Structural Design Analysis: Proposed Two (2) - Storey Residential Building

This document provides a structural design analysis of a reinforced concrete footing (F1) for a proposed two-storey residential building. It includes calculations to check for adequate shear capacity and punching shear. The footing is 2.1m x 2.1m x 0.35m deep and supports a column of 0.35m x 0.35m. Calculations show the footing has adequate shear capacity and punching shear capacity to resist factored loads of 413.453kN from service and self-weight loads. Reinforcement of 16mm diameter bars at a ratio of 0.027969 is also adequate.

Uploaded by

Jc Jüsäyän
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
67% found this document useful (3 votes)
10K views

Structural Design Analysis: Proposed Two (2) - Storey Residential Building

This document provides a structural design analysis of a reinforced concrete footing (F1) for a proposed two-storey residential building. It includes calculations to check for adequate shear capacity and punching shear. The footing is 2.1m x 2.1m x 0.35m deep and supports a column of 0.35m x 0.35m. Calculations show the footing has adequate shear capacity and punching shear capacity to resist factored loads of 413.453kN from service and self-weight loads. Reinforcement of 16mm diameter bars at a ratio of 0.027969 is also adequate.

Uploaded by

Jc Jüsäyän
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

STRUCTURAL DESIGN

ANALYSIS

PROPOSED TWO(2)-STOREY
RESIDENTIAL BUILDING

Prepared by:

JULIE ANNE CLAIRE A. LORILLA


Civil Engineer
PRC No.: 162198 Validity: JULY 6,2021

PTR No.: 2185852 Date Issued: JANUARY 4, 2021


TIN No.: 739-542-579 Place Issued:
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN CRITERIA
I. DESIGN LOADING
1. DEAD LOADS
A. Concrete = 24.00 kN/m³
B. Soil = 18.30 kN/m³
C. Steel = 77.00 kN/m³
D. CHB 100mm thk. = 2.15 kPa
E. CHB 150mm thk. = 2.75 kPa
F. Wall Finish = 0.50 kPa
For each face plastered, 0.24 kPA
G. Floor / Floor Finish = 1.85 kPa
Ceramic/Quarry Tile, 0.45 kPa
Mortar, 0.35 kPa / 12.50 mm thk.
Thickness: 50.00 mm thk.
H. Ceiling = 0.20 kPa
Gypsum board (per mm thickness), 0.008 kPa
Thickness: 12.50 mm thk.
Suspended Steel Channel System, 0.10 kPa

2. LIVE LOADS
A. Residential
1) Basic Floor Area = 1.90 kPa
2) Exterior Balconies = 2.90 kPa
3) Deck = 1.90 kPa
4) Storage = 1.90 kPa
5) Roof = 1.00 kPa

II. DESIGN STRESSES


1. CONCRETE
A. For Footing, Columns, Beams, and Slabs. fc' = 20.70 MPa
Compressive Strength @ 28 DAYS

2. REINFORCING STEEL BAR


A. For Footing, Columns and Beams
For bars 16mmØ and Greater Intermediate Grade fy = 275.00 MPa
Deformed Bar
B. For Slab on Fill, Suspended Slabs, Ties and Stirrups
For bars 12mmØ and Lower Intermediate Grade fy = 230.00 MPa
Deformed Bar
C. For Trusses, Purlins, Bracings and Struts fy = 248.00 MPa

III. DESIGN SOIL BEARING


1. ALLOWABLE SOIL BEARING PRESSURE qa = 96.00 kPa
NOTE: No Footing Shall Rest on Fill
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE FOOTING


Footing: F1
Location: B3
I. FOOTING PROPERTIES
Design Footing: Unfactored Loads:
Length, L= 2.10 m Service LC, Po = 232.032 kN
Width, W= 2.10 m Ftng. Self Wt. Wfn = 37.044 kN
Depth, d= 0.350 m Total, Po Po t = 269.076 kN
Eff. Depth, d eff. = 0.267 m Factored Loads:
Fdn. Depth, D= 1.50 m Service LC, Pu = 369.000 kN
Min. Fdn. Depth D min. = 1.16 m Ftng. Self Wt. Wfu = 44.453 kN
Column, b= 0.350 m Total, Pu Pu t = 413.453 kN
h= 0.350 m Minimum Footing Dimension:
Material Properties: Length, L= 2.01 m
Concrete, fc' = 20.70 Mpa Width, W= 2.01 m
Steel, fy = 275.00 Mpa Steel Requirements:
Reduction Factor: Reinf Steel Bar Dia Ø= 16 mm
Bending, ф= 0.90 ρ bal = 0.85 β fc' 600 / fy(600+fy)
Shear, ф= 0.75 = 0.037292
bot steel cover, sc = 0.075 m ρ min = 1.40 / fy = 0.005091
Bearing Pressure: ρ max = 75% ρ bal = 0.027969
ESBP, qe = 66.555 kN/m²
USBP, qu = 93.754 kN/m²

II. DETAILED CALCULATIONS


Wide Beam Shear:
a. Along Length, b. Along Width
A= Wx A= Ly
= 2.10 x 0.608 = 2.10 x 0.608
= 1.277 m² = 1.277 m²
Vu = qu A Vu = qu A
= 93.75 x 1.277 = 93.75 x 1.277
= 119.724 kN = 119.724 kN
Vc = √fc' W d / 6 Vc = √fc' L d / 6
= √20.70 x 2.10 x 0.267 / 6 = √20.70 x 2.10 x 0.267 / 6
= 425.172 kN = 425.172 kN
x = L/2 - b/2 - d FS = фVc / Vu y = W/2 - h/2 - d FS = фVc / Vu
= 2.10/2 - 0.350/2 - 0.267 = 0.75 x 425.17 / 119.72 = 2.10/2 - 0.350/2 - 0.267 = 0.75 x 425.17 / 119.72
= 0.608 m = 2.66 >1 .'. Adequate! = 0.608 m = 2.66 >1 .'. Adequate!
Punching Shear:
x= b+d A = LW - xy Vc = √fc' bo d / 3
= 0.350 + 0.267 = (2.10 x 2.10) - (0.617 x 0.617) = √20.70 x 2.468 x 0.267 / 3
= 0.617 m = 4.029 m² = 999.356 kN
y= h+d Vu = qu A FS = фVc / Vu
= 0.350 + 0.267 = 93.75 x 4.029 = 0.75 x 999.36 / 377.74
= 0.617 m = 377.735 kN = 1.98 >1 .'. Adequate!
bo = 2x + 2y
= (2 x 0.617) + (2 x 0.617)
= 2.468 m
Reinforcing Steel Bars:
a. Along Length, b. Along Width,
Mu = qu A Mu = qu A
= 93.75 x 1.838 = 93.75 x 1.838
= 172.320 kN-m = 172.320 kN-m
Ru = Mu / ф W d² Ru = Mu / ф L d²
= 172.32x10^6 / = 172.32x10^6 /
(0.90 x 2.10 x 0.267²) (0.90 x 2.10 x 0.267²)
= 1.2789 MPa = 1.2789 MPa
ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')] ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')]
= [0.85(20.70/275.00)] {1 - √1 - = [0.85(20.70/275.00)] {1 - √1 -
[(2 x 1.2789) / (0.85 x 20.70)]} [(2 x 1.2789) / (0.85 x 20.70)]}
= 0.004833 = 0.004833
use ρ = 0.005091 use ρ = 0.005091
x = L/2 - b/2 As = ρ W d y = W/2 - h/2 As = ρ L d
= 2.10/2 - 0.350/2 = 0.005091 x 2.10 x 0.267 = 2.10/2 - 0.350/2 = 0.005091 x 2.10 x 0.267
= 0.875 m = 2854.524 mm² = 0.875 m = 2854.524 mm²
A= Wx Qty = As / Ab A= Ly Qty = As / Ab
= 2.10 x 0.875 = 2,854.524 / π16²/4 = 2.10 x 0.875 = 2,854.524 / π16²/4
= 1.838 m² = 15 L - 16mmØ RSB = 1.838 m² = 15 L - 16mmØ RSB
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE FOOTING


Footing: F1
Location: B4
I. FOOTING PROPERTIES
Design Footing: Unfactored Loads:
Length, L= 2.00 m Service LC, Po = 191.277 kN
Width, W= 2.00 m Ftng. Self Wt. Wfn = 33.600 kN
Depth, d= 0.350 m Total, Po Po t = 224.877 kN
Eff. Depth, d eff. = 0.267 m Factored Loads:
Fdn. Depth, D= 1.50 m Service LC, Pu = 304.000 kN
Min. Fdn. Depth D min. = 1.07 m Ftng. Self Wt. Wfu = 40.320 kN
Column, b= 0.350 m Total, Pu Pu t = 344.320 kN
h= 0.350 m Minimum Footing Dimension:
Material Properties: Length, L= 1.84 m
Concrete, fc' = 20.70 Mpa Width, W= 1.84 m
Steel, fy = 275.00 Mpa Steel Requirements:
Reduction Factor: Reinf Steel Bar Dia Ø= 16 mm
Bending, ф= 0.90 ρ bal = 0.85 β fc' 600 / fy(600+fy)
Shear, ф= 0.75 = 0.037292
bot steel cover, sc = 0.075 m ρ min = 1.40 / fy = 0.005091
Bearing Pressure: ρ max = 75% ρ bal = 0.027969
ESBP, qe = 66.555 kN/m²
USBP, qu = 86.080 kN/m²

