Sepam s40 Oc Ef Relay

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 12

Commissioning Service Department

Commissioning Standard Test Formats

Description: SEPAM S40 OC/EF PROTN. RELAY Record No. :


ACDB Panels Drawing ref.: Sheet : 1 of 12
Contractor : Contract no.: Substation No :

1. GENERAL DATA AND INFORMATION:

Bay No. Designation

Bay Name ACDB Order No.

MAKER Schneider Serial No.

Dwg & Sh No. Aux. Voltage 24 - 250 VDC

Frequency 60 Hz Rated Current in Service 5A

CT Ratio 1600 / 5 A

2. MECHANICAL CHECKS AND VISUAL INSPECTION:

ITEM DESCRIPTION CHECKED

1 Inspect for any physical damage or defects.

2 Check tightness of all bolted connections.

3 Check all grounding connections are securely fix

4 Verify connections as per approved drawing

5 Check apparatus lists

6 Check Ferrules

3. ELECTRICAL TESTS:

3.1. FUNCTION TEST:

ITEM DESCRIPTION CHECKED

1 Test switch / plug checked for correct function

2 Indication checked

3 Alarm contacts checked

4 Trip contacts checked

5 Watchdog contacts checked

6 All output contacts resistance measured

7 All inputs checked

3.2. Operating DC Supply Current:

Tested by: ENG. Witnessed by:

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: SEPAM S40 OC/EF PROTN. RELAY Record No. :


ACDB Panels Drawing ref.: Sheet : 2 of 12
Contractor : Contract no.: Substation No :

DC Volts (V) DC Current W/O Fault (mA) DC Current during Fault (mA) Calculated Watt (W)

Maximum burden of the aux. supply 11W SEPAM manual PCRED301006EN

4. TESTING AND COMMISSIONING:

4.1. 1A: 50/51 & 50N/51N PICK UP and DROP OFF (I> & I0> Test)

Ratio : 1600/5A
In = 1600 A , I setting = I threshold (0.4 In to 24 In , 0.1 In0 to 15 In0)
2A: 50/51 = OFF
50N/51N = OFF
3A: 50/51 = OFF
50N/51N = OFF
4A: 50/51 = OFF
50N/51N = OFF

Current Over Current Relay Current Earth Fault Relay


Setting R Y B Setting (N)
IThreshold IThreshold
(50 / 51) P/U D/O P/U D/O P/U D/O (50N / 51N) P/U D/O
Amps A A A A A A Amps A A

2.5 A 1.0 A

5.0 A 1.5 A

10.0 A 4.0 A

For the phase over current Accuracy: ±5% or  0.01 In


(AS MANUAL SEPAM PCRED301006EN page 3/28)
For the earth fault Accuracy: ±5% or  0.01 In0
(AS MANUAL SEPAM PCRED301006EN page 3/34)
DROP-OFF/ PICK-UP Ratio: 93.5%  5%
(AS MANUAL SEPAM PCRED301006EN page 3/28 & 3/34)

4.2. 1A: 50/51 & 50N/51N RELAY OPERATING VALUE AS PER CURVE (I> & I0> Curve Test)

Ratio : 1600/5A
Tested by: ENG. Witnessed by:

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: SEPAM S40 OC/EF PROTN. RELAY Record No. :


ACDB Panels Drawing ref.: Sheet : 3 of 12
Contractor : Contract no.: Substation No :

In = 1600 A
50/51 Threshold = 320A
I injected = 10 * I threshold = 3200 A P (10 A S)
50N/51N Threshold = 160A
I0 injected = 10 * I0 threshold = 1600A P (5.0 A S)
2A: 50/51 = OFF
50N/51N = OFF
3A: 50/51 = OFF
50N/51N = OFF
4A: 50/51 = OFF
50N/51N = OFF

Operating Time (s)


TMS Calculated
Function Range (s)
Setting Value (s)
R Y B N
IEC Very Inverse Time
1 1.425 – 1.575 1.5
VIT/B
IEC Extremely Inverse Time
1 0.768 – 0.848 0.808
EIT/C
IEC Standard Inverse Time
1 2.822 – 3.120 2.971
SIT/A
IEC Long Inverse Time
0.937 11.868 – 13.118 12.493
LTI/B

