Ds0h Ufaa68 Proposal

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

® MODELS

DS0H-UFAAM0 DS0H-UFAA60
DS0H-UFAAN0 DS0H-UFAA98
FIRE PUMP ENGINES DS0H-UFAA68 DS0H-UFAA92

FM-UL-cUL APPROVED RATINGS BHP/KW


DS0H RATED SPEED
MODEL
  1470 1760 2100 2350
DS0H-UFAAM0 520 388 530 395
DS0H-UFAAN0 542 404 575 429
DS0H-UFAA68 522 389.5 587 438
DS0H-UFAA60 614 458 606 452
DS0H-UFAA98 650 485
DS0H-UFAA92 722 538.5

 All Models are available for Export

 = Non-Emissionized

Picture shown represents the DS0H-UFAA98 and UFAA92 engine models

SPECIFICATIONS
DS0H MODELS
ITEM UFAAM0 UFAAN0 UFAA68 UFAA60 UFAA98 UFAA92
Number of Cylinders 10
Aspiration TRWA
Rotation* CW

Overall Dimensions – in. (mm) 76.7 (1947) H x 61.7 (1568) L x 53.9 (1369) W

Crankshaft Centerline Height – in. (mm) 23.5 (597)


Weight – lb (kg) 3200 (1450)
Compression Ratio 14.6:1
Displacement – cu. in. (l) 1115 (18.3)
Engine Type 4 Cycle, 2 Valves per Cylinder, Vee
Bore & Stroke – in. (mm) 5.04 x 5.59 (128 x 142)
Installation Drawing D665
Wiring Diagram AC C07651
Wiring Diagram DC C071842
Speed Interpolation None

Abbreviations: CW – Clockwise TRWA – Turbocharged with Raw Water Aftercooling L – Length W – Width H - Height
*Rotation viewed from Heat Exchanger / Front of engine

CERTIFIED POWER RATING ENGINE RATINGS BASELINES


• Each engine is factory tested to verify power and performance. • Engines are to be used for stationary emergency standby fire pump service only. Engines
are to be tested in accordance with NFPA 25.
• Engines are rated at standard SAE conditions of 29.61 in. (752.1 mm) Hg barometer and
77°F (25°C) inlet air temperature [approximates 300 ft. (91.4 m) above sea level] by the
testing laboratory (see SAE Standard J 1349).
• A deduction of 3 percent from engine horsepower rating at standard SAE conditions shall
be made for diesel engines for each 1000 ft. (305 m) altitude above 300 ft. (91.4 m)
• A deduction of 1 percent from engine horsepower rating as corrected to standard SAE
conditions shall be made for diesel engines for every 10°F (5.6°C) above 77°F (25°C)
FM ambient temperature.
® MODELS
DS0H-UFAAM0 DS0H-UFAA60
DS0H-UFAAN0 DS0H-UFAA98
FIRE PUMP ENGINES DS0H-UFAA68 DS0H-UFAA92

ENGINE EQUIPMENT
EQUIPMENT STANDARD OPTIONAL
Air Cleaner Direct Mounted, Washable, Indoor Service with Drip Shield Disposable, Drip Proof, Indoor Service Outdoor Type, Single or
Two Stage (Cyclonic)
Alarms Overspeed Alarm & Shutdown, Low Oil Pressure, Low & High Low Coolant Level, Low Oil Level, Oil Filter Differential Pressure,
Coolant Temperature, High Raw Water Flow, High Raw Water Fuel Filter Differential Pressure, Air Filter Restriction
Temperature
Alternator 24V-DC, 45 Amps with Dual (2) V-Belt Drive with Guard
Coupling Bare Flywheel Non-Listed SC2160A Driveshaft; Vertical Turbine Drivedisc
Engine Heater 230V-AC, 2500 Watt
Exhaust Flex Connection SS Flex, 150# Flange Connection, 5” SS Flex, 150# Flange Connection, 6”
Exhaust Protection Blankets
Flywheel Housing SAE #1
Flywheel Power Take Off 14.0” Industrial Flywheel Connection
Fuel Connections Fire Resistant, Flexible, USA Coast Guard Approved, Supply and
Return Lines
Fuel Filter Primary and Secondary
Fuel Injection System Direct Injection, Inline Pump
Fuel Solenoid 24V-DC Energized to Stop
Governor, Speed Variable Speed, Mechanical
Heat Exchanger Tube and Shell Type, 60 PSI (4 BAR), NPT(F) Connections – Sea
Water Compatible
Instrument Panel Tachometer, Hourmeter, Water Temperature, Oil Pressure and
Two (2) Voltmeters, Front Opening
Junction Box Integral with Instrument Panel; For DC Wiring Interconnection to
Engine Controller
Lube Oil Cooler Engine Water Cooled, Plate Type
Lube Oil Filter Full Flow with By-Pass Valve
Lube Oil Pump Gear Driven, Gear Type
Manual Start Control On Instrument Panel with Control Position Warning Light
Overspeed Control Electronic with Reset and Test on Instrument Panel
Raw Water Cooling Loop – Galvanized Sea Water, All 316SS, High Pressure
w/ Alarms
Raw Water Cooling Loop - Automatic from Fire Pump Controller and from Engine Instrument Not Supplied (for Vertical Turbine Fire Pump Applications)
Solenoid Operation Panel (for Horizontal Fire Pump Applications)
Run – Stop Control On Instrument Panel with Control Position Warning Light
Starters One (1) 24V-DC with Two (2) Start Contactors
Throttle Control Adjustable Speed Control, Tamper Proof
Water Pump Centrifugal Type, Dual (2) V-Belt Drive with Guard
Abbreviations: DC – Direct Current, AC – Alternating Current, SAE – Society of Automotive Engineers, NPT(F) – National Pipe Tapered Thread (Female), SS – Stainless Steel

