Fire Safety in Purpose Built Flats
Fire Safety in Purpose Built Flats
Fire Safety in Purpose Built Flats
Environment, housing,
Fire safety in purpose-built
blocks of flats
Foreword
Flats have been used to house people since Victorian times. From the early tenements for
the poor to mansion blocks for the affluent, these buildings were often seen as innovative
solutions to the country’s housing needs.
However, it was the post war demand for affordable housing that, in the 1940s and 50s,
spurred on the building of high-density, purpose-built blocks of flats. In the 1960s, in
particular, high-rise blocks began to dominate the skyline of towns and cities across the
country. Each flat represented a self-contained, domestic dwelling, the block where it was
located having all the necessary facilities and amenities each household needed to live
independently of others.
Given that most fires occur in domestic dwellings, it was recognised that a block of flats –
as a building containing many such dwellings – had the potential for a higher risk to people
should fire break out. Accordingly, the fire safety standards that were developed to address
this risk sought to afford the same level of safety found in houses to those living in blocks of
flats.
These standards have been embodied in Building Regulations, which, now as then, ensure
that adequate fire safety provisions are incorporated in blocks of flats when they are
constructed.
The Regulatory Reform (Fire Safety) Order 2005 (the FSO) came into force in October 2006.
It brought the common parts of blocks of flats within the scope of mainstream fire safety
legislation for the first time.
Guidance on the FSO and its requirements has been issued in a series of guides. Blocks of
flats are included, among many other types of residential premises, in the HM Government
guide ‘Fire safety risk assessment: sleeping accommodation’ published by the Department
for Communities and Local Government (DCLG).
However, application of the FSO to blocks of flats has proved problematic: it has led to widely
varying outcomes. In some buildings, significant work to upgrade fire safety standards within
the common parts has been undertaken to satisfy this legislation. In others, none has been
considered necessary.
There has also been confusion over the scope of this legislation: how it relates to those who
live in the flats, and, indeed, to what extent, if any, this legislation can require improvements
beyond the flat entrance door. These are just two of the questions that tax those seeking to
apply and enforce it.
This guide is intended to meet the needs of housing providers and enforcing authorities for
guidance tailored to purpose-built blocks of flats. These buildings are only a small part of the
scope of other guidance documents. This document is intended to assist responsible persons
to comply with the FSO and the Housing Act 2004. Accordingly, it is expected that enforcing
authorities will have regard to this guide.
Acknowledgments 9
Introduction 11
2. Purpose 11
4. Intended readership 13
7. Appendices 17
8. Glossary 17
9. Bibliography 17
Part B: Fire safety – how blocks of flats differ from other residences 22
15. Introduction 23
17. Compartmentation 26
22. Fire-fighting 30
30. Introduction 42
41. Introduction 52
42. Smoking 52
43. Arson 53
44. Housekeeping 55
45. Recycling 61
48. Lightning 65
50. Introduction 68
54. Compartmentation 71
59. Escape from flats with external balcony or deck access approach 90
81. Inspection, testing and maintenance of fire safety systems and equipment 122
83. Monitoring the common parts and being alert to new hazards 127
Appendix 1: History of fire safety design standards for purpose-built blocks of flats 133
Appendix 6: Fire detection and fire alarm systems for blocks of flats 156
Appendix 10: Case study – Mixed-use block, with inadequate compartmentation 168
Appendix 11: Case study – Block containing two-storey flats, without adequate
alternative exits 170
Appendix 12: Case study – Block containing single storey flats, without adequate
alternative exits 172
Glossary 177
Bibliography 181
Index 185
Local Government Group entrusted responsibility for this guide to a sector-led group of
stakeholders, comprising:
2. Purpose
2.1 This document is a guide to ensuring adequate fire safety in purpose-built blocks of
flats, regardless of age. Practical advice is offered on how to assess the risk from fire
and how to manage fire safety in such buildings. The document also includes case
studies based on the commonly found issues in blocks of flats, with suggested fire
safety solutions.
2.2 This guide does not introduce new standards or regulations, but builds on existing good
practice and guidance currently in place. In particular, it will help landlords, managing
agents, enforcing officers and those undertaking fire risk assessments to understand
the legislative requirements relating to blocks of flats and to apply them in a consistent
and reasonable manner.
2.3 This document does not set prescriptive standards. Its aim is to provide guidance
and recommendations for use when assessing the adequacy of existing fire safety
provisions in purpose-built blocks of flats.
2.4 While it includes definitive criteria for determining the level of safety, these are only
intended to act as useful benchmarks against which comparisons can be made.
Similarly, the methodology outlined here is only intended to assist in making such
comparisons. Alternative fire risk assessment methods may be equally valid in order to
comply with fire safety law. Alternative approaches to individual fire safety solutions may
be acceptable as long as an equivalent level of safety is achieved.
2.5 It should be noted that building design varies considerably and no guide can ever
provide specific solutions for all possible circumstances. Accordingly, this guide sets out
only general principles.
2.6 While aimed at a broad readership, its use in assessing risk and determining an
appropriate package of fire safety provisions in some buildings may require particular
3.2 The scope of this guide excludes buildings converted into blocks of flats. However
the guidance contained in this document will largely be applicable to such buildings,
provided that – at the time of conversion – the work was carried out in accordance
with the then current Building Regulations. In particular the guidance is likely to be
relevant to conversions in which, as a result of compartmentation, a ‘stay-put’ policy is
appropriate.
3.3 Within this guide, the term ‘flat’ is used to describe a self-contained domestic dwelling
within a building. Other terms, such as ‘apartment’, are commonly used to describe such
accommodation. The term ‘flats’ is intended to include those arranged on more than one
storey, such as maisonettes (duplex apartments).
3.4 This guide also includes flats within sheltered housing schemes and blocks containing
flats intended for multiple occupation by, for example, students or key workers.
However, the guide does not address buildings of this nature in which, in the event of a
fire in a flat, the entire building is evacuated simultaneously.
3.6 This guide does not address ancillary or communal facilities, such as a lounge, gym or
a hairdresser in a sheltered housing scheme. Although such facilities must be included
in the scope of the fire risk assessment for the block, the fire precautions should be
considered on a case-by-case basis, following general guidance applicable to buildings
other than flats.
1 Guidance to Part B of these Regulations (Fire Safety) for blocks of flats is contained in the DCLG publication ‘Approved Document B
Volume 2’.
3.8 While the guide includes fire safety within the flats themselves, this only applies to flats
occupied as single-family households. A flat in multiple occupation is a form of HMO and
is, therefore, outside the scope of the guidance in this document.
3.9 This guide applies to purpose-built blocks of flats regardless of the tenure of the flats (ie
whether owner-occupied, social housing or private rented sector). The term ‘residents’ is
used when referring to the occupants of the flats. This is intended to cover all those who
live in the building, whether tenants or leaseholders. However, the term ‘tenant’ is used
when specifically referring to tenants, but not other forms of resident.
3.10 The guide is concerned only with the safety of those who live in, visit, or work in blocks
of flats. It is also restricted to those lawfully on the premises.
3.11 It does not provide guidance on protecting property. Nor does it include
recommendations specifically to address certain consequences of fire, such as the need
to re-house residents at short notice.
3.12 By virtue of including guidance on the provision and maintenance of facilities for use
by fire and rescue services in fighting fires in blocks of flats, the needs of fire-fighters
are, to some extent, covered in this guide. However, the document is not a guide to
operational fire-fighting in such buildings.
3.13 The guide applies only to England. However, it is likely to be relevant in Wales, where
the same fire safety legislation applies.
4. Intended readership
4.1 This guide is particularly aimed at those who manage, give advice on and enforce standards
in purpose-built blocks of flats. This specifically includes those undertaking fire risk
assessments of such buildings, including those contracted to do this on a commercial basis.
4.3 The guide is not specifically intended for residents. However, it is recommended in the
guide that landlords and others responsible for managing fire safety in blocks of flats
should engage and communicate with those who live in the buildings in their care.
4.4 It is recognised that some readers will be primarily interested in the practical application
of this guide as it relates to managing fire safety in blocks of flats. Accordingly, particular
advice of this nature is highlighted in the text and, where appropriate, key points are
summarised. This can be found in the shaded boxes. However, to achieve an adequate
standard of fire safety, it is important that all sections of the guidance are taken into
account.
5.2 Certain blocks of flats are also included within the scope of the LACoRS guide ‘Housing
– fire safety: guidance on fire safety provisions for certain types of existing housing’.
However, the blocks addressed in that document comprise purpose-built blocks and
conversions that, in either case, do not meet the standards applied under the Building
Regulations since 1992.
5.3 This present guide covers all purpose-built blocks of flats (both common parts and the
flats themselves), including those within the scope of the DCLG and LACoRS guides. It
is, therefore, the more appropriate guide to use for purpose-built blocks of flats.
This is intended to put the risk from fire in these buildings into context and draw
comparisons with the risk to people living in other forms of housing.
Part B outlines the general principles of fire safety in purpose-built blocks of flats.
It is always intended that the occupants of a flat where a fire occurs should evacuate
immediately. The concept of ‘stay put’ as a strategy, where other residents remain in
their flats, is explained here along with the implications this has for building design.
The alternative of evacuating some or all of the other residents at the same time is also
discussed. The particular differences that might apply in special circumstances, such as
sheltered housing schemes, are also highlighted.
Part C provides an overview of the legal framework in relation to fire safety in purpose-
built blocks of flats.
In particular, it aims to help landlords, and those managing fire safety in these buildings,
to understand their obligations under housing legislation, as well as under the FSO.
The extent of these obligations, particularly where, under a lease, landlords do not have
control over certain fire safety provisions, is also addressed.
This is aimed not only at those undertaking such assessments, but also enforcing
authorities responsible for auditing them. It is also intended to assist landlords and
others when commissioning third parties to carry out fire risk assessments on their
behalf.
While there is other guidance available on fire risk assessment, the focus here is on its
specific application to these types of premises. It includes guidance on the following
aspects of the fire risk assessment process:
• who should carry out a fire risk assessment and what level of competence is required
• what fire risk assessments should cover, particularly in relation to fire safety within the
flats themselves
• how intrusive they should be with regard to assessing aspects of the construction of
the building
• when they should be carried out and how often they should be reviewed
• how they should be recorded.
Parts E and F describe how various fire safety measures may be applied to reduce risk.
In Part E, beginning with fire prevention, a series of practical measures are outlined to
address the commonly found fire hazards in blocks of flats. This is particularly aimed at
landlords and those managing fire safety in blocks of flats. However, it will also serve to
While concentrating on the hazards arising in the common parts, reference is made to
sources of guidance available to residents.
Part F outlines benchmarks relating to various fire safety measures employed in fire
safety design to make a building safe. These measures include:
A methodology is included for comparing the standard found in the building to that of the
benchmarks set out in this part of the guide.
To illustrate the application of this approach, case studies are included in the
appendices. These are only examples of fire safety solutions for particular sets of
circumstances. Other solutions may be equally valid and, accordingly, those described
must not be used as ‘off-the-peg’ solutions.
Part G is particularly aimed at landlords and others with the responsibility for the
ongoing control of fire safety in blocks of flats. It will also be useful to those considering
the standard of fire safety management when assessing risk.
Advice on the possible need for emergency plans and fire procedures is given. This
includes suggestions for engaging with tenants and residents to improve awareness
of hazards and preparedness for fire emergencies. The benchmarks for testing and
maintaining fire safety provisions are included with good practice on what should be
recorded and how records should be kept.
This part also includes guidance relating to changes that might introduce new risks.
Alterations to buildings can inadvertently affect fire safety standards, and examples of
where this might occur are given.
These comprise:
8. Glossary
8.1 The glossary is intended as a plain English guide to some terms used in this document.
9. Bibliography
9.1 The bibliography offers sources of further reading for those seeking greater detail
or researching the source of some of the guidance. It also lists the full titles of all
references included in the guide.
Key points
• People living in flats experience more fires than people living in houses. However, a fire in
a flat is no more dangerous than a fire in a house.
• High-rise does not mean high-risk!
• To keep fire risk to a minimum, it is just as important to prevent fires as to provide
measures to protect people when fire occurs.
• The most significant influences on fire risk are social and lifestyle factors and advanced
age, not the type of dwelling in which people live.
• All dwellings should have working smoke alarms.
• Very few people die as a result of a fire in a neighbour’s flat or the common parts. Nearly all
fire deaths occur in the flat in which fire starts.
• In blocks of flats, each flat is designed to be a fire-resisting ‘box’. It is important to maintain
the integrity of this compartment, particularly when building work and alterations take place.
• It is important to ensure that fires cannot start in the common parts or common facilities.
Proportion
600 dwelling fir
10.2 This significant reduction in domestic in blocks o
flats
fire deaths is almost certainly the result
of a number of factors, one of the most
important of which is the great increase
400
in the provision of smoke alarms
in homes. There is overwhelming
evidence to show that, where
occupants of a dwelling are given an
early warning of fire by a smoke alarm, 200
10.3 In addition, undoubtedly many lives have been saved by government, and individual fire
and rescue services’ ‘community fire safety’ (CFS) initiatives. CFS involves proactive
efforts to reduce the incidence and impact of fire through education, information
and publicity. Significant CFS initiatives include the provision of smoke alarms to
householders, education in schools and free home fire-safety checks.
1000
11. Relative risk in flats
Proportion of
people living
11.1 In England, around 10 per cent3 of the in flats
dwelling fires
cent of dwelling fires occurred within in blocks of
flats
purpose-built blocks of flats. As a result,
in that year, 23 per cent of all fire deaths Proportion of
domestic fire
600
in dwellings occurred in these blocks. deaths in
blocks of
flats
200
11.2 This suggests that the number of fire deaths in purpose-built flats appears significantly
disproportionate to the number of people who live in these dwellings. But this is simply
the result of number of fires in such dwellings, most of which are started accidentally.
There is no evidence from fire statistics to suggest that those living in purpose-built
blocks of flats are at greater danger from fire, once it breaks out, than those who live in
houses4.
11.3 Once a fire occurs in a block of flats, the likelihood of a death is actually less than the
likelihood of a death when fire occurs in a bungalow or a house. The lower frequency of
deaths when fire occurs is paralleled by a lower rate of injury. One possible reason for
this is that greater protection is afforded to escape routes in flats than in bungalows and
two-storey houses.
11.4 In addition, because, in a block of flats, each individual flat is totally enclosed in fire-
resisting construction, the vast majority of fires are contained within the flat (and, in the
majority of cases, the room) where they start. It is certainly rare for anyone, outside the
flat where a fire starts, to die as a result of a fire in a flat.
13.2 Obviously, above first floor level, escape via windows is impossible, and, above the
third floor, rescue by fire and rescue service ladders is unlikely to be possible; even high
reach appliances have their limits. However, this is taken into account in the design,
layout and means of escape in modern blocks of flats. They are designed so that
escape or rescue via windows should not be necessary.
4 Source: Fire and Rescue Service Incident Reporting System Data 2009-2010
5 Source: Fire and Rescue Service Incident Reporting System Data 2009-2010
13.4 Therefore, as in all dwelling types, the risk to people from fire (ie risk of death or injury)
in a block of flats is governed primarily by the likelihood of fire occurring and whether
smoke alarms are installed, rather than the type of dwelling in which people live, the
height of the dwelling above ground or the architectural design of the block.
14.2 This highlights the importance of fire prevention within the individual flats. It is also
clear that much can be done by landlords, other housing providers and the fire and
rescue service (through their CFS activities) to reduce the risk to all residents. This is
particularly true in the case of the most vulnerable people, such as older or disabled
people, socially deprived people and those who engage in drug or alcohol abuse.
14.3 The assessment of risk from fire also needs to take social factors into account,
particularly in the case of accommodation provided specifically for certain high-
risk groups. Guidance on fire risk assessment is given in Part D of this guide, while
measures to prevent fire occurring are discussed in Part E of this guide.
14.4 Notwithstanding the importance of fire prevention, to ensure that, in any block of flats,
when a fire occurs the risk to people is minimised, various fire safety measures need to
be provided. These are specific to blocks of flats, and take account of the differences
between flats and traditional houses. The principal differences are discussed in Part B
of this guide.
15.2 The potential for fire to spread from one flat to another has long been recognised. While
fire safety standards have developed over the years, they have always aimed to ensure
that the level of safety for those living in blocks of flats is equivalent to that for those
living in houses. Fundamental to this is the ability to escape safely.
16.2 There are situations in which fire and rescue services need to rescue people by using
ladders. While some dwellings, including those within blocks of flats, are within reach of
ladders or high-reach appliances, many are not. In addition, modern traffic conditions,
including congestion and restricted access due to parking, can significantly impact on
the ability to carry out such rescues. It is, therefore, a fundamental principle that escape
route design should not rely on external rescue by the fire and rescue service.
16.3 To enable people to leave in time, most houses are designed with an alternative means
of escape if the occupants cannot use the normal way out of the dwelling. Alternatively,
to ensure that it can be used safely, the main exit route is ‘protected’, ie enclosed in fire-
resisting construction. In bungalows and two storey houses, windows are recognised as
an alternative means of escape.
16.4 Dropping from a window is not, of course, a feasible option in the case of blocks of flats
above two storeys in height. Alternatives in this case usually involve access to a stairway,
even if via a corridor or linking balcony. Using a linking balcony to gain access to a
neighbour’s flat has been an approach used in the past but is now considered unsuitable.
16.5 It is, however, possible to design a block of flats without alternative means of escape
from the flats. Indeed, this is by far the norm. Even in blocks with two or more stairways,
it is often necessary to escape from the flat into a single common corridor to reach both
stairways.
16.7 While it is clear from the above that the internal escape from flats is designed on similar
principles to that of houses and bungalows, the key difference in fire safety design in a
block of flats relates to the fact that, once out of the flat, there is further to go to reach
ultimate safety. Escape for residents therefore depends on the common parts being
suitably designed and maintained for use in an emergency.
16.8 While the flats, themselves, are outside the scope of the FSO, those elements of the
common parts that afford escape for residents once outside their flats are included (see
Part C of this guide).
16.10 These assumptions dictate the appropriate protection for the communal means of
escape.
16.11 Older people and people with certain disabilities may require particular consideration
to be given to their needs in the event of fire. Meeting people’s needs for normal living
may mean that, in certain cases, specially adapted dwellings need to be provided, for
example, on the ground floor. Sheltered housing is clearly an example of purpose-built
accommodation intended for people with a particular set of needs. Accordingly, fire
safety design in such buildings includes consideration of the implications for means of
escape and other fire safety measures.
16.12 However, it is reasonable to expect that the occupants of a ‘general needs’ block of
flats will reflect the diverse range of physical and mental capabilities of the general
population as a whole. Although inclusive design is fundamental to new ‘general needs’
purpose-built blocks, the Building Regulations do not stipulate additional fire safety
measures that must be provided as a consequence.
17. Compartmentation
17.1 The high degree of fire separation between flats and the common parts is achieved
by making each flat a fire-resisting enclosure. This is known as compartmentation. A
compartment is simply a part of a building bounded by walls and floors that will resist the
passage of fire for a specified period of time. The fire resistance of this construction is
such that, normally, a fire will burn itself out before spreading to other parts of the building.
17.3 The building’s elements of structure are required to possess sufficient fire resistance
when exposed to a fire of predicted severity to not only prevent fire-spread, but also to
prevent structural collapse.
18.2 Compartmentation requires a higher standard of fire resistance than that normally
considered necessary simply to protect the escape routes. This is to ensure that a fire
should be contained within the flat of fire origin. Accordingly, those in flats remote from
the fire are safe to stay where they are. Indeed, in the majority of fires in blocks of flats,
residents of other flats never need to leave their flats.
18.3 This is the essence of the ‘stay put’ principle. It has underpinned fire safety design
standards from even before the 1960s, when national standards were first drafted. It
still the basis upon which blocks of flats are designed today. In the majority of existing
blocks, it remains entirely valid.
18.4 Inevitably, fires do occur in which, for operational reasons, the fire and rescue service
decides to evacuate others in the building. Fires have been known to spread beyond
the flat of origin to involve other flats or to spread across the top of blocks through the
roof voids. In these cases, total evacuation of the block has sometimes been necessary.
Fortunately, these fires are rare. They are usually the fault of failings in the construction.
• When a fire occurs within a flat, the occupants alert others in the flat, make their way
out of the building and summon the fire and rescue service.
• If a fire starts in the common parts, anyone in these areas makes their way out of the
building and summons the fire and rescue service.
• All other residents not directly affected by the fire would be expected to ‘stay put’ and
remain in their flat unless directed to leave by the fire and rescue service.
19.3 The alternative to a ‘stay put’ policy is one involving simultaneous evacuation.
19.5 Simultaneous evacuation is sometimes applied to buildings converted into blocks of flats,
but usually only where it has not been possible to achieve the level of compartmentation
required for a ‘stay put’ policy. In purpose-built blocks of flats, experience has shown that
most residents do not need to leave their flats when there is a fire elsewhere. Indeed, in
some circumstances, they might place themselves at greater risk when they do so.
19.6 Some enforcing authorities and fire risk assessors have been adopting a precautionary
approach whereby, unless it can be proven that the standard of construction is adequate
for ‘stay put’, the assumption should be that it is not. As a consequence, simultaneous
evacuation has sometimes been adopted, and fire alarm systems fitted retrospectively,
in blocks of flats designed to support a ‘stay put’ strategy.
19.7 This is considered unduly pessimistic. Indeed, such an approach is not justified by
experience or statistical evidence from fires in blocks of flats (see Part A of this guide).
It is also differs from the principles of fire risk assessment (see Part D of this guide).
Accordingly, proposals of fire risk assessors, and requirements of enforcing authorities,
based on a precautionary approach (eg abandonment of a ‘stay put’ policy simply
because of difficulties in verifying compartmentation), should be questioned. Before
committing resources, it might be appropriate to seek a second opinion.
20.2 Although purpose-built blocks of flats are not normally provided with communal fire
detection and alarm systems, there are exceptions. The most common example is a
sheltered housing scheme, but this is a special case, and, even then, a ‘stay put’ policy
is normal.
20.4 In ‘general needs’ blocks designed to support a ‘stay put’ policy, it is unnecessary and
undesirable for a fire alarm system to be provided. A communal fire detection and alarm
system will inevitably lead to a proliferation of false alarms. This will impose a burden on
fire and rescue services and lead to residents ignoring warnings of genuine fires.
20.5 A fire alarm system ought to be provided only in a building in which some control can
be achieved over the occupants to ensure that they respond appropriately. For most
blocks of flats, it would be unrealistic to expect this. Nor is it necessarily desirable that
evacuation should take place from areas remote from the fire, unless and until these
areas themselves become threatened by the fire.
20.6 The ability to manage a fire alarm system is rarely possible in a block of flats unless
staffed at all times, eg by a concierge or caretaker. Allowing residents to silence and
reset a system is inappropriate in these circumstances. Access to use of these facilities
also enables major disablement of a fire alarm system. This could expose landlords and
others with responsibility for managing fire safety to liability if, through the actions of a
resident, the system is left inoperative and fails to perform correctly in the event of a fire.
20.7 In view of the above, only in unusual circumstances will a communal fire detection and
alarm system be appropriate for a ‘general needs’ purpose-built block of flats.
• where it can be demonstrated that the assumptions and principles outlined earlier are
not met and cannot readily be achieved
• where the flats are not sufficiently separated from commercial premises below.
20.9 It may not always be necessary to adopt simultaneous evacuation when providing a
communal fire alarm system (see Appendix 6). There may be circumstances in which
the objective of the system is to compensate for a particular shortcoming in an aspect
of, say, escape route design or compartmentation in a building, which otherwise is
suitably designed for a ‘stay put’ policy. In these cases, it may, for example, only be
necessary to alert the fire and rescue service in the event of activation of the system.
20.10 Use of such systems will only be applicable in specific circumstances, and will require
careful consideration by those carrying out a fire risk assessment. Fire alarm systems
should only be fitted in existing blocks of flats where there is clear justification, and only as
a last resort when it is impossible to upgrade other measures to enable a ‘stay put’ policy
to be adopted.
21.2 Similarly, fire exit signs might need to be displayed to assist in the use of an escape
route with which people are unfamiliar. In a single stairway building, there is rarely a
need for such signs. It is not usually considered necessary to signpost the route that
residents normally use to gain access to their flats.