II. DETAILED CALCULATIONS


Wide Beam Shear:
a. Along Length, b. Along Width
A= Wx A= Ly
= 2.00 x 0.558 = 2.00 x 0.558
= 1.116 m² = 1.116 m²
Vu = qu A Vu = qu A
= 86.08 x 1.116 = 86.08 x 1.116
= 96.065 kN = 96.065 kN
Vc = √fc' W d / 6 Vc = √fc' L d / 6
= √20.70 x 2.00 x 0.267 / 6 = √20.70 x 2.00 x 0.267 / 6
= 404.926 kN = 404.926 kN
x = L/2 - b/2 - d FS = фVc / Vu y = W/2 - h/2 - d FS = фVc / Vu
= 2.00/2 - 0.350/2 - 0.267 = 0.75 x 404.93 / 96.07 = 2.00/2 - 0.350/2 - 0.267 = 0.75 x 404.93 / 96.07
= 0.558 m = 3.16 >1 .'. Adequate! = 0.558 m = 3.16 >1 .'. Adequate!
Punching Shear:
x= b+d A = LW - xy Vc = √fc' bo d / 3
= 0.350 + 0.267 = (2.00 x 2.00) - (0.617 x 0.617) = √20.70 x 2.468 x 0.267 / 3
= 0.617 m = 3.619 m² = 999.356 kN
y= h+d Vu = qu A FS = фVc / Vu
= 0.350 + 0.267 = 86.08 x 3.619 = 0.75 x 999.36 / 311.52
= 0.617 m = 311.524 kN = 2.41 >1 .'. Adequate!
bo = 2x + 2y
= (2 x 0.617) + (2 x 0.617)
= 2.468 m
Reinforcing Steel Bars:
a. Along Length, b. Along Width,
Mu = qu A Mu = qu A
= 86.08 x 1.650 = 86.08 x 1.650
= 142.032 kN-m = 142.032 kN-m
Ru = Mu / ф W d² Ru = Mu / ф L d²
= 142.03x10^6 / = 142.03x10^6 /
(0.90 x 2.00 x 0.267²) (0.90 x 2.00 x 0.267²)
= 1.1069 MPa = 1.1069 MPa
ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')] ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')]
= [0.85(20.70/275.00)] {1 - √1 - = [0.85(20.70/275.00)] {1 - √1 -
[(2 x 1.1069) / (0.85 x 20.70)]} [(2 x 1.1069) / (0.85 x 20.70)]}
= 0.004160 = 0.004160
use ρ = 0.005091 use ρ = 0.005091
x = L/2 - b/2 As = ρ W d y = W/2 - h/2 As = ρ L d
= 2.00/2 - 0.350/2 = 0.005091 x 2.00 x 0.267 = 2.00/2 - 0.350/2 = 0.005091 x 2.00 x 0.267
= 0.825 m = 2718.594 mm² = 0.825 m = 2718.594 mm²
A= Wx Qty = As / Ab A= Ly Qty = As / Ab
= 2.00 x 0.825 = 2,718.594 / π16²/4 = 2.00 x 0.825 = 2,718.594 / π16²/4
= 1.650 m² = 14 L - 16mmØ RSB = 1.650 m² = 14 L - 16mmØ RSB
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE FOOTING


Footing: F3
Location: A3
I. FOOTING PROPERTIES
Design Footing: Unfactored Loads:
Length, L= 1.80 m Service LC, Po = 157.666 kN
Width, W= 1.80 m Ftng. Self Wt. Wfn = 31.104 kN
Depth, d= 0.400 m Total, Po Po t = 188.770 kN
Eff. Depth, d eff. = 0.317 m Factored Loads:
Fdn. Depth, D= 1.50 m Service LC, Pu = 281.000 kN
Min. Fdn. Depth D min. = 1.10 m Ftng. Self Wt. Wfu = 37.325 kN
Column, b= 0.250 m Total, Pu Pu t = 318.325 kN
h= 0.350 m Minimum Footing Dimension:
Material Properties: Length, L= 1.69 m
Concrete, fc' = 20.70 Mpa Width, W= 1.69 m
Steel, fy = 275.00 Mpa Steel Requirements:
Reduction Factor: Reinf Steel Bar Dia Ø= 16 mm
Bending, ф= 0.90 ρ bal = 0.85 β fc' 600 / fy(600+fy)
Shear, ф= 0.75 = 0.037292
bot steel cover, sc = 0.075 m ρ min = 1.40 / fy = 0.005091
Bearing Pressure: ρ max = 75% ρ bal = 0.027969
ESBP, qe = 66.270 kN/m²
USBP, qu = 98.248 kN/m²

II. DETAILED CALCULATIONS


Wide Beam Shear:
a. Along Length, b. Along Width
A= Wx A= Ly
= 1.80 x 1.233 = 1.80 x 0.408
= 2.219 m² = 0.734 m²
Vu = qu A Vu = qu A
= 98.25 x 2.219 = 98.25 x 0.734
= 218.012 kN = 72.114 kN
Vc = √fc' W d / 6 Vc = √fc' L d / 6
= √20.70 x 1.80 x 0.317 / 6 = √20.70 x 1.80 x 0.317 / 6
= 432.679 kN = 432.679 kN
x= L-b-d FS = фVc / Vu y = W/2 - h/2 - d FS = фVc / Vu
= 1.80 - 0.250 - 0.317 = 0.75 x 432.68 / 218.01 = 1.80/2 - 0.350/2 - 0.317 = 0.75 x 432.68 / 72.11
= 1.233 m = 1.49 >1 .'. Adequate! = 0.408 m = 4.50 >1 .'. Adequate!
Punching Shear:
x = b + d/2 A = LW - xy Vc = √fc' bo d / 3
= 0.250 + 0.317/2 = (1.80 x 1.80) - (0.409 x 0.667) = √20.70 x 1.485 x 0.317 / 3
= 0.409 m = 2.967 m² = 713.920 kN
y= h+d Vu = qu A FS = фVc / Vu
= 0.350 + 0.317 = 98.25 x 2.967 = 0.75 x 713.92 / 291.50
= 0.667 m = 291.502 kN = 1.84 >1 .'. Adequate!
bo = 2x + y
= (2 x 0.409) + 0.667
= 1.485 m
Reinforcing Steel Bars:
a. Along Length, b. Along Width,
Mu = qu A Mu = qu A
= 98.25 x 2.790 = 98.25 x 1.305
= 274.112 kN-m = 128.214 kN-m
Ru = Mu / ф W d² Ru = Mu / ф L d²
= 274.11x10^6 / = 128.21x10^6 /
(0.90 x 1.80 x 0.317²) (0.90 x 1.80 x 0.317²)
= 1.6838 MPa = 0.7876 MPa
ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')] ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')]
= [0.85(20.70/275.00)] {1 - √1 - = [0.85(20.70/275.00)] {1 - √1 -
[(2 x 1.6838) / (0.85 x 20.70)]} [(2 x 0.7876) / (0.85 x 20.70)]}
= 0.006448 = 0.002931
use ρ = 0.006448 use ρ = 0.005091
x= L-b As = ρ W d y = W/2 - h/2 As = ρ L d
= 1.80 - 0.250 = 0.006448 x 1.80 x 0.317 = 1.80/2 - 0.350/2 = 0.005091 x 1.80 x 0.317
= 1.550 m = 3679.229 mm² = 0.725 m = 2904.925 mm²
A= Wx Qty = As / Ab A= Ly Qty = As / Ab
= 1.80 x 1.550 = 3,679.229 / π16²/4 = 1.80 x 0.725 = 2,904.925 / π16²/4
= 2.790 m² = 19 L - 16mmØ RSB = 1.305 m² = 15 L - 16mmØ RSB
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE FOOTING


Footing: F3
Location: C3
I. FOOTING PROPERTIES
Design Footing: Unfactored Loads:
Length, L= 1.80 m Service LC, Po = 148.402 kN
Width, W= 1.80 m Ftng. Self Wt. Wfn = 31.104 kN
Depth, d= 0.400 m Total, Po Po t = 179.506 kN
Eff. Depth, d eff. = 0.317 m Factored Loads:
Fdn. Depth, D= 1.50 m Service LC, Pu = 255.000 kN
Min. Fdn. Depth D min. = 1.05 m Ftng. Self Wt. Wfu = 37.325 kN
Column, b= 0.250 m Total, Pu Pu t = 292.325 kN
h= 0.350 m Minimum Footing Dimension:
Material Properties: Length, L= 1.65 m
Concrete, fc' = 20.70 Mpa Width, W= 1.65 m
Steel, fy = 275.00 Mpa Steel Requirements:
Reduction Factor: Reinf Steel Bar Dia Ø= 16 mm
Bending, ф= 0.90 ρ bal = 0.85 β fc' 600 / fy(600+fy)
Shear, ф= 0.75 = 0.037292
bot steel cover, sc = 0.075 m ρ min = 1.40 / fy = 0.005091
Bearing Pressure: ρ max = 75% ρ bal = 0.027969
ESBP, qe = 66.270 kN/m²
USBP, qu = 90.224 kN/m²

II. DETAILED CALCULATIONS


Wide Beam Shear:
a. Along Length, b. Along Width
A= Wx A= Ly
= 1.80 x 1.233 = 1.80 x 0.408
= 2.219 m² = 0.734 m²
Vu = qu A Vu = qu A
= 90.22 x 2.219 = 90.22 x 0.734
= 200.207 kN = 66.224 kN
Vc = √fc' W d / 6 Vc = √fc' L d / 6
= √20.70 x 1.80 x 0.317 / 6 = √20.70 x 1.80 x 0.317 / 6
= 432.679 kN = 432.679 kN
x= L-b-d FS = фVc / Vu y = W/2 - h/2 - d FS = фVc / Vu
= 1.80 - 0.250 - 0.317 = 0.75 x 432.68 / 200.21 = 1.80/2 - 0.350/2 - 0.317 = 0.75 x 432.68 / 66.22
= 1.233 m = 1.62 >1 .'. Adequate! = 0.408 m = 4.90 >1 .'. Adequate!
Punching Shear:
x = b + d/2 A = LW - xy Vc = √fc' bo d / 3
= 0.250 + 0.317/2 = (1.80 x 1.80) - (0.409 x 0.667) = √20.70 x 1.485 x 0.317 / 3
= 0.409 m = 2.967 m² = 713.920 kN
y= h+d Vu = qu A FS = фVc / Vu
= 0.350 + 0.317 = 90.22 x 2.967 = 0.75 x 713.92 / 267.70
= 0.667 m = 267.695 kN = 2.00 >1 .'. Adequate!
bo = 2x + y
= (2 x 0.409) + 0.667
= 1.485 m
Reinforcing Steel Bars:
a. Along Length, b. Along Width,
Mu = qu A Mu = qu A
= 90.22 x 2.790 = 90.22 x 1.305
= 251.725 kN-m = 117.742 kN-m
Ru = Mu / ф W d² Ru = Mu / ф L d²
= 251.73x10^6 / = 117.74x10^6 /
(0.90 x 1.80 x 0.317²) (0.90 x 1.80 x 0.317²)
= 1.5463 MPa = 0.7233 MPa
ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')] ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')]
= [0.85(20.70/275.00)] {1 - √1 - = [0.85(20.70/275.00)] {1 - √1 -
[(2 x 1.5463) / (0.85 x 20.70)]} [(2 x 0.7233) / (0.85 x 20.70)]}
= 0.005894 = 0.002687
use ρ = 0.005894 use ρ = 0.005091
x= L-b As = ρ W d y = W/2 - h/2 As = ρ L d
= 1.80 - 0.250 = 0.005894 x 1.80 x 0.317 = 1.80/2 - 0.350/2 = 0.005091 x 1.80 x 0.317
= 1.550 m = 3363.116 mm² = 0.725 m = 2904.925 mm²
A= Wx Qty = As / Ab A= Ly Qty = As / Ab
= 1.80 x 1.550 = 3,363.116 / π16²/4 = 1.80 x 0.725 = 2,904.925 / π16²/4
= 2.790 m² = 17 L - 16mmØ RSB = 1.305 m² = 15 L - 16mmØ RSB
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE FOOTING


