Installation Instructions Model XDLC: Class X (DCLC) Device Loop Card

This document provides installation instructions for the Siemens Model XDLC Device Loop Card. The XDLC interfaces smoke detectors, manual stations, and other devices to the Desigo Fire Safety Modular/Cerberus PRO Modular System. It contains 16 LEDs to diagnose problems and supports up to 252 intelligent field devices on four Class A or Class X loops. The microprocessor controls isolators to isolate faulty zones while keeping other zones operational. It can continue monitoring devices and activate selected outputs if communication with the main CPU fails, providing degraded operation.

Uploaded by

Miguel Coronado
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
2K views10 pages

Installation Instructions Model XDLC: Class X (DCLC) Device Loop Card

This document provides installation instructions for the Siemens Model XDLC Device Loop Card. The XDLC interfaces smoke detectors, manual stations, and other devices to the Desigo Fire Safety Modular/Cerberus PRO Modular System. It contains 16 LEDs to diagnose problems and supports up to 252 intelligent field devices on four Class A or Class X loops. The microprocessor controls isolators to isolate faulty zones while keeping other zones operational. It can continue monitoring devices and activate selected outputs if communication with the main CPU fails, providing degraded operation.

Uploaded by

Miguel Coronado
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Installation Instructions

Model XDLC
Class X (DCLC) Device Loop Card

INTRODUCTION The Model XDLC Device Loop Card from Siemens Industry, XDLC
Inc., is the interface for connection of Desigo Fire Safety
Modular/Cerberus PRO Modular smoke detectors, Multi- RESET
POWER
Criteria detectors including Carbon Monoxide, manual CARD FAIL
stations, monitor devices, and control devices to the Desigo HNET FAIL

Fire Safety Modular/Cerberus PRO Modular System. The GND FAULT


ALARM
XDLC uses one network address on the system. The TROUBLE
application program that is loaded into the on-board micro- OPEN
SHORT
processor controls the XDLC operation.
1
ZONE 1
The XDLC contains 16 LEDs for diagnosis of problems. 2
3
Ground fault detection is provided by the loop. 4
ZONE 2

5
ZONE 3
All field devices connected to the XDLC are addressed and 6
7
tested using the Device Programming Unit (DPU). 8
ZONE 4

OPERATION The XDLC initializes, operates, and maintains all devices


residing on the loop. The XDLC communicates all relevant
device and event information, such as alarms and troubles, USB
to the PMI-2/PMI-3/OI-C/OI-D (PMI). The sensitivity of any
intelligent smoke detector can be checked and adjusted
from the PMI through the XDLC. All information about the
devices on the loop can be displayed on the PMI. The XDLC
allows the System polarity insensitive devices to be HUNDREDS
connected without generating errors.
NOTE: PMI = PMI-2/PMI-3/FCM2041 TENS

The XDLC supports four Class A (DCLA) or Class X (DCLC) ONES

loops (eight Class B [DCLB] parallel lines/stubs) of up to HNET

252 Desigo Fire Safety Modular/Cerberus PRO Modular


intelligent field devices as well as device accessories (relay
bases, audible bases, and remote lamps) in any combina-
tion. The microprocessor controls the on-board isolators to
isolate any zone from the loop if one of them is shorted.
When one zone is isolated from the loop, the other zones
will still work. Figure 1
XDLC Device Loop Card
The on-board microprocessor provides the XDLC with the
ability to function and initiate alarm conditions even if the
main PMI CPU fails. The XDLC accomplishes this “degrade” mode of operation by
monitoring the communications with the PMI. In the case of the failure of the PMI,

Siemens Industry
Industry,, Inc.
A6V101040156_en--_c Building Technologies Di
echnologies vision
Division
the XDLC continues to monitor its associated devices, and if any alarm device
activates, the XDLC will activate the outputs selected for “degrade” mode of operation.
Similarly, it will also signal other modules within its backplane as to the degrade alarm
condition. Note that output activation in degrade may take up to 60 seconds and that
outputs controlling releasing agents are not activated by “degrade” operation.

The “Degrade” mode operation is not the same as “Degraded Mode” as in ULC-
S527.

Controls and Indicators The front panel of the XDLC contains one reset switch, 16 LEDs, and three HNET
address switches, as shown in Figure 1. A reset switch is located on the top of the
front panel. Pushing the reset switch re-initializes the XDLC operation.

The LEDs follow the reset switch and their functions are defined as follows:

POWER (Green) Normally ON. When illuminated, indi-


cates the power for the XDLC is applied
to the card. Blinks during firmware
download or if download has failed.

