WAU 100 Operators Manual 4189350083 UK

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

Operator's manual Document no.

: 4189350083A

Wind Alarm Unit

WAU 100
DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com
1. Introduction
1.1 About the Operator's manual.............................................................................................................................................................................................. 3
1.1.1 General purpose ................................................................................................................................................................................................................3
1.1.2 Intended users of the Operator's manual.................................................................................................................................................................3
1.1.3 List of technical documentation for WAU 100........................................................................................................................................................ 3
1.1.4 Technical support .............................................................................................................................................................................................................. 3
1.2 Legal information....................................................................................................................................................................................................................... 3
1.2.1 Trademarks........................................................................................................................................................................................................................... 3

2. Overview of the unit


2.1 Introduction ................................................................................................................................................................................................................................. 4
2.2 General functionality................................................................................................................................................................................................................5

3. Wind mode
3.1 Introduction...................................................................................................................................................................................................................................6
3.2 High 1 alarm .................................................................................................................................................................................................................................6
3.3 High 2 alarm.................................................................................................................................................................................................................................. 7
3.4 Printed alarm log........................................................................................................................................................................................................................ 7

4. Alarm log
4.1 Introduction ................................................................................................................................................................................................................................. 8
4.2 Alarm state ................................................................................................................................................................................................................................... 8
4.3 USB alarm log.............................................................................................................................................................................................................................. 9

5. Option settings
5.1 Introduction ............................................................................................................................................................................................................................... 10
5.2 Wind speed alarm set points............................................................................................................................................................................................ 10
5.3 Save alarm log...........................................................................................................................................................................................................................10
5.4 Printer............................................................................................................................................................................................................................................ 10
5.5 Brightness and offline UTC time..................................................................................................................................................................................... 11
5.6 Synchronise UTC date and time from NMEA........................................................................................................................................................... 11

6. Information menu
6.1 Introduction................................................................................................................................................................................................................................ 13
6.2 Service mode............................................................................................................................................................................................................................. 13

7. Troubleshooting
7.1 General troubleshooting..................................................................................................................................................................................................... 14

OPERATORS MANUAL 4189350083A UK Page 2 of 14


1. Introduction

1.1 About the Operator's manual


1.1.1 General purpose

This is the Operator's manual for DEIF’s Wind Alarm Unit 100, WAU 100. The Operator's manual provides information for the correct
operation of the WAU 100.

1.1.2 Intended users of the Operator's manual

This is the operator's manual for DEIF's Wind Alarm Unit, WAU 100. The manual is for the operator who uses the WAU 100. The
manual includes an introduction to the unit (LEDs, push-buttons and screen), basic operator tasks, alarms, logs, more advanced
operator tasks, and trouble shooting.

1.1.3 List of technical documentation for WAU 100

Document Contents

• System description
Data sheet • Technical specifications
• Ordering information

• Mounting
Installation instructions
• Default wiring for the controller

• Unit push-buttons and LEDs


• Operating the unit
Operator's manual • Alarms and log
• Using the unit
• Troubleshooting

1.1.4 Technical support

You can read about service and support options on the DEIF website, http://www.deif.com. You can also find contact details on the
DEIF website.

You have the following options if you need technical support:

• Technical documentation: Download all the product technical documentation from the DEIF website: http://www.deif.com/
documentation
• Support: DEIF offers 24-hour support. See http://www.deif.com for contact details. There may be a DEIF subsidiary located near
you. You can also e-mail http://deif.com.

1.2 Legal information


1.2.1 Trademarks

DEIF is a trademark of DEIF A/S.

Exxon Mobil is a trademark of Exxon Mobil Corporation.

All trademarks are the properties of their respective owners.

OPERATORS MANUAL 4189350083A UK Page 3 of 14


2. Overview of the unit

2.1 Introduction
Wind Alarm Unit 100, WAU 100, monitors wind speed and direction, and can activate alarms if their limits are exceeded.

INFO
Alarms must be both configured and the unit operating.

Exxon Mobil Corporation governs the rules for cargo ships and DP ships chartered to be operated for Exxon Mobil. Depending
on the chartering type, different rules apply. WAU 100 is made to support the most complex requirements.

Figure 2.1 Wind Alarm Unit, WAU 100

No. Item Notes

1. AGI Touch screen for general control of the system

2. Printer Prints alarms (if configured)

• USB connection, with protective cap mounted


3. USB 2.x
• USB storage to record data log

4. On/Off Switch the unit on or off

5. High 1 alarm acknowledge Indication and acknowledge high 1 alarm on touch screen

6. High 2 alarm acknowledge Indication and acknowledge high 2 alarm on touch screen

7. Mute high 1 alarm Mute button for high 1 alarm

8. Mute high 2 alarm Mute button for high 2 alarm

9. Buzzer Internal buzzer, active when alarm is present

OPERATORS MANUAL 4189350083A UK Page 4 of 14


2.2 General functionality
The WAU 100 is typically installed in the cargo room location.

When the wind speed requires monitoring, the unit is switched on at the front.