21.3 It is rare for there to be a need for fire-fighting equipment to be used by people present
in the common parts of blocks of flats. It is, nevertheless, usually provided in plant
rooms and other such rooms, for use by the staff and contractors.
21.4 The provision of fire extinguishers and other forms of fire-fighting equipment in common
parts for use by residents is problematic. It is not expected that residents should need
to tackle a fire in their flats to make their escape. Indeed, to obtain a fire extinguisher
located in the common parts for this purpose would involve the person leaving their flat
in the first place.
21.5 This does not preclude residents from providing their own fire extinguishers and fire
blankets. Indeed, it may be appropriate for landlords, and others responsible for the
common parts, to encourage this as part of the process of engaging with, and educating
residents on, fire safety.
22. Fire-fighting
22.1 Special facilities for use by the fire and rescue service in effecting rescue and fighting
a fire are provided in tall blocks of flats. These normally comprise suitably protected
stairways and lobbies, specially designed lifts for use by fire-fighters and fire mains by
which the fire and rescue service can obtain water.
22.2 Normally, the presence (or indeed absence) of these facilities has no direct bearing
on the evacuation strategy of the block. It would not normally be appropriate to seek
improvements to such facilities to address issues relating to escape route design and
compartmentation in blocks of flats.
23.2 While many of the design principles have not changed, there have been changes in
the benchmark standards that are applied. There have also been changes to some of
the approaches to applying these principles. For example, smoke dispersal by means
of cross-ventilation is no longer accepted as an effective means of keeping common
escape routes clear of smoke.
23.3 It is wholly inappropriate to impose the current guidance for new blocks of flats
retrospectively to existing buildings. Nevertheless, current guidance can be considered
when setting benchmarks against which to assess the adequacy of fire protection within
existing blocks of flats.
23.4 However, it should be recognised that benchmarks are intended simply to make
comparisons. Judgement is needed by fire risk assessors and others when reviewing
fire safety in a particular block.
23.5 It will often need to be accepted that it is neither realistic to meet current benchmark
standards, nor risk proportionate to impose many of the solutions available today to the
situations found in the designs of existing buildings.
23.6 There have been many variations in the design of blocks of flats over the years. As
a result, older blocks will not comply with current benchmark standards. Fire safety
professionals may not be familiar with older designs that are not consistent with the
standards of today.
23.7 It is recognised that, with older blocks, it can be difficult to discern what the original
design intent was, and whether it has been preserved or altered subsequently. Similarly,
it can also be difficult to determine what standard has been achieved, especially in
relation to compartmentation, given that some of the relevant elements of structure are
often hidden and inaccessible.
23.8 Nevertheless, when assessing the adequacy of fire protection in existing blocks of flats,
it is considered essential to endeavour to determine the benchmark standards that
applied when the block was built. It is important to establish just how far removed the
original standards are to what is considered acceptable today, and whether this has
given rise to an unacceptable level of risk.
23.9 This is needed to inform decisions regarding the need or otherwise to upgrade fire
protection when considering the fire risk in a particular block.
24.2 Some elements of fire safety design are no longer considered acceptable, eg escape
into a neighbour’s flat via a linking balcony. Also, the approach taken to meeting fire
safety principles has changed. For example, smoke containment is now preferred as the
means of keeping common escape stairways clear of smoke, while smoke dispersal is
deprecated.
24.3 New forms of smoke control, using mechanical means, rather than natural ventilation,
have been introduced. For example, systems using pressurisation to keep escape
routes clear are now available, and smoke extract systems are now being used in fire
engineering designs for blocks of flats to facilitate extended travel within ‘dead ends’.
24.4 Another key development has been the use of sprinklers. Although more commonly
associated with other types of building, systems specifically intended for domestic and
residential premises have been developed, along with appropriate standards to govern
their use. Guidance under the Building Regulations now calls for blocks of flats over
30m in height to be fitted with sprinklers in the flats. Their use can also provide design
freedoms, for example in open plan layouts.
24.5 Water mist systems are also now available. These too have been developed for
domestic and residential applications as well as for more commercial and industrial
applications.
24.6 The extent to which such developments in technology can, and should be, taken into
account when assessing existing blocks of flats needs to be considered carefully. It
is important that the cost, practicality and benefit gained are all taken into account.
Strategies to address shortcomings in fire safety should be proportionate to the risk.
This is a key principle in fire risk assessment (see Part D of this guide).
24.7 While smoke alarms can easily be retrofitted, other fire safety technology cannot always
readily be applied to existing buildings. It is unlikely that retrofitting sprinklers or water
mist systems would be reasonably practicable for existing blocks, nor would retrofitting
Key points
• Material alterations to existing blocks of flats, including alterations to individual flats, are
controlled under the Building Regulations 2010, and need to be approved by a building
control body otherwise an offence is committed.
• All residents of flats need to be made aware of the importance of maintaining in place
the fire safety measures required by legislation at the time of construction of the block.
Alterations by residents within their own flats may not only put those residents at risk, but
also other residents in the block.
• Even if the block satisfied earlier legislation, proposed alterations must be considered in
the light of the current Building Regulations; it is not sufficient to carry out alterations on the
basis of the earlier legislation.
• Under the Housing Act 2004, the housing authority must inspect properties if they become
aware of significant fire hazards. Housing authorities have powers of entry for this purpose.
• The housing authority may make requirements for improvements in fire precautions. In
the event of serious risk, the housing authority has the power to take emergency remedial
action.
• The FSO applies to all parts of a block of flats, other than within the individual flats.
• The FSO imposes duties on persons who may include freeholders, landlords, managing
agents and contractors who maintain fire safety measures and those who carry out fire risk
assessments.
• All fire safety measures must be adequately maintained.
• An offence is committed if inadequate fire safety measures place people at risk of death or
serious injury in case of fire.
25.2 The above legislation and its application is discussed in this part of the guide.
26.3 It can sometimes be difficult for the responsible person to judge whether or not an alteration
is material. In practice, any proposals to carry out alterations – to fire alarm systems, means
of escape or smoke control arrangements, structural alterations and alterations to facilities
for the fire and rescue service – should be submitted to a building control body to determine
if approval is necessary (and, if so, to obtain approval of the proposals) under the Building
Regulations.
26.4 It should be noted that quite minor alterations and building works can often result in a
contravention of the Building Regulations, which is an offence under the Building Act
1984. For example, removal of cross-corridor fire doors, or replacement of a fire door
within a flat by a non-fire-resisting door, would normally result in such a contravention.
Prosecution proceedings for such offences can be instituted for 24 months after
completion of the unauthorised work.
26.6 There is no requirement under the Building Regulations for upgrading existing fire
safety measures to current standards. However, existing non-compliances with the
current Building Regulations must not be made any worse in the course of alterations or
building works.
26.7 Powers also exist under the Building Regulations to require unauthorised material
alterations to be rectified if a breach of the Regulations resulted from the work.
These powers only exist for 12 months after the work has been carried out. However,
at any time, an application can be made to the local authority building control for
‘regularisation’ of unauthorised work carried out after 1985, enabling retrospective
approval to be granted, subject to the work being satisfactory.
27.2 Assessment of the conditions within flats or the common parts of blocks of flats is
carried out by means of the Housing Health and Safety Rating System (‘HHSRS’)
specified in the Act. The purpose of the HHSRS is to provide a means of assessment
that identifies hazards and allows a judgement to be made as to whether the
consequent risk to people is acceptable. A total of 29 hazards, including the hazard of
fire, must be considered in carrying out the HHSRS. The assessment is carried out on
each individual flat, rather than the entire block as a single building.
27.3 Assessed hazards are classified under the Act as either Category 1 or Category 2,
according to the extent of risk to the most vulnerable occupants. Category 1 hazards
create greater risk than Category 2 hazards. If a local housing authority becomes aware
that a Category 1 or Category 2 hazard may exist, they are obliged to carry out an
inspection.
27.4 If it is confirmed that a Category 1 hazard exists, the housing authority have a duty to
take one of a number of possible enforcement actions. (However, the local authority
cannot take enforcement action against itself.) Enforcement actions include the serving
of various forms of notice, which may require the person on whom the notice is served
to take remedial action, or may prohibit the use of the building or part of the building.
In the case of serious risk, the housing authority may, itself, take emergency remedial
action.
27.6 A person on whom a notice is served has the right of appeal to the Residential Property
Tribunal.
28.2 The FSO imposes requirements and duties on the ‘responsible person’. In the case of
a block of flats, the responsible person is the person having control of the premises.
However, if any part of the block is a workplace, the responsible person in that
workplace is the person who employs people to work there. Commonly, the responsible
person is, therefore, not a named individual, but a company or organisation.
28.3 Typically, the responsible person is the freeholder or landlord, but may be a ‘residential
management company’ (RMCo) or a ‘right to manage company’ (RTMCo). However,
responsibilities and duties imposed on the responsible person also apply to any other
person having control of the premises. This includes anyone who, “under a tenancy or
contract, has a responsibility for maintenance or repair of the premises, maintenance
or repair of anything in or on the premises, or for the safety of the premises”. This can
include a wide variety of people, including fire risk assessors.
28.4 Managing agents will normally be either a responsible person or another person having
control of the premises. The same responsibilities and duties are imposed on the
managing agent in each case.
28.5 Other than any part of the block that is a workplace, the responsibilities and duties
imposed are limited to matters over which the person has control. Sometimes, flat
entrance doors may be outside the control of a freeholder. For example, often,
under each resident’s lease, the door is legally part of the demised premises and so
responsibility for maintenance of the flat entrance door rests with the resident. The
landlord has no legal right to force a tenant to upgrade the door to the current standard,
nor to carry out the works unilaterally. However, in case of impasse, a landlord should
refer the matter to the relevant enforcing authority.
28.7 The FSO imposes a general duty of fire safety care in respect of ‘relevant persons’. This
includes anyone lawfully on the premises. The duty is primarily to ensure that the fire
safety measures within the common parts, plant rooms, and so forth are such as may
reasonably be required in the circumstances of the case to ensure that the premises are
safe. (If any part of the block is a workplace, the fire safety measures must, so far as is
reasonably practicable, ensure the safety of the employees.)
28.8 The fire safety measures within the common parts, that must be adequate for
compliance with the FSO, comprise the following.
• Measures to reduce the risk of fire and the risk of spread of fire.
• The means of escape from fire.
• The measures necessary to assist people in the use of the escape routes, such as
emergency escape lighting, fire exit signs and measures for smoke control. (Some
of these measures may not be necessary in all buildings: for example, where escape
routes are straightforward, easily identifiable and likely to be well-known to occupants,
fire exit signs will normally be unnecessary.)
• Where necessary, fire extinguishing appliances. (These are not normally necessary
within common parts, but might be necessary within a plant room, caretaker’s office or
other non-domestic parts of the block.)
• Any fire alarm system necessary to ensure the safety of occupants. (Normally, a fire
alarm system within the common parts is not necessary or appropriate.)
• An emergency plan. (In a small block of flats, this may be as simple as a fire
action notice, but it is important that the procedure to adopt in the event of fire is
disseminated to all residents.)
• Maintenance of all of the above measures.
• Maintenance of measures required by legislation (including the Building Regulations)
for the safety of, or use by, fire-fighters.
28.9 The FSO requires that the appropriate fire safety measures are determined by means
of a fire risk assessment. The fire risk assessment must be ‘suitable and sufficient’ to
ensure that the general duty of fire safety care is satisfied within the common parts. This
fire risk assessment does not address the safety of residents from fire within their own
flat.
28.11 The FSO is normally enforced by the fire and rescue authority, who carry out
inspections to audit compliance with the order. If the fire and rescue authority identify
a breach of the FSO, they will notify the responsible person, and may issue an
enforcement notice requiring that steps be taken to remedy the breach. In the case of
serious risk, a prohibition notice, prohibiting or restricting the use of the premises, may
be issued.
28.12 A person on whom a notice is served has the right of appeal to the Magistrates’ Court
for 21 days after service of the notice. Alternatively, if the responsible person and the
fire and rescue authority cannot agree on the measures necessary to remedy a breach
of the FSO, the two parties may agree to refer the matter for a determination by the
Secretary of State. The Secretary of State’s decision is binding on the fire and rescue
authority.
28.13 Failure to provide adequate fire safety measures is an offence if the failure places
one or more persons at risk of death or serious injury in case of fire. Each such offence
is punishable by a fine (currently of up to £5,000) in the Magistrates’ Court, or by an
unlimited fine and/or two years imprisonment in the Crown Court.
29.2 Common examples of the influence of fire safety measures within flats on the fire safety
of the common parts include the following.
Front doors
The flat entrance doors are critical to the safety of the common parts in the event of a
fire within a flat. The doors must be self-closing and afford an adequate degree of fire
resistance. Where these doors are, under tenancy agreements, the responsibility of the
In the case of many existing leasehold flats, the responsibility for maintenance of the flat
entrance doors rests with the residents. In this case, the freeholder’s power to arrange
for defects to be rectified may be limited or non-existent, making enforcement action on
the freeholder inappropriate.
Under these circumstances, the residents might be regarded as other persons having
control of premises (as defined by Article 5(3) of the FSO), with a duty to ensure the
adequacy of the flat entrance doors. However, use of powers under the Housing Act
may be a more appropriate and better defined route to achieving compliance with the
FSO. In new leases, ideally the freeholder should retain control over all flat entrance
doors.
Internal doors
To protect the common parts from a fire within a flat, reliance is sometimes placed on
internal fire doors within every flat (see Part F of this guide). In determining compliance
with the FSO, it may be necessary to establish whether these doors are present.
Reliance may need to be placed on the powers of the Housing Act to address this issue.
Ventilation systems
29.3 A protocol has been developed that sets out an interrelationship between local housing
authorities and fire and rescue authorities with regard to which enforcing authority
takes the lead enforcement role in different properties, including purpose-built flats.
The protocol describes the manner in which the two enforcing authorities can work
collaboratively to discharge their legislative powers under the Housing Act and the
FSO in respect of fire safety. The protocol, to which many local housing authorities
and fire and rescue authorities have signed up, allows the application of common fire
safety standards and describes which body takes the lead in different circumstances.
Under the Protocol, arrangements are put in place for consultation and communication
between the local housing authority and the fire and rescue authority, so that
unnecessary duplication is avoided and one authority can take the lead in any given
case.
Key points
• A fire risk assessment is required by legislation. Its purpose is to evaluate the risk to people
from fire.
• It enables the responsible person to determine the necessary fire safety measures
required.
• It is normally only necessary to consider the common parts to satisfy the FSO.
• Where a landlord has concern regarding risk to residents within their flats, the fire risk
assessment may extend to the flats themselves.
• Intrusive fire risk assessments (involving destructive exposure) will only be necessary
where there is justifiable concern regarding structural fire precautions.
• A fire risk assessment need not always be carried out by specialists, but where external
specialists are used, care should be taken to ensure their competence.
• Fire risk assessments should be reviewed regularly and when circumstances change.
30.2 A suitable and sufficient fire risk assessment carried out by, or on behalf of, the
responsible person will help to ensure that the chance of fire occurring in the areas
under the control of the responsible person is minimised. It also helps to ensure that,
in the event of a fire anywhere in the block, people can, if necessary, use the common
parts safely to evacuate the building. The fire risk assessment will also ensure that
appropriate managerial arrangements, such as fire procedures and maintenance of fire
safety measures, are in place.
31.2 The fire and rescue authority will examine the fire risk assessment at the time of any
audit of the building. They do not carry out the fire risk assessment, but may give a
certain amount of advice to the responsible person. The fire risk assessment should
not be confused with an assessment carried out by the local housing authority for the
purpose of the Housing Health and Safety Rating System.
32.2 The purpose of a fire risk assessment is to evaluate the risk to people from fire,
taking into account existing fire safety measures, and to determine whether additional
measures are necessary.
• A fire risk assessment is not carried out at the design stage of a building.
• A fire risk assessment is not a building snagging exercise, carried out just prior to
occupation; it can only be completed after the building is in use.
• A fire risk assessment need not always be carried out by specialists, such as
consultants. Use of this guide might enable the responsible person to carry out their
own fire risk assessment, particularly in small, simple blocks of flats.
• Normally, fire risk assessments need not involve destructive inspection of the
building, such as opening up of construction. However, where practicable, it may be
appropriate to lift a sample of accessible false ceiling tiles, or to open a sample of
service risers.
• Although the scope of a fire risk assessment is limited to the common parts, it
is essential that the fire resistance between the flats and the common parts is
considered. In particular, it will be necessary to examine at least a sample of flat
entrance doors to ensure that they are fire-resisting and self-closing. Care should be
taken to look out for other obvious ready routes where fire might spread between the
flats and the common parts, such as meter or milk delivery cupboards, windows, and
so forth.
• A fire risk assessment is not an exercise to identify failings in workmanship and
materials at the time a new building is handed over. It is equally not intended to
identify all latent defects in existing buildings. It is undoubtedly the case that a fire
may reveal hidden shortcomings that could not reasonably be identified by a fire risk
assessment.
• Simply because the FSO requires that, where necessary, certain fire safety measures
are required, it does not mean that such measures are necessary in all cases. For
example, the FSO requires that, where necessary, all premises to which the Order
applies have adequate fire extinguishers and fire alarm systems. In a purpose-built
block of flats, these measures are not normally necessary in the common parts.
• It is not sufficient for a fire risk assessment to consider only the measures needed to
assist residents to escape from fire. For example, measures to prevent a fire within
the common parts must be considered, as must the maintenance of any measures
that were required under Building Regulations for the safety of, or use by, the fire and
rescue service.
• Although the FSO only applies to the common parts, residents within flats are
‘relevant persons’, whose safety from a fire that starts in or spreads to the common
parts, must be considered.
34.2 The relevant fire safety measures and managerial arrangements that must be
considered in a fire risk assessment are, in effect, the fire safety duties set out in Articles
10-22 of the FSO.
34.3 In summary, the fire risk assessment must consider the ‘general fire precautions’
defined in the FSO. Of these, the principal ones for a purpose-built block of flats are:
• measures to reduce the risk of fire and the risk of the spread of fire
• means of escape from fire
• measures to ensure that escape routes can be safely and effectively used
• an emergency plan, including procedures for residents in the event of fire
• measures to mitigate the effects of fire.
34.4 ‘General fire precautions’ also include fire extinguishing equipment and fire alarm
systems. While these are not normally necessary, if such measures are present,
consideration needs to be given as to whether they are appropriate or whether they are,
in fact, undesirable.
34.5 The fire risk assessment must also consider the maintenance arrangements for all
measures required under the FSO or, in the case of equipment and facilities for the fire
and rescue service, under Building Regulations.
A Type 1 fire risk assessment is the basic fire risk assessment required for the purpose
of satisfying the FSO.
Where there are demountable false ceilings in the common parts, it may be appropriate
to lift a sample of readily accessible false ceiling tiles. In addition, it will normally be
appropriate to open a sample of service risers, provided access is practicable at the
time of inspection.
The scope and objectives of a Type 2 fire risk assessment are generally similar to
those of a Type 1 fire risk assessment, except that there is a degree of destructive
inspection, carried out on a sampling basis. This will usually necessitate the presence
of a contractor for the purpose of opening up construction and making good after the
inspection.
In order to check the integrity of separating construction, the areas in which destructive
inspection is carried out might sometimes include a sample of flats. However, because
of the nature of the work, this can often only be carried out in vacant flats.
A Type 2 fire risk assessment is usually a one-off exercise, which is carried out only
if there is good reason to suspect serious structural deficiencies that could lead to
spread of fire beyond the flat of fire origin. The age of the block alone is not generally
sufficient to warrant a Type 2 inspection. The need for a Type 2 fire risk assessment
may sometimes be identified in a Type 1 fire risk assessment, but should not simply be
recommended as a matter of course.
A Type 3 fire risk assessment includes the work involved in a Type 1 fire risk
assessment, but goes beyond the scope of the FSO (though not the scope of the
Housing Act). This risk assessment considers the arrangements for means of escape
and fire detection (ie smoke alarms) within at least a sample of the flats. Within the flats,
the inspection is non-destructive, but the fire resistance of doors to rooms is considered.
Measures to prevent fire are not considered unless (eg in the case of maintenance
of the electrical and heating installations) the measures are within the control of, for
example, the landlord.
A Type 3 fire risk assessment may sometimes be appropriate for rented flats if there
is reason to suspect serious risk to residents in the event of a fire in their flats. (This
might be, for example, because of the age of the block or reason for suspicion of
widespread, unauthorised material alterations). This type of fire risk assessment will not
be possible in the case of long leasehold flats, as there is normally no right of access for
freeholders.
A Type 4 fire risk assessment has the same scope of work as a Type 3 fire risk
assessment, except that there is a degree of destructive inspection, in both the common
parts and the flats, carried out on a sampling basis. This will usually necessitate the
presence of a contractor for the purpose of opening up construction and making good
after the inspection. However, the nature of the work is such that, often, destructive
inspection within flats can only be carried out in those that are vacant.
This is the most comprehensive fire risk assessment, but will only be appropriate in
limited circumstances – such as when a new landlord takes over a block of flats in
which the history of works carried out is unknown and there is reason to suspect serious
risk to residents from both a fire in their own flats and a fire in neighbours’ flats.
Note: Before destructive inspection is to be carried out, the risk of disturbing asbestos
should be considered (eg by examination of the asbestos register).
36.3 If the responsible person employs five or more people in the organisation (regardless
of where they are employed to work), the significant findings of the fire risk assessment
must be documented. (Under certain circumstances, this can be required where less
than five persons are employed.)
36.4 The minimum information that must be recorded in the above circumstances comprises:
• the measures that have been taken, or are in place, to satisfy the FSO
• the measures that will be taken to achieve compliance (the action plan)
• any group of persons identified by the fire risk assessment as especially at risk.
36.5 There is no legal requirement to use any particular style or format for recording the
findings of a fire risk assessment. (DCLG guidance and PAS 79 contain templates that
can be used, but are simply examples, and other formats can be equally acceptable.)
• Will the plan, once implemented, achieve adequate safety for people?
• Will any hazards to health and safety be created?
• Are the actions reasonably practicable, taking cost, effort and risk into account?
• What will the view of residents be if the actions are implemented?
• Will it be practicable to maintain the precautions in place during normal use of the
building?
• Do the proposed actions have any implications for accessibility and safety of disabled
people?
38.2 In the case of taller blocks of flats (eg comprising more than a ground and three
upper storeys), more specialist knowledge may be necessary to carry out a fire risk
assessment, particularly if the block was designed and constructed before 1992.
However, the decision as to whether to use outside specialists to carry out a fire risk
assessment rests with the responsible person.
38.3 Regardless of who carries it out, the Responsible person will be liable to prosecution if,
as a result of an inadequate fire risk assessment, people are placed at the risk of death
or serious injury in case of fire. Equally, anyone carrying out the fire risk assessment
for the responsible person has the same liability. Nevertheless, external services can
only be advisory in nature and there will still be a need for some involvement of the
responsible person in the fire risk assessment process – even if only to provide certain
information and arrange access.
39.2 Guidance on selecting a suitable professional fire risk assessor is given in Appendix 3 to
this guide.
40.2 For compliance with the FSO, fire risk assessments need to be reviewed:
40.3 Review of a fire risk assessment is not necessarily the same as a repeat of the entire
fire risk assessment process. If a thorough fire risk assessment has been carried out, a
shorter review exercise might be carried out regularly, with a more fundamental new fire
risk assessment competed at less regular intervals.
40.4 The frequency with which fire risk assessments should be reviewed in the absence of
any known changes is not defined in the FSO. The date by which a fire risk assessment
should be reviewed should be determined as part of the process of carrying out a fire
risk assessment.
40.5 The frequency of review should take into account the rate with which changes, including
those arising from the need for maintenance work, are likely to occur, and the risk to
people that might arise from changes. This means that a less frequent review might
be acceptable if there is close management control of the common parts, including
frequent routine inspections.
40.6 As a general guide, for a low risk, modern, low-rise block (eg a block of no more than
three storeys above ground, built within the last 20 years), a review every two years
might be sufficient, with a new fire risk assessment completed every four years. For
blocks with higher risk – arising from social factors, the age of the building, and so forth
– and blocks over four storeys in height, an annual review might be more appropriate,
with a new fire risk assessment every three years. In extreme cases, for the highest risk
premises, an annual fire risk assessment might be appropriate.