Footing: F4
Location: B1
I. FOOTING PROPERTIES
Design Footing: Unfactored Loads:
Length, L= 1.70 m Service LC, Po = 134.888 kN
Width, W= 1.70 m Ftng. Self Wt. Wfn = 24.276 kN
Depth, d= 0.350 m Total, Po Po t = 159.164 kN
Eff. Depth, d eff. = 0.267 m Factored Loads:
Fdn. Depth, D= 1.50 m Service LC, Pu = 237.000 kN
Min. Fdn. Depth D min. = 1.04 m Ftng. Self Wt. Wfu = 29.131 kN
Column, b= 0.250 m Total, Pu Pu t = 266.131 kN
h= 0.350 m Minimum Footing Dimension:
Material Properties: Length, L= 1.55 m
Concrete, fc' = 20.70 Mpa Width, W= 1.55 m
Steel, fy = 275.00 Mpa Steel Requirements:
Reduction Factor: Reinf Steel Bar Dia Ø= 16 mm
Bending, ф= 0.90 ρ bal = 0.85 β fc' 600 / fy(600+fy)
Shear, ф= 0.75 = 0.037292
bot steel cover, sc = 0.075 m ρ min = 1.40 / fy = 0.005091
Bearing Pressure: ρ max = 75% ρ bal = 0.027969
ESBP, qe = 66.555 kN/m²
USBP, qu = 92.087 kN/m²

II. DETAILED CALCULATIONS


Wide Beam Shear:
a. Along Length, b. Along Width
A= Wx A= Ly
= 1.70 x 0.458 = 1.70 x 1.083
= 0.779 m² = 1.841 m²
Vu = qu A Vu = qu A
= 92.09 x 0.779 = 92.09 x 1.841
= 71.736 kN = 169.532 kN
Vc = √fc' W d / 6 Vc = √fc' L d / 6
= √20.70 x 1.70 x 0.267 / 6 = √20.70 x 1.70 x 0.267 / 6
= 344.187 kN = 344.187 kN
x = L/2 - b/2 - d FS = фVc / Vu y= W-h-d FS = фVc / Vu
= 1.70/2 - 0.250/2 - 0.267 = 0.75 x 344.19 / 71.74 = 1.70 - 0.350 - 0.267 = 0.75 x 344.19 / 169.53
= 0.458 m = 3.60 >1 .'. Adequate! = 1.083 m = 1.52 >1 .'. Adequate!
Punching Shear:
x= b+d A = LW - xy Vc = √fc' bo d / 3
= 0.250 + 0.267 = (1.70 x 1.70) - (0.517 x 0.484) = √20.70 x 1.485 x 0.267 / 3
= 0.517 m = 2.640 m² = 601.314 kN
y = h + d/2 Vu = qu A FS = фVc / Vu
= 0.350 + 0.267/2 = 92.09 x 2.640 = 0.75 x 601.31 / 243.11
= 0.484 m = 243.110 kN = 1.86 >1 .'. Adequate!
bo = x + 2y
= 0.517 + (2 x 0.484)
= 1.485 m
Reinforcing Steel Bars:
a. Along Length, b. Along Width,
Mu = qu A Mu = qu A
= 92.09 x 1.233 = 92.09 x 2.295
= 113.543 kN-m = 211.340 kN-m
Ru = Mu / ф W d² Ru = Mu / ф L d²
= 113.54x10^6 / = 211.34x10^6 /
(0.90 x 1.70 x 0.267²) (0.90 x 1.70 x 0.267²)
= 1.0410 MPa = 1.9376 MPa
ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')] ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')]
= [0.85(20.70/275.00)] {1 - √1 - = [0.85(20.70/275.00)] {1 - √1 -
[(2 x 1.0410) / (0.85 x 20.70)]} [(2 x 1.9376) / (0.85 x 20.70)]}
= 0.003905 = 0.007483
use ρ = 0.005091 use ρ = 0.007483
x = L/2 - b/2 As = ρ W d y= W-h As = ρ L d
= 1.70/2 - 0.250/2 = 0.005091 x 1.70 x 0.267 = 1.70 - 0.350 = 0.007483 x 1.70 x 0.267
= 0.725 m = 2310.805 mm² = 1.350 m = 3396.534 mm²
A= Wx Qty = As / Ab A= Ly Qty = As / Ab
= 1.70 x 0.725 = 2,310.805 / π16²/4 = 1.70 x 1.350 = 3,396.534 / π16²/4
= 1.233 m² = 12 L - 16mmØ RSB = 2.295 m² = 17 L - 16mmØ RSB
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE FOOTING


Footing: F5
Location: C4
I. FOOTING PROPERTIES
Design Footing: Unfactored Loads:
Length, L= 1.70 m Service LC, Po = 134.888 kN
Width, W= 1.70 m Ftng. Self Wt. Wfn = 27.744 kN
Depth, d= 0.400 m Total, Po Po t = 162.632 kN
Eff. Depth, d eff. = 0.317 m Factored Loads:
Fdn. Depth, D= 1.50 m Service LC, Pu = 237.000 kN
Min. Fdn. Depth D min. = 1.07 m Ftng. Self Wt. Wfu = 33.293 kN
Column, b= 0.250 m Total, Pu Pu t = 270.293 kN
h= 0.350 m Minimum Footing Dimension:
Material Properties: Length, L= 1.57 m
Concrete, fc' = 20.70 Mpa Width, W= 1.57 m
Steel, fy = 275.00 Mpa Steel Requirements:
Reduction Factor: Reinf Steel Bar Dia Ø= 16 mm
Bending, ф= 0.90 ρ bal = 0.85 β fc' 600 / fy(600+fy)
Shear, ф= 0.75 = 0.037292
bot steel cover, sc = 0.075 m ρ min = 1.40 / fy = 0.005091
Bearing Pressure: ρ max = 75% ρ bal = 0.027969
ESBP, qe = 66.270 kN/m²
USBP, qu = 93.527 kN/m²

II. DETAILED CALCULATIONS


Wide Beam Shear:
a. Along Length, b. Along Width
A= Wx A= Ly
= 1.70 x 1.133 = 1.70 x 0.358
= 1.926 m² = 0.609 m²
Vu = qu A Vu = qu A
= 93.53 x 1.926 = 93.53 x 0.609
= 180.133 kN = 56.958 kN
Vc = √fc' W d / 6 Vc = √fc' L d / 6
= √20.70 x 1.70 x 0.317 / 6 = √20.70 x 1.70 x 0.317 / 6
= 408.641 kN = 408.641 kN
x= L-b-d FS = фVc / Vu y = W/2 - h/2 - d FS = фVc / Vu
= 1.70 - 0.250 - 0.317 = 0.75 x 408.64 / 180.13 = 1.70/2 - 0.350/2 - 0.317 = 0.75 x 408.64 / 56.96
= 1.133 m = 1.70 >1 .'. Adequate! = 0.358 m = 5.38 >1 .'. Adequate!
Punching Shear:
x = b + d/2 A = LW - xy Vc = √fc' bo d / 3
= 0.250 + 0.317/2 = (1.70 x 1.70) - (0.409 x 0.667) = √20.70 x 1.485 x 0.317 / 3
= 0.409 m = 2.617 m² = 713.920 kN
y= h+d Vu = qu A FS = фVc / Vu
= 0.350 + 0.317 = 93.53 x 2.617 = 0.75 x 713.92 / 244.76
= 0.667 m = 244.760 kN = 2.19 >1 .'. Adequate!
bo = 2x + y
= (2 x 0.409) + 0.667
= 1.485 m
Reinforcing Steel Bars:
a. Along Length, b. Along Width,
Mu = qu A Mu = qu A
= 93.53 x 2.465 = 93.53 x 1.148
= 230.544 kN-m = 107.369 kN-m
Ru = Mu / ф W d² Ru = Mu / ф L d²
= 230.54x10^6 / = 107.37x10^6 /
(0.90 x 1.70 x 0.317²) (0.90 x 1.70 x 0.317²)
= 1.4995 MPa = 0.6983 MPa
ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')] ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')]
= [0.85(20.70/275.00)] {1 - √1 - = [0.85(20.70/275.00)] {1 - √1 -
[(2 x 1.4995) / (0.85 x 20.70)]} [(2 x 0.6983) / (0.85 x 20.70)]}
= 0.005707 = 0.002592
use ρ = 0.005707 use ρ = 0.005091
x= L-b As = ρ W d y = W/2 - h/2 As = ρ L d
= 1.70 - 0.250 = 0.005707 x 1.70 x 0.317 = 1.70/2 - 0.350/2 = 0.005091 x 1.70 x 0.317
= 1.450 m = 3075.502 mm² = 0.675 m = 2743.540 mm²
A= Wx Qty = As / Ab A= Ly Qty = As / Ab
= 1.70 x 1.450 = 3,075.502 / π16²/4 = 1.70 x 0.675 = 2,743.540 / π16²/4
= 2.465 m² = 16 L - 16mmØ RSB = 1.148 m² = 14 L - 16mmØ RSB
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE FOOTING


