Concrete Column Design Based On ACI 318-19: Input Data & Design Summary

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
70 views3 pages

Concrete Column Design Based On ACI 318-19: Input Data & Design Summary

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

PROJECT : PAGE :

CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Concrete Column Design Based on ACI 318-19

INPUT DATA & DESIGN SUMMARY


CONCRETE STRENGTH fc' = 4 ksi, (28 MPa)
REBAR YIELD STRESS fy = 60 ksi, (414 MPa)
SECTION SIZE Cx = 20 in, (508 mm)
Cy = 12 in, (305 mm)

FACTORED AXIAL LOAD Pu = 500 kip, (2224 kN), (227 Tn)


FACTORED MAGNIFIED MOMENT Mu,x = 200 ft-kips, (271 kN-m)
Mu,y = 100 ft-kips, (136 kN-m)
FACTORED SHEAR LOAD Vu,x = 60 kip, (267 kN), (027 Tn) THE COLUMN DESIGN IS ADEQUATE.
= Vu,y 40 kip, (178 kN), (018 Tn)
COLUMN VERT. REINFORCEMENT 5 # 6 at x dir.
(Total12 # 6)
3 # 6 at y dir.
LATERAL REINF. OPTION (0=Spirals, 1=Ties) 1 Ties
LATERAL REINFORCEMENT 4 legs,# 4 @ 12 in. (305 mm), o.c., at x dir.
3 legs,# 4 @ 12 in. (305 mm), o.c., at y dir.

ANALYSIS


f Pn (k)

0
0 500

-
f Mn (ft-k) Solid Black Line - Tension Controlled
Solid Red Line - Transition
Dash Line - Compression Controlled

Note:
1. Between compression & tension controlled is         2
 c  c  , for 0 
 e f C 2   s E s , for  s   ty
'
Transition, which the f should be by linear    c o
interpolation. (ACI 318-19 Tab. 21.2.2 & Fig. R10.4.2.1) fC     o    o   , f S 
2. ACI 318-19 changed f (Fig.R21.2.2b) and keeps   f y , for  s   ty
  e f C , for  c   o
'

be (22.2.2.4.1) and ecu (Fig. R21.2.2a) the same.
But AISC 360/341-16 has different f (0.9 only) and 
2  e f 'C  fy 
 ty , for compression controlled
o  ,  ty  , t  
 0.003 , for tension controlled
be (1.0 or 0.7). Ec Es  ty

'
E c  57 f C , E s  29000ksi ,  e  0.85 ,  cu  0.003
CHECK FLEXURAL & AXIAL CAPACITY
f Pmax =F f [ 0.85 fc' (Ag - Ast) + fy Ast] = 4315 kips., (at max axial load, ACI 318-19 22.4)
where f = 0.65 , (ACI 318-19 Fig. R21.2.2b) > Pu [Satisfactory]
F = 0.8 , (ACI 318-19 Tab. 22.4.2.1) Ag = 240 in 2 Ast = 5.30 in2
f Mn = 2812 ft-kips @ Pu = 1440 kips > Mu = 2550 ft-kips [Satisfactory]
r max = 0.06 (ACI 318-19 18.7.4.1) rprovd = 0.012
rmin = 0.01 (ACI 318-19 18.7.4.1& 10.6.1.1) [Satisfactory]

CHECK SHEAR CAPACITY (ACI 318-19 10 & 22.5)

1.19 < 1.5 (ACI 318-19 22.5.1.11) [Satisfactory]

V u, x V u, x
 
V n, x V n, x
f Vn = f (Vs + Vc) (ACI 318-19 22.5)

where f = 0.75 (ACI 318-19 21.2) fy = 60 ksi


d A0 Av Vc = 2 (fc')0.5A0 Vs = MIN (d fy Av / s , 4Vc) f Vn
x 37.5 1240 0.80 192.1 150.0 257
y 33.5 1240 0.60 192.1 100.5 219

smax = 16 (ACI 318-19 25.7) sprovd = 12 in


smin = 1 [Satisfactory]
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Magnified Moment Calculation for Concrete Column Based on ACI 318-19

INPUT DATA & DESIGN SUMMARY


EFFECTIVE LENGTH FACTOR k = 1.6 , (ACI 6.2.5)
COLUMN UNSUPPORTED LENGTH Lu = 12 ft
LARGER FACTORED MOMENT M2 = 200 ft-k
SMALLER FACTORED END MOMENT M1 = 100 ft-k, (positive if single curvature.)
CONCRETE STRENGTH fc' = 4 ksi
COLUMN DIMENSIONS h = 20 in
b = 20 in
FACTORED AXIAL LOAD Pu = 400 k
SUMMATION FOR ALL VERTICAL LOADS IN THE STORY S Pu = 1200 k
SUMMATION FOR ALL CRITICAL LOADS IN THE STORY S Pc = 13600 k, (ACI 6.6.4)

