Fire Fighting NBC Norms Summary

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 6

FIRE FIGHTING NBC NORMS SUMMARY

1. The fire fighting norms are applicable to,


a) all high rise buildings; and
b) special buildings, those are,
1) hotel, educational, institutional, business, mercantile, industrial, storage, hazardous and
mixed occupancies, where any of these buildings have floor area more than 500 m2 on
any one or more floors;
2) educational buildings having height 9 m and above;
3) institutional buildings having height 9 m and above;
4) all assembly buildings;
5) buildings, having area more than 300 m2
of incidental assembly occupancy on any
floor; and
6) buildings with two basements or more,
or with one basement of area more than
500 m2.
2. Atrium . A large-volume space created by a floor opening or series of floor openings connecting two or
more stories that is covered at the top of the series of openings and is used for purposes other than an enclosed
stairway; lifts hoist-way; an escalator opening; or as a utility shaft used for plumbing, electrical, air conditioning, or
communications facilities.

3. Automatic Fire Detection and Alarm System : A system comprising components and sub-systems required for
automatically detecting smoke, heat or fire initiating an alarm and other actions as appropriate.
This system also includes manually operated electronic fire alarm system.

4. Down-comer: An arrangement of firefighting within the building by means of down-comer pipe connected to
terrace tank through terrace pump, gate valve and non-return valve and having mains not less than 100 mm internal
diameter with landing valves on each floor/landing. It is also fitted with inlet connections at ground level for charging
with water by pumping from fire service appliances and air release valve at roof level to release trapped air inside.

5. Dry Riser: An arrangement of firefighting within the building by means of vertical rising mains not less than 100
mm internal diameter with landing valves on each floor/landing which is normally dry but is capable of being charged
with water usually by pumping from fire service appliances.

6.Emergency Lighting System: A complete but discrete emergency lighting installation also fed from the standby
power source to the emergency lighting lamp(s).

7. Escape Lighting: That part of the emergency


lighting which is provided to ensure that the escape
route is illuminated at all material times,

8.Fire Barrier (or Fire Resisting Barrier):. A


fire barrier is a vertically or horizontally aligned
member such as a wall or a fire curtain, or a floor. These
may be with discontinuities created by openings with a
specified fire resistance rating, where such members
are designed and constructed with a specified fire resistance rating
to limit the spread of fire that also restricts the movement of smoke.

9. Fire Compartment . A space within a building that is enclosed by fire barrier or fire resistant walls on
all sides, including the top and bottom.

10.Fire Door and Fire Door Assembly: Any combination of fire door, frame, hardware and other
accessories that together provide a specific fire resistant rating to the opening in terms of its stability, integrity and
insulation properties, when installed in the openings in fire separation walls. Fire door is a component of fire door
assembly.
11. Firefighting Shaft (Fire Tower): An enclosed shaft having protected area of 120 min fire resistance rating
comprising protected lobby, staircase and fireman’s lift, connected directly to exit discharge or
through exit passageway with 120 min fire resistant wall at the level of exit discharge to exit discharge.
These shall also serve the purpose of exit requirement/ strategy for the occupants. The respective floors shall be
approachable from fire-fighting shaft enabling the fire fighters to access the floor and also enabling the fire fighters to
assist in evacuation through fireman’s lift. The firefighting shaft shall be equipped with
120 min fire doors. The firefighting shaft shall be
equipped with firemen talk back, wet riser and landing
valve in its lobby, to fight fire by fire fighters.

12. Fireman’s Lift . A lift or a group of lifts invariably


associated with all the features and requirements of a
fire-fighting shaft. These are installed to enable fire
services personnel to reach different floors with minimum
delay. This lift also serves the
purpose of meeting the requirement of evacuation lift
for assisted evacuation.

13. Fire Resistance . Fire resistance is a property


of an element of building construction and is the
measure of its ability to satisfy for a stated period, some
or all of the following criteria:
a) Load bearing capacity (Stability) (R) . The
ability of a load bearing element to withstand
fire exposure without any loss of structural
stability.
b) Integrity (E) . Resistance to penetration of
flame and hot gases.
c) Insulation (I) . Resistance to temperature
rise on the unexposed face up to a maximum
of 180°C at any single point and average
temperature of 140°C.

