump Installation Layout” drawing in the front of
Carefully lower the pump this manual.
into the tank. Place pump so Install vent assembly in cover
anti-siphon check valve is on assembly. Hole size for vent
opposite side of discharge grommet is 3 inches. The vent
in tank. Refer to “Installation must be installed per national
Layout” drawing in the front of and local codes to ensure
this manual. proper operation. Failure to
Rotate discharge hose and properly vent tank will result in
male adapter to create a loop faulty operation and will void
or coil. Slide male adapter into warranty.
slide face receiver until it seats. Connect the pump to the
Push down on slider valve as- alarm panel. New cable should
sembly to open. (Fig. 11) be installed between tank and Figure 8
Hang power cable, breath- electrical panel per National
er tubing with Equalizer, and Electric Code and local codes. be used to ensure proper op-
lifting rope to prevent them Maximum distance between eration. When an underground
from laying in sewage. Keep pump and panel is 100 feet. splice is needed, use E/One-
between 18 inches and 24 Minimum burial depth without approved splice kit, E/One part
inches of power supply cable in conduit is 24 inches. Note: number PC0606G01. If existing
tank. The Equalizer should be Environment One cable should cable is used, test for ground
10
Figure 9 Figure 10

Figure 11

11
short (results from damaged performed with the pump and for 120 VAC service). Higher
cable underground). Replace alarm breakers inside the panel amperage readings equal a
if a short is found. Plug and OFF): higher discharge pressure. If
seal all electrical components the amperage is greater than 8
(junction box, conduit, etc.) • Green/yellow to red (16 for 120 VAC service) check
inside tank and control panel to • Green/yellow to black the discharge line for a block-
ensure a watertight connection. • Green/yellow to brown age. Note the amperage.
Failure to seal all moisture • Brown to yellow Within the first 1 to 3 minutes,
may cause premature pump the alarm will turn off. Within
failure and void warranty. All of these tests must read the following 1 to 2 minutes,
Waterlogged junction boxes an open circuit. A short at any the pump will turn off (in a 24-
are one of the most common of these test points will cause inch diameter tank).
sources of grinder pump prob- premature pump failure if not Clear/Reset the alarm panel:
lems. corrected.
Power source to the panel Turn on power at main power • Sentry and T260 panels:
must be 240 VAC (or 120 VAC supply only. Check voltage Reset is not required.
for a 120V model). A dedicated from the main power supply. • Protect Panel: Turn pump
30-amp breaker with ground The voltage must be 240 VAC and alarm breakers off and
and separate neutral is re- (or 120 VAC for a 120V model) back on simultaneously.
quired before all alarm panels. within 10 percent. Note the • Protect Plus Panels:
Additionally, a dedicated 40 voltage. Perform a “cold start” from
amp breaker is required before Turn on the alarm power the Initialize System menu.
a 120V duplex alarm panel. circuit breaker. Leave pump Any user setting that were
15. Test Procedure breaker off. previously chosen will not be
Make certain that all dis- Fill tank with water until alarm reset.
charge shutoff valves are fully turns on. This will be about 30
open (curb stops, slider valve, inches from bottom of tank. If any Trouble or alarm
etc.). Turn off water. Turn on pump conditions are indicated after
Turn off power at main power power circuit breaker. Pump the panel is reset, contact your
supply and panel. (Ignore all should immediately turn on. local service provider.
Trouble indications, LEDs and/ Within one minute the alarm Close and lock the alarm
or messages until the panel is will turn off. Within three min- panel.
reset at the end of this proce- utes the pump will turn off. Inspect the lid gasket and
dure.) Take a current (amperage) install new gasket material as
Use an ohmmeter set at the 2 reading off the black lead to the required. Fasten lid to tank.
meg scale. Check the continu- pump. The reading should be Call your local E/One dis-
ity between the following leads between 5 and 8 amps for 240 tributor if you experience any
from the pump (tests should be VAC service (10 to 16 amps problems. Please have ready
the unit serial number, voltage,
amperage read during startup,
type of application, and a de-
scription of the problem.

12
Grinder Pump Station Ballast Calculations
Any buried vessel that is submerged, or partially submerged, in water will be acted on by an upward
buoyant force that attempts to return the vessel to a non-submerged state. The magnitude of this
buoyant force is equal to the volume of the vessel that is submerged multiplied by the density of
water. On most in-ground installations a ballast, or concrete anchor, of proper volume and weight is
required to resist the buoyant force.

The amount of ballast needed is equal to the weight it would take to counterbalance the buoyant
forces that are exerted on the station. The total ballast is a combination of the concrete poured to
create a ring around the bottom of the station and the soil above that ring which act as a weight.
The ballast force, the force holding the station down, must be greater than the buoyant force, the
force pushing the station up, in order to have an acceptable installation.