Operate the WAU 100 by using the touch screen. At the bottom of the screen are the four menu icons.

Figure 2.2 WAU 100 display - Wind mode

Icon Item Notes

Wind mode Daily operation showing wind speed, direction and information about any alarms. *

Alarm log Display the list of alarms.

Options Display/edit general settings, including alarm set points.

Information Display contact information.

NOTE: * This is the display shown in the figure above.

OPERATORS MANUAL 4189350083A UK Page 5 of 14


3. Wind mode

3.1 Introduction

Select Wind mode to display the current wind speed and direction on the display.

Alarms High 1 and High 2 are shown if they are activated.

By default, alarms are printed by the integrated printer. *

Figure 3.1 Wind mode display

The alarms provide notification if the wind speed exceeds the configured set points.

• High 1 alarm is intended as a first warning, configured on the first set point.
• High 2 alarm is intended as a critical warning, configured on the second set point.

NOTE: * If this feature is not required, the printer can be disabled in the Options menu.

3.2 High 1 alarm

Configure the set point High 1 under Options .

Value

High 1 alarm activates if the wind speed exceeds the set point.
Set
point
The alarm response is based on the High 1 wind speed alarm set point.
0
time

OPERATORS MANUAL 4189350083A UK Page 6 of 14


1. When the wind speed exceeds the High 1 set point, the High 1 ack. icon flashes on the display and the buzzer activates.
• If the relay output is configured for High 1 alarm this activates.
2. The buzzer can be disabled/muted by pressing the yellow push-button under the display.

3. To acknowledge the High 1 alarm, press the alarm symbol on the screen.

4. When the high 1 alarm is acknowledged the symbol will stop flashing and be present until the wind speed falls below the
defined high 1 alarm limit.

3.3 High 2 alarm

Configure the set point High 2 under Options .

Value
High 2 alarm activates if the wind speed exceeds the set point.

The alarm response is based on the High 2 wind speed alarm set point. Set
point

This is a critical alarm and any necessary actions must be taken to continue operation. 0
time

1. When the wind speed exceeds the High 2 set point, the High 2 ack. icon flashes on the display and the buzzer activates.
• If the relay output is configured for High 2 alarm this activates.
2. The buzzer can be disabled/muted by pressing the yellow push-button under the display.

3. To acknowledge the High 2 alarm, press the alarm symbol on the screen.

4. When the high 2 alarm is acknowledged the symbol will stop flashing and be present until the wind speed falls below the
defined high 2 alarm limit.

3.4 Printed alarm log


The printer function is enabled by default. The printer records information about the date, time, alarm type, wind speed, and wind
angle when an alarm occurs.

Figure 3.2 Example printed alarm

INFO
If you do not need the printed log, you can disable the printing function in the Options menu.

OPERATORS MANUAL 4189350083A UK Page 7 of 14


4. Alarm log

4.1 Introduction

Select Information to display the internally stored alarm log.

Figure 4.1 Alarm log

The alarm log provides you with an overview of all recorded alarms and their state.

Use the filter bar at the top of the display to select a different interval for viewing.

The alarm log is always stored on the internal memory of the unit. The internal log can hold 2000 alarm events, after which the log is
automatically overwritten. The oldest events are replaced by new entries.

Extend the alarm log recording by using a USB memory device. With USB memory deivce plugged in, after 2000 alarms the USB
device will be used for recording. If the USB device has been removed, a warning window is displayed requesting the USB device
be plugged back in. If the USB device is not plugged back in, the log is automatically overwritten as above.

You can also manually save the alarm log to a USB device under Options. Press Save log for 3 seconds to save the log.

4.2 Alarm state


In the alarm log the name of the alarm High 1 or High 2, state and time is logged. To explain the different states of the alarm an
example used. Here is shown the different alarm stages when the wind speed exceeds or falls below a set alarm limit.

OPERATORS MANUAL 4189350083A UK Page 8 of 14


Figure 4.2 Alarm states

No. Alarm condition Alarm state * Notes

1 Active Triggered Not Acked Wind speed goes above the alarm set point.

2 Not active Not Triggered Not Acked No acknowledgment but the wind speed goes below the alarm set point.

3 Active Triggered Not Acked Wind speed exceeds the alarm set point.

4 Active Triggered Acked Alarm is acknowledged.

5 Not active Not Triggered Wind speed drops below alarm set point.

NOTE: * Alarm state shows the text recorded in the alarm log.