For SIT/A : K = 0.14 ,  = 0.02 (For SIT/A)


TMS∗K T
t ( s) = TMS= ; β=2.97 ( For SIT / A)
I inj α
β
( ) −1
I set

The accuracy for IDMT curves for phase over current or Earth fault
is class 5 or Calculation (-10 ms : +25 ms) at 10 Is or 10 Is0
(AS MANUAL SEPAM PCRED301006EN )

4.3. 1A: 50/51 & 50N/51N TIME MULTIPLIER TESTS (I> & I0> TMS Test)

Ratio : 1600/5A , In = 1600 A ,

Tested by: ENG. Witnessed by:

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: SEPAM S40 OC/EF PROTN. RELAY Record No. :


ACDB Panels Drawing ref.: Sheet : 4 of 12
Contractor : Contract no.: Substation No :

50/51 Threshold = 320A , Curve: IEC Standard Inverse Time SIT/A


I injected = 10 * I threshold = 3200A P (10 A S)
50N/51N Threshold = 160A , Curve: IEC Standard Inverse Time SIT/A
I0 injected = 10 * I0 threshold = 1600A P (5.0 A S)
50/51 Threshold = 320A , Curve: IEC Standard Inverse Time SIT/A
I injected = 2 * I threshold = 640A P (2 A S)
50N/51N Threshold = 160A , Curve: IEC Standard Inverse Time SIT/A
I0 injected = 2 * I0 threshold = 320A P (1.0 A S)
2A: 50/51 = OFF
50N/51N = OFF
3A: 50/51 = OFF
50N/51N = OFF
4A: 50/51 = OFF
50N/51N = OFF

Delay R – Phase (s) Y – Phase (s) B – Phase (s) E / F N (s)


Range
=
(s)
TMS Calc. Actual Calc. Actual Calc. Actual Calc. Actual

0.2 0.598 0.598 0.598 0.598 0.564 – 0.620

0.4 1.188 1.188 1.188 1.188 1.129 – 1.247

0.5 1.485 1.485 1.485 1.485 1.411 – 1.56

I injected = 2 * I setting

0.2 2.006 2.006 2.006 2.006 1.906 – 2.106

0.4 4.012 4.012 4.012 4.012 3.814 – 4.213

0.5 5.015 5.015 5.015 5.015 4.735 – 5.265

The accuracy for IDMT curves for phase over current or earth fault is
class 5 or -10ms - +25ms at 10 Is or 10 Is0
(AS MANUAL SEPAM PCRED301006EN page 3/28 & 3/34)

4.4. 1A: 50/51 & 50N/51N DEFINITE TIME CHARACRISTICS (I> & I0> Definite Time Test)

Ratio : 1600/5A

Tested by: ENG. Witnessed by:

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: SEPAM S40 OC/EF PROTN. RELAY Record No. :


ACDB Panels Drawing ref.: Sheet : 5 of 12
Contractor : Contract no.: Substation No :

In = 1600 A , I inj = 2 * Is
I threshold = 1600 A , Curve: Definite
I0 threshold = 1600 A , Curve: Definite
2A: 50/51 = OFF
50N/51N = OFF
3A: 50/51 = OFF
50N/51N = OFF
4A: 50/51 = OFF
50N/51N = OFF

Current Current Operating


Setting Operating Time (s) Setting
Delay Delay Time (s)
IThreshold IThreshold
Set (s) Set (s)
(50 / 51) R Y B (50N / 51N) (N)
Amps Amps

10 10

5A 5 5A 5

2 2

The accuracy for definite curves for phase over current or earth fault is
Class 2% or -10ms - +25ms at 10 Is or 10 Is0
(AS MANUAL SEPAM PCRED301006EN page 3/28 & 3/34)

Tested by: ENG. Witnessed by:

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: SEPAM S40 OC/EF PROTN. RELAY Record No. :


ACDB Panels Drawing ref.: Sheet : 6 of 12
Contractor : Contract no.: Substation No :

4.5. 1A: 50/51 = OFF


50N/51N = OFF
2A: 50/51 & 50N/51N SETTING ELEMENT TEST (I>> & I0>> Test)
Ratio : 1600/5A
In = 1600 A , I setting = I threshold
3A: 50/51 = OFF
50N/51N = OFF
4A: 50/51 = OFF
50N/51N = OFF

