Auto Transfer Switch Control Module: Comprehensive Feature List To Suit A Wide Variety of Ats Applications
Auto Transfer Switch Control Module: Comprehensive Feature List To Suit A Wide Variety of Ats Applications
Auto Transfer Switch Control Module: Comprehensive Feature List To Suit A Wide Variety of Ats Applications
dseAts
dse333
ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
AUTO TRANSFER SWITCH CONTROL MODULE EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
FEATURES EMC Generic Emission Standard for
the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
The DSE333 is an Automatic Once the mains (utility) supply The modules can be easily including Electrical Business Equipment
Transfer Switch Controller for returns to within limits, the module configured using the DSE
TEMPERATURE
genset and other applications. The will command a return to the mains Configuration Suite PC Software. BS EN 60068-2-1
module will monitor the voltage and (utility) supply and shut down the Selected front panel editing is also Ab/Ae Cold Test -30 oC
frequency of the incoming AC generator after a suitable cooling available. BS EN 60068-2-2
Bb/Be Dry Heat +70 oC
mains (utility) supply and in the run.
event of a failure, will issue a start Configurable volt-free digital inputs VIBRATION
BS EN 60068-2-6
command to the generator control Various timing sequences are and outputs make the DSE333 fully Ten sweeps in each of three
system. available to prevent nuisance flexible to suit a wide variety of major axes
starting on minor supply breaks. applications. 5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
Once the generator is available and
producing an output within limits, The DSE333 supports many When there is no DC supply, a HUMIDITY
BS EN 60068-2-30
the DSE333 will control the transfer topologies and features include compatible self-seeking power Db Damp Heat Cyclic 20/55 oC
device and switch the load from the mains (utility) rated volt-free relays, supply is available (DSE160). @ 95% RH 48 Hours
mains (utility) to the generating set. a clear back-lit LCD 4-line text BS EN 60068-2-78
Cab Damp Heat Static 40 oC
display, showing system status and @ 93% RH 48 Hours
warnings and red and green LEDs
SHOCK
indicating operational status. BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the optional sealing gasket.
1 10 1
DSE333
7
OTHER
MAINS (UTILITY) SENSING N/C VOLT FREE OUTPUTS LOAD CURRENT N/O VOLT FREE OUTPUTS GENERATOR SENSING
VOLTS VOLTS
ISSUE 2
®
dseAts
dse333
SPECIFICATION
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
FEATURES Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUT A (MAINS/UTILITY)
Normally closed volt-free output
8 A AC at 250 V AC
OUTPUT B (GENERATOR)
Normally open volt-free output
8 A AC at 250 V AC
OUTPUT D
Changeover volt-free output
8 A AC at 250 V AC
OUTPUT E
Normally open volt-free output
8 A AC at 250 V AC
GENERATOR
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
KEY FEATURES • PC configuration KEY BENEFITS
• Volt-free relays • Front panel configuration • Fully automatic monitoring and DIMENSIONS
• Supports many topologies • LED indicators switch-over control minimises OVERALL
215 mm x 158 mm x 42 mm
• Automatic switch-over between • Back-lit 4-line text LCD display the effects of power disruptions
8.5” x 6.2” x 1.6”
supplies • External mains (utility) or • Real-time clock provides
• Check sync feature genset failure inputs accurate event information for PANEL CUT-OUT
182 mm x 137 mm
• Real-time clock • Auto start inhibit easy maintenance diagnostics
7.2” x 5.4”
• 10 configurable inputs • Load inhibit • User-friendly set-up and button
• 5 configurable outputs • Manual restore to mains (utility) layout MAXIMUM PANEL THICKNESS
8 mm
• Event log (10) • Optional current monitoring • Will work with external
0.3”
• Configurable timers synchroniser for seamless
• Automatic shutdown or return to mains (utility) OPERATING TEMPERATURE RANGE
warning when fault conditions -30°C to +70°C
RELATED MATERIALS
TITLE PART NO’S
DSE333 Installation Instructions 053-066
DSE333 Operator Manual 057-118
DSE333 Configuration Suite PC Manual 057-106
DSE160 Self-Seeking Power Supply Data Sheet 055-076
DSE160 Operator Manual 057-108
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-080/10/10 (4)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457