MR-2100/MR-2200 Features
Intelligent Addressable Fire Alarm • Listed to UL 864, 9th edition
Control Panels • MR-2100 provides a Single Addressable Input Signaling
Line Circuit (SLC) for up to 198 Addressable Devices
• MR-2200 provides Dual Addressable Input Signaling
Line Circuits for up to 396 Addressable Devices
• SLCs are selectable for either Class A (Style 6) or Class
B (Style 4) operation
• Two Notification Appliance Circuits (NACs), Class A
(Style Z) or Class B (Style Y); expandable to eight NACs
with optional MRNC2 modules
• Four programmable functions relays, Form C; expandable
to sixteen relays with MRRL4 modules
• Programmable cross-zoning functions, day/night mode,
and selective control operations
• Two aux. power outputs, 500 mA @ 24 VDC each
• 6.0 A Power supply with integral battery charger provides
2.5 A for NACs and Auxiliary Outputs; Expandable to
provide up to 7 A NAC Current
• Four additional communications ports for Dialer, PC
Interface, Voice Evacuation System, and Remote
Annunciators
• Optional Style 7 (DCLR) MR network peer-to-peer
MR-2100/MR-2200 Fire Alarm Control Panel communications
(shown with optional LED modules) • LCD/LED system status display with optional MRLD8
LED zone display modules (required for ULC listed
Description applications)
Secutron's MR-2100 and MR-2200 intelligent addressable • Surface/flush mount cabinet with dead front construction
fire alarm control panels provide flexible and cost effective allows up to 12 Ah batteries internally mounted
operation to satisfy system requirements for both economy • Battery charger is capable of charging up to 35 Ah
and capability. Their modular design assures that as system mounted in an external battery cabinet
needs and applicable codes evolve, fire alarm control panel
functions can be updated as required. • Cabinet doors are removable for easy installation
• Terminal blocks are removable for easy wiring
Optional networking modules allows the MR-2100 and
MR-2200 to be connected to a Secutron network to provide • Operating program and database can both be uploaded/
additional input circuits, visual zones, programmable downloaded using a Windows® based PC with Secutron
notification appliance (bell) circuits, and relays. Up to 254 Programming Software
control and annunciator units can be networked together. The • Non-volatile event history log stores 1000+ events
network is a DCLR (Data Communications Link, Redundant)
configuration loop.
The MR-2100 models provide a single addressable input Programming the MR-2100/MR-2200 consists of two
Signaling Line Circuit for support of up to 198 addressable convenient and easy operations. Input circuit programming
devices; up to 99 detectors and up to 99 control/monitor and special features (such as cross zoning functions, day/
modules. night mode, selective control operations, etc.) is performed
from an externally generated database produced on a
The MR-2200 models provide two SLCs for support of Windows® based PC. System parameters and control panel
198 devices on each allowing a total capacity of up to 396 display and operation functions are conveniently programmed
addressable devices; up to 198 detectors and up to 198 from the on board LCD and keypad.
control/monitor modules total.
Option modules are available and can be conveniently field
installed. Modules are available for: additional NAC output
circuits & function relays, local LED annunciation, additional MEA
approved
NAC power, and Central Station (DACT) or Remote Station
(DACT or CITY Module) connection. S6619 S6619 7135-1656:106 352-03-E
7170-1656:117
The panel local sounder will beep once when a valid key is Auxiliary Outputs
pressed and beep three times if an invalid or unavailable key Two auxiliary power outputs are provided, each rated for 500
is pressed. Key presses are recorded in the history log. mA at a nominal 24 VDC, filtered and regulated.
AC
1 2 3 ENTER
Power Supply and Expansion Transformer
MONITOR
4 5 6 CLEAR Each MR-2100 / MR-2200 fire alarm control panel is shipped
with a 120 VAC / 240 VAC transformer. Total NAC power
User Assigned
BYPASS
7 8 9
can be increased by adding a second transformer, MR-XPS.
HOME
GROUND FAULT
During normal conditions the display is the main menu Both the outer door and dead front doors are removable.
which includes the date and a 24 hour clock. During alarm The hardware plate holds the main printed circuit board
conditions, the first or last (selectable) events of highest and transformer(s). This enclosure holds two transformers,
priority will be displayed instead of the main menu. A up to three NAC or Relay expander modules, and one
status summary screen lists the number of active alarm, communicator module.
supervisory, or trouble events indicating “SYSTEM OFF
NORMAL.” The backbox is included with the fire alarm control panel and
includes an outer lip around the perimeter to provide a built in
trim for semi-flush mounting applications. The door conceals
the outer lip and provides a neat and clean appearance for
surface mounted box applications.
