Installation Instructions Model XDLC: Class X (DCLC) Device Loop Card
Installation Instructions Model XDLC: Class X (DCLC) Device Loop Card
Model XDLC
Class X (DCLC) Device Loop Card
INTRODUCTION The Model XDLC Device Loop Card from Siemens Industry, XDLC
Inc., is the interface for connection of Desigo Fire Safety
Modular/Cerberus PRO Modular smoke detectors, Multi- RESET
POWER
Criteria detectors including Carbon Monoxide, manual CARD FAIL
stations, monitor devices, and control devices to the Desigo HNET FAIL
5
ZONE 3
All field devices connected to the XDLC are addressed and 6
7
tested using the Device Programming Unit (DPU). 8
ZONE 4
Siemens Industry
Industry,, Inc.
A6V101040156_en--_c Building Technologies Di
echnologies vision
Division
the XDLC continues to monitor its associated devices, and if any alarm device
activates, the XDLC will activate the outputs selected for “degrade” mode of operation.
Similarly, it will also signal other modules within its backplane as to the degrade alarm
condition. Note that output activation in degrade may take up to 60 seconds and that
outputs controlling releasing agents are not activated by “degrade” operation.
The “Degrade” mode operation is not the same as “Degraded Mode” as in ULC-
S527.
Controls and Indicators The front panel of the XDLC contains one reset switch, 16 LEDs, and three HNET
address switches, as shown in Figure 1. A reset switch is located on the top of the
front panel. Pushing the reset switch re-initializes the XDLC operation.
The LEDs follow the reset switch and their functions are defined as follows:
PRE-INSTALLATION Set the three-digit HNET network address for the XDLC using the three rotary dial
switches located near the bottom of the front panel. (Refer to Figure 1 for the
location of the switches.) The address for the XDLC must be the same as the
HUNDREDS
address selected for it in the Zeus Programming Tool. To set the address, turn the
TENS
pointers on each of the three dials to the numbers for the selected address. For
ONES example, if the address is 123, set the pointer for the HUNDREDS dial to “1”, set the
HNET
pointer for the TENS dial to “2”, and set the pointer for the ONES dial to “3”. The range
of allowable addresses is from 001 to 251 (leading zeros must be used).
USB CONNECTOR
The USB connector provides an interface to download new Firmware to the XDLC.
Using a standard USB A-B cable connected to a PC running Zeus, a new XDLC
Firmware can be downloaded. The Zeus Configuration Program is used to select the
new Firmware and initiate the download to the XDLC.
Both the power LED and the Ground Fault LED will blink during download. The power
LED will blink alone if the firmware was not completely downloaded to the XDLC.
In addition to Firmware Download, the USB port provides a diagnostic log of the
XDLC internal functions for field support personnel.
INSTALLATION The XDLC plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin
DIN connectors and can occupy any slot in the card cage. (Refer to Figure 2.)
Figure 2
Installing The XDLC
Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)
All field wiring to the XDLC is connected to the terminal blocks of the CC-5 card cage
slot in which it is installed.
Connect +24V from the PSC-12 to terminal 17 and -24V from the PSC-12 to terminal
18 of the slot in the CC-5 where the XDLC will be installed. (Refer to Figure 3.)
ZONE 1 ZONE 2
LINE 2 (RETURN)
LINE 2 (RETURN)
LINE 1 (RETURN)
LINE 1 (RETURN)
LINE 1 (OUT)
LINE 1 (OUT)
LINE 2 (OUT)
LINE 2 (OUT)
+ + - - + + - -
1 2 3 4 5 6 7 8
ZONE 3 ZONE 4
LINE 2 (RETURN)
LINE 2 (RETURN)
LINE 1 (RETURN)
LINE 1 (RETURN)
LINE 1 (OUT)
LINE 2 (OUT)
LINE 2 (OUT)
LINE 1(OUT)
+ + - - + + - -
9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24
24V+ 24V-
DO NOT USE
Figure 3
Wiring The 24VDC Power Lines To The XDLC Slot In The CC-5
T-TAPPING ALLOWED
INITIATING
DEVICE
* *SHIELD (OPTIONAL)
TERMINATE IN ENCLOSURE
WITH THE XDLC. TERMINATE
AT ONE END ONLY.
TERMINATE TO EARTH
GROUND.
INITIATING
DEVICE
* *SHIELD (OPTIONAL)
TERMINATE IN ENCLOSURE
WITH THE XDLC. TERMINATE
CLASS A or CLASS X WIRING** AT ONE END ONLY.
TERMINATE TO EARTH
LINE 1
LINE 2
LINE 1
LINE 1
GROUND.