• specify what type of fire risk assessment is required – remember Type 1 will often
suffice and other types involve extra time, cost and disruption that may not be justified
unless there is good reason to suspect serious deficiencies in fire safety
• ensure you provide the fire risk assessor with relevant information on the building, the
occupants and arrangements for management of fire safety
• recognise that all risk assessments will involve a degree of access to a sample of flats –
you will need to assist in arranging access
• where you specify a risk assessment requiring destructive surveys, expect to employ a
contractor to open up the construction – rarely do third party fire risk assessors have in-
house resources to carry this out
• recognise that no risk assessment can be exhaustive – expect recommendations for
further investigation if there is difficulty in establishing, for example, the suitability of
floors and walls to resist fire-spread – however, challenge generic recommendations
which are not supported by justified concern that serious deficiencies are present,
taking into account all relevant sections of this guidance
• consider specifying the style and format you require for the fire risk assessment
reports – consider adopting recognised templates, such as those in PAS 79 or the HM
Government guide ‘Fire safety risk assessment: sleeping accommodation’.
• insist that action plans include a clear priority and timescale for all recommendations
and differentiate between those recommendations essential to satisfy legislation and
those that are a matter of good practice
• remember that using an external specialist does not absolve you of your responsibilities
under the FSO
• ensure your fire risk assessor is competent
• establish that your fire risk assessor has suitable experience and knowledge of carrying
out fire risk assessments in the type of buildings within your housing stock.
Key points
• Prevention of fire, as far as possible, is essential.
• The most likely place for fire to start is within a flat. However, fires within the common parts
are particularly dangerous.
• There should be vigilance to ensure that people do not smoke in the common parts.
• Arson is a common cause of fire, so good security is part of fire prevention.
• Poor housekeeping in the common parts is a significant fire hazard.
• There should be a clear policy on whether common parts must remain completely sterile
(‘zero tolerance’) or may be subject to ‘managed use’.
• Fixed electrical installations should be subject to periodic inspection and test every five
years in the case of the common parts, and every ten years for the installations in flats.
• Heating and ventilation systems should be maintained regularly, particularly where they
serve the common parts or are common to more than one flat.
• Any lightning protection systems should be subject to regular maintenance.
41.2 This part of the guide is aimed primarily at giving guidance on fire prevention within the
common parts of blocks of flats. However, the most likely place for a fire to start within
a block of flats is the flats themselves. It is recognised that the scope for landlords to
take steps to prevent fires within flats is limited. Nevertheless, there are opportunities in
rented flats through, for example, regular gas safety checks and periodic inspections of
electrical installations to impact on the potential for certain fires within flats.
41.3 It is strongly recommended that landlords and those managing blocks of flats take every
suitable opportunity to engage with, and educate, residents on basic fire prevention.
This is discussed further in Part G of this guide.
41.4 Common hazards and possible measures to control or eliminate them are set out below.
However, a guide such as this cannot be exhaustive, and landlords and those managing
fire safety must be vigilant for other hazards that might be present or new hazards that
might materialise in the future.
42. Smoking
42.1 By law, smoking is not allowed in the common parts of blocks of flats. There still
exists the very real need to remain vigilant, not only because of people inadvertently
smoking in areas where the law prohibits it, but also because of illicit and surreptitious
smoking. Indeed, with regard
to smoking, people’s efforts
to conceal their actions, can
often result in increased risk.
43. Arson
43.1 In 2008, deliberate ignition was the cause of some 17 per cent of fires in dwellings – the
third largest cause of fires in dwellings. These fires resulted in 59 deaths and nearly 1,600
non-fatal casualties6. Security is therefore a key element of fire prevention in blocks of flats.
43.2 The nature of deliberate fires experienced in blocks of flats varies, but can range from
people setting fire to rubbish and storage left within the common parts to igniting flammable
liquid poured through letter boxes of front doors. The profile of those carrying out such acts
clearly varies. Anti-social behaviour can be a factor in accounting for some of these fires.
Basic security can often be very effective in countering these fires.
43.3 However, it must be recognised that some fires are started by those with the deliberate
intent of causing serious harm to people. It is unlikely to be practical to implement physical
measures completely to counter this risk. Vigilance by residents, along with visiting staff
and contractors, will continue to be key to any programme of arson prevention.
Measures that can be used to address the potential for arson include:
• good physical security, with suitable locks on doors and windows in common parts
• where appropriate, access control linked to entry-phones in flats
• effective lighting, both externally and internally, in the common parts
• where appropriate, CCTV, particularly on entrances and external façades
• maintaining common areas free from combustible material
• where possible, maintaining a presence by people such as caretakers and concierges
• where appropriate, for communal letterboxes, use of suitable enclosures designed to
contain burning material
• supporting initiatives to address anti-social behaviour.
43.5 Residents should also be encouraged to make their homes secure. Advice on crime
prevention in the home is available from
43.6 Residents may take their own measures, including fitting additional locks to front
doors and installing intruder alarm systems. Again, care is needed to ensure that any
measures taken do not conflict with the need to escape in the event of fire. Where
possible, leases should be used to constrain the fitting of excessive security measures,
such as grilles, gates and shutters, that might:
Security doors that achieve 30 minutes fire resistance are available. Security doors
that can be easily removed by the fire and rescue service in an emergency are also
available.
44. Housekeeping
44.1 Good housekeeping is fundamental
to reducing risk in blocks of flats.
Controlling the presence of combustible
materials and ignition sources not only
reduces the potential for accidental fires
to start and develop in the common
parts, it also significantly reduces
the scope for deliberate fires. It also
ensures escape routes are free of
obstructions that might hinder the
evacuation of people from the building
and access for fire-fighters.
44.6 The inappropriate actions of residents in this regard could also be exposing landlords
and others who manage the common parts to liability under fire safety law.
• rubbish bags
• wheeled bins
• buggies and prams
• mobility scooters, bicycles and motor cycles
• lockers and cabinets
• washing machines, tumble dryers and other goods awaiting disposal
• unwanted bedding and mattresses
• upholstered seating
• children’s toys and play furniture
• shopping trolleys.
44.9 This suggests that it might be possible to allow some items to be present without unduly
exposing residents to risk. However, the difficulties landlords and others responsible for
the common parts face is how to manage use of the building in this way.
44.10 Unrestricted use of common parts is clearly not acceptable. It will, therefore, be
necessary to adopt one of the following alternatives:
i. ‘zero tolerance’
ii. ‘managed use’
44.11 A ‘zero tolerance’ approach is one in which residents are not permitted to use the
common parts to store or dispose of their belongings or rubbish. No exceptions
would apply. It would ensure that the common parts are effectively ‘sterile’ ie free of
combustible material, ignition sources and obstructions.
• by not taking into account the specific circumstances, this policy might not be risk
proportionate
• it unduly penalises those who could manage their common parts effectively
• it denies residents an opportunity to personalise and improve their living environment.
44.14 The alternative is ‘managed use’. This approach allows strictly defined use of common
parts and limits the items allowed, to control fire load and ease of ignition. It includes
strict conditions on where such items can be kept. For example, a ‘managed use’ policy
might permit residents to:
• place pot plants and door mats outside their front doors
• have framed pictures and notice boards on walls
• store bicycles, prams and mobility scooters in places that are out of the way and not
likely to cause obstruction.
44.15 This approach also has advantages and disadvantages. The benefits include:
• by making the common areas ‘homely’, it fosters a sense of pride and value in the
block, which can impact positively on anti-social behaviour
• it benefits older and disabled people in particular, by allowing them to store mobility
aids at the point of access
• it allows the specific risk factors in the building to be taken into account.
• it is more difficult to adopt as it requires a clearly defined policy with a list of ‘dos and
don’ts’
44.17 The most appropriate approach will depend on the specific circumstances, and whatever
approach is taken should be considered within the overall context of the fire safety
measures in the building. It should be considered as part of the fire risk assessment for
the block. A managed use and its constraints can often be agreed by consultation with
residents.
44.18 While it may be easier for landlords to take the ‘zero tolerance’ approach, it should
be recognised that residents may be put at significant inconvenience and resort to
infringements of the policy through frustration. Consideration of the needs of residents in
ways that encourage them to follow the constraints of such an approach can contribute
significantly to fire safety. Providing suitable communal storage facilities and, for example,
charging rooms for mobility scooters, can greatly assist.
• carry out a specific risk assessment taking into account the particular circumstances in
the building
• consider whether residents are disposed towards keeping ‘rules’, and avoid ‘managed
use’ where this is not the case
• ensure that there are clearly defined ‘do’s and don’ts’ that residents can easily follow
• only apply it where there is a suitable standard of fire protection – particular care should
be taken when applying it to situations such as single stairway buildings and ‘dead end’
corridors
• limit it to buildings in which the main elements of structure are made of concrete, brick
and other non-combustible materials
45. Recycling
45.1 Recycling initiatives encourage residents to avoid waste and use resources sustainably.
However, collection schemes often involve materials being set out in corridors, lobbies
and stairways within the common parts, giving rise to a potentially serious fire hazard.
45.2 Bags of clothes for charity and boxes and bags of newspapers and plastic containers
represent a significant fire load. The material is in a form in which it can be easily ignited
and lead to extensive fire-spread and smoke production.
45.4 While only transitory, such material is nevertheless wholly inappropriate. It cannot be
considered acceptable even where ‘managed use’ policies apply. Landlords should put
in place alternative arrangements for recycling that do not rely on collection from within
the common parts.
46.2 Ignition of combustible materials through overheating or arcing can result when faults
develop in wiring or in appliances. Such faults are often evident before a fire occurs.
Householders can considerably reduce the likelihood of a fire developing by being
vigilant when appliances do not work or circuit-breakers keep tripping, and arranging
for these faults to receive attention. Residents should also be encouraged to take
preventive action by arranging for their electrical installation to be inspected and tested
periodically.
46.4 An interval of 10 years between such inspections would be appropriate for flats where
a long term tenancy agreement is in place. An interval of five years might be more
appropriate for situations where the tenancy is shorter.
46.5 Where tenant turnover is high, the landlord would be well advised to have a thorough
visual inspection of the accessible parts of the electrical installations. For example,
landlords should look for signs of damage to installed equipment and accessories which
have made access to live parts possible or other defects or deterioration which may
pose a danger to the next tenants.
46.6 The interval between inspection and testing can be extended where no damage
has been observed which would make the flat unsafe over a number of inspections.
Conversely, the interval should be reduced where the inspector finds evidence of
significant damage or deterioration.
46.7 Current guidance states that the electrical installations supplying the flats and the
common parts of the block should also be subject to periodic inspection and test. This
should be undertaken every five years.
46.9 Any portable electrical appliances that might be present in the common parts and other
areas under the control of the responsible person should also be subject to inspection
and test on a regular basis. Guidance on the nature and frequency of this can be
found in the IET Code of Practice for In-Service Inspection and Testing of Electrical
Equipment.
• be vigilant during inspections for any obvious damage to electrical fittings and
equipment within the common parts
• make sure electrical distribution boards are located in secure cupboards or rooms,
within which there is no storage or rubbish
• stop residents from connecting wiring from their flats to decorative lights or other
equipment in the common parts
• look out for residents using sockets in the common parts to charge their appliances or
power equipment within their flats – running extension leads compounds the hazard by
compromising the fire separation between the flats and the common parts
• consider installing key-operated socket outlets within common parts to restrict access to
cleaners and other legitimate users.
47.2 The hazards arising from communal heating and ventilation systems include both a
potential for ignition and a route for fire-spread through common ducts and risers.
Planned preventive maintenance is the key to minimising the likelihood that, for
example:
a fire within supply and extract fans or in ductwork will spread smoke and flames
through a building.
47.3 Where portable heaters are used – eg in TRA lounges and community rooms – these
should be suitable for their intended use and not subject to easily being knocked over or
damaged. Portable gas heaters should not be used.
48. Lightning
48.1 Lightning is a source of ignition in a small proportion of fires. However, the risk depends
on factors such as:
A risk assessment tool for determining the need for lightning protection on a block of
flats can be found in BS EN 62305-2, but normally needs a specialist to apply it.
49.2 There are other hazards that might only be present on occasions. Good examples
are the hazards associated with building works and contractors operations. This is
considered in Part G of this guide.
Key points
• Benchmarks should be used to assess the standard of fire protection in a block of flats.
These are not prescriptive, and the aim should be to use them to determine a reasonable
approach to improving fire safety where the fire protection measures have been found to
be inadequate.
• Initially, these benchmarks might be those that were in place when the block was built,
rather than those that currently apply.
• However, upgrading existing buildings to meet current benchmarks may be appropriate in
situations in which the original standards are far removed from what is acceptable today,
and, as a result, there is unacceptable risk.
• While the appropriate solution might be to restore what was originally in place, upgrading
to achieve current benchmarks should take place when the opportunity arises, such as
through the normal process of refurbishment.
• When upgrading fire precautions, fire protection products and services should be fit for
purpose and properly installed. Third party certification schemes are available for many
such products and services.
• Effective compartmentation is fundamental to ensuring adequate fire safety in blocks of
flats. It is therefore vital that floors and walls are in good condition and that there are no
openings that would permit uncontrolled spread of fire and smoke.
• Particular attention should be given to the potential for fire-spread through common
ventilation ducts.
• Escape routes from flats in some older blocks may involve forms of alternative exit, such
as linking balconies and pass doors, that are no longer recommended. Compensatory
measures may need to be provided where this is the case.
• Increases in travel distance and other departures from current benchmark design guidance
may need to be accepted. Compensatory measures may again be required in some cases.
• Original flat entrance doors in many older blocks will not meet current standards. In
some situations, it will be appropriate to accept the door as it is; in others, upgrading or
replacement of the doors will be necessary. This will depend on the risk.
• The fitting of suitable self-closing devices to flat entrance doors is an essential short-term
measure.
50.2 Set out below are benchmarks, against which the standard of safety in a particular block
can be assessed, but these should not be seen as prescriptive standards.
50.3 Initially, a fire will only present a threat to those in its immediate vicinity. The majority
of fires in purpose-built blocks of flats do not spread beyond the location of origin.
However, it has also to be assumed there is a small chance that, at some stage, fire
might spread to affect other areas of the building, including the common parts and the
communal escape routes.
52.2 Initially, these benchmarks might be those that were in place when the block was built and
not those that currently apply. Indeed, it is normally inappropriate to retrospectively upgrade
existing blocks to meet current benchmarks without justification on the basis of fire risk.
52.3 Nevertheless, there may be situations in which the original benchmarks of the day
are far removed from what is acceptable today and, as a result, there may be an
unacceptable risk.
• the benchmark standards recommended by current design codes and guides for the
design of modern blocks of flats
• the most commonly found differences between newly built blocks and those designed
to meet the standards of the day that applied when an existing block was built
• possible solutions that might be suitable where the standard found in an existing
building has not been maintained in line with the original design intent, or falls far
short of the standard considered acceptable today.
52.5 The following illustrates a framework used when carrying out a fire risk assessment for
comparing the standard of fire safety found in a particular block with these benchmarks.
Prioritise requirements NO
52.6 The aim is to determine a reasonable approach to improving fire safety in existing
blocks of flats where the existing fire safety measures have been found to be
inadequate.
52.7 It must be recognised that it will not always be reasonably practicable to achieve
solutions that conform to today’s standards. The appropriate solution may simply be
to restore what was originally there until such time as it can be upgraded through the
normal process of refurbishment of the building. The objective is to establish whether
the departures from current benchmarks create significant risk and, if they do, to
determine a realistic solution that can be implemented within the constraints of an
existing building.
52.8 An example that illustrates this approach is the replacement of a flat entrance door by
a resident with a non-fire-resisting door that is not self-closing. As discussed later, the
current benchmark standard is for flat entrance doors to be self-closing doors, capable
of providing 30-minute fire resistance and incorporating intumescent strips and smoke
seals (FD30S). If the door that had been replaced was in a block dating from, say, the
1960s, it is most likely that the original door would be fire-resisting, but might only be
fitted with rising butt hinges. It would not incorporate intumescent strips and smoke
seals.
52.9 In the situation described above, the replacement door does not meet current
benchmark standards. It also does not meet the standards of the day the block was
built. Those standards have not been relaxed. The new door, if replaced with a door
similar to the one originally fitted, would still not meet current standards. As explained
later, the lack of a positive action self-closing device at the very least is considered to
create significant risk. In practice, replacement of the new door with an FD30S door,
fitted with a positive action self-closing device, would be the appropriate solution.
52.10 As another example, it is frequently found that residents have also removed original
self-closing devices from internal doors within flats, which were required by the
standards of the day. However, these self-closing devices are not now required for
compliance with current Building Regulations. Accordingly, under most circumstances,
they are no longer necessary within existing flats (see paragraph 56.23).
52.11 Other examples of the application of this approach and the guidance that follows
below are contained in Appendices 7–12.
52.12 Appendix 1 contains a history of fire safety design standards for purpose-built blocks
of flats. It is therefore, a reference source for determining the standard that applied
when a particular block was built.
53.2 Third-party certification schemes for fire protection products and related services are an
effective means of providing the fullest possible assurances, offering a level of quality,
reliability and safety that non-certificated products may lack. This does not mean goods
and services that are not third-party approved are less reliable, but there is no obvious
way in which this can be demonstrated.
53.3 Third-party quality assurance can offer comfort, both as a means of satisfying you
that goods and services you have purchased are fit for purpose, and as a means of
demonstrating that you have complied with the law.
54. Compartmentation
54.1 Adequate compartmentation is a basic requirement in all purpose-built blocks of flats.
The standard of fire separation, whether between individual flats, between flats and the
common parts, or between the common parts and ancillary accommodation, such as
refuse chutes and plant rooms, should be a key consideration when undertaking a fire
risk assessment.
54.2 The standard of compartmentation and fire separation recommended in design guides for
blocks of flats has changed over the years, particularly in comparison to those published
prior to the 1960s. This has inevitably led to variations, both in the nature of the construction
and in the periods of fire resistance that can be found in existing blocks of flats.
54.3 Current benchmark design guidance for new purpose-built blocks of flats recommends
that the following should be constructed as compartment walls and floors:
• every floor (unless it is within a multi-level flat)
• every wall separating a flat from any other part of the building
• every wall and floor enclosing a refuse storage room.
54.4 The current minimum level of fire resistance is 60 minutes (higher in the case of high-
rise blocks, but normally 30 minutes in small, two-storey blocks of flats). Previous
design standards for older, traditionally built blocks of flats, with timber floors, permitted
a lower level of fire resistance, typically 30 minutes.
54.5 In practice, the materials that were used, and the method of construction adopted, in
older blocks of flats, might not achieve these periods of fire resistance. Traditionally,
the combination of a lath and plaster ceiling below a timber floor was only considered
54.6 In principle, the potential risk to the occupants of flats increases with the height of the
block, the size of the building and the number of flats present. It may, therefore, be
reasonable to accept reduced levels of fire resistance for compartment floors and walls
in existing small, low-rise blocks. However, this would depend on other inter-related
factors, most importantly the provision of adequate means of escape. Benchmark levels
are set out below.
As a benchmark, the minimum levels of fire resistance for compartment walls and
floors for existing blocks of flats should be:
• three-storey – notional 30 minutes fire resistance – typically timber floors with lath and
plaster ceilings.
• four- and five-storey – full 30 minutes fire resistance – typically timber floors with
plasterboard ceilings.
• six-storey and above – 60 minutes fire resistance.
54.7 In certain situations, in existing blocks where these periods of fire resistance are not met
or cannot readily be achieved by upgrading, compensatory fire protection measures may
need to be considered. These measures might include one or more of the following:
• improving the means of escape by providing an alternative escape route or upgrading
protection to the enclosure of escape routes to current benchmark design standards, eg
FD30S doors
• provision of an automatic fire detection and alarm system to compensate for the
reduced levels of fire resistance
• provision of a sprinkler, or other suitable fixed automatic suppression, system.
54.8 It is vital that floors and walls are in good condition and that there are no openings,
whether intentional or unintentional, that would permit the uncontrolled spread of fire and
smoke. The potential for fire to spread through any service ducts and risers, ventilation
ducts and refuse chutes, and by means of openings around gas, electricity, water,
drainage and telecommunications services, should be considered.
54.9 Obvious openings between floors, and in walls between flats and other ancillary
accommodation (eg plant rooms) and the common parts, should be considered. Particular
attention should be paid to service ducts or risers and any common ventilation systems.
54.11 Small bore pipes, typically less than 40mm in diameter, are not normally considered
to be of concern. Larger pipes, especially if made of a combustible material, could, in a
fire, give rise to an opening that will allow significant fire and smoke-spread. Proprietary
fire seals, including externally mounted collars, or fire-resisting enclosures, are used in
new buildings and could be used to address this problem in older blocks. However, the
difficulties of retrofitting such seals in an occupied block of flats may mean that it will only
be practicable to undertake this on a long-term basis as and when flats become vacant.
54.12 In addition, in some designs of blocks of flats, use will be made of common ventilation
ducts to provide extract from bathrooms and, less commonly, kitchens. These ducts
may well travel the full height of the building, serving a large number of flats and
terminating at roof level.
54.13 It has been traditional for many years for the common extract from bathrooms to
incorporate shunt ducts, which reduce the likelihood of fire and smoke-spread between
flats. Some earlier designs used the same arrangement for kitchen extract, although this
was not a preferred method.
Inner rooms
56.2 An inner room is a room from which escape is only possible by passing through another
room (access room). These situations can commonly occur in larger flats and will also
occur in open plan layouts and galleries. In addition, it is not uncommon for the occupants
of flats to remove internal doors or partitions, thereby creating inner room situations.
Access room
Inner room
56.6 The provision of alternative exits via linking balconies, pass-doors between adjoining
flats and break-out panels within the flat has featured in previous guidance and can
be found in many existing blocks of flats. However, these arrangements are no longer
recommended (see 56.27).
56.7 Where none of the above arrangements are practicable, a fire engineering solution
based on automatic fire detection and a sprinkler, or other suitable fixed automatic
suppression system, could be considered. However, in this case, the access room
should not be a kitchen.
Flats with no floor more than 4.5m above ground or access level
56.8 Current benchmark design guidance for new purpose-built blocks of flats recommends
the following.
• Single storey flats on ground or first-floor levels: all habitable rooms, except kitchens,
should open directly onto a hallway leading to the entrance door or an alternative exit,
or be provided with an escape window or door.
• In flats on two levels: on the ground floor, all habitable rooms, except kitchens, should
open directly onto a hallway leading to the entrance door or an alternative exit, or be
provided with an escape window or door. On the first floor, all habitable rooms, except
kitchens, should be provided with an alternative exit via an escape window or door, or
open directly onto an internal protected stairway leading to an exit.
Single-storey flats located more than 4.5m above ground or access level
56.11 There are three commonly acceptable approaches to providing adequate means of
escape from flats where all rooms and the entrance door are on a single level. These
are:
• limit the travel distance within the flat Figure 3 – Flat with limited
travel distance
• provide a protected entrance hall
• provide an alternative exit.
56.15 Compensatory measures might include increased levels of automatic detection and
fire-resisting doors to any kitchen or lounge.
56.16 With a protected entrance hall, the escape route within the flat should remain relatively
smoke free in the early stages of a fire in a room. But, as an additional safeguard, the
length of travel in the entrance hall is limited (see figure 4).
56.20 Fitting self-closing devices to internal fire-resisting doors that open onto protected
entrance halls was a normal requirement of previous benchmark standards. In many
cases, in older blocks, these would have been rising butt hinges, which, over the years,
have often become ineffective.
56.22 This then raises the question as to whether or not internal fire-resisting doors that were
originally required to have self-closing devices should have these devices reinstated to
meet the standard of the day.
56.24 It is not uncommon to find in some circumstances that residents have either changed
internal fire doors to non-fire-resisting doors or have removed doors and, in some
cases, partitions, altogether, thus creating inner rooms. Reinstating the fire doors and
partitions will ensure adequate means of escape. This may be necessary to protect the
common means of escape where there is dependence on the protection of the internal
hallway to safeguard the communal escape routes.
56.25 Current design guidance for flats with alternative exits is as follows.
56.29 Despite the above, in many existing flats, the provision of other, more suitable
alternative exit routes, such as common balconies or stairways, will be impractical
to achieve. In these situations, either one of the other two approaches (limited travel
distance or protected entrance hallway) should be adopted, or compensatory measures
will need to be considered. The latter include:
56.30 However, there may be circumstances where, even with these additional measures,
the access to the linking balcony or the pass doors might still be retained for use as a
last resort.