Peer-to-Peer Networking
MR-2100/2200 control panels can be networked to other
control units for up to a total of 254 network members, each
using Style 7 (DCLR) loop communications. One control unit
is designated as the master control unit for the network and
diagnostics can be done at any control unit.
Mechanical
Overall Dimensions with Door 16-7/8” W x 29-1/2” H x 5-1/4” D (429 mm x 749 mm x 133 mm) [see page 5 for mounting box detail]
Environmental
Temperature Range 32° to 120°F (0° to 49° C)
Humidity Range Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Signaling Line Circuit Ratings
Voltage 24 VDC nominal, 27.5 VDC maximum
MR-2100, Single SLC: 198 total, 99 detector, 99 control/monitor modules
Max. number of devices
MR-2200, Dual SLCs: 396 total, 198 detectors, 198 control/monitor modules
Compatible devices Refer to list on page 5
Maximum line length 3045 m (10,000 ft) (12 AWG, 3.31 mm2)
Available as Style 6 (Class A) or Style 4 ( Class B); T-tapping is allowed with Style 4 (Class B) connections
Operation modes
only
Notification Appliance Circuit Output Circuits, Standard and Expansion NACs
NAC Output Ratings 2 A maximum per NAC; 24 V full wave rectified DC output; power limited
NAC Current, Standard with Total of NACs + Auxiliary Power = 2.5 A maximum
One Transformer (if Aux. Power Total = 500 mA; NAC power = 2 A maximum)
Total NAC current = 7 A maximum
NAC Current with Optional
Total of NACs + Auxiliary Power = 8 A maximum
Transformer
(optional transformer MR12VAC or MR24VAC)
Function Relay Output Circuits, Standard and Expansion Relays
All Relays 2 A @ 30 VDC resistive; Form C contacts; requires power limited source
Power Output Circuits
Auxiliary Power Outputs Each output is rated 500 mA @ 24 VDC, filtered, regulated, and power limited; maximum ripple voltage
(two outputs) = 600 mVpp
Battery Information
Battery Charger current limited float charger for sealed lead acid batteries
Float Charge 27.5 VDC
Charging Current 2.7 A maximum, no auxiliary loads; 1.7 A nominal with 0.5 A on each Auxiliary output
12 Ah maximum size internal to cabinet;
Maximum Battery Capacity
35 Ah maximum size allowed, requires model MR2978 External Battery Cabinet
Communications Ports
Fixed baud rate @ 4800 bps; for use with MR-2614 or MR-2644 Annunciators (refer to individual product
ANN (annunciator port)
Installation Instructions for capacities and wiring distances)
Fixed baud rate @ 9600 bps; 20 ft (6m) maximum distance; for use with MV-2700 Voice Evacuation
RS-232-2 (MV-2700 or GRID)
System or GRID Graphical PC Display
CON4 (Dialer/City Module Port) Fixed baud rate @ 4800 bps; for use with MRDL Digital Communicator Module or MRCTYB City Module
J1 (Service port or serial printer Fixed baud rate @ 9600 bps; 6 m (20 ft) maximum distance; for use with Service/Programming PC
port) (using Windows 95 or 98); or for serial input printer
Network Ports
Standard Protocol: 10km (33,000 feet; 6.2 miles) maximum distance between nodes, minimum 28
COM1, COM2 AWG wires (0.081 mm2);
(Secutron MR peer to peer Total panel capacity varies with programmable baud rate: up to 254 panels with 9600, 4800, and
network, redundant DCLR) 2400; up to 200 panels at 1200
RS-232 Protocol: up to 20 m (66 ft), typically for connection to external modem
Baud Rate Maximum Capacitance Maximum Network Nodes
Network Wiring Parameters 9600 100 nF 254
(maximum line resistance = 4800 220 nF 254
680 ohms) 2400 470 nF 254
1200 680 nF 200
4"
3" (76 mm) (102 mm)
5-1/4"
(133 mm)
29"
21-3/4" (740 mm)
27-1/2"
(552 mm)
(699 mm)
26-1/2"
(673 mm) 1-1/4"
(32 mm)
8-1/2"
(216 mm)
• Alarm (Without smoke detector verification) Each of the indicating circuits may be configured for
• Verified Alarm (With smoke detector one of the following modes of operation:
verification)
• Waterflow Alarm (Water flow sensors) • Silenceable Signal
• Sprinkler Alarm (Sprinkler flow sensors) • Non-Silenceable Signal
• Latching Supervisory • Silenceable Strobe
• Non-Latching Supervisory • Non-Sileneceable Strobe
• Monitor (non-latching input used mainly for
correlating to a relay circuit) The MR-2300 has built-in sync protocols for the
following strobe manufacturers; Secutron, Amseco,
• Trouble-Only (for monitoring a trouble condition System Sensor, Gentex, Faraday and Wheelock.