14. Refuge Area . An area within the building for a temporary use during egress. It generally serves as a
staging area which is protected from the effect of fire and smoke.

15.Water Based Systems

-Hydrant System . A distribution system having a network of piping installed underground/above- ground around
and/or through inside of a building with internal and/or external hydrants fitted with landing
valves at regular intervals according to the occupancy. The distribution system is connected to water supply system
for firefighting.

-Automatic Sprinkler System . A system of water pipes fitted with sprinkler heads at suitable intervals
and heights and designed to actuate automatically, control and extinguish a fire by the discharge of water.

-Automatic Water Spray Systems . A special fixed pipe system connected to a reliable source of fire
protection water supply and equipped with water spray nozzles for specific water discharge and distribution
over the surface or area to be protected. The piping system is connected to the water supply through an
automatically actuated deluge valve which initiates flow of water. Automatic actuation is achieved by operation of
automatic detecting equipment installed along with water spray nozzles. There are two types of systems namely high
velocity and medium velocity systems.

-Water Mist Systems . A distribution system connected to a pumping and water supply system that is equipped with
nozzles capable of delivering water mist to the part/entire enclosure or area, intended to
control, suppress, or extinguish fire and is capable of meeting the specified performance requirements.

-Foam Protection System . Firefighting systems where foam is made by mechanically mixing air with a
solution consisting of fresh water to which a foaming agent (liquid concentrate) has been added. Firefighting foam is a
stable aggregation of small bubbles of density lower than oil or water, and shows tenacious qualities for covering
horizontal surfaces. There are three types of foam applications that is, low, medium and high expansion foams
depending upon the application.
-Wet Riser . An arrangement for firefighting within the building by means of vertical rising mains
not less than 100 mm nominal diameter with landing valves on each floor/landing for firefighting purposes and
permanently charged with water from a pressurized supply.

16. A high rise building during construction shall be provided with the following fire protection measures, which
shall be maintained in good working condition at all the times:
a) Dry riser of minimum 100 mm diameter pipe with hydrant outlets on the floors constructed with a fire
service inlet to boost the water in the dry riser and maintenance should be in accordance with good
practice.
b) Drums of 2000 litre capacity filled with water with two fire buckets on each floor;
c) A water storage tank of minimum 20 000 litre capacity, which may be used for other construction
purposes also.

17. Service ducts and shafts: Openings in walls or floors which are necessary to be provided to allow passages of all
building services like cables, electrical wirings, telephone cables, plumbing pipes, etc, shall be protected by enclosure
in the form of ducts/shafts having a fire resistance not less than
120 min
Shaft door opening inside the building, the shafts shall have inspection doors having fire resistance rating not less than
30 min.

18.Refuse chutes: Refuse chutes, if any provided in a building, shall have opening at least 1 m above roof level for
venting purpose and they shall have an enclosure wall of non-combustible material with fire resistance of not less than
120 min. They shall not be located within the staircase enclosure or service shafts, or air conditioning shafts. Refuse
chutes inspection panel and doors shall be tight fitting with 60 min fire resistance. Sprinkler protection system shall be
provided for the refuse chutes. Refuse chutes shall be
at least 6 m away from exits.

19. Signage: Exit signs shall be clearly visible and be provided such that no point in an exit access is more than 30 m
from a visible exit directional sign.

20. Fire or fire/smoke dampers: These dampers shall be evaluated to be located in supply air ducts, fresh air and
return air ducts/ passages at the following points:
a) At the fire separation wall,
b) Where ducts/passages enter the vertical shaft,
c) Where the ducts pass through floors, and
d) At the inlet of supply air duct and the return air duct of each compartment on every floor.

21. Basement
a) Basement exits shall be sufficient to provide for the capacity of the basement as determined. In no case shall there
be less than two independent basement exits.
b) Basements having incidental occupancies to main occupancy shall be planned with exit requirements of the
basements for the actual occupancy within the basement.
c) Where basement is used for car parking and also there is direct approach from any occupancy above to the
basement, door openings leading to the basement shall need to be protected with fire doors with 120 min fire rating,
except for exit discharge doors from the basements.