Current Over Current Relay Current Earth Fault Relay


Setting R Y B Setting (N)
IThreshold IThreshold
(50 / 51) P/U D/O P/U D/O P/U D/O (50N / 51N) P/U D/O
Amps A A A A A A Amps A A

5.0 A 2.5 A

7.5 A 3.75 A

10.0 A 5.0 A

For the phase over current Accuracy:  5% or  0.01 In


(AS MANUAL SEPAM PCRED301006EN page 3/28)
For the earth fault Accuracy:  5% or  0.01 In0
(AS MANUAL SEPAM PCRED301006EN page 3/34)
DROP-OFF/ PICK-UP Ratio: 93.5%  5%
(AS MANUAL SEPAM PCRED301006EN page 3/28 & 3/34)

Tested by: ENG. Witnessed by:

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: SEPAM S40 OC/EF PROTN. RELAY Record No. :


ACDB Panels Drawing ref.: Sheet : 7 of 12
Contractor : Contract no.: Substation No :

4.6. 1A: 50/51 = OFF


50N/51N = OFF
2A: 50/51 & 50N/51N TIMING TEST (I>> & I0>> Timing Test)
Ratio : 1600/5A
In = 1600 A , I inj = 2 * Is
Curve: Definite
3A: 50/51 = OFF
50N/51N = OFF
4A: 50/51 = OFF
50N/51N = OFF
Current
Current Setting
Operating Time
Setting Injected Set Operating Time (m sec) IThreshold
(m sec)
IThreshold Current Delay (50N / 51N)
(50 / 51) Amps (m sec) Amps
Amps
R Y B (N)

2.5 A 5.0 A 0 1.5 A

3.75 A 7.5 A 400 2.5 A

5.0 A 10.0 A 500 5.0 A

The accuracy for instantaneous phase over current or earth fault is


< 50 ms at 2 Is or 2 Is0;Is>= 0.3In
<70 ms at 2 Is or 2 Is0; Is = 0.3In
(AS MANUAL SEPAM PCRED301006EN page 3/28 & 3/34)

Tested by: ENG. Witnessed by:

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: SEPAM S40 OC/EF PROTN. RELAY Record No. :


ACDB Panels Drawing ref.: Sheet : 8 of 12
Contractor : Contract no.: Substation No :

4.7. 1A: 50/51 = OFF


50N/51N = OFF
2A: 50/51 = OFF
50N/51N = OFF
3A: 50/51 & 50N/51N SETTING ELEMENT TEST (I>>> & I0>>> Test)
Ratio : 1600/5A
In = 1600 A , I setting = I threshold
4A: 50/51 = OFF
50N/51N = OFF

Current Over Current Relay Current Earth Fault Relay


Setting R Y B Setting (N)
IThreshold IThreshold
(50 / 51) P/U D/O P/U D/O P/U D/O (50N / 51N) P/U D/O
Amps A A A A A A Amps A A

5.0 A 2.5 A

7.5 A 3.75 A

10.0 A 5.0 A

For the phase over current Accuracy:  5% or  0.01 In


(AS MANUAL SEPAM PCRED301006EN page 3/28)
For the earth fault Accuracy:  5% or  0.01 In0
(AS MANUAL SEPAM PCRED301006EN page 3/34)
DROP-OFF/ PICK-UP Ratio: 93.5%  5%
(AS MANUAL SEPAM PCRED301006EN page 3/28 & 3/34)

Tested by: ENG. Witnessed by:

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: SEPAM S40 OC/EF PROTN. RELAY Record No. :


ACDB Panels Drawing ref.: Sheet : 9 of 12
Contractor : Contract no.: Substation No :

4.8. 1A: 50/51 = OFF


50N/51N = OFF
2A: 50/51 = OFF
50N/51N = OFF
3A: 50/51 & 50N/51N TIMING TEST (I>>> & I0>>> Timing Test)
Ratio : 1600/5A
In = 1600 A , I inj = 2 * Is
Curve: Definite
4A: 50/51 = OFF
50N/51N = OFF
Current
Current Setting
Operating Time
Setting Injected Set Operating Time (m sec) IThreshold
(m sec)
IThreshold Current Delay (50N / 51N)
(50 / 51) Amps (m sec) Amps
Amps
R Y B (N)