Fire Protection Products, Inc. UK, Ltd.


100 Progress Place, Cincinnati, Ohio 45246 Grange Works, Lomond Rd., Coatbridge, ML5-2NN
United States of America United Kingdom
Tel +1-513-475-(FIRE)3473 Fax +1-513-771-8930 Tel +44-1236-429946 Fax +44-1236-427274
www.clarkefire.com www.clarkefire.com

C134251 revM Specifications and information contained in this brochure subject to change without notice. .
01FEB18
FIRE PUMP MODEL: DS0H-UFAA68
Heat Exchanger Cooled/T urbocharged
Raw Water Charge Cooling
18.3 Liter
Brake Horsepow er - BHP (kw )

ENGINE SPEED - RPM


RESTRICTED:
Use only for Stand-By Fire Pump Applications

NAMEPLATE BHP (MAXIMUM PUMP LOAD)

ENGINE PERFORMANCE:
STANDARD CONDITIONS: (SAE J1349, ISO 3046)
77°F (25°C) AIR INLET TEMPERATURE
29.61 IN. (751.1MM) HG BAROMETRIC PRESSURE
#2 DIESEL FUEL (SEE C13940)
THIS DRAWING AND THE INFORMATION CREA TED DA TE CREA TED
HEREIN ARE OUR PROPERTY AND MAY
BE USED BY OTHERS ONLY AS 09/16/11
AUTHORIZED BY US. UNPUBLISHED --
ALL RIGHTS RESERVED UNDER THE
COPYRIGHT LAWS.
ENGINE MODEL DS0H-UFAA68
DRA WING NO . REV
Kevin Kunkler 16SEP11 C134162 A
DS0H-UFAA68
INSTALLATION & OPERATION DATA (I&O)
USA Produced
Basic Engine Description
Engine Manufacturer ......................................................................................................................................................
PU180TI
Ignition Type ......................................................................................................................................................
C ompression (Diesel)
Number of C ylinders ......................................................................................................................................................
10
Bore and Stroke - in (mm) ......................................................................................................................................................
5.04 (128) X 5.59 (142)
Displacement - in³ (L) ......................................................................................................................................................
1115 (18.3)
C ompression Ratio ......................................................................................................................................................
14.6:1
Valves per cylinder
Intake ......................................................................................................................................................
1
Exhaust ......................................................................................................................................................
1
C ombustion System ......................................................................................................................................................
Direct Injection
Engine Type ......................................................................................................................................................
Vee, 4 stroke cycle
Fuel Management C ontrol ......................................................................................................................................................
Mechanical, Inline Pump
Firing Order (C W Rotation) ......................................................................................................................................................
1-6-5-10-2-7-8-3-4-9
Aspiration ......................................................................................................................................................
Twin Turbocharged
C harge Air C ooling Type ......................................................................................................................................................
Raw Water C ooled
Rotation, viewed from front of engine, C lockwise (C W) ......................................................................................................................................................
Standard
Engine C rankcase Vent System ......................................................................................................................................................
C losed
Installation Drawing ......................................................................................................................................................
D665
Weight - lb (kg) ......................................................................................................................................................
3200 (1450)

