CLEANROOM SPRINKLER
TECHNICAL DATA
COVER ASSEMBLIES

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

1. DESCRIPTION
Viking Cleanroom Cover Assemblies are low-profile covers intended for use in cleanroom
environments with Viking Mirage® Concealed Pendent Sprinkler VK462, MRI Sprinkler
VK462 (listed as quick response), Sprinkler VK464 (listed as standard response for this
application) or MRI Sprinkler VK464 (listed as standard response for this application).
Note: Adding the seal does NOT change sprinkler VK462 QR listing. The silicone cover
gasket is pre-assembled with the concealed cover for an acceptable sprinkler seal for use
in a cleanroom or clean zone. The cover assembly is installed flush with the ceiling to
provide a smooth appearance, and is available in several standard decorative finishes
to meet design requirements. Viking concealed cover plate assemblies may also be
custom ordered with any color by any paint manufacturer.
The low-profile cover assembly is designed with a threaded adapter and provides up
to ½” (13 mm) of vertical adjustment. The two-piece sprinkler and cover plate design
allows installation and testing of the sprinkler prior to installation of the cover plate.
The “push-on”, “thread-off” design of the concealed cover plate assembly allows easy
installation of the cover plate after the system has been tested and the ceiling finish
has been applied. The cover assembly can be removed and reinstalled, allowing tem-
porary removal of ceiling panels without taking the sprinkler system out of service or
removing the sprinkler.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
Refer to the Approval Chart and Design Criteria for cULus Listing requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Refer to the appropriate sprinkler technical page for sprinkler specifications.
Material Standards:
Cover Plate: Copper UNS-C11000 or Stainless Steel UNS-S30400
Base: Brass UNS-C26000 or UNS-C26800
Gasket: Silicone
Springs: Nickel Alloy
Solder: Eutectic
Ordering Information: (Also refer to the current Viking list price book.)
Base Part No. 23174-/CR (3-5/16” diameter) for Sprinkler VK462, VK464, and MRI Sprinklers VK462 and VK464.
Specify finish and temperature rating of the cover plate assembly by first adding the appropriate suffix for the finish and then
the appropriate suffix for the cover temperature rating to the base part number:
• Finish Suffix: Polished Chrome = F, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/B
• Temperature Suffix: 135 °F (57 °C) = A, 165 °F (74 °C) = C
For example, cover 23174-/CR with a Painted White finish and a 165 °F (74 °C) temperature rating = 23174MC/W/CR.
Stainless Steel Base Part No. 23183-/CR (3-5/16” diameter) for Sprinkler VK462.
Temperature Suffix: 135 °F (57 °C) = A
For example, cover 23183-/CR with a 135 °F (57 °C) temperature rating = 23183A/CR.
Available Cover Plate Finishes And Temperature Ratings: Refer to Table 1.
4. INSTALLATION
A. After installation of Mirage® Concealed Pendent Sprinkler VK462 or VK464, testing of the system, repairing of all leaks, and
installation and painting of the ceiling, the concealed sprinkler cover plate assembly may be attached.
1. Remove the plastic protective cap from the sprinkler.
2. Remove the cover plate assembly from the protective box, taking care not to damage the assembly.
3. Gently place the base of the cover plate assembly over the sprinkler protruding through the 2-1/4” (57.2 mm) ceiling opening.
4. Carefully push the cover plate assembly onto the sprinkler until the cover plate flange fits tightly against the ceiling surface.
The maximum adjustment available is ½” (12.7 mm). DO NOT MODIFY THE UNIT. If necessary, re-cut the sprinkler nipple.
Form No. F_022409 20.01.06 Rev 20.1 Replaces Form No. F_022409 Rev 19.1.
© 2020 Viking Group Inc. All rights reserved (Replaced cover part numbers.)
Page 2 of 5