2.5 A 5.0 A 50 2.5 A

5.0 A 10.0 A 50 5.0 A

The accuracy for instantaneous phase over current or earth fault is


< 50 ms at 2 Is or 2 Is0; Is>= 0.3 In
<70 ms at 2 Is or 2 Is0; Is = 0.3 In
(AS MANUAL SEPAM PCRED301006EN page 3/28 & 3/34)

Tested by: ENG. Witnessed by:

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: SEPAM S40 OC/EF PROTN. RELAY Record No. :


ACDB Panels Drawing ref.: Sheet : 10 of 12
Contractor : Contract no.: Substation No :

4.9. 1A: 50/51 = OFF


50N/51N = OFF
2A: 50/51 = OFF
50N/51N = OFF
3A: 50/51 = OFF
50N/51N = OFF
4A: 50/51 & 50N/51N SETTING ELEMENT TEST (I>>>> & I0>>>> Test)
Ratio : 1600/5A
In = 1600 A , I setting = I threshold

Current Over Current Relay Current Earth Fault Relay


Setting R Y B Setting (N)
IThreshold IThreshold
(50 / 51) P/U D/O P/U D/O P/U D/O (50N / 51N) P/U D/O
Amps A A A A A A Amps A A

5.0 A 2.5 A

7.5 A 3.75 A

10.0 A 5.0 A

For the phase over current Accuracy:  5% or  0.01 In


(AS MANUAL SEPAM PCRED301006EN page 3/28)
For the earth fault Accuracy:  5% or  0.01 In0
(AS MANUAL SEPAM PCRED301006EN page 3/34)
DROP-OFF/ PICK-UP Ratio: 93.5%  5%
(AS MANUAL SEPAM PCRED301006EN page 3/28 & 3/34)

Tested by: ENG. Witnessed by:

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: SEPAM S40 OC/EF PROTN. RELAY Record No. :


ACDB Panels Drawing ref.: Sheet : 11 of 12
Contractor : Contract no.: Substation No :

4.10.1A: 50/51 = OFF


50N/51N = OFF
2A: 50/51 = OFF
50N/51N = OFF
3A: 50/51 = OFF
50N/51N = OFF
4A: 50/51 & 50N/51N TIMING TEST (I>>>> & I0>>>> Timing Test)
Ratio : 1600/5A
In = 1600 A , I inj = 2 * Is
Curve: Definite
Current
Current Setting
Operating Time
Setting Injected Set Operating Time (m sec) IThreshold
(m sec)
IThreshold Current Delay (50N / 51N)
(50 / 51) Amps (m sec) Amps
Amps
R Y B (N)

2.5 A 5.0 A 50 2.5 A

5.0 A 10.0 A 50 5.0 A

The accuracy for instantaneous phase over current or earth fault is


< 50 ms at 2 Is or 2 Is0; Is>= 0.3 In
<70 ms at 2 Is or 2 Is0; Is = 0.3 In
(AS MANUAL SEPAM PCRED301006EN page 3/28 & 3/34)

Tested by: ENG. Witnessed by:

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: SEPAM S40 OC/EF PROTN. RELAY Record No. :


ACDB Panels Drawing ref.: Sheet : 12 of 12
Contractor : Contract no.: Substation No :

4.11. Measurement Test:


In = 1600 A ;
Ratio : 1600 / 5 A

Display Measurement Readings (A)


I injected/ph
I1 (A) I2 (A) I3 (A) Io (A)

2.5

5.0

Accuracy for the phase current measurement is:


 0.5% and for the earth current measurement is 1%
SEPAM manual PCRED301006EN (sheet 2/3)

4.12. Relay Features Check:

Sr. Relay Features Description Remarks

1 Language has been set to English

2 Frequency has been set to 60 Hz

3 Relay Model No. has been checked in the display

4 Resetting of alarms through HMI checked

5 Active setting group checked Group-A

6 Setting has not been changed after DC fail

4.13. Output Relay Contact Resistance Check:

Output Contact 01 03 04

Resistance (ohms)

Tested by: ENG. Witnessed by:

Signature & Date: Signature & Date: