ARCON STM150
For ARCON RDI Range
Operating Manual
Table of contents :
4. MODULE OPERATION............................................................................................................................................ 8
COMMISSIONING ................................................................................................................................................................. 8
4.1.1. Starting with mains present: ........................................................................................................................... 8
4.1.2. Starting without mains present: ...................................................................................................................... 8
STARTING AND RUNNING SEQUENCE ................................................................................................................................... 9
5. USER INTERFACE.................................................................................................................................................. 10
DISPLAY MODE MENU ....................................................................................................................................................... 11
PARAMETRIC MODE MENU................................................................................................................................................. 13
CONFIGURATION MODE MENU ........................................................................................................................................... 15
MENU SUMMARY (DISPLAY AND PARAMETRIC MENUS) ..................................................................................................... 15
6. PROTECTION AND ALARMS .............................................................................................................................. 16
INTERNAL ELECTRONIC PROTECTION................................................................................................................................. 16
FUSES PROTECTION ........................................................................................................................................................... 16
REMOTE CONTROL AND ARCON STM FREE POTENTIAL CONTACTS. ............................................................................... 16
PAYMENT PROTECTION ..................................................................................................................................................... 16
7. TROUBLESHOOTING GUIDE.............................................................................................................................. 17
ALARMS AND DISPLAY STATUS (MESSAGES LIST) ............................................................................................................. 17
ERROR MESSAGE LIST........................................................................................................................................................ 17
MENU IN FACTORY MODE. ................................................................................................................................................ 18
8. HOW TO ORDER ?.................................................................................................................................................. 19
MODEL : ARCON STM150 STATIC SWITCH FOR RDI INVERTER ......................................................................... 19
9. APPENDIX : ARCON STM 150 FAILURE SHEET REPORT ........................................................................... 20
1. Unit description
The ARCON STM 150 is an ultra-fast switch intended for the transfer of one load from a redundant
inverters system to a second source of AC voltage or vice-vers
It allows the redundant inverters system to work on an ‘’ON LINE’’ or ‘’ OFF LINE’’ mode.
It is provided with :
Alphanumeric display allowing:
• message display giving the system status (load position, system fault, inverter defect,
synchronism or not, overload,..) in several languages (selection by user).
• value display of the voltage, the current, the power and the frequency
Control push buttons.
On / Off switch to control the start and stop of inverter modules in the system.
Rear connections for Power and RDI digital bus.
12 1 2 3 4 9 10 5 67 8 11
Module information (status) as well as various measurements are accessible through LCD display and
menu push button.
Parameters adjustment can also be performed thanks to menu push button in parametric mode.
Please refer the "Parametric mode" menu section.
RDI
ARCON
STM150
RDI
RDI Bus
RDI
Entering in the configuration menu through the buttons on the front panel allows the user to choose
between 2 operating modes:
• ON-LINE mode: Load supplied permanently by the inverters with assistance (general power
failure) or temporary assistance (overload, short-circuit, module break-down) from the mains if
necessary.
• OFF-LINE mode: Load supplied permanently by the mains with assistance (non conformity of
the voltage or frequency mains out of range ) from the inverter system if necessary.
Operating principle
Fig. 1 shows the operating principle of a parallel inverter system assisted by a ARCON STM150.
In the normal state, the loads are supplied by the inverters which the emergency system holds
synchronous by means of the SY (synchronisation) process located in the ARCON STM 150.
When a fault occurs on the AC power bus of the inverters, ARCON STM 150 detects it and an
uninterrupted commutation sequence is started thanks to the 2 thyristor pairs TH1 and TH2.
After 2 seconds, if the AC power bus of the inverters is back to normal, the loads are
reconnected without cut-off, to the inverter system.
Operating principle
Normally, the loads are supplied by the auxiliary source. The inverters set in parallel are running in a
no-load mode and synchronised to the mains by means of a the SY process located in the ARCON
STM 150.
ARCON STM 150 monitors permanently the MAINS and in case of any fault detected, an
uninterrupted commutation sequence is started thanks to the 2 thyristor pairs TH1 and TH2.
5 seconds after the AC mains returns to normal, the loads are reconnected, without cut-off to the
mains.