from an external device)
MR-2306-DDR Six Zone LCD Display Fire Alarm Control MR-2312-DDR Twelve Zone LCD Display Fire Alarm Control
Panel Panel with UDACT/Digital Communicator
The MR-2306-DDR is equipped with six Class “B” (Style “B”) The MR-2312-DDR is equipped with twelve Class “B” (Style “B”)
initiating circuits and two Class “B” (Style “Y”) indicating circuits initiating circuits and four Class “B” (Style “Y”) indicating circuits
rated @ 1.7 Amps maximum. (Total of 5 Amps) The MR-2306- @ 1.7 Amps maximum. (Total of 5 Amps). Two MR-2300-A Six
DDR is equipped with a built-in UDACT/Digital Communicator. Initiating Circuit Class A Converter Module may be used for Class
One MR-2300-A Six Initiating Circuit Class “A” Converter Modules “A” (Style “D”) wiring of the initiating circuits. One MR-2300-NC4
may be used for Class “A” (Style “D”) wiring of the initiating Four Indicating Circuit Class “A” Converter Module may be used
circuits. One MR-2300-NC2 Two Indicating Circuit Class “A” for Class “A” (Style “Z”) wiring of the Indicating circuits. The
Converter Module may be used for Class “A” (Style “Z”) wiring MR-2312-DDR has a built-in UDACT/Digital Communicator and
of the indicating circuits. The cabinet will support up to 12 AH the cabinet will support up to 12 AH batteries. The panel can
batteries. The panels can be semi-flush mounted with the optional be semi-flush mounted with the optional MR-2312-FT trim ring.
MR-2300TRB trim ring. Note: Not ULC listed. Note: Not ULC listed.
Dimensions Dimensions
MR-2306-DDR: 20”H x 14.5”W x 4.5”D MR-2312-DDR: 26”H x 14.5”W x 4.5”D
MR-2306-FT: 22.5”H x 17”W MR-2312-FT: 28.5”H x 17”W
MR-2300-A Six Initiating Circuit Class “A” Converter MR-2306-R6/MR-2312-R12 Relay Circuit Adder
Module Modules
The MR-2300-A converts six Class “B” (Style “B” initiating The MR-2306-R6 provides six configurable relay circuits,
circuits on the MR-2300 main board to Class “A” (Style “D”) rated @ 28 VDC, 1 amp (resistive). The MR-2312-R12
circuits. The MR-2300-A is equipped with wire leads to provides twelve Form C configurable relay circuits, rated @
connect to the MR-2300 main board. It mounts to the right 28 VDC, 1 amp (resistive). On both models each circuit can
of the main board Class “B” (Style “B”) initiating circuits. be configured as a Normally Open (N.O.) or Normally Closed
Two MR-2300-A modules are required to convert all twelve (N.C.) contact. Each relay is equipped with an LED that is lit
initiating circuits on an MR-2312 series panel. when the relay is energized. The relays can be configured
as relay per zone (1 to 1), Common on Alarm, Common on
Supervisory or programmable for logical or adjacent zone
configuration. An adjacent zone configuration will turn on
adjacent zone when configured zone is active. A chaining
configuration allows for multiple relays to turn on.