CARD FAIL (Yellow) Normally OFF. When illuminated, indi-


cates the card microprocessor has failed.

HNET (Yellow) Normally OFF. When illuminated, indi-


cates that the HNET communication with
the XDLC has terminated and the card
goes into degrade mode on HNET
failure.

GND FAULT (Yellow) Normally OFF. When illuminated, indi-


cates that the XDLC has detected either
a negative or positive ground fault on its
field wiring. Blinks during firmware
download.

ALARM (Red) Normally OFF. When illuminated, indicates


that the XDLC has detected an alarm.

TROUBLE (Yellow) Normally OFF. When illuminated, indi-


cates that the XDLC has detected a
trouble on its field wiring; or incapability
between firmware in either the PMI,
XDLC, or both.

OPEN Normally OFF. When illuminated, indi-


cates that the XDLC has detected an
open on its field wiring.

SHORT Normally OFF. When illuminated, indi-


cates that the XDLC has detected a
short on its field wiring.

LINE LEDS 1-8 Normally Off. When illuminated, indi-


cates a trouble (open or short) on the
associated line or loop.

Siemens Industry, Inc. 2 A6V101040156_en--_c


Building Technologies Division
Three rotary dial switches at the bottom of the front panel are used to set the HNET
network address of the XDLC. All field devices connected to the XDLC are ad-
dressed and tested using the Device Programming Unit (DPU). Refer to the DPU
Manual, P/N 315-033260 for further information.

PRE-INSTALLATION Set the three-digit HNET network address for the XDLC using the three rotary dial
switches located near the bottom of the front panel. (Refer to Figure 1 for the
location of the switches.) The address for the XDLC must be the same as the
HUNDREDS
address selected for it in the Zeus Programming Tool. To set the address, turn the
TENS
pointers on each of the three dials to the numbers for the selected address. For
ONES example, if the address is 123, set the pointer for the HUNDREDS dial to “1”, set the
HNET
pointer for the TENS dial to “2”, and set the pointer for the ONES dial to “3”. The range
of allowable addresses is from 001 to 251 (leading zeros must be used).

USB CONNECTOR

The USB connector provides an interface to download new Firmware to the XDLC.
Using a standard USB A-B cable connected to a PC running Zeus, a new XDLC
Firmware can be downloaded. The Zeus Configuration Program is used to select the
new Firmware and initiate the download to the XDLC.

Both the power LED and the Ground Fault LED will blink during download. The power
LED will blink alone if the firmware was not completely downloaded to the XDLC.

In addition to Firmware Download, the USB port provides a diagnostic log of the
XDLC internal functions for field support personnel.

INSTALLATION The XDLC plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin
DIN connectors and can occupy any slot in the card cage. (Refer to Figure 2.)

Insert the XDLC card into the card guides rightside


up (lettering on the front panel is legible)

Slide the card in until the card edge connectors


contact the receptacles on the motherboard.

Verify that the DIN connectors of the card and the


card-cage are aligned properly. The card can only be
plugged into the card cage in one direction; if it does
not align, DO NOT FORCE the card.

Place thumbs on the front panel adjacent to the


captive screws and gently apply even pressure on
the card until the connectors seat in the receptacles
on the motherboard.

Secure the card with the captive screws.

Figure 2
Installing The XDLC

Siemens Industry, Inc. 3 A6V101040156_en--_c


Building Technologies Division
WIRING

Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)

All field wiring to the XDLC is connected to the terminal blocks of the CC-5 card cage
slot in which it is installed.

To Connect External Wiring

1. Loosen the screw of the terminal by turning it counterclockwise.


2. Insert the wire into the side of the terminal block.
3. Tighten the screw of the terminal block by turning it clockwise.

Connect +24V from the PSC-12 to terminal 17 and -24V from the PSC-12 to terminal
18 of the slot in the CC-5 where the XDLC will be installed. (Refer to Figure 3.)

ZONE 1 ZONE 2

LINE 2 (RETURN)
LINE 2 (RETURN)
LINE 1 (RETURN)

LINE 1 (RETURN)
LINE 1 (OUT)

LINE 1 (OUT)
LINE 2 (OUT)

LINE 2 (OUT)
+ + - - + + - -
1 2 3 4 5 6 7 8

ZONE 3 ZONE 4
LINE 2 (RETURN)

LINE 2 (RETURN)
LINE 1 (RETURN)

LINE 1 (RETURN)
LINE 1 (OUT)

LINE 2 (OUT)

LINE 2 (OUT)
LINE 1(OUT)

+ + - - + + - -

9 10 11 12 13 14 15 16

ONE SLOT OF CC-5

17 18 19 20 21 22 23 24

24V+ 24V-
DO NOT USE

TO 24VDC FROM THE PSC-12

Figure 3
Wiring The 24VDC Power Lines To The XDLC Slot In The CC-5

Siemens Industry, Inc. 4 A6V101040156_en--_c


Building Technologies Division
CLASS B WIRING***

T-TAPPING ALLOWED

ZONE 1-1 ZONE 2-3

INITIATING
DEVICE

* *SHIELD (OPTIONAL)
TERMINATE IN ENCLOSURE
WITH THE XDLC. TERMINATE
AT ONE END ONLY.
TERMINATE TO EARTH
GROUND.