CLEANROOM SPRINKLER
TECHNICAL DATA
COVER ASSEMBLIES

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
B. DISASSEMBLY: Cover plates can be removed by gently unthreading them from the sprinkler body.
C. RE-ASSEMBLY: The push-on feature of these cover plate assemblies allows easy installation of the cover plates.
1. Gently place the base of the cover plate assembly over the sprinkler.
2. Push the cover plate assembly onto the sprinkler until the cover plate flange fits tightly against the surface of the ceiling.
5. OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches.
Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter,
releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler de-
flector, forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Concealed Sprinklers VK462 and VK464 and Cleanroom Cover Assemblies are available through a network of domestic
and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

TABLE 1: AVAILABLE COVER PLATE ASSEMBLY TEMPERATURE RATINGS AND FINISHES


Sprinkler Temperature Sprinkler Nominal Maximum Ambient Temperature Rating of Cover Sprinkler Cover Plate
Classification Temperature Rating1 Ceiling Temperature2 Assembly (Required) Bulb Color Part No.3
Ordinary 155 °F (68 °C) 100 °F (38 °C) 135 °F (57 °C) Red 23183-/CR4
Ordinary 155 °F (68 °C) 100 °F (38 °C) 135 °F (57 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) 165 °F (74 °C) Yellow 23174-/CR
Intermediate 200 °F (93 °C) 150 °F (65 °C) 165 °F (74 °C) Green
Cover Plate Finishes: Polished Chrome, Painted White, Painted Ivory, or Painted Black
Footnotes
1. The sprinkler temperature rating is stamped on the sprinkler deflector.
2. Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific
installation standards.
3. Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.

4. Stainless Steel versions are not available with any finishes or paint.

CUSTO
LIED M
P
All custom color painted cover plates will have an
PA
P
CTORY A

INT

identifying label affixed to the inside of the cover that


indicates the custom color and will have a representative
COLO

sample (a paint dot) of the paint on the label.


FA

Figure 1: Identification of Custom Paint for Concealed Covers

Form No. F_022409 20.01.06 Rev 20.1


© 2020 Viking Group Inc. All rights reserved
Page 3 of 5

CLEANROOM SPRINKLER
TECHNICAL DATA
COVER ASSEMBLIES

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Sprinkler and 2-1/4” (57 mm)


Adapter Assembly diameter opening
• Protective cap Sprinkler Wrench required in the
removed Part No. 14047WB** ceiling.
• Use wrench
14047WB**

Step 1: Step 2:
Carefully slide the Carefully press the wrench upward and
wrench sideways around turn slightly to ensure engagement with
the deflector and pins the sprinkler wrench flats.

NEVER install the sprinkler by applying the installation Sprinkler


wrench across the frame arms. DO NOT overtighten. wrench flat
Use only the designated sprinkler wrenches, Viking Sprinkler
Part Numbers 14047WB** or 14031**. A leak tight seal frame arms
should be achieved by turning the sprinkler clockwise
1 to 1-1/2 turns beyond finger tight.

Figure 2: Sprinkler Installation and Proper Wrench Usage


** A 1/2” ratchet is required (Not available from Viking)

Form No. F_022409 20.01.06 Rev 20.1


© 2020 Viking Group Inc. All rights reserved
Page 4 of 5

CLEANROOM SPRINKLER
TECHNICAL DATA
COVER ASSEMBLIES

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Approval Chart
Mirage® Concealed Pendent Sprinklers VK462 and VK464
and MRI Sprinklers VK462 and VK464 with Large Diameter Cleanroom Cover Assembly 23174-/CR
Nominal Maximum Water Listings and Approvals3
Sprinkler Base NPT Thread Size (Refer also to Design Criteria below and
SIN K-Factor Working Pressure on the applicable sprinkler data page.)
Part Number1
Inch mm U.S. metric 2
psi bar cULus4 FM NYC
Quick Response Applications
13503A VK462 1/2” 15 5.6 80.6 175 12 AW1, BX1, AY2 -- --
15480A VK462 (MRI) 1/2” 15 5.6 80.6 175 12 AW1, BX1 -- --
Standard Response Applications
13614A VK464 3/4” 20 8.0 115.2 175 12 AW1, BX1 -- --
15481A VK464 (MRI) 3/4” 20 8.0 115.2 175 12 AW1, BX1