For detailed description of available controls, monitoring functions and operation please, refer to the
appropriate section.
2. Technical datasheet
Please refer to figure 2 of this manual for item identification and the simplified connection schematic
figure hereunder.
2. Fix the module to the cradle by screwing the front handles to the cabinet frame
RDI bus
Rear view
Neutral
4. Module operation
4.1. Commissioning
If the ARCON STM is configured in “OFF LINE“ each inverter starts and runs without load.
As soon an AC voltage is connected to the mains terminal the auxiliary power supply starts.
The front switch on/off is used to start the inverters modules of the system.
The choice of configuration between “on line” and “off line” mode will govern the following steps.
The load position indicates the current path in the static switch (even if the output voltage is 0)
By pressing the push button “MENU”, the user can display informations about the system or the
ARCON STM unit.
For more details on installation and commissioning please refer to this section.
5. User interface
If only the AC of inverters is present and mains not present when the system is started:
Briefly pushing the button the following screen can be seen if the system is running:
Each brief pushing of the button allows to display the other following screens:
Synchro State : This screen shows if the inverter system is (or not)
synchronised
(Not) Synchronised
ON (OFF) LINE
Brief pushing button “menu” after this screen goes back on the first screen
• Pressing more than 2 seconds the button → activates the parametric mode menu.
• Pressing more then 2 seconds the button →, user will EXIT the parametric mode menu
and activate the display mode.
Please note that all parameters you have modified will be recorded when you exit from the
menu.
Synchro Mode: Pressing the keys ↑ and ↓ it is possible to choose between the
ON LINE and OFF LINE mode. (Note: the change of mode can be
>> ON LINE used to test the transfer availability)
After the previous screen, pushing briefly the key , the user can see all the following menus
and modify the parameters:
Contrast: >> 50 The contrast can be modified to higher or lower values with the
keys ↑ and ↓
Vconform Mains Menu to set the max voltage of mains over which the mains is
not conform. This voltage can be set :
Max >> 264Vac - in the range 250…275V (230VAC version, factory value 264V)
(135) - in the range 125….150V (120VAC version, factory value 145V)
Vconform Mains Menu to set the min voltage of mains under which the mains is not
conform. This voltage can be set :
Min >> 195Vac - in the range 180…210V (230VAC version, factory value 195V)
(100) - in the range 95…110V (120VAC version, factory value 100V)
Vconform Inv Bus Menu to set the max output voltage of inverter over which the
inverter is not conform. This voltage can be set :
Max >> 250Vac - in the range 250…275V (230VAC version, factory value 264 V)
(135) - in the range 125….150V (120VAC version, factory value 145V)
Vconform Inv Bus Menu to set the min output voltage of inverter under which the
inverter is not conform. This voltage can be set :
Min >> 195Vac - in the range 180…210V (230VAC version, factory value 195 V) -
(100) in the range 95…110V (120VAC version, factory value 100 V )
Overload return Menu to set the percentage Imax under which the load come
back to the inverter system.
90% This percentage can be set in the range 75..95%
(the factory value is 90%)
Briefly pressing the key the following menu is only activated if the payment
protection is activated.
Code: 025 >> 253 To introduce the 3 last figures of the code
Time: 11620
Note: In case the mains is present once, alarm will be automatically re-activated. System will
consider the AC has been connected. Alarm can be de-activated through the menu again.
Next push on key will come back to the first screen in parametric mode.
Pressing the key during 2 sec allows to store the parameters in EEPROM and to
come back in visualisation menu.
Pressing more than 2 sec on key ↓ allows to enter in the first menu in configuration mode.
Freq Vout Range To introduce the selected voltage (230 or 115V) and
the frequency range (50 or 60 Hz)
>>50Hz 230V
The ARCON STM 150 static switch is provided with internal electronic protections.
All thyristors will open if the current is above 450A for 50 periods.
The ARCON STM 150 static switch controller is internally protected by fuses (Type : T-2A).
A remote control is available on the connector located on the rear side of the unit
Function is to Start / stop remote of inverters via external potential free contact
If the remote ON / OFF switch is not used, the pins must be short circuited
Free potential contacts are available for alarms if a controller SYS 3000 is not used in the system
Information concerning the system status are displayed on the ARCON STM 150 LCD: the load
position (mains or inverter), the functional mode (“on” or “off” line) and other usual measurements of
inverter system (see the “menu” section).