Flats with more than one storey, with a floor at more than 4.5m above ground
level
56.31 The internal means of escape from flats with more than one storey (eg maisonettes
and cross-over flats), with a floor at more than 4.5m above ground level, provide
additional issues to those encountered in flats on one level. Nevertheless, the basic
approaches of providing either a protected exit route or an alternative exit remain the
same.
56.32 Current benchmark design guidance recommends four approaches to the planning of
means of escape from these flats:
i. provide an alternative exit from each habitable room that is not on the entrance level
ii. provide a single alternative exit from each level, other than the entrance level, and
provide a protected landing and hallway
iii. provide a protected route and install additional automatic detection
iv. provide a protected route and install an automatic suppression system.
57.2 Adequate levels of fire protection need to be provided to the communal escape routes
so that smoke and heat from a fire in a flat or ancillary room will not prejudice use of the
corridors, lobbies, external balconies or stairways. This will include provisions to ensure
that the common escape routes remain relatively smoke free and safe to use in the
event of a fire.
57.3 In general, in existing blocks of flats, to access the flat entrance doors, it is necessary
to use either an internal corridor or lobby, or an external balcony or deck, off a common
stairway. The provisions required to safeguard the escape routes in each of these
scenarios will vary.
• provide protected corridors and lobbies leading to a stairway and limit the distance of
horizontal travel
• provide independent alternative escape routes from each flat, either by way of a
common internal corridor at another level or by an external common balcony, in both
cases leading to a stairway.
58.2 The corridors and lobbies used for means of escape need to be protected routes ie
enclosed in construction with at least 30 minutes fire resistance. As discussed earlier,
walls between flats and the common parts need to be compartment walls and, as
such, will provide the necessary fire resistance. Ancillary rooms, risers and other areas
opening onto corridors and lobbies also need to provide this protection.
58.3 Doors from ancillary rooms, as well as flat entrance doors, need to be fire-resisting.
The current benchmark for doors opening into internal corridors and lobbies should be
capable of providing 30 minutes fire resistance and – with the exception of risers and
ancillary rooms – the doors need to be self-closing.
58.5 Stairways should lead directly to a final exit, or to a protected route leading to a final
exit. The stairways should not contain any significant fire hazards and should, ideally,
not contain anything other than lifts or protected electrical meter cupboards. Ideally, gas
installations should not be located within protected stairways.
58.6 It is unlikely that the width of stairways will be a significant issue with regard to their
capacity for use for escape, as there is normally no requirement for simultaneous
evacuation of purpose-built blocks of flats. Therefore, the number of people expected
to use a stairway in the event of a fire will be limited. Widths of 1,000 millimetres (mm)
would normally be considered adequate for means of escape in most cases. Indeed,
narrower stairways may well be found in some existing buildings, and these will
generally be acceptable depending on the circumstances.
58.7 In single stairway buildings, other than in small blocks of flats (less than four storeys), the
stairway should, ideally, not continue down to serve a basement or enclosed car park. In
multiple stairway buildings, where the stairways serve basements and car parks, one of the
stairways should, preferably, be terminated at ground level. Other stairways may extend to
serve basements, providing they have lobby or corridor protection at basement level.
58.8 Except in small blocks of flats, a single stairway should, ideally, not serve any boiler
room, fuel storage room or other similar high-risk ancillary rooms. In multiple stairway
blocks of flats, the ancillary rooms should, normally, be separated from the stairways by
a protected lobby or corridor.
Smoke control
58.9 Both current design guidance and previous standards for purpose-built blocks of flats
recommend that measures be provided to ensure that escape routes remain free of
smoke. However, different approaches have been employed in order to achieve this,
and, indeed, the philosophy behind smoke control design has changed over the years.
58.10 The current benchmark design guidance is based on using smoke control to protect
the common stairways. While this might afford some protection to the corridors and other
horizontal routes, this is not the design intent. The emphasis in previous design guidance
has been on protecting not only the stairways, but also the entire horizontal route to them.
58.11 The current approach is that of smoke containment, with ventilation of lobbies and
corridors where they adjoin a stairway. That ventilation can be achieved by natural or
mechanical means.
58.13 Current guidance states that vents in lobbies or corridors adjoining single stairways
should be operated automatically (AOVs). In multiple stairway blocks, manually
openable vents will suffice.
58.14 Protected stairways also need means to ventilate any smoke that may enter the
stairway during evacuation or fire fighting and allow a route for air to reach ventilated
lobbies and corridors. A vent of at least 1m2 needs to be provided at the head of the
stairway for this. Current guidance states that, in blocks of flats with more than one
escape stairway, this vent can be opened manually. But, in blocks of flats with a single
stairway, it is recommended that the vent is operated automatically (an AOV).
58.15 Mechanical ventilation systems can achieve the same objective in protecting a stairway
and, in some respects. More effectively, given that they are less influenced by wind
effects. These usually comprise pressurisation systems to keep smoke out of the stairway.
58.16 A further part of the containment principle is the subdivision of corridors linking
stairways and the separation of any dead-end sections from the rest of the corridor. This
is to ensure that smoke will not affect access to more than one stairway or, in the case
of the dead ends, affect access to the nearest stairway.
58.17 The surface finishes of walls and ceilings in escape corridors, lobbies and stairways can
significantly affect the rate of fire-spread and contribute to the development of a fire. It is,
therefore, important to control the fire performance of linings within the common parts.
58.18 Combustible surface finishes should not be permitted in escape corridors, lobbies or
stairways. Products and materials that will afford a ‘Class 0’ (or European class B-s3, d2)
58.20 However, in existing blocks of flats, it is often difficult to identify the classification of
existing surface finishes, particularly if the materials used are not obvious. Even those
finishes normally considered acceptable may have been subject to many instances of
over-painting. This can affect their performance when exposed to fire.
58.21 Multiple layers of paint have, over the years, been applied to walls and ceilings in the
common parts of blocks of flats. The build-up of paint layers can give rise to rapid fire-
spread. In these situations, where the risk is considered significant, action should be
taken to remove or treat the paint. Proprietary products are available that can be used
to treat the surfaces to provide a protective outer coating that will reduce the extent of
fire-spread. Treatments are also available for timber linings.
58.22 False ceilings can sometimes be found in the common corridors and lobbies of
blocks of flats. The materials used to construct the ceilings and the surface finishes
should preferably be non-combustible or, at least, Class 0. There should be little or no
additional fire hazards within the false ceilings. On this basis, there may not be a need
for cavity barriers to sub-divide the voids, but this would need to be considered in each
circumstance.
Benchmark guidance
58.23 The following reflects the current benchmark design guidance for both single and
multiple stairway blocks of flats with corridor or lobby access.
58.24 Current benchmark design guidance for flats with a single escape route from a flat
entrance door to the stairway is as follows.
• Every flat should be separated from the common escape stairway by a protected
corridor or lobby.
• The distance of travel between the flat entrance door and the door to a lobby or
stairway should be limited to 7.5m.
• Smoke control should be provided by natural or mechanical ventilation in the lobby or
corridor adjacent the stairway.
• The smoke vents on the fire floor and the vent at the head of the stairway should be
operated automatically by means of smoke detectors in the common access corridor
or lobby to the flats.
F F F F
F F F F
F F
Note:
hazard.
Key: F F
F = flat
Shaded area indicates a zone where
smoke ventilation should be provided.
(An external wall vent or smoke shaft
located anywhere in the shaded area)
58.25 Where a single-stairway building is small, relaxations in the provisions apply, providing:
• the top floor of the building is no more than 11m above ground level
• there are no more than three storeys above the ground level storey
• the stairway does not connect to a covered car park
• the stairway does not serve ancillary accommodation, unless the ancillary
accommodation is separated from the stairway by a protected lobby or corridor with a
permanent natural vent or ventilation by a mechanical smoke control system
• there is an openable vent provided on each floor level for use by the fire and rescue
service, or alternatively, there is a remotely operated vent at the head of the stairway.
58.26 Current benchmark design guidance for small, single stairway blocks is as follows:
• every flat is separated from the common escape stairway by a protected corridor or lobby
• the distance of travel from flat entrance doors to the stairway should be limited to 4.5m
– if smoke control is provided in the lobby, the travel distance can be increased to 7.5m
• in single-stairway buildings with only two flats per floor, the lobby between the
stairway and the flats is not essential, providing the flats have protected entrance
halls – in these circumstances, the vent at the head of the stairway should be an AOV
operated by smoke detectors.
58.27 Current benchmark design guidance for blocks with more than one common escape
stairway and alternative routes from the flat entrance door to a stairway is as follows.
• every flat should be separated from each common escape stairway by a protected
corridor or lobby
• the travel distance from a flat entrance door to the door to the nearest stairway or
lobby should be limited to 30m
• a common corridor that connects two or more escape stairways should be sub
divided by a self closing fire-resisting door to ensure smoke will not affect access to
more than one stairway – this door can be omitted if the maximum travel distance
from a flat entrance door to a stairway or lobby is not more than 15m
• any dead-end section of an access corridor should be separated from the rest of the
corridor by a self-closing fire-resisting door – the single direction of travel in the dead-
end section of corridor should be limited to 7.5m
• smoke control by natural or mechanical ventilation should be provided in the lobby or the
corridor adjacent the stairway to protect the stairway
• an openable vent should be provided at the head of the stairway.
F F F F F F F
F F F F F F F
F F F F F F F
F F F F F F F
Key:
F = flat
fd = fire door
Shaded area indicates a zone where smoke ventilation
58.28 The maximum distances of travel specified above do not apply in flats with both single
and multiple escape stairways, where all flats on a storey have independent alternative
means of escape leading to an access corridor or access lobby at another level. In
these situations, the distances specified for fire and rescue service access detailed in
71.5 will apply.
59.2 Ideally, there should be no additional fire hazards, such as stores or other ancillary
rooms, located off the balcony or deck.
59.3 There are no limitations on travel distance in the common escape routes for flats with
external balcony or deck approach. However, the distances specified for fire-fighting
access later will apply. All areas of a flat should be within 45m of the fire-fighting vehicle
access point, or within 45m of a landing valve of a dry rising main (60m when the
landing valve is in a fire-fighting shaft).
59.4 In blocks of flats where there is alternative escape available from each flat entrance
along the open balcony or deck to two or more escape stairways, the separating walls
between the flats and access balcony or deck and the flat entrance doors are not
required to be fire-resisting.
59.5 In flats with a single direction of escape to a single escape stairway, the separating
walls between the flats and the balcony or deck should be fire-resisting up to a height of
1.1m from balcony or deck level. The flat entrance doors in these situations should be
self-closing fire-resisting doors.
59.6 This will allow residents, if they wish, to pass a fire in an adjoining flat to reach the
stairway. In flats with alternative independent escape to another balcony or deck on the
same level, which leads back to the single stairway, only one of the enclosures between
the flats and the balcony needs to be fire-resisting.
60.2 In these situations, it should be ensured that the stairway remains safe to use at all times
in the event of a fire. External stairways need to be protected from a fire in the building by
means of fire-resisting partitions, fire-resisting glazing and self-closing fire-resisting doors.
61.2 Not only do some existing blocks of flats utilise escape across a roof, there are some in
A. Multi-stair building
OV OV
OV
F F F F F F F
–2
which upward escape is necessary to reach the roof. In these situations, fire-resisting
doors need to be provided across the stairways to separate the route down from the
route up.
1.8m
1.8m
3m
3m
• both buildings and/or stairways are under the same control of the landlord or owner, or,
alternatively, there are legal agreements in place to ensure right of access to use the route
• the route across the roof is adequately defined and guarded
• there is adequate emergency lighting and signage as necessary
• the part of the roof forming the escape route and its supporting structure is fire-resisting.
The latter will be particularly relevant in blocks of flats designed on the principles of smoke
dispersal, where increased travel distances were permitted. Also, the requirement for
lobby protection in single stairway blocks of flats was also different in earlier guidance,
with flats in some blocks over four storeys in height opening directly onto the stairways
and the number of flats per floor exceeding current recommendations for small blocks.
62.2 In these circumstances, upgrading to current standards, although ideal, may not be
possible, due to the physical constraints in the building, or justifiable on the basis of risk.
Therefore, there will be a need to consider the overall risk.
62.3 In some blocks, restoring the block back to the standard of the day might be all that is
needed. In others, compensatory measures might need to be considered. In exceptional
circumstances, automatic fire detection and alarm systems and automatic fire
suppression systems might also need to be considered.
62.4 The acceptance of standards in existing blocks of flats, where they significantly differ
from current benchmarks, should be subject to careful scrutiny. This may require
assessment by a suitable specialist. However, the following general guidance may
assist when considering the available options for means of escape.
62.6 The travel distances specified earlier have been found to achieve the requisite level of
safety, but were never intended to be hard and fast, and different limits have applied
in the past (see Appendix 1). The acceptance of increased distances of travel may be
considered appropriate in individual circumstances. This will be particularly relevant
in older types of property, where there will be little scope to reduce the existing travel
distances or provide alternative means of escape.
62.7 Small increases in travel distance can be accepted in most situations without any
additional measures. However, additional measures may need to be considered if there
are significant increases in travel distance. These might include:
• In unventilated lobbies, increases from the 4.5m limit to 6m are likely to be acceptable
with no additional measures.
• In unventilated lobbies, increases up to 7.5m will require additional measures, such as
‘upgraded FD30S’ doors (see later). Beyond 7.5m, the lobby should be ventilated.
• In ventilated lobbies and corridors, increases from 7.5m up to 10m are likely to be
acceptable in most situations with no additional measures.
• In ventilated lobbies and corridors, travel distances of ten to 15m may be acceptable,
providing all doors to the common corridor or lobby are at least ‘upgraded FD30S’
doors (see later) and the smoke ventilation comprises PVs or AOVs.
• In ventilated lobbies and corridors, travel distances over 15m are likely to be unusual,
and cannot be considered acceptable without additional measures, which might include
‘replacement FD30S’ doors, AOVs or automatic fire detection. The advice of specialists
will be necessary.
• Increases from 30m to 40m (eg resulting from a change from smoke dispersal to smoke
containment) should be acceptable in most situations without the need for additional
measures.
• Travel distances in excess of 40m will only be acceptable with additional measures,
which might include ‘replacement FD30S’ doors, AOVs and/or automatic fire detection.
The advice of specialists will be necessary.
62.8 As indicated in Appendix 1, previous regulations and guidance have permitted flats to
open directly onto stairways above the limits in height currently considered acceptable.
The introduction of common lobbies in these buildings is not a realistic proposition. A
possible approach to this situation when found in existing buildings is as follows.
Benchmarks for existing blocks of flats with flats opening directly on to a single
stairway
62.9 Although there have been changes in smoke control design, it is still appropriate, when
assessing an existing building’s smoke control arrangements, to review these in the light of
the standards that were in place at the time the block was built. Start by ensuring that what
is there continues to work as originally intended before considering the need to improve
the arrangements. However, in relation to smoke dispersal previous benchmark design
guidance is far removed from what is acceptable today.
62.11 An approach to three commonly found situations, in which there are unsatisfactory
smoke control provisions, is as follows.
• In single staircase blocks up to six storeys, in which flats open directly onto the
stairway, manually opening vents or windows would be acceptable.
• In single stairway blocks over six storeys, in which flats open directly onto the stairway,
AOVs should be provided.
• In single stairway blocks with corridor or lobby approach requiring smoke ventilation,
and with travel distances of 7.5 to 10m, OVs in corridors or lobbies are acceptable up
to six storeys in height. If this travel distance exceeds 10m, or the number of storeys
exceeds six, or the ventilation is provided in the stairway and not the corridor or lobby,
AOVs or PVs are required.
• In blocks of flats designed with corridor smoke dispersal systems, consideration should
be given to providing cross-corridor doors to change to a smoke containment approach,
but maintain the OVs or PVs to ventilate the sections of corridor remaining. Advice from
a specialist should be sought if smoke dispersal is present in single stairway buildings.
Fire-resisting doors
62.12 Under current benchmark design guidance, doors forming part of the protected
entrance halls and stairways within flats are normally specified as 20-minute fire-
resisting doors (designated FD20). Similarly, doors forming part of the protected escape
route from the flat entrance door to the final exit, including the flat entrance door itself,
are normally specified as 30-minute fire-resisting doors with smoke seals (designated
FD30S).
62.13 At the time they were fitted, the vast majority of these doors would have complied with
the test standard or specification of the day for a 20 or 30-minute fire-resisting door. In
addition, many of these doors have performed satisfactorily in a fire situation and, are
likely to continue to do so, providing they remain in good condition.
62.14 A modern (FD30S) fire-resisting door has intumescent strips and cold smoke seals
fitted along its side and top edges (or within the frame in these locations). Letter boxes
would be of a type incorporating intumescent materials to protect the opening. The
62.17 It will not be practicable to test existing doors to confirm their actual fire resistance.
Therefore, three options exist in relation to original fire-resisting doors that do not meet
current benchmark standards. These are:
• accept the door as it is, provided it is a good fit in its frame and that it satisfied the
standard applicable to fire-resisting doors at the time of construction of the building or
manufacture of the door (‘notional FD30’ door)
• upgrade the door by, for example, fitting intumescent strips and smoke seals along
the edges, and fitting a protected letter box (‘upgraded FD30S’ door)
• replace the door with an FD30S door (‘replacement FD30S’ door).
62.19 It is essential that, irrespective of which option is chosen, fire-resisting flat entrance
doors, and doors provided to protect common corridors, lobbies and stairways, should
be fitted with suitable positive action self-closing devices. The self-closing device
should be capable of closing the door in its frame from any angle and overcoming
the resistance of any latch. Rising butt hinges used to be acceptable under previous
benchmark guidance, but are no longer considered suitable devices because they are
unreliable in the effective closure of a door.
62.22 Any new or replacement doors within an existing block of flats should meet current
standards for fire-resisting doors (BS 476-22 or BS EN 1634 parts 1, 2 and 3). Similarly,
any letterboxes that are fitted should be of a protected type, eg lined with intumescent
material to seal the opening when exposed to fire. It may also be appropriate to
consider the upgrading or replacement of doors at the time of any major refurbishment
work.
62.23 The following is general guidance only and will depend on the specific circumstances
in a block. It refers to flat entrance doors, but a similar approach could be undertaken
when considering other doors in the common parts.
Benchmarks for existing blocks with corridor or lobby access – single and multiple
stairway blocks:
• Where means of escape, particularly travel distances are satisfactory, ‘notional FD30’
doors should continue to be acceptable.
• Where means of escape are not satisfactory, such as where there are excessive travel
distances, upgraded or replacement FD30S doors are likely to be necessary, particularly in
dead ends.
Benchmarks for existing blocks with external balcony or deck access – single
stairway or within a dead end with acceptable travel distances:
There was an error on page 100 of the guide issued on 31st July 2011.
This version is the correct version. Dated 28th September 2011
63.2 Flats with a single staircase, regardless of the number of floors, would, for example, not
usually require any fire exit signage.
63.3 In other blocks, fire exit signage may be required in circumstances where there are:
63.4 In general, ‘Fire Door Keep Locked Shut’ signs should be provided on:
63.5 In general, ‘Fire Door Keep Shut’ signs should be provided on both faces of fire-resisting
doors forming part of the protection to the common escape routes and on cross-corridor
fire doors. However, this does not apply to flat entrance doors. (In the unusual case of
fire doors that are held open, but release on operation of smoke detectors, the signs
should read ‘Automatic Fire Door Keep Clear’).
64.2 It is not necessary to provide escape lighting in small blocks of flats of no more than two
storeys, with adequate levels of natural or street lighting (borrowed lighting). However,
emergency escape lighting should be provided within all common escape routes,
including, where necessary, external stairways, balconies and roof level escape routes.
Where borrowed lighting is not reliable, eg street lighting switched off during part of the
night, emergency escape lighting may be required even in two storey blocks.
64.3 Although many existing blocks of flats may not have emergency escape lighting,
the likelihood of loss of normal lighting within escape routes, as a result of fire, at a
time when residents may need to use the escape routes, is very low. Therefore, the
installation of emergency escape lighting, particularly in low-rise blocks, is unlikely to be
a high priority compared to other improvements, such as fitting self-closing devices on
doors. However, other considerations, such as the height of the building and inadequate
normal lighting may dictate the urgency with which emergency escape lighting should
be installed.
64.4 Emergency escape lighting should conform to the recommendations and requirements
of the relevant parts of BS 5266. It should provide illumination for three hours in the
event of power failure.
64.5 One or more test switches should be provided, so that the emergency escape lighting
can be tested every month by simulating failure of the normal power supply to the
luminaires without the need to isolate normal lighting circuits.
• ideally be approached directly from the open air or by way of a protected lobby with
permanent ventilation
65.3 However, chute rooms can often be found within stairways, corridors and on balconies
on some existing blocks. In these situations, the rooms should be enclosed in fire-
resisting construction and have permanent ventilation direct to open air, designed such
that the ventilation will not prejudice any escape route in the event of fire.
65.4 Refuse chutes and access hatches can sometimes be found directly opening onto
protected corridors, lobbies and stairs, so providing the potential for the spread of fire
and smoke to the common escape routes. In these situations, an automatic fire-resisting
shutter should be fitted at the base of the refuse chute to restrict the spread of fire and
smoke from a fire in the bin room. The shutter should, as a minimum, be operated on a
fixed temperature fusible link. Further protection can be provided by a sprinkler system
located over the bins, with either frangible bulb or fusible link sprinkler heads, or open
sprinkler heads with water discharge controlled by smoke detectors. The provision of
sprinklers should always be considered where access hatches open into protected
stairways or lobbies containing more than two flat entrance doors.
66.1 In all flats, early warning of fire should be provided by means of smoke alarms installed
in accordance with BS 5839-6. A category LD3 system should be considered the
minimum in all circumstances. This is a system where there is one or more smoke
alarms solely in the circulation spaces of a flat. Flats with more than one level and those
with more than one hallway or circulation space will always require more than one
smoke alarm. Provision of smoke alarms in flats is discussed further in Appendix 6.
66.2 As stated earlier, more extensive coverage of smoke alarms (and heat alarms in certain
rooms) may be an appropriate additional compensatory measure when the escape
route design falls far short of acceptable benchmark standards. This is again discussed
further in Appendix 6.
66.3 Fire detection and alarm systems are not normally provided in the common parts of
blocks of flats (with the exception of sheltered housing schemes). This has been the
benchmark standard for many years (see Appendix 1) and continues to be the case for
new blocks of flats under the current guidance in Approved Document B.
66.4 As indicated earlier, there may be circumstances in which such a system needs to be
66.5 In any block of flats where a communal fire alarm system is installed, the system should
be of the type to which BS 5839-1 applies. Domestic smoke alarms are not appropriate for
the common parts of blocks of flats, nor is it appropriate to apply the recommendations of
BS 5839-6 to a communal fire alarm system. Where domestic smoke alarms exist in the
common parts of a block, they may, and often should, be removed and replaced (if this is
essential) with a fire alarm system of the type to which BS 5839-1 applies.
67.3 Any proposal for the provision of fire extinguishing appliances, or continued presence
of existing equipment, should be based only on full justification of the proposal by a
fire risk assessment. Where hose reels are currently provided in a block of flats, it is
recommended that, subject to consultation with the fire and rescue service, they be
removed.
67.4 Notwithstanding the above, it is appropriate to provide portable fire extinguishers in:
67.5 This does not preclude residents in any block of flats from providing their own
equipment, such as fire blankets or fire extinguishers to tackle a fire in their own flat
should they wish to do so.
67.6 Where fire extinguishers are provided, they should be installed in accordance with the
recommendations of BS 5306-8.
68.2 As flat entrance doors are required to be self-closing, there is a risk that any self-locking
security devices fitted to the doors could accidently lock residents outside of their own
flats. As well as being a general nuisance for residents who may leave their keys inside
the flat, there is also a risk during a fire if residents leave their flat and dependent family
members remain inside the flat. The danger in these circumstances is that residents
may resort to removing or disconnecting the self-closing device. Flat entrance doors
should, where possible, be fitted with a suitable lock that can only be locked on the
outside by the use of a key operated deadlock, but that can still be opened from the
inside by a handle or lever without the use of a key.