Cover Plate Assembly Temperature Ratings5 Finishes of the


Sprinkler Temperature Ratings Cover Plate Assembly6
W - 135 °F (57 °C) cleanroom cover assembly 23174-A/CR 1
A - 155 °F (68 °C) 1 -Polished Chrome, Painted White,
X - 165 °F (74 °C) cleanroom cover assembly 23174-C/CR1
B - 175 °F (79°C) and 200 °F (93 °C) Painted Ivory, or Painted Black
Y - 135 °F (57 °C) cleanroom cover assembly 23183A/CR1 2 - Stainless Steel7

Footnotes
1. Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2. Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

3. This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals.

4. Listed by Underwriter’s Laboratories for use in the U.S. and Canada.

5. The 135 °F (57 °C) cover has an orange label. The 165 °F (74 °C) cover has a white label.

6. Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals
apply for any paint manufacturer. Contact Viking for additional information.
7. Stainless Steel is not considered a finish.

 NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.

DESIGN CRITERIA
(Also refer to the Approval Chart above.)
cULus Listing Requirements:
Viking Cleanroom Sprinkler Cover Assembly 23174-/CR is cULus Listed for use with the Mirage® Concealed Pendent Sprinklers VK462 (QR), VK464
(SR), and MRI Sprinklers VK462 (QR) or VK464 (SR) in a cleanroom or clean zone for installation in accordance with the latest edition of NFPA 13 for
cleanrooms when the following conditions are met:
• Wet systems shall be provided throughout the facility containing cleanrooms and clean zones.
• Sprinklers shall be installed in the plenum and interstitial space above cleanrooms and shall be hydraulically designed for a density of 0.2 gpm
(8.15 L/min m2) over a design area of 3000 ft2 (278.8 m2).
• Sprinklers installed in duct systems shall be hydraulically designed for a density of 0.5 gpm (1.9 L/min) over an area derived by multiplying the
distance between the sprinklers in a horizontal duct by the width of the duct. Minimum discharge shall be 20 gpm (76 L/min) per sprinkler from
the five (5) hydraulically most remote sprinklers.
• Sprinklers installed in ductwork shall be spaced a maximum of 20 ft (6.1 m) apart horizontally and 12 ft (3.7 m) apart vertically.
• A separate indicating control valve shall be provided for sprinklers installed in ductwork.
• The sprinklers shall be acessible for periodic inspection and maintenance.
NOTE: Sprinkler VK464 is cULus Listed as a standard response sprinkler when using Cleanroom Sprinkler Cover Assembly 23174-A/CR. However, it
is listed as a quick response sprinkler as indicated on sprinkler technical data page 55a-e when using Cover Assembly 23174 (for non-cleanroom
applications).
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to the applicable sprin-
kler data page, and page F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be
installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards,
whenever applicable.

Form No. F_022409 20.01.06 Rev 20.1


© 2020 Viking Group Inc. All rights reserved
Page 5 of 5

CLEANROOM SPRINKLER
TECHNICAL DATA
COVER ASSEMBLIES

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

1/2” (15 mm) NPT

2-3/16” 2-5/8” 2-1/8”


(55 mm) (67 mm) (54 mm)

Gasket Maximum Minimum

Cover NOTE: Upon sprinkler activation, the deflector descends


to approximately 13/16” (21 mm) below the sprinkler body.

Figure 3: Sprinkler VK462 Dimensions and Cover Installation

3/4” (20 mm) NPT

2-1/4” 2-11/16” 2-3/16


(57 mm) (68 mm) (56 mm)

Gasket Maximum Minimum

Cover NOTE: Upon sprinkler activation, the deflector descends


to approximately 13/16” (21 mm) below the sprinkler body.

Figure 4: Sprinkler VK464 Dimensions and Cover Installation

Form No. F_022409 20.01.06 Rev 20.1 Replaces Form No. F_022409 Rev 19.1.
© 2020 Viking Group Inc. All rights reserved (Replaced cover part numbers) .