22. Exit width: The unit of exit width, used to measure the
capacity of any exit, shall be 500 mm. A clear
width of 250 mm shall be counted as an
additional half unit. Clear widths less than
250 mm shall not be counted for exit width.

23. Exit doors: No exit doorway shall be less than 1000 mm in width
except assembly buildings, where door width shall be not less than 2000
mm. Doorways shall be not less than 2000 mm in height.
e) Revolving doors can be accepted as a component in a means of
egress where the following requirements are fully complied with:
1) Doors shall be capable of collapsing to a book fold position with
parallel egress paths, of width not less than 1000 mm.
2) Doors shall not be located within 3 m of the foot or top of stairs or escalators. A dispersal area shall be provided
between the stairs or escalators and the doors.
3) Each revolving door shall be provided with a hinged door in the same wall within 3 m thereof, with same exiting
capacity.
4) Each revolving door shall be considered as capable of exiting only 50 persons.

24. Staircase:

- The minimum width of tread without nosing shall be 250 mm for staircase of residential buildings, 300 mm for
assembly, hotels, educational, institutional, business and other buildings, shall prevent slipping.

-The maximum height of riser shall be 190 mm for staircase of residential buildings and 150 mm for other buildings.

-The number of risers shall be limited to 12 per flight.

a) Internal staircases:

- May be constructed with an external wall, or


- Shall be constructed of non-combustible materials throughout, and shall have fire resistant rating of
minimum 120 min.
- Shall not be arranged round a lift shaft.
- Exits shall not be used as a portion of a supply,return or exhaust air system serving adjoining areas. Any
opening(s) shall not be permitted in walls or in doors, separating exits from adjoining areas.
- No flue chimney, electromechanical equipment, air conditioning units, gas piping or electrical panels
shall be allowed in the stairway.

- Minimum width:
1) Residential (A-2) : 1.00 m
2) Residential (A-1, A-3 and A-4) : 1.25 m
3) Residential hotel (A-5 and A-6) : 1.50 m
4) Assembly : 2.00 m, (1.5 m in case of less than 150 persons occupancy)
5) Educational : 1.50 m
6) Institutional : 2.00 m
7) All other occupancies : 1.50 m

- A handrail shall be provided on one side of the staircase of width less than 1500 mm, and on both sides of the
staircase of width 1500 mm and more.
- The projection of handrail(s) in the staircase width shall not be more than 115 mm.
- Handrails may project inside the measured width by not more than 90 mm.

The design of staircase shall also take into


account the following:
1) The minimum headroom in a passage
under the landing of a staircase and under
the staircase shall be 2.2 m
2) Access to exit staircase shall be through
a fire door of a minimum 120 min fire
resistance rating.
3) No living space, store or other fire risk
shall open directly into staircases.
4) The exit (including staircases) shall be
continuous from refuge floors or terrace
level, as applicable, to the level of exit
discharge.
5) No electrical shafts/air conditioning ducts or
gas pipes, etc, shall pass through or open in the staircases.
6) Lifts shall not open in staircase.
7) No combustible material shall be used for decoration/wall panelling in the staircase.
8) Beams/columns and other building features shall not reduce the head room/ width of the staircase.
9) The floor indication board, indicating the location/designated number of staircase, respective floor number and
direction to exit discharge shall be placed inside the staircase, on the wall nearest to the fire
door. It shall be of size not less than 300 mm × 200 mm (see Fig. 9).
10) Individual floors shall be prominently indicated on the wall outside the staircase and facing it.
11) All staircase shall terminate at the level of exit discharge. The access to the basement shall be by a separate
staircase.
12) Scissors type staircases shall not be treated as part of exit.
Curved stairs:
Curved stairs shall not be treated as part means of egress. However, these may be used as part of exit access provided
the depth of tread is not less than 280 mm at a point 350 mm from the narrower end of the tread and the smallest
radius is not less than twice the stair width.