Footing: F6
Location: C1
I. FOOTING PROPERTIES
Design Footing: Unfactored Loads:
Length, L= 1.50 m Service LC, Po = 102.598 kN
Width, W= 1.50 m Ftng. Self Wt. Wfn = 21.600 kN
Depth, d= 0.400 m Total, Po Po t = 124.198 kN
Eff. Depth, d eff. = 0.317 m Factored Loads:
Fdn. Depth, D= 1.50 m Service LC, Pu = 183.000 kN
Min. Fdn. Depth D min. = 1.05 m Ftng. Self Wt. Wfu = 25.920 kN
Column, b= 0.250 m Total, Pu Pu t = 208.920 kN
h= 0.350 m Minimum Footing Dimension:
Material Properties: Length, L= 1.37 m
Concrete, fc' = 20.70 Mpa Width, W= 1.37 m
Steel, fy = 275.00 Mpa Steel Requirements:
Reduction Factor: Reinf Steel Bar Dia Ø= 16 mm
Bending, ф= 0.90 ρ bal = 0.85 β fc' 600 / fy(600+fy)
Shear, ф= 0.75 = 0.037292
bot steel cover, sc = 0.075 m ρ min = 1.40 / fy = 0.005091
Bearing Pressure: ρ max = 75% ρ bal = 0.027969
ESBP, qe = 66.270 kN/m²
USBP, qu = 92.853 kN/m²

II. DETAILED CALCULATIONS


Wide Beam Shear:
a. Along Length, b. Along Width
A= Wx A= Ly
= 1.50 x 0.933 = 1.50 x 0.833
= 1.400 m² = 1.250 m²
Vu = qu A Vu = qu A
= 92.85 x 1.400 = 92.85 x 1.250
= 129.994 kN = 116.066 kN
Vc = √fc' W d / 6 Vc = √fc' L d / 6
= √20.70 x 1.50 x 0.317 / 6 = √20.70 x 1.50 x 0.317 / 6
= 360.566 kN = 360.566 kN
x= L-b-d FS = фVc / Vu y= W-h-d FS = фVc / Vu
= 1.50 - 0.250 - 0.317 = 0.75 x 360.57 / 129.99 = 1.50 - 0.350 - 0.317 = 0.75 x 360.57 / 116.07
= 0.933 m = 2.08 >1 .'. Adequate! = 0.833 m = 2.33 >1 .'. Adequate!
Punching Shear:
x = b + d/2 A = LW - xy Vc = √fc' bo d / 3
= 0.250 + 0.317/2 = (1.50 x 1.50) - (0.409 x 0.509) = √20.70 x 0.918 x 0.317 / 3
= 0.409 m = 2.042 m² = 441.332 kN
y = h + d/2 Vu = qu A FS = фVc / Vu
= 0.350 + 0.317/2 = 92.85 x 2.042 = 0.75 x 441.33 / 189.61
= 0.509 m = 189.606 kN = 1.75 >1 .'. Adequate!
bo = x + y
= 0.409 + 0.509)
= 0.918 m
Reinforcing Steel Bars:
a. Along Length, b. Along Width,
Mu = qu A Mu = qu A
= 92.85 x 1.875 = 92.85 x 1.725
= 174.099 kN-m = 160.171 kN-m
Ru = Mu / ф W d² Ru = Mu / ф L d²
= 174.10x10^6 / = 160.17x10^6 /
(0.90 x 1.50 x 0.317²) (0.90 x 1.50 x 0.317²)
= 1.2833 MPa = 1.1807 MPa
ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')] ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')]
= [0.85(20.70/275.00)] {1 - √1 - = [0.85(20.70/275.00)] {1 - √1 -
[(2 x 1.2833) / (0.85 x 20.70)]} [(2 x 1.1807) / (0.85 x 20.70)]}
= 0.004850 = 0.004448
use ρ = 0.005091 use ρ = 0.005091
x= L-b As = ρ W d y= W-h As = ρ L d
= 1.50 - 0.250 = 0.005091 x 1.50 x 0.317 = 1.50 - 0.350 = 0.005091 x 1.50 x 0.317
= 1.250 m = 2420.771 mm² = 1.150 m = 2420.771 mm²
A= Wx Qty = As / Ab A= Ly Qty = As / Ab
= 1.50 x 1.250 = 2,420.771 / π16²/4 = 1.50 x 1.150 = 2,420.771 / π16²/4
= 1.875 m² = 13 L - 16mmØ RSB = 1.725 m² = 13 L - 16mmØ RSB
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE FOOTING


Footing: F7
Location: A2
I. FOOTING PROPERTIES
Design Footing: Unfactored Loads:
Length, L= 1.50 m Service LC, Po = 95.397 kN
Width, W= 1.50 m Ftng. Self Wt. Wfn = 18.900 kN
Depth, d= 0.350 m Total, Po Po t = 114.297 kN
Eff. Depth, d eff. = 0.267 m Factored Loads:
Fdn. Depth, D= 1.50 m Service LC, Pu = 179.000 kN
Min. Fdn. Depth D min. = 0.96 m Ftng. Self Wt. Wfu = 22.680 kN
Column, b= 0.250 m Total, Pu Pu t = 201.680 kN
h= 0.350 m Minimum Footing Dimension:
Material Properties: Length, L= 1.31 m
Concrete, fc' = 20.70 Mpa Width, W= 1.31 m
Steel, fy = 275.00 Mpa Steel Requirements:
Reduction Factor: Reinf Steel Bar Dia Ø= 16 mm
Bending, ф= 0.90 ρ bal = 0.85 β fc' 600 / fy(600+fy)
Shear, ф= 0.75 = 0.037292
bot steel cover, sc = 0.075 m ρ min = 1.40 / fy = 0.005091
Bearing Pressure: ρ max = 75% ρ bal = 0.027969
ESBP, qe = 66.555 kN/m²
USBP, qu = 89.636 kN/m²

II. DETAILED CALCULATIONS


Wide Beam Shear:
a. Along Length, b. Along Width
A= Wx A= Ly
= 1.50 x 0.983 = 1.50 x 0.308
= 1.475 m² = 0.462 m²
Vu = qu A Vu = qu A
= 89.64 x 1.475 = 89.64 x 0.462
= 132.213 kN = 41.412 kN
Vc = √fc' W d / 6 Vc = √fc' L d / 6
= √20.70 x 1.50 x 0.267 / 6 = √20.70 x 1.50 x 0.267 / 6
= 303.694 kN = 303.694 kN
x= L-b-d FS = фVc / Vu y = W/2 - h/2 - d FS = фVc / Vu
= 1.50 - 0.250 - 0.267 = 0.75 x 303.69 / 132.21 = 1.50/2 - 0.350/2 - 0.267 = 0.75 x 303.69 / 41.41
= 0.983 m = 1.72 >1 .'. Adequate! = 0.308 m = 5.50 >1 .'. Adequate!
Punching Shear:
x = b + d/2 A = LW - xy Vc = √fc' bo d / 3
= 0.250 + 0.267/2 = (1.50 x 1.50) - (0.384 x 0.617) = √20.70 x 1.385 x 0.267 / 3
= 0.384 m = 2.013 m² = 560.822 kN
y= h+d Vu = qu A FS = фVc / Vu
= 0.350 + 0.267 = 89.64 x 2.013 = 0.75 x 560.82 / 180.44
= 0.617 m = 180.437 kN = 2.33 >1 .'. Adequate!
bo = 2x + y
= (2 x 0.384) + 0.617
= 1.385 m
Reinforcing Steel Bars:
a. Along Length, b. Along Width,
Mu = qu A Mu = qu A
= 89.64 x 1.875 = 89.64 x 0.863
= 168.068 kN-m = 77.356 kN-m
Ru = Mu / ф W d² Ru = Mu / ф L d²
= 168.07x10^6 / = 77.36x10^6 /
(0.90 x 1.50 x 0.267²) (0.90 x 1.50 x 0.267²)
= 1.7463 MPa = 0.8038 MPa
ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')] ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')]
= [0.85(20.70/275.00)] {1 - √1 - = [0.85(20.70/275.00)] {1 - √1 -
[(2 x 1.7463) / (0.85 x 20.70)]} [(2 x 0.8038) / (0.85 x 20.70)]}
= 0.006701 = 0.002993
use ρ = 0.006701 use ρ = 0.005091
x= L-b As = ρ W d y = W/2 - h/2 As = ρ L d
= 1.50 - 0.250 = 0.006701 x 1.50 x 0.267 = 1.50/2 - 0.350/2 = 0.005091 x 1.50 x 0.267
= 1.250 m = 2683.751 mm² = 0.575 m = 2038.946 mm²
A= Wx Qty = As / Ab A= Ly Qty = As / Ab
= 1.50 x 1.250 = 2,683.751 / π16²/4 = 1.50 x 0.575 = 2,038.946 / π16²/4
= 1.875 m² = 14 L - 16mmØ RSB = 0.863 m² = 11 L - 16mmØ RSB
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE FOOTING


Footing: F7
Location: A4
I. FOOTING PROPERTIES
Design Footing: Unfactored Loads:
Length, L= 1.50 m Service LC, Po = 104.453 kN
Width, W= 1.50 m Ftng. Self Wt. Wfn = 18.900 kN
Depth, d= 0.350 m Total, Po Po t = 123.353 kN
Eff. Depth, d eff. = 0.267 m Factored Loads:
Fdn. Depth, D= 1.50 m Service LC, Pu = 194.000 kN
Min. Fdn. Depth D min. = 1.04 m Ftng. Self Wt. Wfu = 22.680 kN
Column, b= 0.250 m Total, Pu Pu t = 216.680 kN
h= 0.350 m Minimum Footing Dimension:
Material Properties: Length, L= 1.36 m
Concrete, fc' = 20.70 Mpa Width, W= 1.36 m
Steel, fy = 275.00 Mpa Steel Requirements:
Reduction Factor: Reinf Steel Bar Dia Ø= 16 mm
Bending, ф= 0.90 ρ bal = 0.85 β fc' 600 / fy(600+fy)
Shear, ф= 0.75 = 0.037292
bot steel cover, sc = 0.075 m ρ min = 1.40 / fy = 0.005091
Bearing Pressure: ρ max = 75% ρ bal = 0.027969
ESBP, qe = 66.555 kN/m²
USBP, qu = 96.302 kN/m²

