Gencomm Alarms: Dsegencomm Protocol
Gencomm Alarms: Dsegencomm Protocol
Gencomm Alarms: Dsegencomm Protocol
Highfield House, Hunmanby Industrial Estate, Hunmanby, North Yorkshire YO14 0PH England
TELEPHONE +44 (0) 1723 890099 FASCIMILE +44 (0) 1723 890099 EMAIL [email protected]
DSEGENCOMM PROTOCOL
DSE7200, DSE7300, DSE7400, DSE8600, DSE8700, DSE8800 series
GENCOMM ALARMS
www.deepseaplc.com
www.deepseaplc.com
OVERALL STATUS
For alarm status, read page 3, register 6
This contains a bit field of status information :
Register Name Minimum Maximum Scaling Units Bits/ sign
offset value value factor
0 Manufacturer code 0 65534 1 16
1 Model number 0 65534 1 16
2-3 Serial number 0 999999999 1 32
4 Control mode 0 65535 1 16
5 Unimplemented 0xFFFF 0xFFFF 16
6 Control unit not configured No Yes 16/16
Unimplemented 0 0 15/16
Control unit failure No Yes 14/16
Shutdown alarm active No Yes 13/16
Electrical trip alarm active No Yes 12/16
Warning alarm active No Yes 11/16
Telemetry alarm flag Not active Active 10/16
Satellite telemetry alarm flag Not active Active 9/16
No font file No Yes 8/16
Unimplemented 0 0 1/16-7/16
www.deepseaplc.com
ACTIVE ALARMS
To find which alarms are active, read page 153 for
unnamed (user configured) alarms and page 154 for
named (pre-configured) alarms. :
ALARM CONDITIONS