ZONE 1-2 ZONE 2-4

INITIATING
DEVICE

* *SHIELD (OPTIONAL)
TERMINATE IN ENCLOSURE
WITH THE XDLC. TERMINATE
CLASS A or CLASS X WIRING** AT ONE END ONLY.
TERMINATE TO EARTH

LINE 1

LINE 2

LINE 1

LINE 1
GROUND.

LINE 1

LINE 2

LINE 2

LINE 2
NO T-TAPPING ALLOWED

ZONE 1 ZONE 2
CC-5
1 2 3 4 5 6 7 8

ZONE 3-5 ZONE 4-7

INITIATING
DEVICE

INITIATING
DEVICE

* *
LINE 2 (RETURN)

LINE 2 (RETURN)
LINE 1 (RETURN)

LINE 1 (RETURN)

* * SHIELD (OPTIONAL)
LINE 1 (OUT)

LINE 1 (OUT)
LINE 2 (OUT)

LINE 2 (OUT)

TERMINATE IN ENCLOSURE
WITH THE XDLC. TERMINATE
AT ONE END ONLY.
TERMINATE TO EARTH
GROUND.
CC-5
1 2 3 4 5 6 7 8

ZONE 3 ZONE 4
ZONE 3-6 ZONE 4-8

INITIATING
DEVICE

INITIATING
DEVICE

* * * *SHIELD (OPTIONAL)
TERMINATE IN ENCLOSURE
LINE 1 (RETURN)

LINE 2 (RETURN)

LINE 1 (RETURN)

LINE 2 (RETURN)

WITH THE XDLC. TERMINATE


AT ONE END ONLY.
LINE 1 (OUT)

LINE 1 (OUT)
LINE 2 (OUT)

LINE 2 (OUT)

TERMINATE TO EARTH
LINE 2

LINE 1
LINE 1

LINE 1

LINE 2

LINE 1

LINE 2

GROUND.
LINE 2

CC-5 CC-5
9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16

**OPERATES IN FULL CONFORMANCE WITH CLASS A (ULC DCLA)


***OPERATES IN FULL CONFORMANCE WITH CLASS B (ULC DCLB)

NOTES:
1. NO END OF LINE DEVICE REQUIRED.
2. ALL CIRCUITS SUPERVISED AND POWER LIMITED PER NEC 760.
3. POSITIVE OR NEGATIVE GROUND FAULT DETECTED AT <50K OHMS ON TERMINALS 1-16.
Figure 4
XDLC Wiring Diagram

Siemens Industry, Inc. 5 A6V101040156_en--_c


Building Technologies Division
The XDLC circuit can be wired Class B (DCLB), Class A (DCLA), or Class X (DCLC). The
configuration tool allows selection of Class A, X or B. The XDLC field circuit wiring does
not require twisted, shielded wire, but is recommended. It can be installed in conduit
containing low voltage power, notification appliance circuits, audible and speaker zone
circuits, and RS-485 and other data circuits without restrictions.

Electrical connections for the zones are shown in Figure 4. The wiring style is set in
the Zeus Programming Tool without using external jumpers.

If the return wires in a zone are reversed (in a Class A [DCLA] configuration), the line
numbers and short LEDs associated with the affected zone will be illuminated.
Switch the two return wires to remove this trouble. Eliminate all other troubles
before completing the installation.

NOTE:
1. Devices wired as Class X (DCLC) must have Isolator Mode checked off.
2. For Class A (DCLA) and Class B (DCLB), the option for Isolation Mode is
available for the X-devices as long as the wiring matches the configuration.
3. During system initialization, the XDLC will test the wiring for each device
and produce “XDLC Device Wiring Mismatch” trouble if there is a mismatch
between the Isolation Mode in the configuration and the device wiring.