II. DETAILED CALCULATIONS


Wide Beam Shear:
a. Along Length, b. Along Width
A= Wx A= Ly
= 1.50 x 0.983 = 1.50 x 0.308
= 1.475 m² = 0.462 m²
Vu = qu A Vu = qu A
= 96.30 x 1.475 = 96.30 x 0.462
= 142.045 kN = 44.492 kN
Vc = √fc' W d / 6 Vc = √fc' L d / 6
= √20.70 x 1.50 x 0.267 / 6 = √20.70 x 1.50 x 0.267 / 6
= 303.694 kN = 303.694 kN
x= L-b-d FS = фVc / Vu y = W/2 - h/2 - d FS = фVc / Vu
= 1.50 - 0.250 - 0.267 = 0.75 x 303.69 / 142.05 = 1.50/2 - 0.350/2 - 0.267 = 0.75 x 303.69 / 44.49
= 0.983 m = 1.60 >1 .'. Adequate! = 0.308 m = 5.12 >1 .'. Adequate!
Punching Shear:
x = b + d/2 A = LW - xy Vc = √fc' bo d / 3
= 0.250 + 0.267/2 = (1.50 x 1.50) - (0.384 x 0.617) = √20.70 x 1.385 x 0.267 / 3
= 0.384 m = 2.013 m² = 560.822 kN
y= h+d Vu = qu A FS = фVc / Vu
= 0.350 + 0.267 = 96.30 x 2.013 = 0.75 x 560.82 / 193.86
= 0.617 m = 193.856 kN = 2.17 >1 .'. Adequate!
bo = 2x + y
= (2 x 0.384) + 0.617
= 1.385 m
Reinforcing Steel Bars:
a. Along Length, b. Along Width,
Mu = qu A Mu = qu A
= 96.30 x 1.875 = 96.30 x 0.863
= 180.566 kN-m = 83.109 kN-m
Ru = Mu / ф W d² Ru = Mu / ф L d²
= 180.57x10^6 / = 83.11x10^6 /
(0.90 x 1.50 x 0.267²) (0.90 x 1.50 x 0.267²)
= 1.8762 MPa = 0.8636 MPa
ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')] ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')]
= [0.85(20.70/275.00)] {1 - √1 - = [0.85(20.70/275.00)] {1 - √1 -
[(2 x 1.8762) / (0.85 x 20.70)]} [(2 x 0.8636) / (0.85 x 20.70)]}
= 0.007231 = 0.003221
use ρ = 0.007231 use ρ = 0.005091
x= L-b As = ρ W d y = W/2 - h/2 As = ρ L d
= 1.50 - 0.250 = 0.007231 x 1.50 x 0.267 = 1.50/2 - 0.350/2 = 0.005091 x 1.50 x 0.267
= 1.250 m = 2896.016 mm² = 0.575 m = 2038.946 mm²
A= Wx Qty = As / Ab A= Ly Qty = As / Ab
= 1.50 x 1.250 = 2,896.016 / π16²/4 = 1.50 x 0.575 = 2,038.946 / π16²/4
= 1.875 m² = 15 L - 16mmØ RSB = 0.863 m² = 11 L - 16mmØ RSB
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE FOOTING


Footing: F8
Location: C5
I. FOOTING PROPERTIES
Design Footing: Unfactored Loads:
Length, L= 1.20 m Service LC, Po = 47.571 kN
Width, W= 1.20 m Ftng. Self Wt. Wfn = 10.368 kN
Depth, d= 0.300 m Total, Po Po t = 57.939 kN
Eff. Depth, d eff. = 0.217 m Factored Loads:
Fdn. Depth, D= 1.50 m Service LC, Pu = 86.400 kN
Min. Fdn. Depth D min. = 0.76 m Ftng. Self Wt. Wfu = 12.442 kN
Column, b= 0.250 m Total, Pu Pu t = 98.842 kN
h= 0.350 m Minimum Footing Dimension:
Material Properties: Length, L= 0.93 m
Concrete, fc' = 20.70 Mpa Width, W= 0.93 m
Steel, fy = 275.00 Mpa Steel Requirements:
Reduction Factor: Reinf Steel Bar Dia Ø= 16 mm
Bending, ф= 0.90 ρ bal = 0.85 β fc' 600 / fy(600+fy)
Shear, ф= 0.75 = 0.037292
bot steel cover, sc = 0.075 m ρ min = 1.40 / fy = 0.005091
Bearing Pressure: ρ max = 75% ρ bal = 0.027969
ESBP, qe = 66.840 kN/m²
USBP, qu = 68.640 kN/m²

II. DETAILED CALCULATIONS


Wide Beam Shear:
a. Along Length, b. Along Width
A= Wx A= Ly
= 1.20 x 0.733 = 1.20 x 0.208
= 0.880 m² = 0.250 m²
Vu = qu A Vu = qu A
= 68.64 x 0.880 = 68.64 x 0.250
= 60.403 kN = 17.160 kN
Vc = √fc' W d / 6 Vc = √fc' L d / 6
= √20.70 x 1.20 x 0.217 / 6 = √20.70 x 1.20 x 0.217 / 6
= 197.458 kN = 197.458 kN
x= L-b-d FS = фVc / Vu y = W/2 - h/2 - d FS = фVc / Vu
= 1.20 - 0.250 - 0.217 = 0.75 x 197.46 / 60.40 = 1.20/2 - 0.350/2 - 0.217 = 0.75 x 197.46 / 17.16
= 0.733 m = 2.45 >1 .'. Adequate! = 0.208 m = 8.63 >1 .'. Adequate!
Punching Shear:
x = b + d/2 A = LW - xy Vc = √fc' bo d / 3
= 0.250 + 0.217/2 = (1.20 x 1.20) - (0.359 x 0.567) = √20.70 x 1.285 x 0.217 / 3
= 0.359 m = 1.236 m² = 422.889 kN
y= h+d Vu = qu A FS = фVc / Vu
= 0.350 + 0.217 = 68.64 x 1.236 = 0.75 x 422.89 / 84.84
= 0.567 m = 84.839 kN = 3.74 >1 .'. Adequate!
bo = 2x + y
= (2 x 0.359) + 0.567
= 1.285 m
Reinforcing Steel Bars:
a. Along Length, b. Along Width,
Mu = qu A Mu = qu A
= 68.64 x 1.140 = 68.64 x 0.510
= 78.250 kN-m = 35.006 kN-m
Ru = Mu / ф W d² Ru = Mu / ф L d²
= 78.25x10^6 / = 35.01x10^6 /
(0.90 x 1.20 x 0.217²) (0.90 x 1.20 x 0.217²)
= 1.5387 MPa = 0.6883 MPa
ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')] ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')]
= [0.85(20.70/275.00)] {1 - √1 - = [0.85(20.70/275.00)] {1 - √1 -
[(2 x 1.5387) / (0.85 x 20.70)]} [(2 x 0.6883) / (0.85 x 20.70)]}
= 0.005864 = 0.002554
use ρ = 0.005864 use ρ = 0.005091
x= L-b As = ρ W d y = W/2 - h/2 As = ρ L d
= 1.20 - 0.250 = 0.005864 x 1.20 x 0.217 = 1.20/2 - 0.350/2 = 0.005091 x 1.20 x 0.217
= 0.950 m = 1526.986 mm² = 0.425 m = 1325.696 mm²
A= Wx Qty = As / Ab A= Ly Qty = As / Ab
= 1.20 x 0.950 = 1,526.986 / π16²/4 = 1.20 x 0.425 = 1,325.696 / π16²/4
= 1.140 m² = 8L - 16mmØ RSB = 0.510 m² = 7L - 16mmØ RSB
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE FOOTING


Footing: F9
Location: C5
I. FOOTING PROPERTIES
Design Footing: Unfactored Loads:
Length, L= 1.20 m Service LC, Po = 28.486 kN
Width, W= 1.20 m Ftng. Self Wt. Wfn = 10.368 kN
Depth, d= 0.300 m Total, Po Po t = 38.854 kN
Eff. Depth, d eff. = 0.217 m Factored Loads:
Fdn. Depth, D= 1.50 m Service LC, Pu = 55.300 kN
Min. Fdn. Depth D min. = 0.51 m Ftng. Self Wt. Wfu = 12.442 kN
Column, b= 0.250 m Total, Pu Pu t = 67.742 kN
h= 0.350 m Minimum Footing Dimension:
Material Properties: Length, L= 0.76 m
Concrete, fc' = 20.70 Mpa Width, W= 0.76 m
Steel, fy = 275.00 Mpa Steel Requirements:
Reduction Factor: Reinf Steel Bar Dia Ø= 16 mm
Bending, ф= 0.90 ρ bal = 0.85 β fc' 600 / fy(600+fy)
Shear, ф= 0.75 = 0.037292
bot steel cover, sc = 0.075 m ρ min = 1.40 / fy = 0.005091
Bearing Pressure: ρ max = 75% ρ bal = 0.027969
ESBP, qe = 66.840 kN/m²
USBP, qu = 47.043 kN/m²

II. DETAILED CALCULATIONS


Wide Beam Shear:
a. Along Length, b. Along Width
A= Wx A= Ly
= 1.20 x 0.258 = 1.20 x 0.208
= 0.310 m² = 0.250 m²
Vu = qu A Vu = qu A
= 47.04 x 0.310 = 47.04 x 0.250
= 14.583 kN = 11.761 kN
Vc = √fc' W d / 6 Vc = √fc' L d / 6
= √20.70 x 1.20 x 0.217 / 6 = √20.70 x 1.20 x 0.217 / 6
= 197.458 kN = 197.458 kN
x = L/2 - b/2 - d FS = фVc / Vu y = W/2 - h/2 - d FS = фVc / Vu
= 1.20/2 - 0.250/2 - 0.217 = 0.75 x 197.46 / 14.58 = 1.20/2 - 0.350/2 - 0.217 = 0.75 x 197.46 / 11.76
= 0.258 m = 10.16 >1 .'. Adequate! = 0.208 m = 12.59 >1 .'. Adequate!
Punching Shear:
x= b+d A = LW - xy Vc = √fc' bo d / 3
= 0.250 + 0.217 = (1.20 x 1.20) - (0.467 x 0.567) = √20.70 x 2.068 x 0.217 / 3
= 0.467 m = 1.175 m² = 680.572 kN
y= h+d Vu = qu A FS = фVc / Vu
= 0.350 + 0.217 = 47.04 x 1.175 = 0.75 x 680.57 / 55.28
= 0.567 m = 55.276 kN = 9.23 >1 .'. Adequate!
bo = 2x + 2y
= (2 x 0.467) + (2 x 0.567)
= 2.068 m
Reinforcing Steel Bars:
a. Along Length, b. Along Width,
Mu = qu A Mu = qu A
= 47.04 x 0.570 = 47.04 x 0.510
= 26.815 kN-m = 23.992 kN-m
Ru = Mu / ф W d² Ru = Mu / ф L d²
= 26.82x10^6 / = 23.99x10^6 /
(0.90 x 1.20 x 0.217²) (0.90 x 1.20 x 0.217²)
= 0.5273 MPa = 0.4718 MPa
ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')] ρ act = 0.85 fc'/fy [1- √1 - (2Ru/0.85fc')]
= [0.85(20.70/275.00)] {1 - √1 - = [0.85(20.70/275.00)] {1 - √1 -
[(2 x 0.5273) / (0.85 x 20.70)]} [(2 x 0.4718) / (0.85 x 20.70)]}
= 0.001947 = 0.001739
use ρ = 0.005091 use ρ = 0.005091
x = L/2 - b/2 As = ρ W d y = W/2 - h/2 As = ρ L d
= 1.20/2 - 0.250/2 = 0.005091 x 1.20 x 0.217 = 1.20/2 - 0.350/2 = 0.005091 x 1.20 x 0.217
= 0.475 m = 1325.696 mm² = 0.425 m = 1325.696 mm²
A= Wx Qty = As / Ab A= Ly Qty = As / Ab
= 1.20 x 0.475 = 1,325.696 / π16²/4 = 1.20 x 0.425 = 1,325.696 / π16²/4
= 0.570 m² = 7L - 16mmØ RSB = 0.510 m² = 7L - 16mmØ RSB
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE COLUMN