4 to 12 AH Current Consumption
Indicating Circuits Model Standby Alarm
Power limited / 24VDC unfiltered / 1.7A @ 49°C per MR-2306-DDR 142 mA (112 mA*) 312 mA (282 mA*)
circuit. Maximum 5 Amps. MR-2312-DDR 174mA (104 mA*) 444mA (394 mA*)
Aux supply (non resetable)
MR-2312-LDR 164mA (104 mA*) 424mA (364 mA*)
Power limited / 22.3VDC regulated / 500mA max
4-wire smoke supply (resetable)
Power limited/22.3VDC regulated / 300mA max
Ordering Information
Model Description
Control Units
MR-2306-DDR* Six Zone LCD Display Fire Alarm Control Unit with built-in UDACT/Digital Communicator
MR-2312-DDR* Twelve Zone LCD Display Fire Alarm Control Unit with built-in UDACT/Digital Communicator
MR-2312-LDR Twelve Zone LED Display Fire Alarm Control Unit with built-in UDACT/Digital Communicator
Remote Annunciators and modules
MR-2300-LCDR Remote LCD Annunciator (Red enclosure) (Note: ULC Listed as an Ancillary Device.)
MR-2300-LCDW Remote LCD Annunciator (White enclosure) (Note: ULC Listed as an Ancillary Device.)
MR-2306-ATR Eight zone Remote LED Annunciator (Note: ULC Listed as an Ancillary Device.)
MR-2312-ATR Sixteen zone Remote LED Annunciator (Note: ULC Listed as an Ancillary Device.)
RAM-1016TZDS Sixteen zone Remote LED Annunciator with individual Trouble LEDs
MR-2312-SR12 Remote Relay Module with red enclosure
MMX-BB-1001R Red enclosure for RAM-1016TZDS
Adder Modules
MR-2300-A Six Initiating Circuit Class “A” Converter Module
MR-2300-NC4 Four Indicating Circuit Class “A” Converter Module
MR-2300-NC2 Two Indicating Circuit Class “A” Converter Module
MR-2306-R6 Six Relay Circuit Adder Module
MR-2312-R12 Twelve Relay Circuit Adder Module
MR-2300-PR Polarity Reversal/City Tie Module
MR-2300-X Active End-of-Line Resistor
Accessories
MR-2306-FT Black Semi-Flush Trim Ring for MR-2306 enclosures
MR-2312-FT Black Universal Semi-Flush Trim Ring for MR-2312 enclosures
CFG-300 Configuration Tool for MR-2312-LCDR
UIMA Universal Programming Tool
* Note: Not ULC Listed
MR-2644 Features
Remote LCD Annunciator • Designed to meet the requirements of NFPA 72
RXD
TXD
+ - - Standby Current Draw 30 mA
Maximum/Alarm Current 70 mA
MR-2644
+ Environmental Specifications
- Operating Temperatures 32°F – 120°F / 0°C – 49°C
RX 85% RH non-condensing
Humidity
TX (max.)
Physical Dimensions
MR-2100 / MR-2200 Wiring Diagram (Powered by 4.5” (H) x 10” (W)
external PS) MR-2644 (trim plate) 10.2cm (H) x 25.4cm (W)
MR-2100 / MR-2200
AUX ANN EXTERNAL 4.5” (H) x 10” (W) x 2½” (H)
POWER POWER SUPPLY MR-2644-SM
10.2cm (H) x 25.4cm (W) x 6.4cm (H)
(AUX)
RXD
TXD
+ - - + -
Connections
MR-2644
Maximum Distance 9000 ft. (2700m) 12 AWG
+
Communication/ 12 to 22 AWG non-shielded twisted
- Power Wire pair (two twisted pair required)
RX
TX
RX
• The external power supply must be mounted no further
COM
LINK 3 than 10ft (3m) from the FACP.
TX
GND
* To connect the MR-2644 annunciator to a MR-2900 FACP, a
communications board must be installed in the MR-2900 (Model
#: MR-2109-3).