Power Rating 1470 1760


Nameplate Power - HP (kW) ¹ ......................................................................................................................................................
522 (389.5) 587 (438)

Cooling System - [C051389] 1470 1760


Engine C oolant Heat - Btu/sec (kW) ......................................................................................................................................................
185 (195) 225 (237)
Engine Radiated Heat - Btu/sec (kW) ......................................................................................................................................................
38.6 (40.7) 44.6 (47.1)
Heat Exchanger Minimum Flow
60°F (15°C ) Raw H2O - gal/min (L/min) ......................................................................................................................................................
13 (49.2) 31 (117)
100°F (37°C ) Raw H2O - gal/min (L/min) ......................................................................................................................................................
18 (68.1) 43 (163)
Heat Exchanger Maximum C ooling Raw Water
Inlet Pressure - psi (bar) ......................................................................................................................................................
60 (4.1)
Flow - gal/min (L/min) ......................................................................................................................................................
80 (303)
Typical Engine H2O Operating Temp - °F (°C ) ......................................................................................................................................................
170 (76.7) - 200 (93.3)
Thermostat
Start to Open - °F (°C ) ......................................................................................................................................................
160 (71.1)
Fully Opened - °F (°C ) ......................................................................................................................................................
185 (85)
Engine C oolant C apacity - qt (L) ......................................................................................................................................................
43.3 (41)
C oolant Pressure C ap - lb/in² (kPa) ......................................................................................................................................................
7 (48.3)
Maximum Engine C oolant Temperature - °F (°C ) ......................................................................................................................................................
205 (96.1)
Minimum Engine C oolant Temperature - °F (°C ) ......................................................................................................................................................
160 (71.1)
High C oolant Temp Alarm Switch - °F (°C ) ......................................................................................................................................................
205 (96.1)

Electric System - DC Standard


System Voltage (Nominal) ......................................................................................................................................................
24
Battery C apacity for Ambients Above 32°F (0°C )
Voltage (Nominal)12 ......................................................................................................................................................
12 {C 07633}
Qty. Per Battery Bank ......................................................................................................................................................
2
SAE size per J537 ......................................................................................................................................................
8D
C C A @ 0°F (-18°C ) per J537 ......................................................................................................................................................
1400
Reserve C apacity - Minutes per J537 ......................................................................................................................................................
430
Battery C able C ircuit, Max Resistance - ohm ......................................................................................................................................................
0.0012
Battery C able Minimum Size
0-120 in. C ircuit Length ² ......................................................................................................................................................
00
121-160 in. C ircuit Length ² ......................................................................................................................................................
000
161-200 in. C ircuit Length ² ......................................................................................................................................................
0000
C harging Alternator Maximum Output - Amp, ......................................................................................................................................................
45 {65.26101-7153C }
Starter C ranking Amps, Rolling - @60°F (15°C ) ......................................................................................................................................................
315 {65.26201-7074D}

Page 1 of 2
C 134258 Rev O
* All footnotes are at the bottom of Page 2 C LR 03DEC 20
DS0H-UFAA68
INSTALLATION & OPERATION DATA (I&O)
USA Produced
Exhaust System (Dual Exhaust Outlets) 1470 1760
Exhaust Flow - ft.³/min (m³/min) ......................................................................................................................................................
2631 (74.5) 3069 (86.9)
Exhaust Temperature - °F (°C ) ......................................................................................................................................................
1146 (619) 860 (460)
Maximum Allowable Back Pressure - in H2O (kPa) ......................................................................................................................................................
40 (10) 40 (10)
Minimum Exhaust Pipe Dia. - in (mm) ³ ......................................................................................................................................................
5 (127) 5 (127)

Fuel System 1470 1760


Fuel C onsumption - gal/hr (L/hr) ......................................................................................................................................................
24 (90.8) 29 (110)
Fuel Pressure - lb/in² (kPa) ......................................................................................................................................................
17 (117) - 26 (179)
Minimum Line Size - Supply - in. ......................................................................................................................................................
.75 Schedule 40 Steel Pipe
Pipe Outer Diameter - in (mm) ......................................................................................................................................................
1.05 (26.7)
Minimum Line Size - Return - in. ......................................................................................................................................................
.50 Schedule 40 Steel Pipe
Pipe Outer Diameter - in (mm) ......................................................................................................................................................
0.848 (21.5)
Maximum Allowable Fuel Pump Suction Lift
with clean Filter - in H2O (mH2O) ......................................................................................................................................................
54 (1.4)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - ft (m) ......................................................................................................................................
16 (4.9)
Fuel Filter Micron Size ......................................................................................................................................................
5