Calculate the Buoyant Force:

STATION VOLUME X THE WEIGHT OF WATER PER CUBIC FOOT (62.4 LBS/CU FT) =
BUOYANT FORCES

BUOYANT FORCES – STATION WEIGHT =


NET BUOYANT FORCE

Example: WH101-92,
28.53 cu ft X 62.4 lbs/cu ft = 1780.3 lbs
1780.3 lbs – 270 lbs = 1510.3 lbs

Calculate the Ballast Force:

VOLUME OF CONCRETE X WEIGHT OF CONCRETE WATER (87.6 LBS/CU FT) =


BALLAST FROM CONCRETE

VOLUME OF CONTRIBUTING SOIL X WEIGHT OF SATURATED SOIL (70 LBS/CU FT) =


BALLAST FROM SOIL

BALLAST FROM CONCRETE + BALLAST FROM SOIL = NET BALLAST FORCE

Example: WH101-92,
concrete: 2.7 cu ft X 87.6 lbs/cu ft = 236.5 lbs
soil: 20.4 cu ft X 70 lbs.cu ft = 1430.0 lbs
236.5 lbs + 1430.0 lbs = 1665.5 lbs

Net Ballast Force @ 1665.5 lbs > Net Buoyant Force @ 1510.3 lbs

Acceptable
Example, WH101-92:
Station Volume = 28.5 cu ft
Station Weight = 270 lbs
Contributing Soil Volume = 20.4 cu ft
Recommended Concrete Volume = 2.7 cu ft (O.D. = 36”)

13
Chart 1

NET NET
STATION STATION STATION CONCRETE CONCRETE
BUOYANT BALLAST
MODEL MATERIAL HEIGHT WEIGHT VOLUME VOLUME WEIGHT
FORCE FORCE
(inches) (pounds) (cubic feet) (cubic feet) (pounds)
(pounds) (pounds)
WH101-60 HDPE 60.8 238 19.27 964.45 1108.72 2.7 405
WH101-74 HDPE 73.4 254 23.26 1197.42 1348.82 2.7 405
WH101-92 HDPE 90.1 270 28.53 1510.27 1667.15 2.7 405
WH101-124 HDPE 130.3 280 41.27 2295.25 2433.82 2.7 405
WH101-159 HDPE 158.6 307 50.24 2827.98 2974.22 2.7 405

14
Chart 2

*Ballast is calculated with ground water at grade


STATION
CONCRETE
WEIGHT STATION NET NET
STATION DIAMETER CONCRETE CONCRETE
STATION DIAMETER (pounds) VOLUME BUOYANT BALLAST
MODEL TYPE
MATERIAL (inches)
HEIGHT
station, (cubic FORCE FORCE
(inches) VOLUME WEIGHT
(inches) (ballast 10" (cubic feet) (pounds)
cover, feet) (pounds) (pounds)
thick)
core(s)

60x24 Simplex Fiberglass 24 60 172 15.71 808 1421 36 3.3 490.9


72x24 Simplex Fiberglass 24 72 178 18.85 998 1695 36 3.3 490.9
90x24 Simplex Fiberglass 24 90 210 23.56 1260 2108 36 3.3 490.9
120x24 Simplex Fiberglass 24 120 232 31.42 1728 2795 36 3.3 490.9
144x24 Simplex Fiberglass 24 144 250 37.70 2102 3345 36 3.3 490.9
60x30 Simplex Fiberglass 30 60 195 24.54 1336 1705 42 3.9 589.0
72x30 Simplex Fiberglass 30 72 234 29.45 1604 2035 42 3.9 589.0
90x30 Simplex Fiberglass 30 90 255 36.81 2042 2529 42 3.9 589.0
120x30 Simplex Fiberglass 30 120 339 49.09 2724 3354 42 3.9 589.0
144x30 Simplex Fiberglass 30 144 378 58.90 3298 4014 42 3.9 589.0
60x36 Simplex Fiberglass 36 60 240 35.34 1965 2180 49 5.0 753.3
72x36 Simplex Fiberglass 36 72 257 42.41 2389 2602 49 5.0 753.3
90x36 Simplex Fiberglass 36 90 282 53.01 3026 3235 49 5.0 753.3
120x36 Simplex Fiberglass 36 120 378 70.68 4033 4289 49 5.0 753.3
144x36 Simplex Fiberglass 36 144 489 84.82 4804 5133 49 5.0 753.3
60x42 Duplex Fiberglass 42 60 296 48.10 2706 2930 57 6.7 1012.4
72x42 Duplex Fiberglass 42 72 314 57.73 3288 3497 57 6.7 1012.4
90x42 Duplex Fiberglass 42 90 373 72.16 4130 4347 57 6.7 1012.4
96x42 Duplex Fiberglass 42 96 373 76.97 4430 4631 57 6.7 1012.4
120x42 Duplex Fiberglass 42 120 432 96.21 5571 5765 57 6.7 1012.4
126x42 Duplex Fiberglass 42 126 432 101.02 5872 6048 57 6.7 1012.4
144x42 Duplex Fiberglass 42 144 546 115.45 6658 6898 57 6.7 1012.4
60x48 Duplex Fiberglass 48 60 325 62.83 3596 3790 65 8.7 1309.6
72x48 Duplex Fiberglass 48 72 344 75.40 4361 4523 65 8.7 1309.6
90x48 Duplex Fiberglass 48 90 424 94.25 5457 5624 65 8.7 1309.6
120x48 Duplex Fiberglass 48 120 556 125.66 7285 7457 65 8.7 1309.6
144x48 Duplex Fiberglass 48 144 622 150.79 8787 8924 65 8.7 1309.6
60x60 Quad Fiberglass 60 60 781 98.17 5345 5842 81 13.5 2018.7
96x60 Quad Fiberglass 60 96 947 157.08 8854 9233 81 13.5 2018.7
120x60 Quad Fiberglass 60 120 1108 196.34 11144 11494 81 13.5 2018.7
144x60 Quad Fiberglass 60 144 1204 235.61 13498 13755 81 13.5 2018.7