MR-2900 Wiring Diagram (Powered by external PS)
EXTERNAL
POWER SUPPLY
(AUX)
+ -
Ordering Information
MR-2900
Model Description
+ MR-2644R MR-2644 LCD annunciator, flush mount,
AUX 1
- Red
MR-2644
+ MR-2644G MR-2644 LCD annunciator, flush mount,
AUX 2
+ - White
-
MR-2644-SMR Surface mount backbox for MR-2644,
RX COM Red
LINK 3
TX
GND
MR-2644-SMG Surface mount backbox for MR-2644,
White
MRI-M500 SERIES
Intelligent Modules Features
• Designed to meet a wide range of applications
• SEMS screws for easy wiring
• Panel controlled status LED (except MRI-M501M)
• Analog communications
• Rotary address switches (except MRI-M500X)
• Low standby current
• Mounts in 4” square junction box
The small size of the MRI-M501M allows it to fit inside S6620 S6620 7300-1656:121 (MRI-M500R, MRI-M500S)
227-03-E
devices or junction boxes behind devices. (MRI-M500DM)
Shipping Weight
MRI-M500DM Specifications
M501M: 1.2 oz (37g) Others: 6.3 oz (196g)
Standby Current
750 µA max. @ 24 VDC (one communication every 5 sec. with
MRI-M500M, MRI-M500S, MRI-M501M Specifications 47k EOL)
Standby Current Alarm Current
400 µA max @ 24 VDC (one communication every 5 sec. with 970 µA max. (one communication every 5 sec.) 6 mA (with LED
47k EOL) 550 µA max @ 24 VDC (one communication every 5 latched on)
sec. with EOL<1k) 5.5 mA (with LED latched on)
End-of-Line Resistance
End-of-Line Resistance 47 kΩ (two included)
47 kΩ (included)
MRI-M500X Specifications
MRI-M500R Specifications Standby Current
Standby Current 450 µA max
300 µA @ 24 VDC (one communication every 5 sec. with LED Isolation Current
enabled)
5 mA max
LED Current
Fault Detection Delay
5.5 mA (with LED latched on) 250 ms min.
Relay Contact Ratings Fault Detection Threshold
3.0 A @ 30 VDC resistive 4 Volts
0.9 A @ 110 VDC resistive
Line Restoration Threshold
0.9 A @ 125 VAC resistive
0.5 A @ 125 VAC inductive (PF=.35) 7 Volts
0.7 A @ 75 VAC inductive (PF=.35)
Ordering Information
Model Description
MRI-M500M Monitor Module
MRI-M500R Relay Module
MRI-M500S Supervised Control Module
MRI-M501M Mini Monitor Module
MRI-501MA Mini Monitor Module (ULC listed for Canada)
MRI-M502M Zone Interface Module
MRI-M500X Isolator Module
MRI-M500DM Dual Input Monitor Module
Add suffix "A" for Canadian model.
Description
Secutron's low profile addressable plug-in smoke
and heat detectors with integral communications
provide features that surpass conventional detectors.
Sensitivity is continuously monitored and reported
to the panel where the desired detector sensitivity Model MRI-5251B uses an innovative thermistor
can be programmed. Point ID capability allows each sensing circuit to produce 135°F fixed temperature
detector’s address to be set with decade address detection in a low profile package. These thermal
switches, providing exact detector locations for detectors provide cost effective, intelligent property
selective maintenance when chamber contamination protection in a variety of applications.
reaches an unacceptable level.
Model MRI-5251RB provides both 135°F fixed
Model MRI-2251B photoelectric smoke detector and rate-of-rise thermal detection. These thermal
provides a unique optical sensing chamber that senses detectors provide cost effective, intelligent property
smoke produced by a wide range of combustion protection in a variety of applications.
sources.
Model MRI-5251H provides 190°F (88°C) fixed
Model MRI-2251BR is a remote test capable detector temperature detection for high temperature applications.
for use with DNR(W) duct smoke detectors.
Model MRI-2251TB adds dual electronic thermistors
to the MRI-2251B to provide 135°F (57°C) fixed
temperature thermal sensing.
Model MRI-2251TMB is a photoelectric smoke detector
with supplementary 135°F thermal. Also known as
Acclimate™, it uses advanced on-board software
to combine the signals from the photo and thermal APPROVED
Shipping Weight 9 levels: 0.02, 0.03, 0.05, 0.10, 0.20, 0.50, 1.00, 1.50, 2.00%/ft.
obscuration
Heat: 4.8 oz. (137 g) (0.06, 0.10, 0.16, 0.33, 0.66, 1.65, 3.24, 4.85, 6.41%/m obscuration)
Photo/Photo with Heat: 5.2 oz. (147 g)
Ion: 5.4 oz. (154 g) Drift Compensation (PinnacleTM)
Pinnacle: 5.6ox. (159 g) High sensitivity maintenance alert signal
Relative Humidity Low sensitivity maintenance alert signal
Maintenance urgent signal
10% - 93% noncondensing
Ordering Information
Addressable Detectors
Model Description
MRI-2251B Intelligent Photoelectric Detector
MRI-2251BR Intelligent Photoelectric Detector. Remote test capable. For use with DNR(W) duct detectors.