Payment protection is deactivated when the ARCON STM leave the factory.
It is only activated for customers in chronic state of overdue payment.
The protection only can be deactivated introducing the apposite code the customer can get
from CE+T after payment (each inverter has its own code).
See the menu “payment protection” in parametric menu to deactivate the protection.
When the protection is deactivated it becomes quite invisible for the user.
When the protection is activated, the message “limited working” is displayed every 5 seconds.
After running 90 days, the protection avoids to start the module the module becomes
unusable.
If the module runs when the time limit is reached, it continues to run but gives alarms each 10 seconds
with alarm relay and is definitively stopped after the first stop after that it is impossible to restart
the module without having to deactivate the protection.
7. Troubleshooting guide
With an ARCON STM 150 the system can only start switching “ON” the local switch of the
ARCON STM but only after the local ON push button of each inverter is switched ON.
If the system don’t start after the previous verification please contact your supplier.
The unit ARCON STM 150 can take a decision to transfer the load on the emergency source for
internal or external reason.
The errors list gives the various reasons to display alarms messages. In case the user identifies an
internal fault in the ARCON STM 150, the unit has to return in factory for inspection: please contact
your supplier.
Major alarms:
Cable not conn. An internal cable is not connected
Inv Switch Fail The inverter thyristor pair has a problem (the ARCON STM is locked)
Mains Switch Fail The mains thyristor pair has a problem (the ARCON STM is locked)
Cable disconnect The internal flat cable X9 is not connected (load is supplied by mains)
RDI Bus Error The RDI bus is not connected
Mains Failure Mains failure (in the “off line” mode)
Inv Bus Failure Inverter fault ( in the “on line” mode)
Mains Not Conform Mains voltage out of range (in the “off line” mode)
Inv Bus Not Conform Inverter voltage out of range ( in the “on line” mode)
OVERLOAD Imax Inverter current > I nominal (when the load is supplied by mains in both modes)
Vout Not Conform no voltage (or bad) on load ( in both mode)
BAD CONFIG The inverter system and the ARCON STM have different frequency
Freq out of Rang Frequency is outside of the specified range
Inv Bus off The inverter is switched off by the local front switch or by the SYS 3000 controller
(Major alarm in "on line mode)
Minor alarms:
This single Minor alarm can appear on the first line of the display in Blinking mode:
Out of synchro Inverter system not synchronised
Other Minor alarms can appear on the second line of the display in Blinking mode:
Time elapsed The running time in relation with payment protection is elapsed
Limited running The payment protection is activated.
Overload Imax I > I nominal of the inverter
Imminent Switch Imminent supply by mains (after 5" in Off line mode)
Mains Failure Mains failure (in “on line mode”)
Inv Bus Failure Inverter system fault (in “off line mode”)
Mains Not Conform Mains voltage out of range
Inv Bus Not Conform System inverter voltage out of range (in “off line” mode)
Inv Bus off The inverter is intentionally switched off by the local front switch or by the SYS 3000
controller.
Overload back Switch Come back of the load to the inverter system if the overload disappears and the load
actual value is under the set load threshold (between 75 and 95% of the nominal
value) otherwise the load remains on mains.
Module defect One module is stopped or out of order
Factory mode is a helpful menu for our engineers when you are in contact with them to analyse a
specific problem on site.
By giving those information to our R&D engineers they can help you and focus directly to your
problem.
To enter in Factory mode press the push button ↑ for at least 2 seconds.
8. How to order ?
The scope of this sheet is to receive as much as information to identify the reasons and gives
to the user a report on what happened in this faulty case. Further to this it will help our service
and quality department to improve the quality of our products. Please fill this document
carefully and return it with the defect unit or FAX it to your supplier.
Configuration Answer
Number of inverter installed in the system :
Module type and model :
Serial module number :
SYS3000 installed in the system ;
Model and serial number of the ARCON STM150 in the system :
Fault description : Please describe the fault conditions, type of load, output current
Contractor :