15
16
17
A Precision Castparts Company

Environment One Corporation


2773 Balltown Road
Niskayuna, New York 12309–1090

Voice: (01) 518.346.6161


Fax: 518.346.6188

www.eone.com
NA0067P01 Rev L
10/18
18
User Instructions for the Environment One Grinder Pump
General Information
Your home is served by a low pressure sewer system; the key element is an Environment One grinder pump.
The tank collects all solid materials and wastewater from the house. The solid materials are then ground to a
small size suitable for pumping as a slurry with the wastewater. The grinder pump generates sufficient pressure
to pump this slurry from your home to the wastewater treatment receiving line and/or disposal plant.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: 1) this
device may not cause harmful interference; and 2) this device must accept any interference received, including
interference that may cause undesired operation. Any changes or modifications not expressly approved by the
party responsible for compliance could void the user’s authority to operate this equipment.

Care and Use of your Grinder Pump


The Environment One grinder pump is capable of accepting and pumping a wide range of materials, and an
extensive grind test is required in order to obtain NSF approval. However, regulatory agencies advise that the
following items should not be introduced into any sewer, either directly or through a kitchen waste disposal unit:
Glass Seafood shells Diapers, socks, rags or cloth Syringes
Cotton swabs Personal/cleaning wipes & sponges Disposable toothbrushes Latex/vinyl items
Metal Plastic objects (toys, utensils, etc.) Kitty litter Dental floss
Aquarium gravel Sanitary napkins or tampons Cigarette butts

Caution: Kitchen garbage disposals do not keep grease/oil out of the plumbing system

In addition, you must never introduce into any sewer:


Explosives Strong chemicals Lubricating oil and/or grease
Flammable material Gasoline
Items introduced into the sewer system from your home can potentially impact the water environment. Proper
disposal of household wastes such as window cleaners, unused/expired pharmaceuticals, paint thinners, fats,
fruit labels, etc. is important. For more information, visit http://www.wef.org.

Periods of Disuse
If your home or building is left unoccupied for longer than a couple of weeks, perform the following procedure:
Purge the System. Run clean water into the unit until the pump activates. Immediately turn off the water and
allow the grinder pump to run until it shuts off automatically.
Duplex Units. Special attention must be taken to ensure that both pumps turn on when clean water is added to
the tank.
Caution: Do not disconnect power to the unit

Power Failure
Your grinder pump cannot dispose of wastewater without electrical power. If electrical power service is
interrupted, keep water usage to a minimum.

Pump Failure Alarm


Your Environment One grinder pump has been manufactured to produce an alarm signal (120 volt) in the
event of a high water level in the basin. The installer must see that the alarm signal provided is connected
to an audible and/or visual alarm in such a manner as to
provide adequate warning to the user that service is required.
During the interim prior to the arrival of an authorized service
technician, water usage must be limited to the reserve
capacity of the tank.
For service, please call your local distributor:

19
E/One SewersTM

Limited Warranty
For E/One Extreme D-Series,
W-Series & Upgrade
Environment One Corporation offers
a limited warranty that guarantees
its product to be free from defects in
material and factory workmanship
for a period of two years from
the date of installation, or 27
months from the date of shipment,
whichever occurs first, provided
the product is properly installed,
serviced and operated under
normal conditions and according to
manufacturer’s instructions. Repair
or parts replacement required as a
result of such defect will be made
free of charge during this period
upon return of the defective parts or
equipment to the manufacturer or its
nearest authorized service center.

Model Number:_______________________
Serial Number:________________________
Installation Date:______________________

SEWER SYSTEMS
2773 Balltown Rd • Niskayuna NY USA 12309
(01) 518.346.6161 • www.eone.com

20

You might also like