COMPATIBILITY 1. The XDLC supports compatible devices with the model numbers listed in
Table 1 for UL 864 and in Table 2 for UL2572. Use any combination of those
listed in Table 1 or Table 2, as applicable.
2. The XDLC supports a maximum of 252 Desigo Fire Safety Modular/
Cerberus PRO Modular intelligent field devices distributed across four Class
A (DCLA) loops or eight Class B (DCLB) loops. A mix of Class A (DCLA) and
Class B (DCLB) is supported. The XDLC supports a maximum of 190 Desigo
Fire Safety Modular/Cerberus PRO Modular intelligent field devices wired in
isolation mode distributed across four Class X (DCLC) loops. A mix of Class
A (DCLA) and Class X (DCLC) wiring is supported where the maximum total
number of devices across four loops is 252 with a limit of 190 of those
Desigo Fire Safety Modular/Cerberus PRO Modular intelligent field devices
wired in isolation mode.
3. All circuits are power limited to NFPA 70 per NEC 760. The XDLC supports
the use of 12-22 AWG non-shielded, twisted, thermoplastic fixture wire
without conduit, if permitted by local building codes.
4. No end of line device is required.
5. Total circuit resistance of each zone must not exceed 50 ohms. (Refer to
the chart on page 7.)
Maximum capacitance: 0.5μF between line+ and line-
1.0μF between line and chassis
6. T-tapping is not allowed on Class A (DCLA) or Class X (DCLC) loops.
7. All models are UL and ULC listed.
8. The Multi-Criteria detectors are programmed using the DPU. A PAD-5,
Document ID A6V101030358, or a SBGA-34 base, connected to a ZIC-4A, P/
N 500-033050, or ZIC-8B, P/N 500-648670, can be used to create Temporal
4 tones in conjunction with the Carbon Monoxide enabled detectors
FDOOTC441 or OOHC941. Using these detectors with the ABHW-4S or
ABHW-4B, the selection of tones are chosen using the panel’s configuration
tool.
Siemens Industry, Inc. 6 A6V101040156_en--_c
Building Technologies Division
TABLE 1
XDLC Compatible Devices
for UL864/ULC-S527
Isolator Mode (I)
Compatible Installation Max Current ABHW-4 or Polarity
Devices Instructions From XDLC (mA) Compatible Insensitive (P)
Capable
ABHW-4B Loop powered A 6V 10405587 7.50 No -
ABHW-4B External powered A 6V 10405587 0.25 No -
ABHW-4S A 6V 10405588 0.25 No -
AD-11P** P/N 315-095659 0.00 No -
AD2-XHR P/N 315-049708 0.05 No -
ADBH-11 P/N 315-033210 0.00 No -
AD-HR P/N 315-033280 0.05 No -
DB-11 P/N 315-094193 0.00 No -
DB-11E P/N 315-094193 0.00 No -
DB-HR P/N 315-033220 0.05 No -
DB2-HR A 6V 10327325 0.20 No -
FDBZ492** A 6V 10336866 0.00 No -
FDBZ492-HR A 6V 10336866 0.05 No -
FDCIO422 A 6V 10324662 1.00 No P
FDO421* A 6V 10323926 0.28 Yes P
FDOOT441* A 6V 10324655 0.68 Yes P
FDOOTC441* A 6V 10324657 0.75 Yes P
FDOT421* A 6V 10323934 0.28 Yes P
FDT421* A 6V 10323930 0.28 Yes P
HCP P/N 315-034860 1.00 No P
HFP-11 P/N 315-033290 0.80 No P
HFPT-11 P/N 315-033290 0.80 No P
HI921* A 6V 10323932 0.28 Yes P
HMS-2S P/N 315-033430 0.90 No P
HMS-M P/N 315-033450 0.90 No P
HMS-S P/N 315-033200 0.90 No P
HMS-SA P/N 315-033430 0.90 No P
HMS-D P/N 315-033200 0.90 No P
HTRI-D P/N 315-049475 1.30 No P
HTRI-M P/N 315-049480 1.30 No P
HTRI-R P/N 315-049475 1.30 No P
HTRI-S P/N 315-049475 1.30 No P
HZM P/N 315-034850 1.00 No P
ILED-HC P/N 315-048637 1.00 No P
ILED-HW P/N 315-048637 1.00 No P
ILED-XC*** A 6V 101055484 0.50 No I, P
ILED-XW*** A 6V 101055484 0.50 No I, P
OH921* A 6V 10323936 0.28 Yes P
OOH941* A 6V 10324659 0.68 Yes P
OOHC941* A 6V 10324661 0.75 Yes P
OP921* A 6V 10323928 0.28 Yes P
PAD-5 A 6V 101030358 0.75 No I
PAD-5-CDC A 6V 101030366 0.75 No I
PAD-5-CLSA A 6V 101030359 1.25 No I
RL-HC P/N 315-033230 0.05 No P
RL-HW P/N 315-033230 0.05 No P
SBGA-34* A 6V 10383428 2.80 Yes P
TSM-1X*** A 6V 101055486 0.50 No I, P
XTRI-D*** A 6V 101055479 0.95 No I, P
XTRI-M*** A 6V 101055487 0.50 No I, P
XTRI-R*** A 6V 101055479 0.75 No I, P
XTRI-S*** A 6V 101055479 0.65 No I, P
*ABHW-4 compatible devices as described in number 8 on page 6.
**There is no curent drawn from XDLC for the Air Duct Housing without detector. The current rating for air duct
housing with detector is the current rating of the detector.
***Devices are suitable for Class X (DCLC) installation.
***Devices which are Class X (DCLC) capable.
P = Polarity Insensitive Device
I = Isolator Mode Capable Device
***These devices can be wired in either Polarity Insensitive or Isolator mode.