Column: C2
Location: A3
I. COLUMN PROPERTIES
Material Properties: Dimensions: Steel Ratio: 1% - 8%
Concrete, fc' = 20.70 MPa Base, b = 0.250 m SR = Ag / As
Main 1, fy = 275 MPa Height, h = 0.350 m = 1.84%
Main 2, fy = 275 MPa Length, L = 3.00 m
Shear, fy = 230 MPa
Reduction Factors: Reinforcing Steel Bar: Result Stresses:
β= 0.85 MB1 RSBØ = 16 mm From Frame Analysis
Axial, ф = 0.70 Qty = 4 pcs Stresses Design F.S.
Flexure, ф = 0.90 MB2 RSBØ = 16 mm Pu kN 75.700 14.45
Shear, ф = 0.85 Qty = 4 pcs Mux kN-m 17.800 3.21
steel cover = 0.040 m Shear RSBØ = 10 mm Muy kN-m 18.200 6.26

Mz(kN-m) My(kN-m) Fx(kN)


20 16 20 20 20 100 84.1 100
13.8 75.7
11.5 12.1
10 10 10 10 50 50

2006 3006 2006 3006 2006 3006


1 2 3 1 2 3 -7.92 1 2 -7.923
10 10 10 -7.57 10 50 50
-13.4
20 -18.2 20 20 -17.8 20 100 100

II. DETAILED CALCULATION


A. Compression Controlled B. Tension Contolled
Pn = 0.80 [0.85 fc' (Ag-As) + Asfy] Moment about X-axis, Moment about Y-axis,
= 1562.88 kN Layer 1: 3 d1' = 0.058 d1 = 0.067 Layer 1: 3 d1' = 0.058 d1 = 0.117
Pu = Φ Pn Layer 2: 0 d2' = 0.000 d2 = 0.000 Layer 2: 0 d2' = 0.000 d2 = 0.000
= 1094.02 kN Layer 3: 0 d3' = 0.000 d3 = 0.000 Layer 3: 0 d3' = 0.000 d3 = 0.000
Stirrups: Summary: d' = 0.058 c= 0.087 fs' = 200.00 d' = 0.058 c= 0.132 fs' = 336.36
16Db = 256 mm 1 at 50 d= 0.192 a= 0.074 fs = 724.14 d= 0.292 a= 0.112 fs = 727.27
48db = 480 mm 8 at 100 Cs 1 = 120.64 Ts 1 = 165.88 Cc = 455.71 Cs 1 = 165.88 Ts 1 = 165.88 Cc = 492.66
least = 250 mm rest at 250 Cs 2 = 0.00 Ts 2 = 0.00 Mnx = 63.40 Cs 2 = 0.00 Ts 2 = 0.00 Mny = 126.51
Smax = 250 mm Cs 3 = 0.00 Ts 3 = 0.00 Mux = 57.06 Cs 3 = 0.00 Ts 3 = 0.00 Muy = 113.86

Column: C-1
Location: Ground Floor Column @ Grid A2
I. COLUMN PROPERTIES
Material Properties: Dimensions: Steel Ratio: 1% - 8%
Concrete, fc' = 20.70 MPa Base, b = 0.250 m SR = Ag / As
Main 1, fy = 275 MPa Height, h = 0.350 m = 2.76%
Main 2, fy = 275 MPa Length, L = 3.20 m
Shear, fy = 230 MPa
Reduction Factors: Reinforcing Steel Bar: Result Stresses:
β= 0.85 Main 1, RSBØ = 16 mm From Frame Analysis
Axial, ф = 0.70 Qty = 4 pcs Stresses Design F.S.
Flexure, ф = 0.90 Main 2, RSBØ = 16 mm Pu kN 265.000 4.57
Shear, ф = 0.85 Qty = 8 pcs Mux kN-m 34.300 1.66
steel cover = 0.040 m Shear RSBØ = 10 mm Muy kN-m 29.900 3.81

Mz(kN-m) My(kN-m) Fx(kN)


29.9
30 30 40 34.3 40 300 276 265 300
20 17.4 20 24 200 200
20 20
10 10 100 100
1006 2006 1006 2006 1006 2006
10 1 2 33.2 10 1 2 33.2 100 -31 1 2 33.2
-31 100
20 20
20 20 -20.3 200 200
-21.3 -28.8
30 -25.3 30 40 40 300 300

II. DETAILED CALCULATION


A. Compression Controlled B. Tension Contolled
Pn = 0.80 [0.85 fc' (Ag-As) + Asfy] Moment about X-axis, Moment about Y-axis,
= 1728.49 kN Layer 1: 3 d1' = 0.058 d1 = 0.067 Layer 1: 3 d1' = 0.058 d1 = 0.117
Pu = Φ Pn Layer 2: 0 d2' = 0.000 d2 = 0.000 Layer 2: 0 d2' = 0.000 d2 = 0.000
= 1209.94 kN Layer 3: 0 d3' = 0.000 d3 = 0.000 Layer 3: 0 d3' = 0.000 d3 = 0.000
Stirrups: Summary: d' = 0.058 c= 0.087 fs' = 200.00 d' = 0.058 c= 0.132 fs' = 336.36
16Db = 256 mm 1 at 50 d= 0.192 a= 0.074 fs = 724.14 d= 0.292 a= 0.112 fs = 727.27
48db = 480 mm 8 at 100 Cs 1 = 120.64 Ts 1 = 165.88 Cc = 455.71 Cs 1 = 165.88 Ts 1 = 165.88 Cc = 492.66
least = 250 mm rest at 250 Cs 2 = 0.00 Ts 2 = 0.00 Mnx = 63.40 Cs 2 = 0.00 Ts 2 = 0.00 Mny = 126.51
Smax = 250 mm Cs 3 = 0.00 Ts 3 = 0.00 Mux = 57.06 Cs 3 = 0.00 Ts 3 = 0.00 Muy = 113.86
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE COLUMN


Column: C1
Location: B3
I. COLUMN PROPERTIES
Material Properties: Dimensions: Steel Ratio: 1% - 8%
Concrete, fc' = 20.70 MPa Base, b = 0.300 m SR = Ag / As
Main 1, fy = 275 MPa Height, h = 0.300 m = 1.79%
Main 2, fy = 275 MPa Length, L = 3.00 m
Shear, fy = 230 MPa
Reduction Factors: Reinforcing Steel Bar: Result Stresses:
β= 0.85 MB1 RSBØ = 16 mm From Frame Analysis
Axial, ф = 0.70 Qty = 4 pcs Stresses Design F.S.
Flexure, ф = 0.90 MB2 RSBØ = 16 mm Pu kN 55.300 20.23
Shear, ф = 0.85 Qty = 4 pcs Mux kN-m 36.300 2.43
steel cover = 0.040 m Shear RSBØ = 10 mm Muy kN-m 14.200 6.21

Mz(kN-m) My(kN-m) Fx(kN)


40 36.3 32.1 40 20 20 80 66.2 80
13.1 14.2 55.3
20 20 10 10 40 40

2008 3007 2008 3007 2008 3007


1 2 3 1 2 3 -1.65 1 2 -1.653
20 20 10 10 40 40
-13.4 -15
40 -35.5 -33.4 40 20 20 80 80

II. DETAILED CALCULATION


A. Compression Controlled B. Tension Contolled
Pn = 0.80 [0.85 fc' (Ag-As) + Asfy] Moment about X-axis, Moment about Y-axis,
= 1598.07 kN Layer 1: 3 d1' = 0.058 d1 = 0.092 Layer 1: 3 d1' = 0.058 d1 = 0.092
Pu = Φ Pn Layer 2: 0 d2' = 0.000 d2 = 0.000 Layer 2: 0 d2' = 0.000 d2 = 0.000
= 1118.65 kN Layer 3: 0 d3' = 0.000 d3 = 0.000 Layer 3: 0 d3' = 0.000 d3 = 0.000
Stirrups: Summary: d' = 0.058 c= 0.109 fs' = 280.73 d' = 0.058 c= 0.109 fs' = 280.73
16Db = 256 mm 1 at 50 d= 0.242 a= 0.093 fs = 732.11 d= 0.242 a= 0.093 fs = 732.11
48db = 480 mm 8 at 100 Cs 1 = 165.88 Ts 1 = 165.88 Cc = 490.90 Cs 1 = 165.88 Ts 1 = 165.88 Cc = 490.90
least = 300 mm rest at 256 Cs 2 = 0.00 Ts 2 = 0.00 Mnx = 98.02 Cs 2 = 0.00 Ts 2 = 0.00 Mny = 98.02
Smax = 256 mm Cs 3 = 0.00 Ts 3 = 0.00 Mux = 88.22 Cs 3 = 0.00 Ts 3 = 0.00 Muy = 88.22