LINE 1
LINE 2
LINE 2
LINE 2
NO T-TAPPING ALLOWED
ZONE 1 ZONE 2
CC-5
1 2 3 4 5 6 7 8
INITIATING
DEVICE
INITIATING
DEVICE
* *
LINE 2 (RETURN)
LINE 2 (RETURN)
LINE 1 (RETURN)
LINE 1 (RETURN)
* * SHIELD (OPTIONAL)
LINE 1 (OUT)
LINE 1 (OUT)
LINE 2 (OUT)
LINE 2 (OUT)
TERMINATE IN ENCLOSURE
WITH THE XDLC. TERMINATE
AT ONE END ONLY.
TERMINATE TO EARTH
GROUND.
CC-5
1 2 3 4 5 6 7 8
ZONE 3 ZONE 4
ZONE 3-6 ZONE 4-8
INITIATING
DEVICE
INITIATING
DEVICE
* * * *SHIELD (OPTIONAL)
TERMINATE IN ENCLOSURE
LINE 1 (RETURN)
LINE 2 (RETURN)
LINE 1 (RETURN)
LINE 2 (RETURN)
LINE 1 (OUT)
LINE 2 (OUT)
LINE 2 (OUT)
TERMINATE TO EARTH
LINE 2
LINE 1
LINE 1
LINE 1
LINE 2
LINE 1
LINE 2
GROUND.
LINE 2
CC-5 CC-5
9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16
NOTES:
1. NO END OF LINE DEVICE REQUIRED.
2. ALL CIRCUITS SUPERVISED AND POWER LIMITED PER NEC 760.
3. POSITIVE OR NEGATIVE GROUND FAULT DETECTED AT <50K OHMS ON TERMINALS 1-16.
Figure 4
XDLC Wiring Diagram
Electrical connections for the zones are shown in Figure 4. The wiring style is set in
the Zeus Programming Tool without using external jumpers.
If the return wires in a zone are reversed (in a Class A [DCLA] configuration), the line
numbers and short LEDs associated with the affected zone will be illuminated.
Switch the two return wires to remove this trouble. Eliminate all other troubles
before completing the installation.
NOTE:
1. Devices wired as Class X (DCLC) must have Isolator Mode checked off.
2. For Class A (DCLA) and Class B (DCLB), the option for Isolation Mode is
available for the X-devices as long as the wiring matches the configuration.
3. During system initialization, the XDLC will test the wiring for each device
and produce “XDLC Device Wiring Mismatch” trouble if there is a mismatch
between the Isolation Mode in the configuration and the device wiring.
COMPATIBILITY 1. The XDLC supports compatible devices with the model numbers listed in
Table 1 for UL 864 and in Table 2 for UL2572. Use any combination of those
listed in Table 1 or Table 2, as applicable.
2. The XDLC supports a maximum of 252 Desigo Fire Safety Modular/
Cerberus PRO Modular intelligent field devices distributed across four Class
A (DCLA) loops or eight Class B (DCLB) loops. A mix of Class A (DCLA) and
Class B (DCLB) is supported. The XDLC supports a maximum of 190 Desigo
Fire Safety Modular/Cerberus PRO Modular intelligent field devices wired in
isolation mode distributed across four Class X (DCLC) loops. A mix of Class
A (DCLA) and Class X (DCLC) wiring is supported where the maximum total
number of devices across four loops is 252 with a limit of 190 of those
Desigo Fire Safety Modular/Cerberus PRO Modular intelligent field devices
wired in isolation mode.
3. All circuits are power limited to NFPA 70 per NEC 760. The XDLC supports
the use of 12-22 AWG non-shielded, twisted, thermoplastic fixture wire
without conduit, if permitted by local building codes.
4. No end of line device is required.
5. Total circuit resistance of each zone must not exceed 50 ohms. (Refer to
the chart on page 7.)
Maximum capacitance: 0.5μF between line+ and line-
1.0μF between line and chassis
6. T-tapping is not allowed on Class A (DCLA) or Class X (DCLC) loops.
7. All models are UL and ULC listed.
8. The Multi-Criteria detectors are programmed using the DPU. A PAD-5,
Document ID A6V101030358, or a SBGA-34 base, connected to a ZIC-4A, P/
N 500-033050, or ZIC-8B, P/N 500-648670, can be used to create Temporal
4 tones in conjunction with the Carbon Monoxide enabled detectors
FDOOTC441 or OOHC941. Using these detectors with the ABHW-4S or
ABHW-4B, the selection of tones are chosen using the panel’s configuration
tool.