Siemens Industry, Inc. 7 A6V101040156_en--_c


Building Technologies Division
TABLE 2
XDLC Compatible Devices
for UL2572/ULC-S576
Isolator Mode (I)
Compatible Installation ABHW-4 or Polarity
Devices Instructions Compatible Insensitive (P)
Capable
FDCIO422 A 6V 10324662 No P
HCP P/N 315-034860 No P
HTRI-D P/N 315-049475 No P
HTRI-M P/N 315-049480 No P
HTRI-R P/N 315-049475 No P
HTRI-S P/N 315-049475 No P
ILED-XC*** A 6V 101055484 No I, P
ILED-XW*** A 6V 101055484 No I, P
PAD-5 A 6V 101030358 No I
PAD-5-CDC A 6V 101030366 No I
PAD-5-CLSA A 6V 101030359 No I
TSM-1X*** A 6V 101055486 No I, P
XTRI-D*** A 6V 101055479 No I, P
XTRI-M*** A 6V 101055487 No I, P
XTRI-R*** A 6V 101055479 No I, P
XTRI-S*** A 6V 101055479 No I, P
P = Polarity Insensitive Device
I = Isolator Mode Capable Device
***These devices can be wired in either Polarity Insensitive Mode or Isolator
Mode.

ELECTRICAL RATINGS

24V Back Plane Current 0

100mA + (max. device


Screw Terminal 24V Current
current per Table 1)

6.2V Back Plane Current 1mA max

100mA + (max. device


24V Standby Current
current per Table 1)

Device Loop: 30VDC max 500mA max (power limited)

Siemens Industry, Inc. 8 A6V101040156_en--_c


Building Technologies Division
PANEL

Out P P P P P CLASS A

XDLC
P P = Device(s)
(Polarity Insensitive)
Return P P P P P No Devices used as Isolators

PANEL

Out P I CLASS A (Mixed Mode)


P I P I
P = Device(s)
XDLC P (Polarity Insensitive)
(Max. 20 Devices between Isolators)
Return P I P I P I I = Isolator Device(s)
(Wired for Isolator Mode)

Figure 5
Class A Device Loop Topologies

PANEL

Out I I I I I
CLASS X

XDLC
I I = Isolator Device(s)
(All wired for Isolator Mode)
Return I I I I I

PANEL

XDLC CLASS B

P = Device(s)
Out P P P P P P P (Polarity Insensitive)

No Devices used as Isolators

Figure 6
Class X and B Device Loop Topologies

Siemens Industry, Inc. 9 A6V101040156_en--_c


Building Technologies Division
Cyber security disclaimer

Siemens products and solutions provide security functions to ensure the secure operation of building comfort,
fire safety, security management and physical security systems. The security functions on these products and
solutions are important components of a comprehensive security concept.

It is, however, necessary to implement and maintain a comprehensive, state-of-the-art security concept that is
customized to individual security needs. Such a security concept may result in additional site-specific preventive
action to ensure that the building comfort, fire safety, security management or physical security system for your
site are operated in a secure manner. These measures may include, but are not limited to, separating networks,
physically protecting system components, user awareness programs, defense in depth, etc.

For additional information on building technology security and our offerings, contact your Siemens sales or
project department. We strongly recommend customers to follow our security advisories, which provide infor-
mation on the latest security threats, patches and other mitigation measures.

http://www.siemens.com/cert/en/cert-security-advisories.htm

Siemens Industry, Inc. Siemens Canada, Ltd. Siemens AG Document ID A6V101040156_en--_c


Building Technologies Division 1577 North Service Road East I BT FS SYS MCH
P/N A5Q00072496