4.3 USB alarm log


On the USB device, the alarm log is saved under a folder named Log. Under this folder the alarm log is saved in folders by year and
month. Under this folder is saved a CSV file with the alarm log events recorded by date and time.

The CSV file can be imported into an appropriate spread sheet editing application.

Figure 4.3 Example of an imported CSV file

OPERATORS MANUAL 4189350083A UK Page 9 of 14


5. Option settings

5.1 Introduction

Select Options to display the settings menu.

Figure 5.1 Options

Here you can configure:

• High 1 / High 2 alarm set points.


• Save the alarm log manually to a USB device.
• Enable or disable the printer.
• Adjust screen brightness and configure offline UTC time.
• Enable to disable NMEA ZDA or NMEA RMC time sync.

5.2 Wind speed alarm set points


Alarm set points for High 1 and High 2 must be configured. With the set points configured the unit can provide alarm monitoring on
low or high wind speed.

5.3 Save alarm log


Use this option to manually save the alarm list to the USB device. Press and hold the option for 3 seconds to save the alarm list.

The info option provides you with information on the file structure on the USB device.

5.4 Printer
INFO
The printer is enabled by default.

OPERATORS MANUAL 4189350083A UK Page 10 of 14


Enable or disable the printer by selecting ON or OFF.

5.5 Brightness and offline UTC time


Brightness

The brightness level of the display can be adjusted by using the + and - icons.

Offline UTC time

By default, the WAU 100 is set to the current UTC date and time. If the date and time needs to be adjusted, then use Service mode
to make any changes.

MORE INFORMATION
See Information mode, Service mode in this document for more information about how to enter the Service mode.

With Service mode active, the Offline UTC button can be selected.

Select Offline UTC to configure the date and time settings manually.

Figure 5.2 Offline UTC settings

Here you can change:


• Year
• Month
• Day
• Hour
• Minute
• Second

Select a button to change a value, a virtual keyboard is shown on the display. Edit the value using the keyboard.

Select OK! to save the new date and time settings.

5.6 Synchronise UTC date and time from NMEA


You can synchronise the UTC date and time using NMEA sentences ZDA or RMC. Synchronisation occurs during power up of the
WAU 100 unit, it then synchronises every hour or by manual synchronisation. Between synchronisations the internal real time clock
controls the date and time of the unit.

OPERATORS MANUAL 4189350083A UK Page 11 of 14


To synchronise manually, toggle either ZDA or RMC ON/OFF.

To configure settings for ZDA or RMC functionality, the unit must be in Service mode.

MORE INFORMATION
See Information mode, Service mode in this document for more information about how to enter the Service mode.

OPERATORS MANUAL 4189350083A UK Page 12 of 14


6. Information menu

6.1 Introduction
The Information menu provides you software version and contact information. It is also where you can enable Service mode for
extra functionality.

Figure 6.1 Information menu

6.2 Service mode


Access the Service mode by selecting the DEIF logo for 5 seconds. A log on prompt is shown on the display.

Figure 6.2 Service mode log on

Enter User name and Password by using the virtual keyboard that is shown.
• User name: service
• Password: 2000

INFO
When logged in with Service mode, extra functionality is available in the options menu. After five minutes the unit
automatically logs out of Service mode back to normal operation.

OPERATORS MANUAL 4189350083A UK Page 13 of 14


7. Troubleshooting

7.1 General troubleshooting

Fault/symptom Cause/solution Check

The alarm log has filtering functionality, so only alarms in a certain time
No alarms shown in the interval are seen. Select a larger interval.
alarm log
The filter function is available in the first line on the screen.

Not possible to change


High 1 alarm must always be set to a lower value than high 2 alarm.
the alarms settings

WAU 100 detects the data received and checks for the validation.
Check the sensor
Data is flashing If the status flag in the NMEA sentence is invalid (V) data will be flashing providing NMEA data.
Wind pointer and digital indication data is incorrect.
readout flashing The sensor could be
The value flashing will be the last valid data value. Both the graphical wind faulty.
direction and the digital read out will be flashing.

Data is flashing WAU 100 detects that data is received continuously. Check the data is
Wind pointer and digital If data has not been received for 10 seconds the wind pointer and digital transmitted from the
readout flashing readout values will be flashing to indicate data is incorrect. sensor.

When using external UTC time to synchronize the time data must be Check time from the
received continuously. NMEA sentence ZDA or
UTC time is flashing
If time data is not received for 10 seconds the date and time will start RMC is transmitted
flashing. correct.

OPERATORS MANUAL 4189350083A UK Page 14 of 14

You might also like