68.3 Residents sometimes also take their own security measures and fit additional locks,
and, in some cases, external security grilles and gates to entrance doors and secondary
exits. In these situations, residents should be advised of the risks these may present
to their safety in the event of a fire within their own flats. Any security locks, grilles or
gates should be easily openable without the use of a key at all times. The fitting of these
should not impair the effective self-closing of flat entrance doors.
68.4 It might be possible to restrict or prevent the use of external grilles or gates under the
terms of the lease, where:
• they do not only present a risk to the individual residents, but impinge on the safety of
others (eg if fitted on external balconies used for common escape)
68.5 All final exit doors from the building should be easily openable from the inside without the
use of a key or code by residents and visitors. A simple turn handle or lever is preferred.
68.6 Any exits fitted with separate electronic locking mechanisms, or such mechanisms
which form part of a security access system, must fail-safe on power failure and have a
standby power supply. In some situations (including mixed commercial and residential
buildings), it might be necessary to consider the provision of suitable override controls in
accordance with BS 7273-4.
68.7 When void flats are secured, it is essential that the flat entrance door remains of a type
that is fire-resisting and self-closing.
69.2 It is equally important that the common means of escape from flats is suitably protected
from the effects of a fire in other occupancies. The common means of escape routes,
including corridors, lobbies and stairways, should be separated from other occupancies
by fire-resisting construction to ensure the escape routes remain safe to use at all times.
69.4 In buildings over four storeys, where the flats are not ancillary to the main use, the flats
should be served by an independent alternative escape stairway that is not shared with
other occupancies in the building. However, a relaxation that permits a shared stairway
may be acceptable in a building where the flats do not form a substantial residential
element of the building.
69.5 Where a block of flats shares a common escape stairway with, for example, commercial
premises below, it is conventional practice to extend the fire alarm system that is
present in the commercial premises to cover the flats. This, in effect, would mean that
a ‘stay put’ policy cannot be adopted. Given the disruption this could cause, options for
designing or configuring the system to reduce the likelihood that the entire block will
need to be evacuated simultaneously should be considered (see Appendix 6).
70.2 Although some schemes still have an on-site scheme manager, many rely on on-call
systems, through social alarm systems, to provide support to residents. In these cases,
there may be only limited day-time cover and no management presence during the night
to provide any assistance to the residents in the event of a fire.
70.3 Sheltered schemes are designed and constructed on similar lines to purpose-built
blocks of flats, with compartment walls and floors and protected escape routes. The
principles of a ‘stay put’ policy apply equally in the same way to sheltered schemes as
they do to purpose-built blocks of flats.
70.4 In ‘extra care’ sheltered schemes, some residents may have difficulty in escaping from
their own flat without outside assistance. Although this, in many ways, is no different
from older persons living in their own home, it does present a particular challenge due
to the number of floors and layout of the buildings, and the lack of any management
support, particularly during the night.
70.5 The limitations of the residents should be taken into account when undertaking
assessments in sheltered schemes, and any particular concerns resulting from the
vulnerability of any residents should be addressed. However, the recommendations in
this guide for sheltered schemes are based on the assumption that residents are able to
70.6 Rather than provide protected entrance halls with self-closing doors, which can be seen
as an obstacle to older residents, planners preferred to design flats with limited travel
distances or provide alternative exits, particularly for those flats on the ground level.
When assessing the suitability of the existing internal means of escape from the flat, the
likely inability of the resident to negotiate self-closing fire doors and use escape doors or
escape windows should be carefully considered. This would include any security locks
or fastenings fitted to escape doors or windows.
70.7 Each flat within a sheltered scheme should be provided with a means of giving warning
in the event of a fire in their own flat. Each flat should have a minimum of a Grade D
Category LD3 system with smoke alarms in the circulation space or entrance hall. This
may need to be extended to a LD2 system, depending on the layout of the flat and the
nature of the resident. (See also Appendix 6 with regard to fire alarm systems covering
the common parts.)
70.8 In sheltered schemes, the distance of travel from a flat entrance door to a door to a
protected stairway, protected lobby or door sub-dividing a corridor should be limited to
allow residents to escape unaided. It cannot be assumed that a scheme manager or
other persons will be available to render assistance. Residents should not be required
to travel far in a smoke-filled corridor to a place of safety, and the current benchmark
limits on travel distance should be met in most cases.
70.9 Fire-resisting doors, including flat entrance doors, are an important element in the
protection of the common means of escape. Although it may be reasonable to accept
‘notional FD30’ doors in the smaller schemes, in many blocks, it might be more
appropriate to provide ‘upgraded FD30S’ doors as a minimum, albeit as part of a long
term programme.
70.10 Most older and disabled residents will find it difficult to negotiate self-closing fire
doors during everyday use of the building. The fitting of hold open devices, particularly
on doors within the horizontal circulation spaces and in communal areas, should be
considered.
70.11 Many older and disabled residents will find it difficult to use stairs in the event of a fire,
and additional measures may need to be considered. These could include temporary
safe refuge areas or spaces within existing protected lobbies and stairs. If lifts are
provided, where reasonably practicable, consideration should be given to the provision
of evacuation lifts that residents may use in the event of a fire.
70.12 All communal facilities – such as kitchens, lounges, laundry rooms and any plant or
service room – should, where necessary, be separated from common escape routes
including corridors and stairways. They should have 30-minute fire-resisting partitions
and fire-resisting doors. High-hazard rooms should be separated from stairways by a
protected lobby.
70.13 Adequate means of escape should be provided from communal areas, such as a
lounge, which, ideally, should have one exit leading direct to open air. Any furniture or
soft furnishings provided in the common parts should be subject to a risk assessment.
71.3 In small blocks of flats, it is usually only necessary to ensure vehicle access is
adequate, and that some means of smoke control is available. In taller blocks facilities –
such as fire mains, fire-fighting shafts and fire-fighting lifts – may be required.
71.4 In other than very unusual circumstances, there should be no requirement to provide
fire-fighting facilities in an existing block of flats or upgrade any facilities if these were
not required at the time of construction to comply with the standards of the day.
71.5 The current benchmark design guidance for fire-fighting facilities for new blocks of flats
is as follows.
• In blocks of flats without an internal fire main, there should be vehicle access for a
fire appliance to within 45m of all points within each flat. In previous guidance, this
distance was 60m.
• In blocks of flats fitted with a fire main, all points within each flat should be within 60m
of a landing valve on the fire main in a fire-fighting shaft (45m if the landing valve is in
a protected stairway).
• Flats over 18m in height should be provided with a fire-fighting shaft, consisting of a
fire-fighting stairway and a fire main located in the stairway, and a fire-fighting lift. The
fire-fighting lift can, in blocks of flats, open into the common corridor giving access to
the flat entrance doors, providing the lift doors are no more than 7.5m from the door to
the stairway.
71.7 In existing blocks of flats, the fire-fighting facilities may not be in accordance with the
above. In these circumstances, the advice of the fire and rescue service may need
to be sought, as it may not be possible, or even appropriate, to consider upgrades to
meet current benchmarks. What is important is that the facilities provided should, at
least, meet the standard of the day when the block was built and that these should be
maintained in efficient working order.
7.5m
Firefighting
Max
stairs
Firefighting
lift in lift
shaft
Minimum fire resistance 60 minutes from both sides with 30 minute fire doors
Minimum fire resistance 120 minutes from accomodation side and 60 minutes
from the shaft with 60 minutes fire doors
72.2 The use of combustible cladding materials and extensive cavities can present a risk,
particularly in high-rise blocks. Restrictions are normally applied to the nature of such
materials and in particular their surface spread of flame characteristics. Cavity barriers
are also required in some circumstances. Assistance from specialists may be required
to determine if the external surfaces of walls are satisfactory and whether there is
adequate provision of cavity barriers.
Key points
• Arrangements for managing fire safety in a block of flats should include the following.
• Developing a fire policy and appointing someone in the organisation to take overall
responsibility for fire safety.
• Making sure someone is designated to provide guidance on fire safety measures required
by the FSO, and supporting this person with help from specialists, where necessary.
• Coordinating and cooperating with other occupiers, particularly on issues such as fire
procedures.
• Using residents’ handbooks, websites and other media to engage with residents and
communicate vital fire safety messages.
• Providing generic training to ensure housing officers and others visiting blocks of flats have
sufficient fire safety awareness.
• Preparing relevant fire procedures and making everyone aware of them.
• Managing the risk from building works, including adopting a ‘hot work’ permit system.
• Putting in place programmes for routine inspection, testing, servicing and maintenance of
fire safety systems and equipment.
• Arranging similar programmes to monitor the condition of other fire safety measures, such
as fire-resisting doors.
• Monitoring the common parts through formal inspections, and as part of day-to-day
activities by staff.
• Carrying out fire risk assessment reviews to monitor standards.
• Putting in place processes for scrutinising planned alterations in order to consider their
impact on fire safety.
• Maintaining suitable records.
• Liaising with the fire and rescue service and encouraging residents to take up the offer of
home fire-safety checks.
73.2 Indeed, there are several fundamental differences between blocks of flats and many
other types of building that impact on how fire safety can, and should be, managed.
These include:
• there is usually no-one on the premises to manage fire safety on a day-to-day basis
• the response to a fire in a block of flats where the evacuation strategy is to ‘stay put’
contrasts with the immediate or progressive evacuation of the occupants in most
other buildings
• parts of the building may be under different ownership eg leasehold flats
• landlords and others responsible for fire safety have limited control over the activities
of tenants within their flats, and even less over leaseholders
• access to flats may not be possible and, even where entry can be gained, restrictions
may apply
• residents are usually a disparate group with no common allegiance – it cannot be
expected that they would respond or behave like the occupants of other types of
residential accommodation, such as hotels and halls of residence
• the level of fire safety knowledge of residents will be variable and rely upon voluntary
cooperation in embracing fire safety initiatives.
73.3 Those responsible for ensuring adequate fire safety in blocks of flats and managing this
on an ongoing basis can include owners, providers and managing agents. Also included
in this are:
73.4 Residents also have their part to play. In addition to communicating the fire prevention
message (see Part E), is a fundamental element of ongoing control over fire safety to
73.5 Fire risk assessors and enforcing authorities must understand what is achievable by
management and be realistic in their expectations. Although circumstances will differ, it
would, for example, normally be inappropriate to relax other fire safety measures in the
building on the assumption that a high level of management will be in place.
73.6 Equally, in stipulating certain fire safety measures, such as communal fire alarm
systems, there will be a consequent level of management needed. This may or may
not be possible, and solutions to fire safety should avoid placing unrealistic burdens on
management.
73.7 There are minimum requirements for fire safety management that should be achieved in
order for the standard of fire safety to be maintained at an adequate level. These, along
with examples of good practice, are discussed below.
74.2 Where responsibility is shared in this way, it is important that there is someone who has
overall control and authority to ensure that everyone’s activities are coordinated and
nothing is missed.
74.3 All organisations should formalise the roles and responsibilities of those contributing to
the management of fire safety. This should form part of a fire safety policy. Such a policy
would normally be part of arrangements required by the FSO for the effective planning,
organisation, control, monitoring and review of the ‘preventive and protective’ measures.
76.2 A key element of this is coordination of fire procedures. However, it does not imply
that, simply because the flats are in a mixed-use building, a ‘stay put’ policy will not be
appropriate.
76.3 The difficulties that can arise when a building or its fire safety systems are shared do need
to be recognised. For example, the detectors needed to operate AOVs in the lobbies to
stairways may be part of a fire alarm system covering commercial areas. As the system is
common to both, it important that a single organisation takes responsibility for its testing and
maintenance and that there is adequate recourse in contracts and leases to take action if
there is a failing on this organisation’s part to effect this.
• how they can prevent fires in their own home and in the common parts
• the importance of maintaining their block secure (making sure doors close behind
them when they enter or leave) and being vigilant for deliberate fire setting
• that they should never store or use petrol, bottled gas, paraffin heaters or other
flammable materials in their flats, on their balcony or in shared areas
• what action they should take if they discover a fire
• how they can ensure they can make their way safely from their flats and how to exit
the building once they have left their flat
• what ‘stay put’ means if there is a fire elsewhere in the building
• what they must do to safeguard communal escape routes, especially taking care to
make sure fire doors self-close properly and are not wedged, tied or otherwise held
open
77.2 Residents’ handbooks are traditionally one way to communicate basic fire safety advice to
new residents in rented accommodation. Similarly, many organisations use their website
to convey information of this nature to their tenants. Where appropriate, and subject to the
policy on use of the common parts, this can be reinforced with notices displayed in the
building. This may include the findings of the fire risk assessment.
77.3 However, specifically targeted campaigns of leafleting and other initiatives to promote
fire safety may be necessary to keep the message fresh in people’s minds, up to date
and relevant to their particular circumstances. The fire and rescue service can assist
with this, joining with landlords, other responsible persons and other agencies on
initiatives to offer free home fire-safety checks to residents.
77.4 General advice to give to residents on domestic fire safety and preventing fires in the
home is available from http://firekills.direct.gov.uk/index.html. ‘Protect yourself in your
rented home’, which is guidance on electrical safety, is also available, in both printed
and online form, from the Electrical Safety Council.
It is important that the needs of non-English speaking residents are taken into account.
Fire safety information in a number of alternative languages is available to download
from www.direct.gov.uk/en/HomeAndCommunity/InYourHome/FireSafety.
Appendix 4 to this guide also contains suitable content for basic advice to include when
communicating with residents. Basic fire action notices are usually the simplest means
of conveying to residents the actions they should take in the event of a fire.
77.5 Appendix 5 contains templates for simple fire action notices applicable both to situations
where a ‘stay put’ policy applies and situations where – by virtue of a communal fire
alarm system – a simultaneous evacuation strategy applies.
It is vital that they have a means to contact someone from the organisation who can
respond quickly if the system is activated when there is no scheme manager, caretaker
or other person responsible for the system on the premises at the time. This should be
displayed prominently by the fire alarm panel.
78.2 It is, however, important that the extent of such training and instruction, and the scope
of the information provided, should reflect the relatively simple nature of these buildings
and the limited fire safety measures present. Blocks of flats are far simpler than many
other residential buildings and often have simple means of escape.
78.3 For most employees, all that is required is basic fire awareness training. This will need
to ensure that they:
• are aware of fire hazards that might be encountered in their workplace, and in the
common parts
• know how to prevent fires
• recognise the importance of good housekeeping
• know when and how to use fire extinguishers and other fire-fighting equipment
• understand what to do if they discover a fire
• know how to escape from the building should they encounter a fire
• are aware of how their actions might adversely affect the fire safety measures present
in the building, eg by propping open fire doors
• are able to spot obvious deficiencies in fire safety measures eg a damaged fire door.
78.5 More extensive training will be required for scheme managers and other staff with a
role to play in responding to alarms and managing evacuations in sheltered housing
schemes. It is important that they are fully conversant with the fire procedures in the
emergency plan (see below).
78.6 While fire drills and practice evacuations are used in many buildings to reinforce fire
awareness training, it is neither practical nor necessary to carry them out in purpose-
built blocks of flats. Even in blocks with communal fire alarm systems, this is unrealistic.
In large sheltered housing schemes incorporating extensive communal amenities, such
as hairdressers, cafeterias and shops, fire drills may be necessary. However, these will
still only apply to people present in the common parts. Residents within their flats would
not be expected to take part in fire drills.
78.7 Employees and others working in offices, workshops and other accommodation
that may be present in the same building as the flats would be expected to receive
appropriate instruction and training and, where necessary, to take part in fire drills.
Suitable guidance on this can be found in the HM Government guide ‘Fire safety risk
assessment, offices and shops’.
78.8 Additional training may be required where in-house staff monitor fire safety as part of
routine visits and inspections. Those tasked with carrying out and/or reviewing fire risk
assessments will need appropriate training to ensure satisfactory competence.
79.2 Where fire action notices are displayed, they must be relevant. Standard fire action
notices often refer to using fire extinguishers, raising the alarm by breaking a fire alarm
call point and, once outside of the building, gathering at an assembly point. Most blocks
of flats have neither a fire alarm system nor fire extinguishers, and, given the ‘stay put’
policy that should be adopted in most blocks of flats, assembly at a designated place
serves little purpose.
79.6 This will apply equally to sheltered housing schemes. Many of these schemes do not
have scheme managers or other people on site all of the time ready to respond to
activations of the fire alarm system.
79.7 In these buildings, emergency plans will need to be more detailed. The role of scheme
managers and others in responding to fire alarm activations received from flats through
the social alarm system needs to be clearly defined. Particular consideration should be
given to the associated risks from entry into a flat where there might be a fire.
79.8 The role of scheme manager and others in assisting with the rescue of the occupants of
flats also needs to be considered. Whether through physical or mental disability, some
residents may have difficulty in leaving their flat quickly. A resident’s needs for support
are usually assessed when they take up occupation, and this should include their ability
to escape unaided in a fire. As with other aspects related to their welfare, this should be
reviewed as a matter of course as a person’s circumstances change.
79.10 Even in sheltered housing schemes, there will be reliance ultimately on rescue by
the fire and rescue service in the event that residents cannot escape by themselves.
However, in sheltered housing schemes, it is commonplace to hold information relating
to any resident with particular mobility or other issues affecting their ability to escape.
This can be made available to the fire and rescue service on arrival at the premises (eg
by keeping it in a ‘premises information box’, which can only be unlocked by the fire and
rescue service, at the main entrance). Details of any residents using oxygen or other
medical gases are also usually kept with this information.
79.11 It is not realistic to expect such an approach to be adopted where there are disabled
people and others requiring assistance in a ‘general needs’ block. Any attempts to keep
information of this kind must
be updated regularly as
inaccurate information could
potentially be more harmful
than no information.
80.2 Irrespective of whether they are undertaken by in-house personnel or a contractor, there is
potential during such works, not only to start fires or create new hazards, but also to impair
fire safety measures, even if only temporarily.
80.3 Landlords and other responsible persons should place strict obligations on those
undertaking works to implement appropriate fire precautions when carrying out works
and to avoid issues such as those above. Incorporating conditions within contracts is
one common means of achieving this, but this should also be reinforced by scrutiny of
method statements and by inspections during the course of the works.
80.4 This is often applied rigorously to major projects, but less so in the case of small works
and maintenance. However, the latter may still involve the potential to create hazards
and it is important that account is taken of this.
80.5 Of most concern is the potential for fires to be started when ‘hot work’ is undertaken. It
is vital that control is exercised over such works. Usually, this is achieved by adopting
a ‘permit to work’ system. This places obligations on those carrying out the work to
inspect the areas in which work is taking place – both before and after the work – and to
take all necessary precautions, including provision of accessible fire extinguishers.
Examples of new hazards or impairments to fire safety measures that can arise from
building works include:
81.2 Some of the inspection and testing can be carried out by in-house staff, provided
they are suitably competent. However, it is anticipated that most landlords and other
responsible persons will need to employ suitable contractors to carry this out. Again, it
is essential that these contractors are competent. Various third party certification and
approval schemes are available that provide landlords and other responsible persons
with confidence that listed companies have been assessed initially in relation to their
capability against a recognised standard, and that this is continually monitored through
surveillance visits.
81.3 Where elements of the testing are carried out by in-house staff or other non-specialists,
it is important that there is access to a suitable contractor to follow up and address
deficiencies identified through the testing. In particular it is important to attend site at
short notice to carry out emergency repairs resulting from the tests eg in the event that
a smoke vent will not close or a fire alarm system will not reset.
81.4 The following details the basic requirements for routine attention in relation to the
various fire safety systems and equipment commonly found in purpose-built blocks of
flats.
81.5 Unless the emergency lighting is of the self-testing type, there will be a need to test
each fitting periodically. In most cases, the testing involved comprises the following.
• A monthly, functional test using a suitable test facility – the purpose of this is simply
to establish by switching from the normal to the standby supply that the fitting has
not failed. This is a quick, simple test that can easily be undertaken by, for example,
housing officers, or indeed as part of value added service from contractors who visit
regularly.
• A full duration discharge test once a year – the purpose of this is to confirm that the
batteries are still capable of supplying the fitting for long enough.
81.6 Care should be taken not to leave a building entirely without escape lighting while
batteries recharge after a test.
Smoke ventilation
81.8 Systems of automatically opening vents, or vents electrically controlled but manually
operated, should be subject to routine testing and periodic servicing. AOVs and
electrically operated OVs should be tested once a month for correct operation using the
manual controls provided. Again this is a simple test that can be undertaken readily by
non-specialists.
81.9 Testing smoke detectors and controls associated with AOVs should take place at least
once a year, and in accordance with the manufacturer’s instructions.
81.10 Other systems of smoke control – including smoke extract systems and pressurisation
systems – should again be tested and serviced periodically in accordance with the
manufacturer’s instructions. This will normally be at least annually, but may involve
monthly or more frequent functional tests where the systems are intended to protect the
means of escape. It is important that those servicing such systems are familiar with the
fire engineering performance parameters used in the design of the system.
81.11 Further guidance on testing and servicing of smoke control systems can be found in
BS 9999.
81.12 Where fire extinguishers and fire blankets are provided, they should be inspected and
maintained every 12 months. This is a task for suitably trained specialists. However,
there is a role for others, such as housing officers, to be alert to any missing or
damaged equipment as part of normal walk-rounds or formal fire safety inspections and
to report this for action.
81.13 Further guidance on inspection and maintenance of fire extinguishing appliances can
be found in BS 5306-3.
81.14 Where provided, fire alarm systems should be subject to routine testing and servicing.
There are two parts to this, regular testing and periodic servicing.
81.15 A simple functional test should be undertaken, once a week, by operating a manual
call point. This can readily be carried out by non-specialists eg housing officers and
in-house maintenance teams. The aim of this test is simply to check that the system
is functional. It is not intended that this test be used to confirm audibility of the alarm,
for example. However, where operation of this system is associated with, say, release
of devices holding open fire doors, or releasing electrically locked fire exits (where
81.16 Periodic servicing should be undertaken at least once every six months.
81.17 Further guidance on testing and servicing of fire alarm systems can be found in BS
5839-1.
81.18 The need for regular testing applies equally to the smoke alarms and other devices
provided for early warning of fire within the flats themselves.
81.19 Rarely are landlords in a position to undertake this on behalf of tenants, and it is
usually the responsibility of residents to test their smoke alarms. However, landlords
should use opportunities that arise to check on the condition of smoke alarms they have
provided. For example, anyone needing to visit a flat can easily check for signs that a
tenant has interfered with a smoke alarm or otherwise disabled it. Damage to the device
and evidence of battery removal can often be readily visible. In addition, a test of a
smoke alarm could be a value added service carried out by any contractor undertaking
a routine visit for the purposes of carrying out a repair or, for example, during annual
gas safety checks.
Fire dampers
81.21 Fire dampers, where provided in communal ductwork or rubbish chutes, should be
subject to inspection and test periodically to ensure that they will still operate in a fire.
Depending on ease of access, this should be undertaken at least once every two years
for those operated by fusible links. For those that are spring operated, this should take
place every year.
81.23 Sprinkler systems and water mist systems, where provided, should be regularly tested
and serviced periodically. It is unlikely that a landlord will have staff with appropriate
specialist knowledge in-house. Suitable contractors will need to be employed. Further
guidance on testing and servicing of sprinkler systems can be found in BS EN 12845 or,
in the case of domestic sprinklers, BS 9251. Further guidance on testing and servicing
of water mist systems can be found in DD 8489-1 and, in the case of domestic water
mist systems, DD 8485-1.
81.24 Fire mains need to be inspected every six months and tested every 12 months.
Inspections largely involve simple checks to confirm that the outlets are not damaged
and padlocks and straps on the landing valves are still in place. This could readily be
incorporated within formal fire safety inspections or fire risk assessment reviews. Testing
will involve pressurising the main, and will, therefore, normally require a specialist
contractor to carry it out.
81.25 Further guidance on testing and maintenance of fire mains can be found in BS 9990.
Fire-fighting lifts
81.26 Lifts used for fire-fighting need to be subject to tests and maintenance on a regular
basis. This will involve weekly operation of override switches and monthly inspections
and annual testing and maintenance of the lifts.
81.27 Further guidance on testing and servicing of fire-fighting lifts can be found in BS 9999.
Fire-resisting doors
82.3 Good practice is to inspect timber fire-resisting doorsets on a six monthly basis as part
of a programme of planned preventive maintenance. These inspections are aimed at
identifying defects such as:
82.4 Flat entrance doors should be included within this programme. Where leasehold flats
are involved, this will only be possible if there is legal right of access, by means of a
condition within the lease to carry this out. It is important that any new leases include
such a condition.