Siemens Industry, Inc. 6 A6V101040156_en--_c
Building Technologies Division
TABLE 1
XDLC Compatible Devices
for UL864/ULC-S527
Isolator Mode (I)
Compatible Installation Max Current ABHW-4 or Polarity
Devices Instructions From XDLC (mA) Compatible Insensitive (P)
Capable
ABHW-4B Loop powered A 6V 10405587 7.50 No -
ABHW-4B External powered A 6V 10405587 0.25 No -
ABHW-4S A 6V 10405588 0.25 No -
AD-11P** P/N 315-095659 0.00 No -
AD2-XHR P/N 315-049708 0.05 No -
ADBH-11 P/N 315-033210 0.00 No -
AD-HR P/N 315-033280 0.05 No -
DB-11 P/N 315-094193 0.00 No -
DB-11E P/N 315-094193 0.00 No -
DB-HR P/N 315-033220 0.05 No -
DB2-HR A 6V 10327325 0.20 No -
FDBZ492** A 6V 10336866 0.00 No -
FDBZ492-HR A 6V 10336866 0.05 No -
FDCIO422 A 6V 10324662 1.00 No P
FDO421* A 6V 10323926 0.28 Yes P
FDOOT441* A 6V 10324655 0.68 Yes P
FDOOTC441* A 6V 10324657 0.75 Yes P
FDOT421* A 6V 10323934 0.28 Yes P
FDT421* A 6V 10323930 0.28 Yes P
HCP P/N 315-034860 1.00 No P
HFP-11 P/N 315-033290 0.80 No P
HFPT-11 P/N 315-033290 0.80 No P
HI921* A 6V 10323932 0.28 Yes P
HMS-2S P/N 315-033430 0.90 No P
HMS-M P/N 315-033450 0.90 No P
HMS-S P/N 315-033200 0.90 No P
HMS-SA P/N 315-033430 0.90 No P
HMS-D P/N 315-033200 0.90 No P
HTRI-D P/N 315-049475 1.30 No P
HTRI-M P/N 315-049480 1.30 No P
HTRI-R P/N 315-049475 1.30 No P
HTRI-S P/N 315-049475 1.30 No P
HZM P/N 315-034850 1.00 No P
ILED-HC P/N 315-048637 1.00 No P
ILED-HW P/N 315-048637 1.00 No P
ILED-XC*** A 6V 101055484 0.50 No I, P
ILED-XW*** A 6V 101055484 0.50 No I, P
OH921* A 6V 10323936 0.28 Yes P
OOH941* A 6V 10324659 0.68 Yes P
OOHC941* A 6V 10324661 0.75 Yes P
OP921* A 6V 10323928 0.28 Yes P
PAD-5 A 6V 101030358 0.75 No I
PAD-5-CDC A 6V 101030366 0.75 No I
PAD-5-CLSA A 6V 101030359 1.25 No I
RL-HC P/N 315-033230 0.05 No P
RL-HW P/N 315-033230 0.05 No P
SBGA-34* A 6V 10383428 2.80 Yes P
TSM-1X*** A 6V 101055486 0.50 No I, P
XTRI-D*** A 6V 101055479 0.95 No I, P
XTRI-M*** A 6V 101055487 0.50 No I, P
XTRI-R*** A 6V 101055479 0.75 No I, P
XTRI-S*** A 6V 101055479 0.65 No I, P
*ABHW-4 compatible devices as described in number 8 on page 6.
**There is no curent drawn from XDLC for the Air Duct Housing without detector. The current rating for air duct
housing with detector is the current rating of the detector.
***Devices are suitable for Class X (DCLC) installation.
***Devices which are Class X (DCLC) capable.
P = Polarity Insensitive Device
I = Isolator Mode Capable Device
***These devices can be wired in either Polarity Insensitive or Isolator mode.
ELECTRICAL RATINGS
Out P P P P P CLASS A
XDLC
P P = Device(s)
(Polarity Insensitive)
Return P P P P P No Devices used as Isolators
PANEL
Figure 5
Class A Device Loop Topologies
PANEL
Out I I I I I
CLASS X
XDLC
I I = Isolator Device(s)
(All wired for Isolator Mode)
Return I I I I I
PANEL
XDLC CLASS B
P = Device(s)
Out P P P P P P P (Polarity Insensitive)
Figure 6
Class X and B Device Loop Topologies
Siemens products and solutions provide security functions to ensure the secure operation of building comfort,
fire safety, security management and physical security systems. The security functions on these products and
solutions are important components of a comprehensive security concept.
It is, however, necessary to implement and maintain a comprehensive, state-of-the-art security concept that is
customized to individual security needs. Such a security concept may result in additional site-specific preventive
action to ensure that the building comfort, fire safety, security management or physical security system for your
site are operated in a secure manner. These measures may include, but are not limited to, separating networks,
physically protecting system components, user awareness programs, defense in depth, etc.
For additional information on building technology security and our offerings, contact your Siemens sales or
project department. We strongly recommend customers to follow our security advisories, which provide infor-
mation on the latest security threats, patches and other mitigation measures.
http://www.siemens.com/cert/en/cert-security-advisories.htm