Sepam s40 Oc Ef Relay
Sepam s40 Oc Ef Relay
Sepam s40 Oc Ef Relay
CT Ratio 1600 / 5 A
6 Check Ferrules
3. ELECTRICAL TESTS:
2 Indication checked
DC Volts (V) DC Current W/O Fault (mA) DC Current during Fault (mA) Calculated Watt (W)
4.1. 1A: 50/51 & 50N/51N PICK UP and DROP OFF (I> & I0> Test)
Ratio : 1600/5A
In = 1600 A , I setting = I threshold (0.4 In to 24 In , 0.1 In0 to 15 In0)
2A: 50/51 = OFF
50N/51N = OFF
3A: 50/51 = OFF
50N/51N = OFF
4A: 50/51 = OFF
50N/51N = OFF
2.5 A 1.0 A
5.0 A 1.5 A
10.0 A 4.0 A
4.2. 1A: 50/51 & 50N/51N RELAY OPERATING VALUE AS PER CURVE (I> & I0> Curve Test)
Ratio : 1600/5A
Tested by: ENG. Witnessed by:
In = 1600 A
50/51 Threshold = 320A
I injected = 10 * I threshold = 3200 A P (10 A S)
50N/51N Threshold = 160A
I0 injected = 10 * I0 threshold = 1600A P (5.0 A S)
2A: 50/51 = OFF
50N/51N = OFF
3A: 50/51 = OFF
50N/51N = OFF
4A: 50/51 = OFF
50N/51N = OFF
The accuracy for IDMT curves for phase over current or Earth fault
is class 5 or Calculation (-10 ms : +25 ms) at 10 Is or 10 Is0
(AS MANUAL SEPAM PCRED301006EN )
4.3. 1A: 50/51 & 50N/51N TIME MULTIPLIER TESTS (I> & I0> TMS Test)
I injected = 2 * I setting
The accuracy for IDMT curves for phase over current or earth fault is
class 5 or -10ms - +25ms at 10 Is or 10 Is0
(AS MANUAL SEPAM PCRED301006EN page 3/28 & 3/34)
4.4. 1A: 50/51 & 50N/51N DEFINITE TIME CHARACRISTICS (I> & I0> Definite Time Test)
Ratio : 1600/5A
In = 1600 A , I inj = 2 * Is
I threshold = 1600 A , Curve: Definite
I0 threshold = 1600 A , Curve: Definite
2A: 50/51 = OFF
50N/51N = OFF
3A: 50/51 = OFF
50N/51N = OFF
4A: 50/51 = OFF
50N/51N = OFF
10 10
5A 5 5A 5
2 2
The accuracy for definite curves for phase over current or earth fault is
Class 2% or -10ms - +25ms at 10 Is or 10 Is0
(AS MANUAL SEPAM PCRED301006EN page 3/28 & 3/34)
5.0 A 2.5 A
7.5 A 3.75 A
10.0 A 5.0 A
5.0 A 2.5 A
7.5 A 3.75 A
10.0 A 5.0 A
5.0 A 2.5 A
7.5 A 3.75 A
10.0 A 5.0 A
2.5
5.0
Output Contact 01 03 04
Resistance (ohms)