b) External staircases:
- Are provided on the external wall/facade, and
- Shall always be kept in sound and usable condition.
- All external stairs shall be directly connected to the ground.
-Entrance to the external stairs shall be separate and remote from the internal staircase.
-Where an external staircase is provided, it shall be ensured that the use of it at the time of fire is not prejudiced by
smoke and flame from openings (for example, windows, doors) in the external face of the building. Care shall be
taken to ensure that no external wall or window opening opens on to or close to an external stair. If such openings
exists within 3 m from an external staircase, they shall be protected with fire rated doors/window assemblies with
rating of at least 60 min
- The external stairs shall be constructed of non- combustible materials, and
any doorway leading to it shall have minimum
120 min fire resistance.
-No external staircase, shall be inclined at an angle greater than 45° from the
horizontal.
-External stairs shall have straight flight not less than 1500 mm wide.
-Handrails, to be provided on both sides, shall be of a height not less than
1000 mm and not exceeding 1200 mm. There shall be provisions of balusters
with maximum gap of
150 mm.
- The use of spiral staircase shall be limited to low occupant load and to a
building not exceeding 9 m in height. A spiral staircase shall be not less than
1500 mm in diameter and shall be designed to give adequate headroom.

25. Compartmentation: All floors shall be compartmented/zoned with area


of each compartment being not more than 750 m2. The maximum size of the compartment shall be as follows,
in case of sprinklered basement/building:

- Requirement of min. two compartments shall not be required, if the floor plate is less than 750 m 2.

- Compartmentation shall be achieved by means of fire barrier having fire resistance rating of 2hrs.

26. Air changes: Smoke exhaust system where provided, for above areas and occupancies shall have a minimum of
12 air changes per hour smoke exhaust mechanism.

27. Smoke Exhaust and Pressurization of Areas Below Ground


- Each basement shall be separately ventilated. Vents with cross-sectional area (aggregate) not less than 2.5 percent
of the floor area spread evenly round the perimeter of the basement shall be provided in the form of grills, or
breakable stall board lights or pavement lights or by way of shafts.
Alternatively, a system of mechanical ventilation system may be provided with following requirements:

a) Mechanical ventilation system shall be


designed to permit 12 air changes per hour in
case of fire or distress call.

b) In multi-level basements, independent airintake and smoke exhaust shafts (masonry or


reinforced concrete) for respective basement
levels and compartments therein shall be
planned with its make-up air and exhaust air
fans located on the respective level and in the
respective compartment.

28. Fire Detection and Alarm


a) For assembly buildings, institutional buildings and all buildings above 30 m in height where fire alarm system is
provided, detectors shall also be provided inside the electrical shafts, and lift machine rooms, etc, besides occupancy
areas.
b) Fire alarm panels shall be connected in peer to peer network or with redundant cables, run in different shafts.

29. First- aid hose reel: In addition to wet riser or down-comer, first- aid hose reels shall be installed in buildings on
all the floors. The first-aid hose reel shall be connected directly to the riser/down-comer
main and diameter of the hose reel shall not be less than 19 mm.

30. Hydrant: Those hydrants planned to be provided near fire exit staircase on the floor shall be within
5 m from exit door in exit access.

31. UG Fire water storage tank: The underground fire water storage tank(s) shall not be more than 7 m in depth
from the level having fire brigade draw-out connection, while the draw-out connection shall not be more than 5 m
away from the tank wall.

-The static water storage tank shall be provided with a fire brigade collecting head with 4 number 63 mm diameter (2
number 63 mm diameter for pump with capacity 1 400 litre/min).
-The same shall be connected to the static tank by a suitable fixed GI pipe not less than 150 mm in diameter to
discharge water into the tank when required at the rate of 2 250 litre/min, if tank is in the basement or not
approachable for the fire engines.
-Each of the static water storage tanks shall also be provided with a fire brigade draw out collecting head
with 63 mm diameter.
-This draw out shall be connected to GI pipe of 100 mm diameter with foot valve arrangement in the tank.

-o0o-

Muskan Batra
Roll No.- 02

You might also like