Column: C-1
Location: Ground Floor Column @ Grid A2
I. COLUMN PROPERTIES
Material Properties: Dimensions: Steel Ratio: 1% - 8%
Concrete, fc' = 20.70 MPa Base, b = 0.350 m SR = Ag / As
Main 1, fy = 275 MPa Height, h = 0.350 m = 1.97%
Main 2, fy = 275 MPa Length, L = 3.20 m
Shear, fy = 230 MPa
Reduction Factors: Reinforcing Steel Bar: Result Stresses:
β= 0.85 Main 1, RSBØ = 16 mm From Frame Analysis
Axial, ф = 0.70 Qty = 4 pcs Stresses Design F.S.
Flexure, ф = 0.90 Main 2, RSBØ = 16 mm Pu kN 354.000 4.39
Shear, ф = 0.85 Qty = 8 pcs Mux kN-m 41.200 4.09
steel cover = 0.040 m Shear RSBØ = 10 mm Muy kN-m 68.200 2.47

Mz(kN-m) My(kN-m) Fx(kN)


80 68.2 80 60 60 400 370 354 400
47.7 38.2 34.4 40
40
40 40 200 200
20 20
1007 2008 1007 2008 1007 2008
1 2 33.2 1 2 33.2 20 -9.7 1 2 -9.7
33.2
20
40 40 200 200
40 -27.9 40
-49 -41.2
-61.7
80 80 60 60 400 400

II. DETAILED CALCULATION


A. Compression Controlled B. Tension Contolled
Pn = 0.80 [0.85 fc' (Ag-As) + Asfy] Moment about X-axis, Moment about Y-axis,
= 2221.15 kN Layer 1: 3 d1' = 0.058 d1 = 0.117 Layer 1: 3 d1' = 0.058 d1 = 0.117
Pu = Φ Pn Layer 2: 2 d2' = 0.058 d2 = 0.117 Layer 2: 2 d2' = 0.058 d2 = 0.117
= 1554.81 kN Layer 3: 0 d3' = 0.000 d3 = 0.000 Layer 3: 0 d3' = 0.000 d3 = 0.000
Stirrups: Summary: d' = 0.058 c= 0.132 fs' = 336.36 d' = 0.058 c= 0.132 fs' = 336.36
16Db = 256 mm 1 at 50 d= 0.292 a= 0.112 fs = 727.27 d= 0.292 a= 0.112 fs = 727.27
48db = 480 mm 8 at 100 Cs 1 = 165.88 Ts 1 = 165.88 Cc = 689.72 Cs 1 = 165.88 Ts 1 = 165.88 Cc = 689.72
least = 350 mm rest at 256 Cs 2 = 110.58 Ts 2 = 110.58 Mnx = 187.46 Cs 2 = 110.58 Ts 2 = 110.58 Mny = 187.46
Smax = 256 mm Cs 3 = 0.00 Ts 3 = 0.00 Mux = 168.71 Cs 3 = 0.00 Ts 3 = 0.00 Muy = 168.71
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE BEAM


Beam: 2FB-1
Location: 3-AB
I. BEAM PROPERTIES
Material Properties: Shear and Moment Diagram:
Concrete, fc' = 20.70 MPa Flexure, fy = 275.00 MPa
Shear, fy = 230.00 MPa Mz(kN-m) Mz(kN-m)
Reduction Factor: 60 54.1 60 100 93.4 100
Flexure, ф = 0.90 β= 0.85
40 40
Torsion, ф = 0.85 steel cover = 0.040 m 50 50
20 25
Shear, ф = 0.85 max. agg. size = 0.025 m 8.07 20
0.219
Type of Beam: Continuous Beam 2006 2007 2007 2008
Dimensions: 20 -11.8 0.5 0.975 20 1 2 2.63
50 -29 50
Width, b = 0.250 m Length, L = 4.00 m
40 40 -49.8
-50.3
Height, h = 0.400 m h min. = 0.333 m
Reinf. Steel Bar Diameter: 60 -54.4 60 100 100
Flexure = 16 mm
Shear = 10 mm Fy(kN) Fy(kN)
Effective Depth (m): 150 150 100 100
d1' = 0.058 m d1 = 0.342 m
115 106
100 100 46.9
d2' = 0.099 m d2 = 0.301 m 50 50
d3' = 0.140 m d3 = 0.260 m 50 50 20.6
Result Stresses (from Frame Analysis): 2006 2007 2007 2008
Stresses Left Midspan Right 50 -20.4 0.5 0.975
-20.4 50 1 2 2.63
-20.6
- Mu 54.10 25.00 93.40 50 50
100 100
+ Mu 11.80 54.40 29.00
Vu 115.00 0.00 99.80 150 150 100 100
-99.8

III. DETAILED CALCULATION


A. Design for Flexure
If pmin < pact < pmax, Singly Reinforced Beams (SRB) LEFT SUPPORT
If pact > pmax, Doubly Reinforced Beams (DRB) TOP BARS: BOTTOM BARS:
• Calculate ρ bal = 0.85fc'β600 / fy(600+fy) = 0.037292 5 Layer 1 3 Layer 1
• Calculate ρ min = 1.4 / fy = 0.005091 2 Layer 2 0 Layer 2
• Calculate ρ max = 0.75 p bal = 0.027969 0 Layer 3 0 Layer 3
Top Bar Reinforcements 7 Total 3 Total
Negative Moment (-Mu) Left Support Midspan Right Support
Area of Steel 1 As1 1005.310 603.186 1005.310 FACTOR OF SAFETY:
Area of Steel 2 As2 402.124 0.000 402.124 FS = 1.84 FS = 4.09
Area of Steel 3 As3 0.000 0.000 0.000 MIDSPAN
Steel Ratio ρ act 0.017102 0.007055 0.017102 TOP BARS: BOTTOM BARS:
Reinf. Beam Type Singly R.B. Singly R.B. Singly R.B. 3 Layer 1 5 Layer 1
Stress Block Depth a 87.990 37.710 87.990 0 Layer 2 2 Layer 2
Extreme Comp. Fiber to Neutral Axis c 103.518 44.365 103.518 0 Layer 3 0 Layer 3
Nominal Moment Mn 110.807 53.602 110.807 3 Total 7 Total
Design Moment Mu 99.730 48.250 99.730
Bottom Bar Reinforcements FACTOR OF SAFETY:
Positive Moment (+Mu) Left Support Midspan Right Support FS = 1.93 FS = 1.83
Area of Steel 1 As1 603.186 1005.310 603.186 RIGHT SUPPORT
Area of Steel 2 As2 0.000 402.124 0.000 TOP BARS: BOTTOM BARS:
Area of Steel 3 As3 0.000 0.000 0.000 5 Layer 1 3 Layer 1
Steel Ratio ρ act 0.007055 0.017102 0.007055 2 Layer 2 0 Layer 2
Reinf. Beam Type Singly R.B. Singly R.B. Singly R.B. 0 Layer 3 0 Layer 3
Stress Block Depth a 37.710 87.990 37.710 7 Total 3 Total
Extreme Comp. Fiber to Neutral Axis c 44.365 103.518 44.365
Nominal Moment Mn 53.610 110.810 53.610 FACTOR OF SAFETY:
Design Moment Mu 48.250 99.730 48.250 FS = 1.07 FS = 1.66

B. Design for Stirrups


• Applied Force Vu max = 115.00 kN • Calculate S = Av Fy d / Vs = -153 mm
• Calculate Vc = 1/6 √fc'bd = 216.11 kN • Check Vs < 1/3 √fc'bd = -80.82 < 129.67 .'. Smax = d/2
• Check Vu < 1/2 ΦVc = 115.00 > 91.85 .'. Required • Calculate Smax = d/2= 171 mm
• Calculate Vn = Vu/ф = 135.29 kN • Summary
• Calculate Vs = Vn - Vc = -80.82 kN 1 @ 50 mm 3 @ 150 mm
• Check beam size Vs > 2/3 √fc'bd = -80.82 < 259.33 .'. Adequate 7 @ 100 mm rest @ 170 mm
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE BEAM


Beam: 2FB-2
Location: 3-BC
I. BEAM PROPERTIES
Material Properties: Shear and Moment Diagram:
Concrete, fc' = 20.70 MPa Flexure, fy = 275.00 MPa
Shear, fy = 230.00 MPa Mz(kN-m)
Reduction Factor: 80 66.6 80
Flexure, ф = 0.90 β= 0.85 51.3
Torsion, ф = 0.85 steel cover = 0.040 m 40 40
Shear, ф = 0.85 max. agg. size = 0.025 m
1.39
Type of Beam: Continuous Beam 2008 2009
Dimensions: 1 2 3 3.33
Width, b = 0.250 m Length, L = 4.00 m 40 -22.7 -27.9 -22.9 40

Height, h = 0.400 m h min. = 0.333 m


Reinf. Steel Bar Diameter: 80 80
Flexure = 16 mm
Shear = 10 mm Fy(kN)
Effective Depth (m): 100 85.3 100
d1' = 0.058 m d1 = 0.342 m
d2' = 0.099 m d2 = 0.301 m 50 50
d3' = 0.140 m d3 = 0.260 m 13.7
Result Stresses (from Frame Analysis): 2008 2009
Stresses Left Midspan Right -13.7 1 2 3 3.33
- Mu 66.00 0.00 51.30 50 50
-55.7
+ Mu 22.70 27.90 22.90
Vu 73.40 0.00 59.90 100 100

