Fresh Chicken Condensing Units

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Fresh Chicken Room

BITZER Software v6.15.2 rev2501 1/20/2021 / All data subject to change. 1/4

Selection: Condensing Units


Input Values
Unit type (LH114/4PES-12Y)
Series Standard
Refrigerant R134a
Reference temperature Dew point temp.
Evaporating SST -2.00 °C
Ambient temp. 46.0 °C
Suction gas temperature 20.00 °C
Useful superheat 100%
Operating mode Auto
Power supply 400V-3-50Hz
Capacity control 100%

Result
Unit type LH114/4PES-12Y-40P
Capacity steps 100%
Cooling capacity 16.34 kW
Evaporator capacity 16.34 kW
Power input 7.04 kW
Current (400V) 12.91 A
Voltage range 380-420V
Mass flow 435 kg/h
Condensing SDT 59.0 °C
Liquid subcooling 3.00 K
Operating mode Standard

Tentative Data.
Since 01.07.2016, available only for regions outside European Union.
Power input compressor, power input fan see ''T. Data''

Application Limits LH114/4PES-12

Legend
additional cooling

suction gas superheat >10K

M1: motor 1

M2: motor 2
Fresh Chicken Room

BITZER Software v6.15.2 rev2501 1/20/2021 / All data subject to change. 2/4

Technical Data: (LH114/4PES-12Y)


Dimensions and Connections

Technical Data
Technical Data
Weight 268 kg
Total width 1356 mm
Total depth 920 mm
Total height 773 mm
Connection suction line 35 mm - 1 3/8''
Connection liquid line 16 mm - 5/8''
Fans: Number 2xAC
Voltage (50Hz, more on request) 230V-1-50Hz (Standard)
Current / Power consumption of each fan (50Hz) 1,41 A / 301 W
Air flow condenser 50Hz 7804 m³/h
Voltage (60Hz, more on request) 230V-1-60Hz (Standard)
Current / Power consumption of each fan (60Hz) 1,93 A / 445 W
Air flow condenser 60Hz 8904 m³/h
Coil Volume 12,0 dm³
Receiver type (Standard) F152H
Max. refrigerant charge 90% at 20°C / 68°F
R22 16,3 kg
R134a 16,6 kg
R407C 15,6 kg
R404A/R507A 14,4 kg
Receiver type (Option) F302H
R22 32,7 kg
R134a 33,1 kg
R407C 31,3 kg
R404A/R507A 28,8 kg
Extent of delivery (Standard)
Discharge line Standard
Protective charge Standard
Available Options
Oil separator Option
Check valve Option
High & low pressure switch Option
Dressed unit Option
Weather protective housing Option
Fans: elect. Speed control Option
Sound measurement
Sound power level (-10°C / 45°C) 82,5 dB(A) @ 50Hz
Sound pressure level @ 1m (-10°C / 45°C) 74,5 dB(A) @ 50Hz

You might also like