Heater System Standard


Engine C oolant Heater
Wattage (Nominal) ......................................................................................................................................................
2500
Voltage - AC , 1 Phase ......................................................................................................................................................
230 (+5%, -10%)
Part Number ......................................................................................................................................................
{C 122194}

Air System 1470 1760


C ombustion Air Flow - ft.³/min (m³/min) ......................................................................................................................................................
1356 (38.4) 1746 (49.4)
Air C leaner ......................................................................................................................................................
Standard Optional
Part Number ......................................................................................................................................................
{C 03244 Qty (2)} {C 03330 Qty 2}
Type ......................................................................................................................................................
Indoor Service Only, C anister,
with Shield Single-Stage
C leaning method ......................................................................................................................................................
Washable Disposable
Air Intake Restriction Maximum Limit
Dirty Air C leaner - in H2O (kPa) ......................................................................................................................................................
14 (3.5) 14 (3.5)
C lean Air C leaner - in H2O (kPa) ......................................................................................................................................................
7 (1.7) 7 (1.7)
Maximum Allowable Temperature (Air To Engine Inlet) - °F (°C ) .....................................................................................................................................................
130 (54.4)

Lubrication System
Oil Pressure - normal - lb/in² (kPa) ......................................................................................................................................................
53 (365) - 89 (614)
Low Oil Pressure Alarm Switch - lb/in² (kPa) ......................................................................................................................................................
11.4 (78.6)
In Pan Oil Temperature - °F (°C ) ......................................................................................................................................................
156 (68.9) - 230 (110)
Total Oil C apacity with Filter - qt (L) ......................................................................................................................................................
34.9 (33)

Lube Oil Heater Optional


Wattage (Nominal) ......................................................................................................................................................
300
Voltage ......................................................................................................................................................
240V (+5%, -10%)
Part Number ......................................................................................................................................................
{C 04560}

Performance 1470 1760


BMEP - lb/in² (kPa) ......................................................................................................................................................
252 (1740) 237 (1630)
Piston Speed - ft/min (m/min) ......................................................................................................................................................
1370 (418) 1640 (500)
Mechanical Noise - dB(A) @ 1m ......................................................................................................................................................
C onsult Factory
Power C urve ......................................................................................................................................................
C 134162