THE MAGNIFIED MOMENT: Mu = 236.7 ft-k , Sway

ANALYSIS
MAGNIFIED MOMENT - NONSWAY
r = 0.3 h = 6.0 in, ACI 6.2.5.1
k Lu / r = 38.4 > 34 - 12(M1 / M2) = 28 < = = Slenderness effect must be considered. (ACI 6.2.5)
Ec = 57000 (fc')0.5 = 3605.0 ksi, ACI 19.2.2
Ig = b h3 / 12 = 13333 in4

0.4 E c I g 0.4 E c I g
EI    0.25 E c I g  1.2E+07 k-in2 , ACI 6.6.4.4.4
1  d 1  0.6

 2EI 
Pc  2234.18 k-in2 , ACI 6.6.4.4.4
 k Lu 
2

M2,min = MAX[ M2 , Pu (0.6+0.03 h) ] = 220 ft-k, ACI 6.6.4


Cm = MAX[ 0.6 + 0.4 (M1 / M2, min) , 0.4 ] = 0.8 , ACI 6.6.4.5

 
 
 Cm 
  MAX , 1.0 1.05 , ACI 6.6.4.5.2
 1  Pu 
 0.75P c 
 

Mu, ns = d M2, min = 210.2 ft-k, ACI 6.6.4.5.1 > 1.05 M2 = 210.0 ft-k [Unsatisfactory] ,(ACI 6.6.4.3)
The column is sway. See calculation as follows.

MAGNIFIED MOMENT - SWAY


k Lu / r = 38.4 > 22 < = = Slenderness effect must be considered. ACI 6.2.5)

   
   
1
 s  MIN  MAX  , 1.0  , 2.5  1.13 , ACI 6.6.4
   Pu  
  1  0.75 P  
  c  

Ag = b h = 400 in2
Lu / r = 24.00 < 35 / [Pu / (fc' Ag)]0.5 = 70.00 [Satisfactory]
M2s = M2 = 200.0 ft-k, as given
M2ns = 5% M2s = 10.0 ft-k, assumed conservatively
Mu, s = M2ns + ds M2s = 236.7 ft-k, ACI 6.6.4.6

Note: For column subject to bending about both principal axis, the moment about each axis shall be magnified separately based
on the conditions corresponding to that axis.
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Rectangular Concrete Column Design

INPUT DATA
f 'c = 4 ksi
fy = 60 ksi
x = 48 in
y = 32 in
Bar Size ==> # 11
No. of Asx = 8 8 # 11
No. of Asy = 9 9 # 11
Total Bars ==> # 30 # 11
r = 3.0%
Pu = 1700 k
Mux = 2900 ft-k ex = 20.5 in
Muy = 1200 ft-k ey = 8.5 in

CHECK COLUMN CAPACITY BY THE BRESLER METHOD


1
P u   0.80   0.70  P o Pn  1 1 1 M nx  M ny  1.0
  M nox M noy
P ox P oy Po
1700.0 < 4407.9 ok 2428.6 < 2953.0 ok 1.270 > 1.0 NG

ANALYSIS
x DIRECTION y DIRECTION
u = 0.003 d = 45.295 in 29.295 in
d' = 2.705 in 2.705 in
As = 12.48 in2 14.04 in2
 = 0.70 b = 32 in 48 in

Mn = 4142.9 ft-k 1714.3 ft-k


1 Mno
= 0.85 = 5237.1 ft-k 3581.1 ft-k
Po = 3626.1 k 5265.9 k

MOMENT STRENGTH (Pn=0)

 As f y  A's u E s 
2
A s f y  As  u E s 
'
 3.4  1 f 'cb As'  u E s d '
c 
1.7  1 f 'cb 4.100781 in 3.701729 in

'  c d'
f s  E s u   29612.16 psi 23425.65 psi
 c 

  1c 
M n  0.85 f c  1cb  d 
'
 As' f 's  d  d '  
2 
4034.011 ft-k 3052.887 ft-k

AXIAL LOAD STRENGTH (Mn=0)

'
P o  0.85 f c( A g  A st )  A st f y  7871.28 k = 7871.28 k

BALANCED CONDITION

 u E s  1d
ab  
 uEs  f y 22.78616 in 14.73718 in

'  d '   u E s  f y 
f sb   u E s 1     60000 psi 60000 psi
 d   u E s 
' '
P b  0.85 f cb a b  As f sb  A s f y 
'
2479.134 k 2405.108 k

'  h ab  ' h ' h 


M b  0.85 f cb a b     A s f sb   d   A s f y   d   5262.137 ft-k 3596.574 ft-k
'

2 2  2  2 