MRI-2251TB Intelligent Photoelectric Detector with 135°F Fixed Temperature Heat Detector
MRI-2251TMB Intelligent AcclimateTM Multicriteria Smoke Detector
MRI-5251B Intelligent Heat Detector, 135°F fixed temperature
MRI-5251RB Intelligent Heat Detector, 135°F fixed temperature with rate-of-rise detection
MRI-5251H Intelligent High Temperature Heat Detector, 190°F fixed temperature
7251 Intelligent PinnacleTM Laser Smoke Detector
Add suffix "A" for Canadian model.
Detector Base
Model Description
B210LP* Flanged Mounting Base; mounts on single gang box; 3-½” and 4” octagonal box; and 4”
square box with 3” mud ring
* Refer to Catalog Number 4001 for additional compatible B200 Series bases.
Features
• Two and four wire models
• UL listed
Description
The SD Series photoelectric smoke detectors are All SD Series smoke detectors come equipped with
engineered to meet strict UL fire safety codes and a sleek low-profile design and durable sensor head.
effectively respond to a wide spectrum of fires. The Utilizing advanced detection and discrimination
SD Series smoke detectors are suitable for use in algorithms, the SD Series smoke detectors provide
commercial, industrial, institutional and residential quality and reliability.
occupancies. The sleek low-profile design of the
detectors emphasizes ease of installation and field
maintenance. Installation Diagram
The SD Series consists of six models:
SD-2WP / SD-2WT / SW-2WP-LED / SD-2WT-LED
The SD-2WP is a two-wire photoelectric smoke
detector for use with electrically compatible fire
alarm control units. The SD-2WT is a two-wire
smoke detector that uses photoelectric technology
in conjunction with a fixed temperature heat sensor
to further extend its sensing capabilities. Additional
two wire models (SD-2WP-LED and SD-2WT-LED)
are available with a remote LED output.
SD-4WP / SD-4WT
The SD-4WP is a four-wire photoelectric smoke
detector. The SD-4WT is a four-wire photoelectric
smoke detector with a fixed temperature heat
sensor.
S6295
5177
CATALOG NUMBER
NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
Electrical Specifications
Standby Alarm Surge Star-Up Permissible
Heat Voltage Alarm
Model 2/4 wire Current Current Current Time Current Frequency
Sensor DC contact
(Max.) (Max.) (Max.) (Max.) (Max.)
SD-4WT 4 135°F 12/24V 370μA 35mA 60 80mA 3-5 Form A
Seconds Seconds
SD-4WP 4 12/24V 370μA 35mA 60 80mA 3-5 Form A
Seconds Seconds
SD-2WT 2 135°F 12~28V 150μA 70mA 160μA 60 80mA 3-5 —
Seconds Seconds
SD-2WP 2 12~28V 150μA 70mA 160μA 60 80mA 3-5 —
Seconds Seconds
SD-2WT-LED 2 135°F 12~28V 150μA 70mA 160μA 60 80mA 3-5 —
Seconds Seconds
SD-2WP-LED 2 12~28V 150μA 70mA 160μA 60 80mA 3-5 —
Seconds Seconds
Ordering Information
Model Description
SD-2WP 2-wire photoelectric smoke detector. Includes 4-inch base.
SD-2WT 2-wire photoelectric smoke detector with heat sensor. Includes 4-inch base.
SD-2WP-LED 2-wire photoelectric smoke detector with heat sensor and remote LED output. Includes 4-inch base
SD-2WT-LED 2-wire photoelectric smoke detector with heat sensor and remote LED output. Includes 4-inch base.