82.6 Further advice on routine inspection and maintenance of fire-resisting doors can be
found in BS 8214.
Fire-separating construction
82.7 Routine inspection of fire-resisting walls and floors cannot be so readily achieved.
Nevertheless, damage to walls or signs of unauthorised work – including DIY by
residents – are likely to be obvious when within the common corridors, lobbies
and stairways. Fire safety inspections and fire risk assessment reviews also offer
opportunities to inspect other areas such as riser cupboards, plant rooms and so forth.
82.8 Other opportunities, such as when flats become vacant or change tenancy, should
be used to inspect the condition of compartmentation and to undertake fire safety
improvements.
82.9 Where external routes, particularly involving metal escape stairways, are part of the
means of escape, they should be subject to periodic inspection and maintenance. Fire
safety inspections should include visual checks to look for:
82.10 Survey by a specialist, at least once every three years, should also be included to
ensure that the stairway still has suitable structural integrity.
82.11 Windows and other non-electrical means provided for venting smoke should be
opened on a regular basis (eg at least once a year), to ensure that they open freely and
have not become stuck.
83.2 The extent to which formal fire safety inspections need to be carried out will vary. It
depends on how successfully standards are being maintained. However, frequent
inspections are likely to be necessary in blocks where there are particular concerns over
anti-social behaviour and the consequent threat of arson, or where a ‘managed use’
83.4 Those undertaking inspections should also be alert to new hazards that might arise from
time to time eg use of extension leads from flats to charge a mobility scooter brought in
by a visitor.
84.2 Audits and formal reviews need not take place every time there is a change of resident.
Nor, indeed, will it be necessary to do so every time minor works take place. Good
practice is to encourage a process of dynamic risk assessment by all those responsible
for fire safety. This way, people continuously think about fire safety during their work
activities.
84.3 However, periodically, and where warranted by the nature of the changes that have
taken place, a formal review needs to be carried out and should be recorded. Periodic
reviews should always include consideration of the action undertaken in response to the
previous risk assessment.
• combustible waste or storage is not present in corridors, lobbies, stairways and chute
rooms
• any notice boards are not overflowing with outdated messages and posters
• other infringements of the policy on the use of the common parts are not taking place
• doors to residents’ store rooms, electrical cupboards, plant rooms, bin stores and other
ancillary rooms are not being left or held open
• front doors and other entrance and exit doors are closing properly
• where provided, fire extinguishing appliances are not missing, discharged or damaged
• there are no signs of damage to fire-resisting walls, doors and glazing between flats
and the common parts
• vents required for smoke control have not been tampered with, forced open and damaged
(eg by residents seeking to air stuffy atmospheres or to remove the smell from illicit
smoking) or blocked up to prevent draughts
• fire exit signs or fire action notices are not missing or defaced
85.2 Processes should be in place for landlords and other responsible persons to scrutinise
alterations and building work within common parts that could have an effect on fire safety
in the block. It is important that Building Regulations approval is obtained where relevant.
85.3 Tenancy agreements should also restrict the works that tenants can undertake within flats
without first seeking permission. Leaseholders should also be suitably constrained from
making detrimental changes by virtue of the conditions within their lease.
87.2 Various methods can be used to keep records, from the commonly-used log book to
electronic devices used to capture data.
87.3 In new buildings, there is an obligation under the Building Regulations 2010 to pass
on information on the fire safety design to those who have responsibility for managing
the building and meeting their obligations under the FSO. This is particularly important
where fire engineering has been employed to produce fire safety designs that are not
code-compliant. This information is usually contained in a fire safety strategy developed
during the building project to support the approval under the Building Regulations.
87.4 It is possible that this may have applied to the larger, more complex blocks of flats
built recently. However, for most existing blocks of flats, it is unlikely that any such
information will have been documented.
87.5 There is an obligation under the FSO to maintain records of the fire safety arrangements
in a building. This is particularly important so those tasked with managing fire safety
are aware of the fire safety features incorporated within the design of the building. It is
important so that fire safety measures can be suitably maintained on an ongoing basis.
It also enables landlords and other responsible persons to ensure that these measures
are preserved and protected during future alterations to the building.
87.6 A record of the fire safety arrangements can often take the form of a simple plan of the
building showing the various fire safety measures. Such plans might be appropriate
for some medium and high-rise blocks of flats but are rarely likely to be warranted
for low-rise blocks. In practice, there will be no need for a specific record of the fire
safety arrangements in many blocks, particularly if the fire safety measures are
detailed sufficiently in the fire risk assessment. Generic policies and procedures
covering maintenance arrangements and so forth would then suffice to meet the FSO’s
requirements in this respect.
87.7 In some cases – particularly where the flats are part of a larger mixed-use development,
or where fire safety engineering has been incorporated within the design – it might be
appropriate to prepare a fire safety manual as a record of the fire safety arrangements.
This might also apply in the case of, say, a large extra care sheltered housing scheme
– particularly where different organisations are involved in the running of the building
and provision of care. Guidance on the content of a fire safety manual can be found in
BS 9999.
• the provision of any special facilities for their use, such as fire-fighting lifts and fire
mains.
88.2 Most blocks of flats would not warrant such a visit, other than possibly in the case of
high-rise blocks. However, crews may also visit larger sheltered schemes. Whether
a particular block of flats needs to be visited is a matter for the discretion of the local
fire and rescue service. Nevertheless, landlords and others with responsibility for the
blocks should welcome such visits, as pre-planning for an emergency in this way can be
invaluable.
88.3 The fire and rescue service are also able to assist landlords and others responsible
for fire safety in reinforcing the fire safety message to residents. Home fire-safety
checks are a key component of the ‘community fire safety’ initiatives of fire and rescue
services and are available to residents of any domestic dwelling. Landlords and other
responsible persons should use suitable opportunities to draw this to the attention of
residents, particularly those with special needs, such as disabled people.
A1.2 This enables a sympathetic approach to old blocks of flats designed in accordance with
superseded standards. It is not appropriate simply to apply current standards to such
blocks, with no consideration of the risk to people from continuation of the original fire
safety measures without expensive upgrading that is not proportionate to the risk. (By
analogy, an old car may not incorporate all the safety features of current models, but
may still meet road traffic legislation.) Requirements for upgrading fire safety measures
in such circumstances should be based on identification of material risk, rather than
prescriptive application of current guidance.
A1.3 General guidance on the relevant legislation and design principles that were typically
adopted at various periods of time are outlined below, along with the relevant
superseded codes of practice, which can often be consulted to obtain further detail.
Many of the codes of practice to which this appendix refers are lengthy and detailed.
They can only be briefly summarised in this guide.
A1.4 Flats built before the 20th century may well have been constructed in accordance with
local legislation and bye-laws. In the Victorian era, mansion-style blocks of flats were
constructed for upper-class people, and tenement blocks were constructed for working-
class people.
A1.5 Typically, these blocks may comprise a single stairway of four or five storeys, with flats
entered directly from the stairway, or blocks with corridors, often of considerable length,
with or without alternative stairways for means of escape from fire. In early tenements,
construction may have originally incorporated lath and plaster ceilings and timber floors,
which would, by today’s standards, not provide sufficient fire resistance between storeys.
A1.7 In the latter part of the 19th century, very basic measures to support means of escape
were sometimes incorporated, such as escape via roofs into adjacent buildings. There
may also have been efforts over the years to upgrade means of escape, by provision of
alternative escape routes comprising routes over roofs and external stairways.
• flats of more than three storeys above ground that are served by a single stairway,
with no alternative means of escape and no lobby protection of the stairway
• inadequate fire resistance between each flat and the common parts – particular note
should be taken of any glazed fanlights or sidelights, as these are unlikely to afford
any significant fire resistance, unless they have been replaced with fire-resisting
glazing or fire-resisting secondary glazing within flats
• panelled flat entrance doors, with less than a notional fire resistance of around 20
minutes if tested in accordance with current fire-resistance tests
A1.9 There were not normally any special measures for smoke control in these blocks, and it
is usually not reasonably practicable to install such facilities today. However, often there
are openable windows within common parts, which are of value to the fire and rescue
service for smoke clearance and should normally be maintained in place.
A1.10 Consideration may need to be given to any common shafts for ventilation (eg from
kitchens or bathrooms), which may have been added over the years and may not
incorporate adequate measures to prevent fire-spread between flats.
A1.11 These flats were, again, often subject to local bye-laws, produced from time to time
over many years, relating to general standards of construction, though not necessarily
to means of escape from fire. The Public Health Act 1936 empowered all local
authorities in England to make such bye-laws for the construction of buildings and the
materials used.
A1.12 The Public Health Act also required local authorities to make such requirements
as considered necessary to ensure adequate means of escape from blocks of flats
over two storeys and with a floor over 20 foot (ft) above ground level. This sometimes
comprised escape routes via roofs or external stairways.
A1.13 The power of local authorities to make bye-laws relating to these matters was withdrawn
by the Public Health Act 1961, by which time there were around 1,400 sets of bye-laws.
This Act also gave the power to ministers to produce national Building Regulations.
A1.14 In London, the London Building Acts (see below) made requirements for the
construction of buildings, and for means of escape from certain blocks of flats. Certain
other Acts, specific to particular cities, also made requirements on such matters.
A1.15 None of the above legislation made specific detailed requirements for the design
of measures such as means of escape. There were no nationally adopted codes of
practice to which reference can now be made until the publication of a British Standard
code of practice, ‘CP3 chapter lV’, in 1948. This code of practice only applied to two-
storey blocks of flats. In view of its obsolescence and very restricted scope, it is not
London legislation
A1.16 Locally applicable guidance was produced by some authorities, most notably the
London County Council (LCC) in support of their local legislation. LCC produced
guidance that applied from 1907-1936, after which it was substantially revised.
A1.17 Under the LCC guidance of 1936, a single, non-combustible stairway was acceptable
in residential blocks not exceeding four storeys above ground level, with each flat
accessed directly from the stairway (or from a protected lobby or corridor).
A1.18 There was a maximum of four flats per storey, where floors were timber and ceilings
were plastered, or six flats if the floors were non-combustible and there was a fire-
resisting screen and door separating the stairway from any common corridor. It was
required that rooms within flats had to be entered from an entrance hall.
A1.19 For blocks exceeding four storeys above ground, or with a floor more than 50ft above
ground, an alternative means of escape, independent of the stairway, was necessary.
Bedrooms in flats over 50ft in height, or on floors inaccessible to fire and rescue service
appliances, had to be entered from an entrance hall or be provided with a pass door to
the common parts or an alternative means of escape.
A1.20 In the case of ‘block dwellings’ (for working class people), access to flats was via open
balconies. In these blocks, a single stairway, partly open to the outer air, was acceptable
for blocks not exceeding four storeys above ground level (or five storeys if the top two
storeys were maisonettes) with accommodation for not more than 150 persons. All
dwellings had to have an entrance hall. The maximum distance of travel between any
flat and the stairway was limited to 80ft (approximately 24m). For blocks with more than
four storeys above ground level, a second stairway was necessary – except that, where
there was only one additional storey, access could be provided from each flat to the
balcony of the flat below (or, in the case of the upper storey of a maisonette, via a link
balcony to the adjacent maisonette).
A1.21 From 1939, (until the current day), Section 20 of the London Buildings Acts
(Amendment) Act 1939 has enabled additional requirements to be made in respect
of construction of blocks of flats with a storey greater than 100ft (approximately 30m)
above ground, or above 80ft (approximately 24m) if the area of the building exceeds
10,000 square feet (approximately 929m2).
A1.22 The requirement for alternative means of escape in the case of buildings with more
than four storeys above ground was subsequently applied where any floor was above
42ft (approximately 13m).
A1.23 New guidance for flats in London was produced in 1946. The maximum travel distance
to a single stairway was increased to 100ft (approximately 30m), or 90ft (approximately
27m) to the nearest stairway in the case of buildings requiring two stairways.
A1.24 The two stairways could be no more than 180ft (approximately 55m) apart, except in
the case of open balcony approach, where no limitation applied.
General
A1.25 Where blocks of flats were built prior to 1962, several of the possible shortcomings
of which it is important to be aware and consider in respect of means of escape are
similar to those previously described for pre-20th-century blocks. However, original flat
entrance doors were likely to have been fire-resisting, as defined by the standards of
the time. These may continue to afford a reasonable degree of fire resistance, other
than in critical situations, such as long dead ends, where upgrading to current standards
may be warranted.
A1.26 In the latter part of this period, shunt ducts may have been used to prevent fire-spread
between flats via common ventilation shafts, but this may need to be confirmed where
there is a ‘stay put’ policy.
A1.27 In 1962, BSI published a new code of practice, ‘CP3 chapter lV part 1’, which provided
recommendations for fire precautions in
blocks of flats over 80ft (approximately
24m) in height. The code of practice
was also considered appropriate for
buildings less than 80ft in height.
A1.29 This strategy has proved appropriate over the last half century, and has worked
satisfactorily in the vast majority of fires in blocks of flats. Accordingly, it should not
readily be abandoned today. Even if a fire alarm system is considered necessary (eg as
a result of serious structural shortcomings that cannot be rectified), complete evacuation
of a high-rise block of flats in the event of a fire in one flat is unlikely to be appropriate
(see also Part F and Appendix 6 of this guide).
A1.30 The code recommended that all flats have an entrance hall, in which there was no fire
hazard. Bedrooms were to either open directly from this entrance hall (and be nearer to
the entrance than any door to a living room, dining room or kitchen), or the bedrooms
were to have an alternative exit leading directly to a main escape route outside the flat.
The living room, dining room and kitchen doors were required to be fire-resisting and
self-closing. This often enables identification of a block of flats built in accordance with
this early version of ‘CP3 chapter lV part 1’. The bedroom doors are often hollow core
domestic doors, without any substantial doorstop, whereas the living room and kitchen
doors are solid fire doors, closing onto a 25mm stop.
A1.31 Maisonettes were, in addition, required to have an alternative means of escape from
the non-entrance level. If the escape route from any room on the upper level passed the
landing at the head of the stairway, a fire-resisting screen with a fire door was required
at the head of the stairway to separate the stairway from the upper level. Alternatively,
pass doors between rooms, or an internal entrance hall, could be used to protect the
upper floor escape route from a fire on the level below.
A1.32 Where alternative exits from a bedroom were necessary, this could be provided via a
balcony leading to a stairway, or via an internal stairway leading to common parts on the
floor above or below the bedroom floor.
A1.33 To facilitate safe escape within the common parts, in the case of flats accessed
via balconies, alternative means of escape from each dwelling to a stairway was
considered necessary. This normally comprised a balcony leading to a stairway at each
end, but alternatively could comprise a balcony at both sides of the block leading to
one or more stairways. In the case of maisonettes, these latter balconies could be on
alternate floors, so ensuring safe escape from a fire within the maisonette, as well as
safe escape from a fire that affected any balcony.
A1.34 For dwellings with a corridor approach, where every dwelling was provided with an
alternative exit to a main stairway (eg via a balcony with escape in two directions), the
maximum travel distance from the flat entrance door to a main stairway was limited
to 100ft (approximately 30m) and the corridor was to be provided with permanent or
openable ventilation.
i. either be no more than 15ft (approximately 4.5m) from the door to the main
stairway (or to a smoke-stop door across the corridor) or not more than 15ft from a
permanently ventilated lobby
ii or open into a permanently ventilated lobby and be not more than 15ft from a
smoke-stop door separating the lobby from the corridor leading to the stairway.
A1.36 Where a single stairway was permitted, access to it was either from a balcony or a
ventilated lobby.
A1.37 Where common ventilation shafts served flats on each storey, a shunt duct was used
to link each flat to the common shaft. Alternatively any horizontal duct from a flat to the
shaft was required to be at least 3ft long. In the latter case, the junctions between the
horizontal sections from each separate dwelling and the main duct were to be at least
one storey apart in height.
A1.38 National Building Regulations, applicable throughout England (other than inner
London) were first produced in 1965. These made no requirements for means of
escape, but did require compartmentation between flats.
London legislation
A1.39 In 1962, London County Council also published guidance on fire precautions in blocks
of flats, in support of the London Building Acts.
A1.40 This guidance required entrance halls within flats. It continued to permit direct access
from flats to a single stairway (or to an internal protected lobby or corridor leading
to a stairway or to an external balcony leading to an open stairway or partially open
stairway) provided no floor was greater than 42ft in height (typically, a block of flats with
up to four upper storeys).
A1.41 For blocks with floors over 42ft in height, an alternative means of escape was required,
but this could comprise access to the roof (with a screen across the stairway to separate
the lower floors from the uppermost floors). From the roof, access was provided to an
adjoining building, a balcony or an external stairway. For balcony approach dwellings
with only one storey above 42ft, a suitable alternative means of escape comprised a
stairway to the balcony below.
A1.42 The maximum distance from a dwelling to a stairway was 100ft (approximately 30m),
or, where there were two stairways, 90ft (approximately 27m) and the two stairways
were not to be more than 180ft (approximately 55m) apart.
A1.44 Additional requirements for blocks over 80ft in height were required under Section 20
of the London Building Acts (Amendment) Act 1939.
A1.45 In 1971, CP3 chapter lV part 1: 1962 was superseded by CP3 chapter lV part 1: 1971,
which provided recommendations for precautions from fire in flats and maisonettes over
two storeys. This code of practice was adopted in London for the purpose of compliance
with the London Building Acts. However, in the case of tall blocks of flats, to which
Section 20 of the London Building Acts (Amendment) Act of 1939 applied, a code of
practice produced in support of that legislation specified additional measures, and, more
generally, was accepted as an alternative code to CP3 chapter lV part 1 in relation to all
the relevant fire precautions.
A1.46 In 1972, the Building Regulations were revised (but were still not applicable in
inner London). The Building Regulations 1972 (and all later versions of the Building
A1.47 The original 1972 version of ‘CP3 chapter lV part 1’ was amended in 1972, 1973,
1976 and 1978. None of the first three amendments are of significance for the purpose
of this guide. The 1978 amendment reproduces advice to owners and occupiers of
flats, originally published in the report of the working group of the Central Fire Brigades’
Advisory Councils for England and Wales and for Scotland on Fire safety in high-rise
blocks of flats. It is of particular note that the advice to occupiers was that, if a fire is
evident or reported elsewhere than their own flat, it will normally be safe to stay within
their flat, closing doors and windows.
A1.48 ‘CP3 chapter lV part 1’ provided numerous options for the design of flats and
maisonettes, and, in acknowledging the difficulty of making comprehensive
recommendations for every situation, the code of practice advocated intelligent
application of its principles and recommendations. As it is still available (from the British
Standards Institution), its recommendations are only broadly summarised below.
A1.49 A number of the principles of the 1962 and 1971 codes are very similar. However, in
contrast with the 1962 version, the 1971 version no longer assumed that a whole floor or
even adjoining dwellings need be evacuated if a fire occurred in a flat. It was considered
that, as a result of the compartmentation in blocks of flats at that time (as a result of
requirements under Building Regulations), the spread of fire and smoke from one dwelling
to another, and the need to evacuate occupants of adjoining dwellings, was unusual.
A1.50 A further contrast with the 1962 code relates to the protected entrance halls within
flats. Both versions recommended the provision of these entrance halls, but the 1962
version recommended that only the lounge, dining room and kitchen doors need be
fire-resisting and self-closing. The 1971 code recommended this for all doors, other than
bathrooms and WCs containing no fire hazard.
A1.51 Bedrooms were to open into an entrance hall and preferably be nearer to the flat
entrance door than the living room and kitchen. The bedroom doors were not to be
further than 7.5m from the entrance door unless there was an alternative means of
escape from the bedrooms, which could comprise a linking balcony to an adjoining flat.
A1.53 For dwellings accessed from a balcony, there was not generally any limit in travel
distance to a stairway. Where there was escape only in one direction along the balcony,
either there was to be an alternative route to a main stairway or construction below
1,100mm above the balcony floor was to be fire-resisting and unglazed.
A1.54 In the case of conventional corridor access (without alternative means of escape from
the dwellings), two alternative methods of smoke control were specified, as follows.
A1.55 In smoke containment, the entrance door of every dwelling was to be no more than
4.5m from a door to a fire door to a main stairway, to a fire door across the corridor or
to the door to a ventilated lobby. If the design was such that the 4.5m distance was
to a cross-corridor door, and any other flat entrance door was located between the
cross-corridor door and the stairway, there was to be an alternative means of escape
to a further stairway. Alternatively, the flats could open into a ventilated lobby and have
entrance doors no further than 4.5m from a door separating the lobby from a corridor
that led to a stairway.
A1.57 In buildings with a single stairway, the stairway could be entered only from a balcony or
a permanently ventilated lobby. However, there was a relaxation for small single stairway
buildings of not more than four floors above ground level. In the latter case, if the net floor
area of dwellings above first floor did not exceed 380m2, the stairway could be entered from
an unventilated lobby; this lobby could be omitted from the topmost floor.
A1.58 Alternatively, if the net floor area of dwellings above first floor did not exceed 720m2,
the stairway could be entered from lobbies with either permanent ventilation or
openable windows.
A1.59 Stairways in all buildings were required to have either permanent ventilation or
openable windows. Where a main stairway was not located against an external wall, or
had no opening windows, it was to have a permanent vent at the top.
A1.61 In particular, it should be noted that smoke dispersal has been shown to be vulnerable
to failure as a result of wind direction, and so may be unreliable. While it might be
appropriate to leave in place existing arrangements of this type, maintained as originally
designed, it might be less appropriate to engage in capital expenditure to restore such
arrangements to their original design, if the expenditure could, instead, provide more
effective smoke control in line with modern standards.
1.62 The Building Regulations were subject to a major restructuring in 1985 (and applied
in Inner London from 1987). Previous editions of the Regulations set out prescriptive
technical requirements for the design of fire precautions. The Building Regulations
1985 were cast in ‘functional form’. That is to say they contained only ‘functional
requirements’, which in effect are objectives that must be achieved, with flexibility and in
general, as to the design of the measures by which the objectives are achieved.
A1.64 For compliance with the functional requirement for means of escape from fire, no
flexibility was afforded. Instead, there were ‘mandatory rules for means for escape’.
No other ways of compliance with the functional requirement were acceptable. The
mandatory rules required that the means of escape complied with specified clauses of
‘CP3 chapter lV part 1: 1971’. These clauses included all those concerned with design
of means of escape, both within the flats and in the common parts.
A1.65 Given the major changes in recommendations for means of escape from flats
contained in later codes of practice, it is to be expected that blocks of flats built before
1992 might well not meet the design principles for means of escape adopted after 1992.
A1.66 Requirement B3 of the Building Regulations 1985 required various structural fire
precautions, including compartmentation to limit fire-spread. Non-mandatory guidance
on means for compliance with Requirement B3 was given in Approved Document B
under the Regulations. This guidance specified that all floors in flats (other than floors
within maisonettes) and all walls separating a flat from another part of the building
should be constructed as compartment floors and walls, with, in the case of flats in
buildings of three or more storeys, at least 60-minute fire resistance.
A1.67 In 1990, ‘CP3 chapter lV part 1’ was superseded by BS 5588-1. However, the
mandatory rules on means of escape still referred to CP3 chapter lV part 1 until they
were withdrawn in 1992. As BS 5588-1 is still current, it is not considered further in
this review of historic standards. However, it is anticipated that BS 5588-1 will be
superseded by a new code of practice, BS 9991, during the course of 2011.
A1.68 The mandatory rules for means of escape were withdrawn in 1992, when the Building
Regulations 1991 came into force. These Regulations were superseded by the Building
Regulations 2000 and then the Building Regulations 2010.
A1.69 From 1992 until the current time, Approved Document B has provided
recommendations on compliance with all the fire safety requirements of the Building
Regulations. This includes Requirement B1 regarding means of escape from fire,
which applies to blocks of any number of storeys and not only to those of three
storeys or more. For less common designs, such as flats entered from above or below,
A1.72 From 2006, Approved Document B no longer specified that there need be alternative
means of escape from maisonettes provided that there is a protected entrance hall
and either smoke alarms in each habitable room (but a heat alarm in the kitchen) or a
sprinkler system. (The smoke alarm option does not apply where the entrance storey to
the maisonette and the floors above and below are more than 7.5m vertically apart.)