NOTE: This engine is intended for indoor installation or in a weatherproof enclosure. ¹ Derate 3% per every 1000 ft. 304.8m above 300 ft. 91.4m and derate 1%
for every 10°F 5.55 °C above 77°F 25°C. ² Positive and Negative Cables Combined Length. ³ Minimum Exhaust Pipe Diameter for each exhaust outlet is based
on: 15 feet of pipe, one 90° elbow, one Industrial silencer and using half of the published Exhaust Flow. A Back-pressure flow analysis must be performed on
each actual field installed exhaust system to assure engine maximum allowable back pressure is not exceeded. See Exhaust Sizing Calculator on
www.clarkefire.com. { } indicates component reference part number.
Page 2 of 2
C 134258 Rev O
C LR 03DEC 20
CLARKE
Fire Protection Products
DR8 & DS0
ENGINE MATERIALS AND CONSTRUCTION
Air Cleaner Crank Pin Bearings
Type…………………………. Indoor Usage Only Type………………………………One Piece
Oiled Fabric Pleats Material………………………… Steel backed, Lead Bronze
Material……..…..…….………. Surgical Cotton
Aluminum Mesh Crankshaft
Material………………………… Forged Steel
Air Cleaner - Optional Type of Balance…………………Dynamical, Screwed on Balanced
Type…………………………. Canister Weights
Material……………………… Pleated Paper
Housing………………..……… Enclosed Cylinder Block
Type………………………………One Piece w/ Non-Siamese Cyl.
Camshaft Material………………………… Cast Iron
Material…………...….……..… Chromium Molybdenum Steel
Nitride Hardening Cylinder Head
Location…………...….……..… In Block Type…….. ………………… Individual, 2 Valve
Drive……………….………..… Gear Material……………………… Cast Iron
Type of Cam…………..…......…Ground
Cylinder Liners
Charge Air Cooler Type…………..………………Centrifugal Cast, Wet Liner
Type………………………….. Raw Water Cooled - All Material…………………….…Alloy Iron Plateau, Honed
Materials (in contact with raw water)
Tubes………………………….. 90/10 CU/NI (Effective Dec 2013)
Tube Header Plate…………… Brass (ASTM C4621) Heat Exchanger - Standard (Sea Water Compatible)
Inlet/Outlet Covers……………… Bronze (BC6) Type………………………… Tube & Shell
Plumbing…………………………Galvanized Steel Pipe Materials (in contact with raw water)
ISO 15540 Hose (Standard) Tubes…...…………………. Copper
Other Materials (Optional) Shell……………………….. Copper
Headers………….………… Copper
Coolant Pump Electrode…………………… Zinc
Type……… .…………………… Centrifugal
Drive……… ……………………. Belt Injection Pump
Type………………………… In Line
Coolant Thermostat Drive………………………… Gear
Type………………………………Full Blocking
Qty………………………………… 3 Lubrication Cooler
Type………………………… Plate
Cooling Loop (Galvanized)
Tees, Elbows, Pipe……………… Galvanized Steel Lubrication Pump
Ball Valves………………………Brass ASTM B 124 Type………………………… Gear
Solenoid Valve………………… Brass Drive………………………… Gear
Pressure Regulator……………… Bronze
Strainer……………………………Cast Iron (1/2"- 1" Loops) Main Bearings
or Bronze (1.25" - 2" Loops) Type..………………………. Precision Half Shells
Material…………………….. Steel Backed, Lead Bronze
Cooling Loop (Sea Water)
Tees, Elbows, Pipe……………… 316 Stainless Steel Piston
Ball Valves………………………316 Stainless Steel Type and Material…………. Aluminum Alloy with Reinforced/Top Groove
Solenoid Valve………………… 316 Stainless Steel Cooling……………………… Oil Jet Spray
Pressure Regulator/Strainer……Cast Brass ASTM B176 C87800
Piston Pin
Cooling Loop (Sea Water) Type ………………………. Full Floating
Tees, Elbows, Pipe……………… 316 Stainless Steel
Ball Valves………………………316 Stainless Steel Piston Rings
Solenoid Valve………………… 316 Stainless Steel Number/Piston…………….. 3
Pressure Regulator/Strainer……316 Stainless Steel Top………………………….. Keystone Barrel Faced-
Hard Chrome Coated
Connecting Rod Second …………………… Tapered Cast Iron
Type………………………………One Piece, Diagonally Split Hard Chrome Coated
Material……………………………
Die Forged Steel Third………………………… Double Rail Type
with Expander Spring

C134774 revC
Emissions Data Not Available

Note:

Emissions data is not available for the following engines series:


KA4H, CJ4H, DP6H, DQ6H, DR8H, DS0H, DS0R and DT2H, JU6H-UFAA/KAPG,
JU6H-UFAA/KAQ8, JU6H-UFAA/KAS0, JU6R-UFAA/KAPF, JU6R-
UFAA/KAQ7, JU6R-UFAA/KAS9, JW6H-UFAA60

For installations requiring emissions requirements please look to use the following
series engines:
JU4H/R, JU6H/R, JW6H, and JX6H

C135589 RevF
DS0H-UFAA68
FIRE PUMP DRIVER

NOISE DATA
Mechanical Engine Noise *
Octave Band

RPM BHP OVERALL 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz 16k Hz


dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
1470 522 113.00 0.00 74.50 83.50 100.70 104.30 108.90 107.10 102.50 101.70 0.00
1760 587 114.00 0.00 75.50 84.50 101.70 105.30 109.90 108.10 103.50 102.70 0.00

Raw Exhaust Engine Noise **


Octave Band

RPM BHP OVERALL 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz 16k Hz


dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
1470-1760 522-587 118.50 0.00 80.00 89.00 106.20 109.80 114.40 112.60 108.00 107.20 0.00

* Values above are provided at 3.3ft (1m) from engine block and do not include the raw exhaust noise.
** Values above are provided at 23ft (7m), 90° horizontal, from a vertical exhaust outlet and does not include noise created mechanically by the engine.
The above data reflects nominal values for a typical engine of this model, speed and power in a free-field environment, tested at a no-load condition.
Installation specifics such as background noise level and amplification of noise levels from reflecting off of surrounding objects, will affect the overall noise
levels observed. As a result of this, Clarke makes no guarantees to the above levels in an actual installation.

C135030 Rev E 07Oct19 DSP