SD-4WP 4-wire photoelectric smoke detector c/w 4-inch base
SD-4WT 4-wire photoelectric smoke detector with heat sensor c/w 4-inch base
Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: (905) 660-4655
Fax: (905) 660-4113
Description
System Sensor’s BEAM1224 is uniquely suited for BEAM1224 has four standard sensitivity selections, along
protecting open areas with high ceilings — areas where with two Acclimate™ settings (adjustable sensitivity).
other methods of smoke detection are difficult to install When one of the two Acclimate settings is selected,
and maintain. the detector will automatically adjust its sensitivity using
advanced software algorithms to choose the optimum
The BEAM1224 is a four-wire conventional reflected
sensitivity for the specific environment.
beam smoke detector, which is uniquely suited for
protecting open areas with high ceilings, where other BEAM1224S is also equipped with an integral sensitivity
methods of smoke detection are difficult to install and test feature, which consists of a test filter attached to a
maintain. It is to be used with UL Listed compatible servo motor inside the detector optics. When the remote
control panels only. An advantage of this single-ended test station RTS451 is used, the motor is activated and
reflective design is that it is much easier to install than moves the filter into the pathway of the light beam, to
the dual-ended projected beam detectors. Alignment test the detector’s sensitivity. This integral sensitivity test
is quickly accomplished via an optical sight and a two- feature allows the user to quickly and easily meet the
digit signal strength meter incorporated into the product. annual maintenance and test requirements of NFPA 72.
Another advantage of the BEAM1224 is that it is listed for
operation in temperatures ranging from –22°F to 131°F.
This means it can be used in open areas to provide early
warning in environments where temperature extremes may
exceed the capability of other types of smoke detectors.
BEAM1224 consists of a transmitter/receiver unit and a
reflector. When smoke enters the area between the unit
and the reflector, the smoke causes a reduction in the
signal. When the smoke level reaches the predetermined MEA
approved
threshold, an alarm is activated. APPROVED
MRM-710ADU Features
Intelligent Manual Station • Dual Action
• Key resettable
• Plastic breakrod
Description Specifications
Secutron’s MRM-710ADU provide manual fire reporting. The manual station shall be Secutron's MRM-710ADU.
This high quality, die-cast metal intelligent fire alarm Operating instructions shall be in raised English
manual station is a dual action unit with a permanently lettering and the unit shall be constructed of high
attached addressable module. The intelligent manual quality die-cast metal and finished in red enamel
station has a pair of rotary decimal switches which paint to provide quick identification. Pulling the handle
allows for two digit address setting. Pulling the handle shall initiate immediate operation of the intelligent
initiates the operation of the addressable module. addressable module. All manual fire alarm stations
The MRM-710ADU is available with CAT-30 keys and shall be installed as per the specific requirements
mount on a standard single gang backbox, Secutron outlined in the UL codes, as well as all other applicable
model MRM-700 interior surface metal backbox, or national or local codes. Final acceptance is subject to
MRM-700WP weather proof backbox. the local authority having jurisdiction.
Operation
The MRM-710ADU Dual Action Intelligent Manual
Station is operated by pushing the bar labelled “PUSH
BAR” and then pulling down the handle marked “PULL
HANDLE”. The MRM-710ADU is reset by opening the
station with the key, placing the handle in the normal
upright position and re-locking the station.
BLK
- BLACK
0-9
RED
ADDRESSABLE MODULE
+ RED
~
NOTES:
1. WIRE AS SHOWN SO THAT SUPERVISION
OF CONNECTIONS IS MAINTAINED.
ADD.SW
PUR
10-99
Ordering Information
Model Description
MRM-710ADU Intelligent Addressable Key Resettable Dual Action Manual Station
MRM-700 MRM-700U Series Interior Surface Mount Backbox, Red Finish
MRM-700WP MRM-700U Series Weatherproof Surface Mount Backbox, Red Finish
MCP5A
Intelligent Call Point
Features
• Anti-Tamper facility
• Backward compatibility
Description
The MCP5A Intelligent Call Point is designed to be used In addition the MCP5A call point helps preserve the
with Secutron's Intelligent Fire Alarm Control Panels. integrity of the overall system as illegal removal of the
It is a dedicated addressable callpoint for installation product lid will result in the call point operating and the
on a two wire communication circuit providing both system going into alarm.
signalling of alarm to the monitoring control panel and The MCP5A may be installed as either a flush or surface
local LED indication of activation. mounted device in a normal internal environment. It
The MCP5A provides a unique ‘plug and play’concept is not intended for use in an externally exposed or
designed specifically to reduce installation time. The hazardous location.
unit utilizes a special terminal block, where all initial The MCP5A may be flush mounted to compatible
installation cabling is terminated. This terminal block is electrical boxes.
then simply connected to the back of the MCP. Simple,
but effective, with no re-termination required and no
time wasted.