A1.73 Guidance on smoke control in the common parts of blocks of flats was also changed in
2006. However, it is not expected that these changes be applied retrospectively.
A1.74 The most major change in guidance on blocks of flats since 1992 is the specification
in Approved Document B for sprinkler protection of blocks of flats that exceed 30m in
height. The sprinklers need only be installed within the flats, but not the common parts.
It is recognised that this will, in the future, greatly enhance the safety of residents from
fire in high-rise blocks of flats, making a death from fire, even in the flat in which fire
starts, unlikely.
2. Identify people at risk (people in and around the premises and people especially at
risk).
3. Evaluate the risk of a fire occurring and the risk to people from fire, remove or
reduce fire hazards. Remove or reduce the risks to people by means of:
4. Record significant findings and action taken. Prepare an emergency plan. Inform
and instruct relevant people. Cooperate and coordinate with others and provide
training.
A2.2 The British Standards Institution publicly available specification, PAS 79, sets out the
following nine steps, which amplify, but do not conflict with, the five steps set out in
government guides.
A fire hazard is any source, situation or unsafe act that can cause a fire. Fire hazards
within the flats and under the control of the residents need not be considered.
Consideration should be given to the potential following causes of fire and to measures
provided to eliminate or reduce the likelihood of each cause:
• arson
• electrical faults (in fixed wiring and any equipment provided)
• smoking
• use of portable heaters
• contractors’ activities
• heating installations
• lightning
• poor housekeeping, including inappropriate storage of refuse and discarded items.
This is based on an understanding of the fire protection measures and fire safety
management. In addition, account needs to be taken of the way occupants are likely to
Fire risk is a combination of the likelihood of fire (identified in Step 2) and the
consequences of fire (identified in Step 6). There is no unique way in which fire
risk should be expressed, but it is innate to the process of carrying out the fire risk
assessment that there be an assessment of fire risk, which it is then appropriate to
document.
One simple method of consistently expressing fire risk is given in PAS 79 and can be
useful for comparing the fire risk in one building to that in another (eg within the single
estate of one organisation). This is reproduced below:
If it is considered that the fire risk and existing fire precautions are such that no
improvements are necessary, this should be recorded within the fire risk assessment.
The action plan should address both physical fire precautions and managerial issues,
and should normally prioritise measures (unless all required measures are relatively
trivial and can be implemented in a short time), so that the appropriate effort and
urgency is clear. Measures within the action plan should be both practicable to
implement and possible to maintain, taking into account the nature of the building and
its occupants.
The fire risk assessment should set a ‘long stop’ date by which it should be reviewed,
even if no changes have taken place in the interim period.
Appendix 3
A3.2 Competence does not necessarily arise from specific qualifications, but will be the result
of a suitable blend of education, training and experience, knowledge and other qualities
that enable a fire risk assessor to carry out a fire risk assessment for a block of flats.
A3.3 It is generally accepted that a competent fire risk assessor appointed by the responsible
person for a block of flats will require an understanding of:
A3.6 Purpose-built blocks of flats are very different in nature from commercial premises, such
as offices, shops and factories. In selecting a fire risk assessor, the responsible person
should ensure that the competence of the fire risk assessor extends specifically to the
principles of fire safety applicable to purpose-built blocks of flats.
The easiest way to protect your home and family from fire is with a working smoke alarm
A smoke alarm can provide an early warning of a fire and allow you to make your escape –
but only if it is working. You are more than twice as likely to die in a fire if you do not have a
working smoke alarm.
You can prevent fire from happening by taking a few simple steps
• Don’t leave cooking unattended, and avoid leaving children in the kitchen alone with
cooking on the hob.
• Be especially vigilant when cooking with oil. Don’t overfill chip pans and NEVER throw
water on a chip pan fire.
• Make sure cigarettes are put out properly, use a proper ashtray and don’t smoke in bed.
• Don’t overload electrical sockets.
• Turn off appliances when not in use. Don’t even leave them on standby.
• Keep matches and lighters out of reach and sight of children.
• Make sure candles are secured in a proper holder and away from materials that may catch
fire – like curtains. Children shouldn’t be left alone with lit candles.
If your home is not already provided with smoke alarms, fit one in your entrance hallway
(and landing of any upper or lower floor). For even better protection, fit one in your lounge
and fit a heat alarm in your kitchen. Make sure your smoke and heat alarms meet British and
Get an electrician to fit mains-powered devices, and buy models that have a standby power
supply in case of mains failure.
Your flat is in a building designed to be fire-resisting. A fire should not spread from one flat to
another, so that you need not leave your home if there is a fire elsewhere in the block. That
said, if in doubt, get out.
Always leave if your flat is affected by smoke or heat or if told to by the fire service.
Your stairway is designed to be safe for escape throughout the course of a fire. Always use
the stairway to descend to ground level if escaping.
Do Not Leave Your Belongings Or Rubbish In Corridors, The Lift Lobby Or The
Stairway.
This could affect you and your neighbours if there was a fire.
If you are in a corridor, lift lobby or stairway and you notice a fire, leave the building
immediately and, if safe to do so, alert other residents in the immediate vicinity on your way
out (knock on their doors).
Do Not Put Yourself At Risk. Do Not Return To Your Flat Until It Is Safe To Do So.
Remember:
Fire Action
• Leave the room where the fire is straight away, then close the door.
• Tell everyone in your home and get them to leave. Close the front door of your flat behind
you.
• Do not stay behind to put the fire out.
• Call the fire service.
• Wait outside, away from the building.
• The building is designed to contain a fire in the flat where it starts. This means it will usually
be safe for you to stay in your own flat if the fire is elsewhere.
• You must leave immediately if smoke or heat affects your home, or if you are told to by the
fire service.
• If you are in any doubt, get out.
• Leave the room where the fire is straight away, then close the door.
• Tell everyone in your home and get them to leave. Close the front door of your flat behind
you.
• Do not stay behind to put the fire out.
• Raise the alarm by using a ‘break glass’ call point.
• Call the fire service.
• Wait outside, away from the building.
• The evacuation plan for this building requires all residents to proceed to the assembly point
when the communal fire detection and alarm system sounds.
• You must also leave IMMEDIATELY if smoke or heat affects your home, or if you are told to
do so by the fire service.
• If you are in any doubt, get out.
A6.1 There has never been any requirement under Building Regulations, local acts or bye-
laws to install a communal fire alarm system in a purpose-built block of flats, nor is there
any such requirement today under the Building Regulations 2010.
A6.2 Sometimes communal fire alarm systems have been, and are being, installed in blocks
of flats. In some cases, where the means of escape and compartmentation can be
demonstrated to be of a very poor standard, this may be warranted. However, fire
alarm systems are often installed as a result of various misconceptions like unless the
compartmentation can be proved to be adequate and uncompromised (which is rarely
possible), communal fire alarm systems should be installed.
A6.3 The real priority, in terms of fire warning, is to ensure that one or more working smoke
alarms are provided in every flat. Indeed, it would be no exaggeration to say that, in
current times, a flat without one or more working smoke alarms is not generally fit for
occupation.
A6.4 Smoke alarms would have been installed in each flat at the time of construction of any
blocks of flats built after 1992. These smoke alarms are mains operated, but those
installed prior to 2006 might not have a standby supply (battery or capacitor). Most of
the models originally installed would have been of the ionisation chamber type. The
typical lifetime of a smoke alarm is often considered to be around ten years, though
smoke alarms may operate satisfactorily for several years longer than this.
A6.5 It is essential that, in all flats, regardless of the date of construction, there is an
adequate number of working smoke alarms (at least one per storey). In leasehold flats
constructed before 1992, smoke alarms may be battery operated.
A6.6 Smoke alarms in rented single-storey flats built before 1992 should only be battery
operated if the battery has an anticipated life in normal service of at least five years,
and if the battery is ’tamper proof‘ (ie removal necessitates the use of a tool). When
any major electrical wiring takes place in rented flats, battery operated smoke alarms
(and mains-operated smoke alarms without a standby supply) should be replaced with
smoke alarms that are mains operated with a standby supply.
A6.8 Generally, any new smoke alarms installed in the circulation spaces within flats should
be of the optical type. These are less prone to false alarms from kitchens, and they
respond better to slow smouldering fires.
A6.9 At least one smoke alarm should be installed in the circulation space on each storey.
For a higher standard of protection, consideration may be given to the installation of
a smoke alarm in the lounge and a heat alarm in the kitchen. This higher standard of
protection might be appropriate in flats occupied by vulnerable occupants or where the
additional alarms are needed to compensate for shortcomings in the means of escape
within the flat. In the latter case, battery-operated alarms should not be used.
A6.10 For the highest standard of protection, a smoke alarm could be installed in all
habitable rooms, other than kitchens, where heat alarms should be installed. This
standard of protection is not normally justifiable, but might be appropriate in flats
specifically designed, or provided, for those who are particularly vulnerable to fire, such
as disabled people and those suffering from serious drug or alcohol abuse.
A6.11 Where more than one alarm is installed these should be interlinked to maximise the
audibility of the fire alarm signal. As well as models that are interlinked by wiring, radio-
linked smoke alarms are available. It is preferable that all smoke alarms incorporate
an alarm silence control, so that false alarms do not cause unnecessary or prolonged
disruption to the residents of a flat.
A6.12 Where occupants of a dwelling are deaf or hard of hearing and are likely to be alone
at any time within a flat, suitable smoke alarm kits complying with BS 5446-3 should
be used. These incorporate one or more flashing beacons, to alert people who are
awake, and vibrating pads to wake people who are asleep. A vibrating pager can be
incorporated in addition to these devices.
A6.13 Although the above paragraphs refer to smoke alarms, a more sophisticated system,
incorporating smoke detectors within an intruder alarm system, can be provided.
Alternatively, a complete fire alarm system of the type found in commercial premises
could be installed, but the cost of this is unlikely to be justifiable in most cases.
A6.14 In sheltered housing, fire alarm signals from individual flats should be relayed to the
same location as alarm signals from any social alarm system. If there is an on-site
scheme manager, fire alarm signals should be investigated by the scheme manager
– eg using a two-way speech communication facility between the scheme manager’s
facility and the dwelling – prior to summoning of the fire and rescue service. If no on-site
scheme manager is present, and fire alarm signals are transmitted to an alarm receiving
centre that has a direct two-way speech facility for communication with the flat, the
A6.15 Where fire alarm signals are transmitted to an alarm receiving centre by the same
equipment as social alarm signals, the two types of signal should be separately
identifiable at the alarm receiving centre. It should be ensured that the receipt of fire
alarm signals cannot be delayed significantly by a previously initiated social alarm
signal.
A6.16 If smoke (and heat) detectors are connected to an existing social alarm system that has no
facilities for discrimination between different types of alarm signal, the recommendation for
distinguishable signals need not be followed in the case of signals transmitted to an on-site
scheme manager. This is provided that the pre-planned response by the scheme manager
to signals from the fire alarm system in any flat is identical to the pre-planned response to
other alarm signals and is an appropriate action in the event of fire.
A6.17 For guidance on the design, installation, commissioning and maintenance of fire alarm
systems and smoke alarms in dwellings, reference should be made to BS 5839-6. Smoke
alarms, heat alarms and fire alarm systems should only be installed by competent persons
that are preferably third-party-certificated to carry out this work.
A6.18 There is normally no need for a communal fire alarm system. However, it is common
for smoke detectors to operate automatically opening vents, which keep the common
parts, particularly stairways, free from smoke.
A6.19 No fire alarm sounders should be connected to these detectors. Any existing sounders
should normally be disconnected.
A6.20 It is not only unnecessary to provide a communal fire alarm system, it is also normally
undesirable. Before installing any form of communal fire alarm system, it will normally
be necessary to get advice from fire safety specialists with substantial experience of
advising on fire safety measures in blocks of flats.
Account should be taken of the need to avoid false alarms and the risk of evacuating
residents who would be safe to remain in their flats, into areas into which they might be
affected by smoke.
A6.23 There are certain special circumstances in which a communal fire alarm system is
always appropriate. The most common examples of these are certain forms of sheltered
housing.
A6.24 In its simplest form, sheltered housing is, architecturally, and in terms of the facilities
provided, no different from a ‘general needs’ block of flats. There may be no need for a
communal fire alarm system in simple sheltered housing of this type.
A6.25 However, at the other extreme, many modern sheltered housing blocks incorporate
communal facilities, such as communal lounges, guest rooms, hairdressers, laundries
and sometimes even restaurants. The communal and commercial premises should be
protected with a fire alarm system complying with the recommendations of BS 5839-1
for a Category L1 or L2 system. Fire detectors and fire alarm sounders should also be
installed throughout the common parts, including corridors containing flats, and in all
communal rooms and non-domestic premises off the common corridors. The system
should also incorporate manual call points.
A6.26 The communal fire alarm system in these cases need not always extend into the
individual flats, provided it is considered that, in the event of a fire anywhere within the
building, residents are safe to remain within their own flats. In that case, the sound
pressure level of the fire alarm system in the common parts should be low enough to
avoid sound pressure levels of more than 45dB(A) within the flats.
A6.27 Where a communal fire alarm system is installed in sheltered housing, fire alarm
signals should be monitored at a 24 hour staffed location, such as an alarm receiving
centre. The smoke detectors within flats, provided to give residents a warning of a fire
in their own flat, may be incorporated in the system, but, since, normally, in the event of
a fire in a flat, a ‘stay put’ policy will apply to other flats, operation of a smoke detector
within a flat should only operate the sounder within that flat.
A6.28 Another situation in which a communal fire alarm system might be appropriate is flats
that form part of a mixed-user development. An example is flats located above shops.
In these cases, unless there is adequate fire resistance between the shops and the flats
immediately above, residents will be at risk from a fire within the shops.
A6.30 In blocks which do not have independent access to the flats, there may also be a need
to extend the fire alarm system into the flats above. However, a system configuration
which avoids having to evacuate all residents simultaneously is to be preferred, subject
to all other aspects of compartmentation and means of escape being able to support a
‘stay put’ policy.
A7.2 Constructed from concrete and brick, the block has rendered timber façades front and
rear. Floors were found to be of concrete, and the building has a concrete stairway.
A7.3 The block had been designed on the ‘stay put’ principle, and, consequently, there was
no communal fire alarm system. As such, it met not only the original design standard,
but also the current benchmark.
A7.4 The block was found not to have a lobby between the flats and the stairway. This
would still meet current benchmark standards, provided there was an internal protected
entrance hall in each flat and an AOV at the top of the stairway, operated by smoke
detectors on each landing.
A7.5 Given that a sample of flats were accessed for this Type 1 fire risk assessment, primarily
to check the standard and condition of flat entrance doors, it was soon established that
the protection to the entrance halls was not in line with current standards. As a result of
the age of the block, the stairway did not have an AOV, although smoke venting could
easily be achieved by opening windows.
A7.6 The front entrance doors to flats were also found to be original and not therefore in line
with the current benchmark standard on these doors. Nevertheless, the original doors
were fire-resisting and met the standard of the day. Part of that standard, however,
permitted the use of rising butt hinges as was the case here.
A7.7 The majority of the flat entrance doors were found to be in good condition, although it
was noted that one had been fitted with a cat flap and another was badly fitting in its
frame.
A7.8 While most doors were the same, there were a number of doors that appeared to have
been changed more recently. It transpired that some leaseholders had replaced the
original doors, but with doors that were not fire-resisting.
A7.10 Overall, the fire risk assessment did not consider that the issues relating to the common
parts posed a high risk to people. However, the action plan included a number of short-term
and long-term solutions to address the findings. In summary, these were as follows.
Short-term solutions
• To require the leaseholders to replace front doors to their flats if they were not fire-
resisting.
• To fit positive action self-closing devices in place of rising butt hinges to all original flat
entrance doors.
• To repair the badly fitting door, or, if a repair was not possible, to replace it with an
FD30S fire-resisting, self-closing door meeting current fire door standards.
• To remove the cat flap and repair the door to at least restore its integrity, to fit a
‘replacement FD30S door’.
Long-term solutions
• As and when the opportunity arose, to upgrade or replace the front entrance doors
to meet current benchmark standards and in particular, to fit intumescent strips and
smoke seals and protected letter boxes. It was suggested to the landlord that this
could be during the course of the normal maintenance programme or at time of major
refurbishment.
A8.2 There are large, openable windows in every corridor and within the stairway that can be
used to vent smoke.
A8.3 The building is of substantial construction, with concrete floors and masonry walls,
providing a good standard of fire resistance between flats, and between flats and the
common parts. This provides support for the ‘stay put’ policy that has always been
adopted and the absence of any communal fire alarm system.
A8.4 A Type 3 fire risk assessment has been carried out. It was noted that the travel distance
from the furthest flat entrance door to the stairway was 12m. Inspection of electrical
risers within common parts revealed that not all cable penetrations between the risers
and the flats were adequately fire stopped.
A8.5 Within a sample of the flats inspected, it was found that there are quite short internal
entrance halls, with substantial doors separating each room from the hallway. Bedrooms
are located nearer to the flat entrance door than kitchens and lounges.
A8.6 From inspection of a sample of flat entrance doors, it was determined that the original
doors met the standard of the day for fire resistance, but some self-closing devices had
been removed by residents.
A8.7 It was found that the landlord had not provided smoke alarms. However, many residents
had installed their own battery-operated smoke alarms. In some cases, batteries had
been removed because of false alarms during cooking.
A8.8 In the course of the fire risk assessment, it was noted that there are common
extract facilities from both kitchens and bathrooms. The configuration of the extract
arrangements needed further investigation. From this investigation, it was determined
that the extract arrangements from each flat do not take the form of shunt ducts, but
simply horizontal ducts that join the main duct. No fire dampers were present.
Short-term solutions
Medium-term solutions
• In view of the extended travel distance, to upgrade all flat entrance doors to upgraded
FD30S standard (along with those to the stairway).
• To fit intumescent fire dampers to kitchen and bathroom extract ducts.
• To provide either PVs or AOVs in the corridors and the stairway.
Long-term solutions
A9.2 The nine-storey, single-stairway block has a total of 51 self-contained ‘general needs’
flats. There are six flats on each of floors one to eight, which are accessed through a
common lobby off the single stairway. The stairway has direct access to a final exit at
the base of the stairs.
A9.3 The block is of concrete framed construction, with concrete floors, internal block walls
to the common parts and a concrete stairway. The block has a flat roof constructed of
concrete, with an asphalt covering. As part of a refurbishment programme, the stairway,
which was open originally on each of the upper floor levels, was enclosed with glazed
partitions and openable windows. The block had been designed on the ‘stay put’
principle, and, consequently, there was no communal fire alarm system.
A9.4 Access to the flats is via a common lobby providing two door protection to the single
stairway, which is consistent with current benchmark standards. The travel distance
within the lobbies to the door to the stairway is approximately 6m, which is in excess of
the current recommended benchmark of 4.5m. The smoke control arrangements in the
lobbies, which are not provided with any means of ventilation, and within the stairway,
which only has openable windows, are not in accordance with current benchmark
guidance, which would require AOV’s in the lobbies and the stairway.
A9.5 In addition, the refuse chutes, which, in the original design, were located off an open
balcony within the stairway on each of the upper floors, are now within an enclosed
stairway and present a risk of fire and smoke spread.
A9.6 The flat entrance doors were also found to be original and not, therefore, in line with the
current benchmark standards. Nevertheless, the original doors were fire-resisting and
met the standard of the day. Part of that standard, however, permitted the use of rising
butt hinges as was the case here.
A9.7 The majority of the flat entrance doors were found to be in good condition, although
it was noted that the original fire-resisting glazing over two of the doors had been
A9.9 Compartmentation within the flats was also considered, and had been checked during
the refurbishment programme, which did not identify any significant defects. The
kitchens were provided with separate extract vents direct to open air, and the service
risers containing electric, water and waste pipes were enclosed in a common duct in
what appeared to be solid construction providing a reasonable period of fire resistance.
The bathrooms were provided with a common vent and duct that served all bathrooms,
with mechanical extract ventilation with a fan at roof level. Further investigation by a
contractor revealed that there were no fire dampers in bathroom extract facilities, and
that shunt ducts were not incorporated.
A9.10 The fire risk assessment identified a number of significant deficiencies within the
common parts. Some of these were as a result of changes made to the block. While it
was not considered reasonably practicable to bring the block fully into line with current
benchmark standards for single stairway buildings, the action plan included a number of
short, medium and long-term solutions to address the findings. In summary, these were
as follows.
Short-term solutions
• To require the two leaseholders to replace the front doors to their flats with
replacement FD30S doors, with positive action self-closing devices.
• To fit positive action self-closing devices in place of rising butt hinges to all flat
entrance doors.
• To replace, the non-fire-resisting glazing over the flat entrance doors, with fire-
resisting glazing.
• As a temporary measure, permanently open one of the windows on each landing
within the stairway to provide permanent ventilation, or alternatively close off the
refuse chutes to prevent their use by residents.
• Provide fire stopping to any openings around pipes and cables in fire-resisting floors
and walls.
• Enclose the refuse chutes on each floor with partitions and self-closing doors
providing 30-minute fire resistance, and provide permanent ventilation to the
enclosure, or, alternatively, permanently seal off the refuse chutes on each floor level.
• To fit intumescent dampers to the vent openings within each of the bathrooms to
prevent the spread of fire between flats.
Long-term solutions
• To upgrade all flat entrance doors and doors to the store rooms, cleaner’s cupboard,
electrical intake room and the stairway to FD30S doors.
• The doors to the riser cupboards on each floor were notional FD30 doors and,
provided the storage is removed, there would be no requirement to upgrade these
doors. However, the doors should be kept locked shut and be provided with suitable
notices.
• As the travel distance within the lobbies is limited, and there is no practical way of
providing ventilation, unventilated lobbies were accepted. However, to compensate for
this and upgrade the smoke control in the stairway, AOVs or PVs were required in the
stairways. If AOVs were installed, smoke detectors would need to be fitted in both the
lobbies and the stairway.
A10.2 The four-storey building had three self-contained flats, one on each of the upper floors.
The ground and basement floors were occupied by two shops.
A10.3 Each of the flats was accessed directly off a single staircase. The common parts
comprised the entrance hall, the staircase and the landings on each upper floor.
Although the two shop units on the ground floor had independent entrances from the
street, one also had a door into the entrance hall.
A10.4 Built with brick walls, the block had timber floors and the staircase was of timber
construction. The original roof had been replaced with a metal-clad roof.
A10.5 The block had been designed on the ‘stay put’ principle, and, consequently, there was
no communal fire alarm system. As such, it met not only the original standard on this but
also the current benchmark.
A10.6 The block was found not to have a lobby between the flats and the stairway. Although
all had entrance hallways, none of these were protected. There was no automatic
vent in the stairway for smoke ventilation and none of the flat entrance doors were
considered even notional FD30 doors.
A10.7 The first and second floor levels had access to alternative exits onto external metal fire
escape stairways. However, these could not be reached from all rooms. The top floor
flat had no access to the external escape stairway, although a ladder gave access to the
roof for residents to await rescue, which is not acceptable today.
A10.8 The works to the building revealed serious deficiencies in both the standard of the
fire separation and its condition. Ceilings were lined with lath and plaster and, in some
parts, a composite of plywood, chipboard and hardboard. Some walls, including those
enclosing the staircase, were of thin timber panels and it was possible to see between a
flat and the stairway through splits in the panels.
A10.10 Despite misgivings over the implications for false alarms, it was decided that a fire
detection and fire alarm system would need to be installed. The alternative of fitting
a sprinkler system was considered as an option, but there was no room to house the
necessary tank and pumps. The communal system provided, a Category L1 system
to BS 5839-1, extended into the flats. This was not only to ensure all residents were
warned of an activation of the system, but also to provide fire detection in all habitable
rooms. Manual call points were also fitted by the ground floor exits, but not on the
upper-floor landings.
A10.11 Given that the detectors were installed in flats to compensate for serious
shortcomings in fire separation, heat detectors were used. These were deemed
sufficient to provide warning before fire-spread between flats and also to reduce the
potential for false alarms from residents. However, in recognition that these would not
provide local warning for the occupants of each flat, smoke alarms were also installed in
each of the flats.
A11.2 This is a four-storey, purpose-built block of flats, with a total of eight, two-storey,
self-contained general needs flats. Four of the flats are entered directly off the single
stairway on the ground floor level, with the remaining four flats entered off the single
stairway on the second floor level.
A11.3 The block itself is of concrete framed construction, with concrete floors, internal block
walls to the common parts and a concrete stairway. The block originally had a concrete
flat roof, but a new timber and tiled pitched roof was installed over the existing flat roof a
number of years ago.
A11.4 The flats open directly off the single stairway and originally had internal protected
entrance halls providing two-door protection to the stairway, which was in accordance
with the benchmark standard of the day. The risk assessment for the common parts was
considered separately and is not included within this case study, which only considers
the fire safety measures necessary to protect the residents from a fire within their own
flat.
A11.5 The flats themselves are arranged on two levels. On the entry level, there is a small
hallway with doors to the kitchen, living room and toilet. An internal stairway provides
access to the upper level, on which there are three bedrooms and a bathroom.
A11.6 The original means of escape arrangements incorporated an alternative fire exit on
the landing, adjacent to the bedrooms, on the upper level of each flat. On the first floor,
the exit led directly into the stairway and, on the third floor, the exit led onto the roof and
then back into the stairway. In addition, the doors to the kitchen and lounge were fire-
resisting doors fitted with rising butt hinges. The doors to the bedrooms on the upper
levels were not fire-resisting.
A11.7 The alternative fire exits from the first floor level of the block remain available, although
a number of the doors were obstructed and, in one case, permanently locked shut. The
alternative fire exits from the fourth-floor level of the block have been removed following
the installation of the pitched roof. In addition, in general, kitchen and living-room doors
A11.8 The flats are fitted with interlinked Grade F smoke alarms, located in the hall and on
the upper-level landings.
A11.9 It was not considered reasonable or physically possible to either re-instate the original
means of escape arrangements, particularly on the third floor, or bring the flats fully into
line with current benchmark fire safety standards.
A11.10 The fire risk assessment identified a significant problem with the internal means of
escape from the upper levels of the flats, particularly at third-floor level, as a result of
changes made to the block, and other less significant issues that could be dealt with
over a longer period of time. The action plan, therefore, included a number of short and
medium-term solutions to address the findings. In summary, these were as follows.
Short-term solutions
• To upgrade the fire detection and alarm system in all flats, with, in the first instance,
particular emphasis on the upper-level flats, to compensate for the removal of
the alternative exits on the fourth floor. A Grade D, Category LD2 system was
recommended, with smoke alarms fitted in the hall, living room and upper-level
landings and a heat alarm fitted in the kitchens.
• To replace any doors removed from the kitchens or living rooms with FD20 doors.
• To inspect existing doors fitted to kitchens and living rooms and ensure that they are a
good fit in their frames and provide a reasonable level of fire resistance.
• To ensure alternative fire exits on the upper landing at first floor level are opened up
and made available and can be easily opened by the residents.
• To provide residents with general fire safety information and emphasise the need to
keep kitchen and living-room doors closed, particularly at night.
Medium-term solutions
• To replace the glazing between the hall and living rooms with fire-resisting glazing.
• In the upper-level flats, to consider the fitting of self-closing devices to kitchens and
living-room doors.
A12.3 The block itself is of traditional construction, with brick exterior walls, timber floors,
internal brick and block walls between the flats and the concrete stairway, and a tiled
timber-pitched roof. The timber floors were in-filled with hollow blocks at the time of
construction to provide fire separation between the floors which was common for
buildings of this age.
A12.4 The flats open directly onto the single stairway and have internal protected entrance
halls providing two-door protection to the stairway, which was common in buildings
of the age and size. The stairway was open at ground floor level and had openable
windows on the landings on the upper floors. The risk assessment for the common
parts was considered separately and is not included within this case study, which only
considers the fire safety measures necessary to protect the residents from a fire within
their own flats.
A12.5 The flats themselves are arranged on one level and are accessed directly off the
single stairway. There was a small entrance hall with doors to the kitchen and the living
room. From the rear of the living room, a further door gave access to an inner hall with
access to the bedrooms and bathroom.
A12.6 The flats were fitted with a Grade D Category LD3 fire detection and alarm system,
with smoke alarms in the entrance hall and inner hall.
A12.8 Over the years, as a result of security concerns, the majority of the panels between
the balconies had been sealed up, and access no longer exists between the flats. In
addition, even where the panel has been retained, access into the adjoining flat and
out of the flat into the stairway would be difficult to achieve due to additional security
measures fitted by residents to balcony and flat entrance doors and could not be
relied on with any degree of certainty. The result of these changes has created an
unsatisfactory means of escape arrangement for residents in the bedrooms. Without
the original alternative means of escape, anyone in the bedrooms would have to pass
through the living room to reach the flat entrance door. Should a fire occur in the living
room, there is a significant risk that the occupants of the bedroom would become
trapped and be unable to escape.
A12.9 In addition, in a number of the flats, the door to the kitchen had been removed or
replaced with a non-fire-resisting door, and some of the doors were also found to be
wedged in the open position. This was mainly due to the limited space within the kitchen
and was common practice. This was an additional concern, which potentially increased
the risk for the occupants of the bedrooms, who would need to use the entrance hall
and pass the kitchen to leave the flat.
A12.10 It was not considered practicable or appropriate to re-instate the original means of
escape arrangements, via the external balcony.
A12.11 The fire risk assessment identified a significant problem with the internal means of
escape from the bedrooms and the removal of fire-resisting doors. The action plan
therefore included a number of short- and medium-term solutions to address the
findings. In summary, these were as follows.
• To ensure that all kitchens off the entrance hall are fitted with either the original fire-
resisting door or replacement FD20 doors.
• To ensure that the door between the living room and the inner hall is at least a FD20
fire-resisting door.
• To provide residents with general fire safety information and emphasise the need to
keep kitchen and living-room doors closed, particularly at night.
• To upgrade the existing fire detection and alarm system to a Grade D Category LD1
system, with smoke alarms in the entrance hall, living room, inner hall and bedrooms,
and a heat alarm in the kitchen.
• To fit an automatic suppression system to cover the living room, kitchen and entrance
hall.
• To upgrade all remaining doors to FD20 standard.
A13.2 A Type 1 fire risk assessment was carried out. The property manager from the agent
accompanied the assessor and after knocking on a lot of doors was able check on one
flat entrance door. This was found to be in good condition fitted with combined smoke
seals and door closer. But it was noted that some other leaseholders had replaced their
front doors with new UPVC doors that appeared not to be fire-resisting.
A13.3 The fire risk assessment found a reasonable standard of compartmentation in common
areas. Suspended ceilings in common parts and above corridor fire doors were lifted.
Only minor openings around pipes and cables were found. The service cupboards were
checked and one was found not be locked. A pre-payment meter had been installed in
a meter cupboard by the utility company without the consent of the RMC. A pram and
bicycle were being stored on the ground floor lobby. No fire instruction notices were
displayed. The agent, having recently been appointed on a 12-month contract, was not
aware of:
A13.4 Following the risk assessment the agent presented the findings to the directors of the
RMC and they agreed:
• to provide a good standard of fire stopping to any openings around cables and pipes
in common areas above fire doors and within service riser cupboards
• a zero tolerance policy
• that the agent would contact the lessee who owned the pram and bicycle and ask that
they be removed from the common parts as an obstruction
• that the agent would contact the utility company and the sub-tenant with the pre-
A13.5 The agent wrote to the two lessees about their front doors. No replies were received.
The agent followed up this letter with a further letter and then a visit to the lessees’
flats. The agent discovered one of the lessees had sublet the flat and was abroad at
the time. The sub-tenant in the flat would not deal with the issue of the door. The agent
wrote again to the addresses he had for the lessees to state that unless the lessees
took action then he would ask the directors to refer the matter to the relevant enforcing
authority. After not getting any responses the agent sought advice about whether to
contact the fire service or the local environmental health authority. With RMC’s directors’
approval the agent invited the environmental health authority to inspect the doors as a
matter covered by the Housing Act 2004, with a view to enforcement action.
This glossary sets out definitions to assist readers in understanding some of the technical
terms used in this guide. In some cases, the definitions relate specifically to this guide
and may therefore differ to some degree from more generically applicable definitions. The
definitions are not exhaustive. More precise definitions may be available in other guidance.
Access room A room through which the only escape route from an inner room
passes.
Alternative escape Escape routes sufficiently separated by either direction and
routes space, or by fire-resisting construction, to ensure that one is still
available, irrespective of the location of a fire.
AOV (automatically A vent provided for smoke control in common parts, which opens
opening vent) automatically when smoke is detected by smoke detectors.
Approved Document B Guidance issued by the government in support of the fire safety
aspects of the Building Regulations.
Cavity barrier A construction provided to close a concealed space against
penetration of smoke or flame, or provided to restrict the
movement of smoke or flame within such a space.
Cluster flat A flat in multiple occupation, typically occupied by a particular
group of people, such as students or key workers.
Combustible material Material that can be burned.
Common balcony A walkway, open to the air on one or more sides, forming part of
the escape route from more than one flat.
Common parts Those parts of a block of flats used by occupants of more than
one flat for access and egress.
Competent person A person with enough training and experience or knowledge and
other qualities to enable them to properly assist in undertaking
the fire safety measures recommended in this guide.
Compartmentation Sub-division of a building by fire-resisting walls or floors for the
purpose of limiting fire-spread within the building.
Compartment wall or A fire-resisting wall or floor that separates one fire compartment
floor from another.
Corridor access A design of a block of flats in which each flat is approached via
a common horizontal access or circulation space, which may
include a common entrance hall.
Dead end Area from which escape is possible in one direction only.
Fire-resisting door – A ‘notional FD30’ door, fitted with intumescent strips and smoke
Upgraded FD30S door seals, and with any other necessary work carried out, such that
it may reasonably be anticipated that it would satisfy the relevant
test requirements for 30 minutes integrity and control of the
passage of smoke at ambient temperature.
General needs block A block of flats intended for occupation by members of the
general public and not those of a specific demographic or
vulnerability.
Habitable room A room within a flat, used, or intended to be used, for dwelling
purposes (including a kitchen, but not a toilet or bathroom).
Inner room A room from which escape is possible only by passing through
another room (the access room).
Material alteration An alteration to the building that significantly affects (usually
lowering or with the potential to lower) the level of risk to people
from fire.
Means of escape A route(s) provided to ensure safe egress from the premises or
other locations to a place of total safety.
Non-destructive fire risk A fire risk assessment that does not involve destructive exposure
assessment (but normally will still involve opening a sample of accessible
service riser doors and, for example, sample inspections where
feasible above accessible demountable ceilings and so forth
without use of tools).
OV (Openable vent) A vent provided for smoke control in the common parts, which is
opened by the fire and rescue service by means of hardware or a
control (which may be located remotely) provided for the purpose.
Protected corridor or A corridor or lobby that is adequately protected from fire in
lobby adjoining accommodation by fire-resisting construction.
Protected entrance hall A circulation area consisting of a hall or space in a flat, enclosed
or landing in fire-resisting construction (other than any part that is an
external wall of the building).
Protected route An escape route that is adequately protected from the rest of the
building by fire-resisting construction.
Protected stairway A stairway that is adequately protected from the rest of the
building by fire-resisting construction.
PV (Permanent vent) A permanently open vent provided for smoke control in the
common parts.
Reasonably practicable Measures that reduce fire risk to an extent where the cost and
measures effort to reduce the risk further would be grossly disproportionate
to the remaining risk.
Relevant person Any person lawfully on the premises and any person in the
immediate vicinity (but not fire-fighters carrying out operational
duties).
Self-closing device Device that is capable of closing a door from any angle and
against any latch fitted to the door.
Sheltered housing A block of flats in which each flat is designed and constructed
for the purpose of providing residential accommodation for
vulnerable or elderly people, who receive, or are to receive, a
support service.
Simultaneous Procedure in which all parts of a block of flats are evacuated
evacuation following the giving of a common alarm of fire.
Smoke alarm Device containing within one housing all the components, except
possibly the energy source, for detecting smoke and giving an
audible alarm.
Smoke containment A method of smoke control involving physical barriers to the
spread of smoke, usually in combination with vents, primarily to
prevent the passage of smoke into escape stairways.
Smoke dispersal A method of smoke control frequently used in older blocks of flats
at the time of their construction (but now deprecated). Vents were
sited in such a way as to achieve uninterrupted natural cross-
ventilation of corridors and lobbies in an endeavour to dilute and
disperse any smoke in these areas.
‘Stay put’ An evacuation strategy based on the principle that only the
residents of the flat of fire origin need to escape initially, while
other residents may remain in their own flats.
Travel distance (within The actual distance to be travelled by a person from any point
a specified area, such within the specified area, to the nearest exit leading to a place of
as a flat, the hallway relative safety in which the person is in no immediate danger from
of a flat or a common fire.
corridor)
Unventilated corridor or Corridor or lobby with no vents or other means of smoke control.
lobby
Ventilated corridor or Corridor or lobby with means of smoke control.
lobby
Legislation
‘The Regulatory Reform’ (Fire Safety) Order 2005
http://www.legislation.gov.uk/uksi/2005/1541/contents/made
Guidance on legislation
HM Government Guide ‘Fire safety risk assessment: sleeping accommodation’, Department
for Communities and Local Government (DCLG), May 2006.
http://www.communities.gov.uk/documents/fire/pdf/151339.pdf
‘Approved document B: Fire safety’ (Volume 2), Department for Communities and Local
Government (DCLG), April 2007.
http://www.canterbury.gov.uk/assets/buildingcontrol/approved-document-b-vol2-2006a.pdf
‘Housing health and safety rating system – guidance for landlords and property related
professionals’, Department for Communities and Local Government (DCLG), May 2006.
http://www.communities.gov.uk/documents/housing/pdf/150940.pdf
‘Housing – fire safety: guidance on fire safety provisions for certain types of existing housing’,
Local Authorities Coordinators of Regulatory Services (LACoRS), (now known as Local
Government Regulation), in partnership with the Chief Fire Officers’ Association and the
Chartered Institute of Environmental Health, July 2008.
http://www.lacors.gov.uk/lacors/NewsArticleDetails.aspx?id=19844
‘Protocol between Local Housing Authorities and Fire and Rescue Authorities to improve fire
safety’, October 2010.
http://www.lacors.gov.uk/lacors/upload/25462.pdf
‘Protocol between Local Housing Authorities and Fire and Rescue Authorities to improve fire
safety’, 2007.
http://www.lacors.gov.uk/lacors/upload/25463.pdf
Other guidance
‘Electrical Safety in Communal Areas of Residential Properties’. The Electrical Safety
Council, 2011.
http://www.esc.org.uk/uploads/tx_escvideolib/filedownload/Communal_Areas_ESC_online-
version_02.pdf
‘Fire safety in construction – Guidance for clients, designers and those managing and
carrying out construction work involving significant fire risks’. Health and Safety Executive, 2nd
edition, 2010.
http://www.hse.gov.uk/pubns/priced/hsg168.pdf
British Standards
British Standard code of practice ‘CP3 chapter IV: precautions against fire’, 1948,
(superseded)
British Standard code of practice ‘CP3 chapter IV part 1: precautions against fire’, 1962,
(superseded)
British Standard code of practice ‘CP3 chapter IV part 1: precautions against fire’, 1971,
(superseded)
BS EN 1634-1: 2008, ‘Fire resistance and smoke control tests for door, shutter and openable
window assemblies and elements of building hardware, Fire resistance tests for doors,
shutters and openable windows’
BS EN 1634-3: 2004, ‘Fire resistance and smoke control tests for door, shutter and openable
window assemblies and elements of building hardware, smoke control test for door and
shutter assemblies’
BS EN 62305-3: 2006, ‘Protection against lightning, physical damage to structures and life
hazard’
BS 476-22: 1987, ‘Fire tests on building materials and structures, methods for determination
of the fire resistance of non-load-bearing elements of construction’
BS 5446-3: 2005, ‘Fire detection and fire alarm devices for dwellings, specification for smoke
alarm kits for deaf and hard of hearing people’
BS 5588-1: 1990, ‘Fire precautions in the design, construction and use of buildings. Code of
practice for residential buildings’ (in the course of revision)
BS 5839-1: 2002, ‘Fire detection and fire alarm systems for buildings, code of practice for
system design, installation, commissioning and maintenance’
BS 5839-6: 2004, ‘Fire detection and fire alarm systems for buildings, code of practice for the
design, installation and maintenance of fire detection and fire alarm systems in dwellings’
BS 7273-4: 2007 ‘Code of practice for the operation of fire protection measures, actuation of
release mechanisms for doors’
BS 9251: 2005, ‘Sprinkler systems for residential and domestic occupancies, code of
practice’
BS 9999: 2008, ‘Code of practice for fire safety in the design, management and use of
buildings’
DD 8489-1: 2011, ‘Fixed fire protection systems, Industrial and commercial watermist
systems, code of practice for design and installation’
Other guidance
‘Electrical Safety in Communal Areas of Residential Properties’, the Electrical Safety Council,
2011.
‘Fire safety in construction – guidance for clients, designers and those managing and carrying
out construction work involving significant fire risks’, Health and Safety Executive, second
edition, 2010.
‘Fire prevention on construction sites – the joint code of practice on the protection from fire
of construction sites and buildings undergoing renovation’ (seventh edition), Fire Protection
Association Publications, 2009.
‘Code of practice: Refurbishment of communal buildings and the fire risk of multi-layer paints’,
Warringtonfire, 2005
‘Requirements for electrical installations: IEE wiring regulations’, 17th edition (BS 7671:
2008). IET, 2008
‘IET Guidance Note 3: Inspection and Testing’, 5th edition, IET, 2008
A
Access for fire-fighters 23, 54, 90, 91, 106, 110, 116, 120, 121, 132
Alarms (see fire alarm systems)
Alterations 18, 34, 35, 49, 94, 112, 114, 121, 129-130, 131, Appendix 1
Anti-social behaviour 53, 55, 59, 61, 127
AOVs (automatically opening vents) 86, 89, 95, 96, 97, 115, 123, Appendices 7, 9
Approved products and services (see third-party certification)
Arson 51, 53, 59, 127, Appendix 2
Assembly point 118, Appendix 2
Automatic fire detection systems (see also fire alarm systems) 72, 76, 83, 94, 95, 96
Automatic fire suppression systems (see fire suppression systems) 22, 76, 81, 83, 94,
Appendix 12
B
Building Regulations 12, 14, 25, 32, 34, 35-36, 38, 43, 70, 79, 129, Appendices 1, 2, 6
C
Car parks 26, 85, 89
Cavity barriers 87, 111, 130
Cladding (see external cladding)
Compartmentation 22, 28, 29, 30, 31, 45, 66, 71-75, 104, 106, 126, Appendices 1, 2, 3, 6, 7,
9, 10, 13
Competence 41, 48, 118, Appendix 3
Competent person 50, 63, 114, 122, Appendices 2, 3, 6
Construction, fire-resisting 20, 23, 25, 78, 85, 103, 106, Appendix 2
Contractors 30, 34, 38, 45, 46, 50, 53, 63, 64, 65, 121, 122, 124, 125, 127, 129, Appendices
2, 9
E
Electrical hazards 62-64
Electrical safety 116
Emergency lighting (see emergency escape lighting)
Emergency escape lighting 30, 38, 67, 102
tests, checks and maintenance 122-123
Emergency plans 38, 44, 118, Appendix 2
Escape lighting (see emergency escape lighting)
Escape routes
alternative exits 20, 22, 23-26, 66, 76, 77, 80-81, 82, 101, 105, 108, Appendices 11, 12
capacity 85
corridors 23, 24, 25, 60, 61, 76, 80, 84, 85, 86, 87, 89, 90, 91, 95, 96, 97, 99, 100, 102,
103, 106, 109, Appendix 1
dead ends 25, 32, 60, 86, 100, Appendix 1
emergency lighting (see emergency escape lighting)
inner rooms 75-76, 79, 130, Appendix 12
F
Fire action notices 38, 116, 118, 119, 128, Appendix 5
Fire alarm systems 22, 28-29, 35, 38, 43, 44, 67, 72, 94, 103-104, 107, 108, 114, 115, 116,
117, 118, 119, 122, 123, Appendices 1, 2, 3, 6, 7, 8, 9, 10
tests and checks 123
Fire blankets 30, 105, 123
Fire dampers 74, 75, 124
Fire detection and alarm systems (see fire alarm systems)
Fire drills 118
Fire extinguisher (see extinguishers)
Fire-fighting lifts (see lifts)
Fire doors (see doors, fire-resisting)
Fire engineering 32, 76, 123, 131
Fire exit signs 30, 38, 67, 101, 102, 128
Fire load 59, 61
Fire mains 30, 91, 110, 116, 121, 125, 128, 132
Fire procedure notices (see fire action notices)
Fire procedures 112, 115, 118
Fire resisting doors (see doors, fire-resisting)
G
Glazing, fire-resisting 26, 91, 100, 128 Appendix 1, 9, 11
H
Heating 26, 46, 51, 64-65, Appendix 2
High-rise blocks 18, 20-21, 67, 71, 111, 131, Appendices 1, 6
Hose reels 67, 104
Housing Act 2004 34, 36-37, 39, 40, 46, Appendix 13
Housekeeping 51, 55-61, 117, Appendix 2
I
Ignition sources 53, 55, 58, Part E 51-65
K
Kitchens 26, 40, 64, 73, 74, 76, 77, 78, 79, 96, 107, Appendices 1, 6, 8, 9, 12
L
Leases 37, 40, 46, 54, 105, 115, 125, 129, Appendices 6, 7, 9, 13
Leasehold flats 40, 46, 65, 75, 113, 125, Appendix 13
Lifts
M
Maintenance 33, 34, 35, 37, 38, 40, 42, 43, 44, 46, 49, 51, 64, 65, 67, 69, 97, 110, 112, 113,
114, 115, 121, 122-126, 131, Appendices 2, 6, 7
emergency escape lighting 122-123
external fire escape routes 126
fire dampers 124
fire detection and warning systems 123-124
fire doors 125-126
fire extinguishers 123
fire-fighting lifts 125
fire mains 125
fire suppression systems 124
smoke control 124
Managed use (of common parts) 51, 58, 59-61, 62, 127
Means of escape 20, 22, 23-25, 35, 38, 44, 46, 74, 75-84, 85, 90, 94, 104, 106, 108, 109,
117, 123, Appendix 1
Mobility scooters 57, 59, 60, 61, 128
N
Non-destructive fire risk assessment 45, 46
O
OVs (openable vents) 86, 88, 89, 97, 123, 127
Overcladding (see external cladding)
P
People with special needs 21, 47, 59, 76, 109, 118, 120, 132, Appendices 1, 2, 3, 6
Personal emergency evacuation plans (PEEPs) 120
R
Rainscreen cladding (see external cladding)
Record-keeping 39, 47, 112, 131
Refuge areas 109
Recycling 61-62
Regulatory Reform (Fire Safety) Order 2005 34, 37-39, 40, 41, 42, 43, 44, 45, 46, 47, 49, 50,
112, 113, 114, 115, 118, 128, 131, Appendices 2, 3
Relevant persons 38, 43
Risers 25, 26, 43, 45, 61, 64, 72, 84, 126, Appendices 8, 9
Rising mains (see fire mains)
Roof exits (see escape roofs, roof exits)
S
Security 51, 53, 54, 55, 61, 105-106
Sheltered housing 25, 29, 37, 56, 65, 67, 103, 105, 107-108, 118, 119, 120, 127, 131
extra care 107, 131
Shunt ducts 73, Appendix 1
Signs (see fire exit signs)
Signs and notices (see fire ext signs)
Simultaneous evacuation 28, 29, 85, 116, Appendix 5
Smoke
control 25, 29, 31, 32, 33, 35, 38, 62, 85-86, 87, 89, 94, 95, 96, 97, 98, 110, 123,
Appendices 1, 2, 7, 8, 9, 10, 13
detection (See automatic fire detection systems)
Smoke alarms 18, 19, 21, 22, 28-29, 32, 46, 67, 77, 103, 104, 108, 116, 124, Appendices 1,
2, 4, 6, 7, 8, 10, 11, 12, 13
T
Third-party certification 66, 71, 122, Appendices 3, 6
Timber frame 130
Travel distance (see escape routes, travel distance)
V
Ventilation
bathroom extract 26, 40, 64, 73, 74
kitchen extract 26, 40, 64, 73, 74
smoke control (see smoke control)
systems 40, 51, 64, 66, 73, 74
W
Water mist (see also fire suppression system) 32, 83, 124
Z
Zero tolerance 51, 58-59, 60