Dimensions
72mm
89mm 27.5mm 32mm 60mm
93mm
72mm
Mechanical Specifications Wiring Diagram
Material
PC/ABS
Weight
110g Flush
160g Surface
Color
Red, Ral301
Ordering Information
Model Description
MCP5A-RP01FG-K013-01 Intelligent Call Point
SR2T Surface mount red backbox
KG1 x 50 Call Point Break Glass. Package of 50.
SEC14-355 Secutron branded Call Point Break Glass. Package of 50.
SEC14-355SPAN Secutron branded Call Point Break Glass, Spanish. Package of 50.
• Pigtail connection
• Red finish
Description Dimensions
GASKET FOR
MOUNTING
ON SURFACE OR
STRIKER WEATHERPROOF
BACKBOX
HEX-BOLT
GONG HORIZONTAL AXIS
NO MORE NO MORE
THAN -6dB THAN -6dB
BB-206WP
WEATHERPROOF
BACKBOX
5"
Specifications
Model Description Voltage Rated Current Sound Level at 10 ft. dB
BL-6B 6” Motorized Steel Bell 24 VDC 20 mA 85
BL-10B 10” Motorized Steel Bell 24 VDC 20 mA 85
Ordering Informtion
Model Description
BL-6B 6” Motorized Steel Bell
BL-10B 10” Motorized Steel Bell
Accessories
BB-206WP Weatherproof Backbox
MP-101 Universal Mounting Plate
M-1995 Yard Hood
SG-206 Grill for 6” Bell Boxes
SG-206S Brushed Stainless Steel Grill for 6” Bell Backbox
SG-210 Grill for 10” Bell Backbox
SG-210S Brushed Stainless Steel Grill for 10” Backbox
Features
• UL and C-UL listed
• 12 VDC with 15, 35 or 60 cd settings
• 24 VDC with 15, 35, 60, 75, 95 or 110 cd settings
• 6 distinct candela settings
• Candela selection view window
• 15/75 ADA compliant on 60cd setting
• 33 sound output settings
• Horn or chime sound output
• Pre-wire back plate
• Universal back plate mounting (single gang, double
gang, octagon, or 4” square)
• Single screw mounting
• For indoor applications
5269
CATALOG NUMBER
NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
Installation
Selector Switch
5 (127)
2 5/16 (59)
High voltage may be present inside the light assembly even though power is not
connected. If access to the component board is required (removal or replacement), the
capacitor must be discharged by touching a wire to both ends of the flash tube.
DO NOT attempt to touch or move the assembly until the capacitor has been
discharged.
Output Reg. 12 VDC Reg. 12 FWR Reg. 24 VDC Reg. 24 FWR 1 ON - Non-temporal
15cd 116 152 62 99 1 OFF - Temporal 1 2 3 4 5 6 7 8
CAT. 5269
NOT TO BE USED FOR INSTALLATION PURPOSES. page 2 of 4
Specifications
Non-Temporal Horn Current
dBA Anechoic
dBA Reverberant
Max. RMS Operating Current Ratings per
Ratings per UL464
(mA RMS Current) CAN/ULC S525
Pattern Volume (dBA @ 10 ft.)
(dBA @ 10 ft.)
Reg 12 Reg 12 Reg 24 Reg 24 Reg 12 Reg 24 Reg 12 Reg 24
VDC FWR VDC FWR VDC/FWR VDC/FWR VDC/FWR VDC/FWR
High 119 79 87 125 87 87 99 100
2400 Hz Mid 44 46 28 74 82 82 94 96
Low 30 30 18 41 79 80 92 92
High 118 77 81 121 86 87 100 100
Electro-Mechanical Mid 43 43 26 67 82 84 96 97
Low 27 29 16 36 79 80 93 93
High 146 125 78 148 86 86 101 102
Broadband Mid 41 63 26 64 81 82 96 98
Low 28 40 16 39 77 79 94 95
High 27 35 21 27 70 70 86 86
Chime Mid 11 15 8 13 62 62 79 80
Low 9 11 7 12 58 57 75 75
CAT. 5269
NOT TO BE USED FOR INSTALLATION PURPOSES. page 3 of 4
Wiring Diagram
FHS-340
(FHS-340) FHS-340
SDM-240
SDM-240
SDM-240
Ordering Information
Model Number Description
FHS-340R Wall Mount Horn/Strobe, Red
FHS-340W Wall Mount Horn/Strobe, White