III. DETAILED CALCULATION


A. Design for Flexure
If pmin < pact < pmax, Singly Reinforced Beams (SRB) LEFT SUPPORT
If pact > pmax, Doubly Reinforced Beams (DRB) TOP BARS: BOTTOM BARS:
• Calculate ρ bal = 0.85fc'β600 / fy(600+fy) = 0.037292 4 Layer 1 3 Layer 1
• Calculate ρ min = 1.4 / fy = 0.005091 2 Layer 2 0 Layer 2
• Calculate ρ max = 0.75 p bal = 0.027969 0 Layer 3 0 Layer 3
Top Bar Reinforcements 6 Total 3 Total
Negative Moment (-Mu) Left Support Midspan Right Support
Area of Steel 1 As1 804.248 603.186 804.248 FACTOR OF SAFETY:
Area of Steel 2 As2 402.124 0.000 402.124 FS = 1.31 FS = 2.13
Area of Steel 3 As3 0.000 0.000 0.000 MIDSPAN
Steel Ratio ρ act 0.014750 0.007055 0.014750 TOP BARS: BOTTOM BARS:
Reinf. Beam Type Singly R.B. - Singly R.B. 3 Layer 1 4 Layer 1
Stress Block Depth a 75.420 37.710 75.420 0 Layer 2 2 Layer 2
Extreme Comp. Fiber to Neutral Axis c 88.729 44.365 88.729 0 Layer 3 0 Layer 3
Nominal Moment Mn 96.415 53.602 96.415 3 Total 6 Total
Design Moment Mu 86.780 48.250 86.780
Bottom Bar Reinforcements FACTOR OF SAFETY:
Positive Moment (+Mu) Left Support Midspan Right Support FS = - FS = 3.11
Area of Steel 1 As1 603.186 804.248 603.186 RIGHT SUPPORT
Area of Steel 2 As2 0.000 402.124 0.000 TOP BARS: BOTTOM BARS:
Area of Steel 3 As3 0.000 0.000 0.000 4 Layer 1 3 Layer 1
Steel Ratio ρ act 0.007055 0.014750 0.007055 2 Layer 2 0 Layer 2
Reinf. Beam Type Singly R.B. Singly R.B. Singly R.B. 0 Layer 3 0 Layer 3
Stress Block Depth a 37.710 75.420 37.710 6 Total 3 Total
Extreme Comp. Fiber to Neutral Axis c 44.365 88.729 44.365
Nominal Moment Mn 53.610 96.420 53.610 FACTOR OF SAFETY:
Design Moment Mu 48.250 86.780 48.250 FS = 1.69 FS = 2.11

B. Design for Stirrups


• Applied Force Vu max = 73.40 kN • Calculate S = Av Fy d / Vs = -96 mm
• Calculate Vc = 1/6 √fc'bd = 216.11 kN • Check Vs < 1/3 √fc'bd = -129.76 < 129.67 .'. Smax = d/2
• Check Vu < 1/2 ΦVc = 73.40 < 91.85 .'. Not Required • Calculate Smax = d/2= 171 mm
• Calculate Vn = Vu/ф = 86.35 kN • Summary
• Calculate Vs = Vn - Vc = -129.76 kN 1 @ 50 mm 3 @ 150 mm
• Check beam size Vs > 2/3 √fc'bd = -129.76 < 259.33 .'. Adequate 7 @ 100 mm rest @ 170 mm
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE BEAM


Beam: 2FB-3
Location: 1-BC
I. BEAM PROPERTIES
Material Properties: Shear and Moment Diagram:
Concrete, fc' = 20.70 MPa Flexure, fy = 275.00 MPa
Shear, fy = 230.00 MPa Mz(kN-m)
Reduction Factor: 80 80
Flexure, ф = 0.90 β= 0.85
61.5 54.9
Torsion, ф = 0.85 steel cover = 0.040 m 40 40
Shear, ф = 0.85 max. agg. size = 0.025 m
1.6
Type of Beam: Continuous Beam 2002 2003
Dimensions: 1 2 3 3.85
Width, b = 0.250 m Length, L = 4.00 m 40 -21.7 -25.5 -22.4 40

Height, h = 0.400 m h min. = 0.333 m


Reinf. Steel Bar Diameter: 80 80
Flexure = 16 mm
Shear = 10 mm Fy(kN)
Effective Depth (m): 80 73.4 80
d1' = 0.058 m d1 = 0.342 m
d2' = 0.099 m d2 = 0.301 m 40 40
d3' = 0.140 m d3 = 0.260 m 11.4
Result Stresses (from Frame Analysis): 2002 2003
Stresses Left Midspan Right -11.4 1 2 3 3.85
- Mu 61.50 0.00 54.90 40 40
+ Mu 21.70 25.50 22.40
-59.9
Vu 73.40 0.00 59.90 80 80

III. DETAILED CALCULATION


A. Design for Flexure
If pmin < pact < pmax, Singly Reinforced Beams (SRB) LEFT SUPPORT
If pact > pmax, Doubly Reinforced Beams (DRB) TOP BARS: BOTTOM BARS:
• Calculate ρ bal = 0.85fc'β600 / fy(600+fy) = 0.037292 3 Layer 1 3 Layer 1
• Calculate ρ min = 1.4 / fy = 0.005091 2 Layer 2 0 Layer 2
• Calculate ρ max = 0.75 p bal = 0.027969 0 Layer 3 0 Layer 3
Top Bar Reinforcements 5 Total 3 Total
Negative Moment (-Mu) Left Support Midspan Right Support
Area of Steel 1 As1 603.186 603.186 603.186 FACTOR OF SAFETY:
Area of Steel 2 As2 402.124 0.000 402.124 FS = 1.19 FS = 2.22
Area of Steel 3 As3 0.000 0.000 0.000 MIDSPAN
Steel Ratio ρ act 0.012399 0.007055 0.012399 TOP BARS: BOTTOM BARS:
Reinf. Beam Type Singly R.B. - Singly R.B. 3 Layer 1 3 Layer 1
Stress Block Depth a 62.850 37.710 62.850 0 Layer 2 2 Layer 2
Extreme Comp. Fiber to Neutral Axis c 73.941 44.365 73.941 0 Layer 3 0 Layer 3
Nominal Moment Mn 81.328 53.602 81.328 3 Total 5 Total
Design Moment Mu 73.200 48.250 73.200
Bottom Bar Reinforcements FACTOR OF SAFETY:
Positive Moment (+Mu) Left Support Midspan Right Support FS = - FS = 2.87
Area of Steel 1 As1 603.186 603.186 603.186 RIGHT SUPPORT
Area of Steel 2 As2 0.000 402.124 0.000 TOP BARS: BOTTOM BARS:
Area of Steel 3 As3 0.000 0.000 0.000 3 Layer 1 3 Layer 1
Steel Ratio ρ act 0.007055 0.012399 0.007055 2 Layer 2 0 Layer 2
Reinf. Beam Type Singly R.B. Singly R.B. Singly R.B. 0 Layer 3 0 Layer 3
Stress Block Depth a 37.710 62.850 37.710 5 Total 3 Total
Extreme Comp. Fiber to Neutral Axis c 44.365 73.941 44.365
Nominal Moment Mn 53.610 81.330 53.610 FACTOR OF SAFETY:
Design Moment Mu 48.250 73.200 48.250 FS = 1.33 FS = 2.15

B. Design for Stirrups


• Applied Force Vu max = 73.40 kN • Calculate S = Av Fy d / Vs = -96 mm
• Calculate Vc = 1/6 √fc'bd = 216.11 kN • Check Vs < 1/3 √fc'bd = -129.76 < 129.67 .'. Smax = d/2
• Check Vu < 1/2 ΦVc = 73.40 < 91.85 .'. Not Required • Calculate Smax = d/2= 171 mm
• Calculate Vn = Vu/ф = 86.35 kN • Summary
• Calculate Vs = Vn - Vc = -129.76 kN 1 @ 50 mm 3 @ 150 mm
• Check beam size Vs > 2/3 √fc'bd = -129.76 < 259.33 .'. Adequate 7 @ 100 mm rest @ 170 mm
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE BEAM


Beam: 2FB-4
Location: C-13
I. BEAM PROPERTIES
Material Properties: Shear and Moment Diagram:
Concrete, fc' = 20.70 MPa Flexure, fy = 275.00 MPa
Shear, fy = 230.00 MPa Mz(kN-m)
Reduction Factor: 60 51.5 60
Flexure, ф = 0.90 β= 0.85 38.1
40 40
Torsion, ф = 0.85 steel cover = 0.040 m
Shear, ф = 0.85 max. agg. size = 0.025 m 20 20
Type of Beam: Continuous Beam 2003 2009
Dimensions: 20 1 2 3.17
3 20
Width, b = 0.250 m Length, L = 4.00 m -20.6 -19.4
40 40
Height, h = 0.400 m h min. = 0.333 m
Reinf. Steel Bar Diameter: 60 60
Flexure = 16 mm
Shear = 10 mm Fy(kN)
Effective Depth (m): 80 80
d1' = 0.058 m d1 = 0.342 m 54
d2' = 0.099 m d2 = 0.301 m 40 40
d3' = 0.140 m d3 = 0.260 m 12.6
Result Stresses (from Frame Analysis): 2003 2009
Stresses Left Midspan Right -12.6 1 2 3.17
3
- Mu 38.40 0.00 51.50 40 40
+ Mu 20.60 20.60 19.40
-61.5
Vu 54.00 0.00 61.50 80 80

III. DETAILED CALCULATION


A. Design for Flexure
If pmin < pact < pmax, Singly Reinforced Beams (SRB) LEFT SUPPORT
If pact > pmax, Doubly Reinforced Beams (DRB) TOP BARS: BOTTOM BARS:
• Calculate ρ bal = 0.85fc'β600 / fy(600+fy) = 0.037292 4 Layer 1 3 Layer 1
• Calculate ρ min = 1.4 / fy = 0.005091 0 Layer 2 0 Layer 2
• Calculate ρ max = 0.75 p bal = 0.027969 0 Layer 3 0 Layer 3
Top Bar Reinforcements 4 Total 3 Total
Negative Moment (-Mu) Left Support Midspan Right Support
Area of Steel 1 As1 804.248 603.186 804.248 FACTOR OF SAFETY:
Area of Steel 2 As2 0.000 0.000 0.000 FS = 1.64 FS = 2.34
Area of Steel 3 As3 0.000 0.000 0.000 MIDSPAN
Steel Ratio ρ act 0.009406 0.007055 0.009406 TOP BARS: BOTTOM BARS:
Reinf. Beam Type Singly R.B. - Singly R.B. 3 Layer 1 4 Layer 1
Stress Block Depth a 50.280 37.710 50.280 0 Layer 2 0 Layer 2
Extreme Comp. Fiber to Neutral Axis c 59.153 44.365 59.153 0 Layer 3 0 Layer 3
Nominal Moment Mn 70.079 53.602 70.079 3 Total 4 Total
Design Moment Mu 63.080 48.250 63.080
Bottom Bar Reinforcements FACTOR OF SAFETY:
Positive Moment (+Mu) Left Support Midspan Right Support FS = - FS = 3.06
Area of Steel 1 As1 603.186 804.248 603.186 RIGHT SUPPORT
Area of Steel 2 As2 0.000 0.000 0.000 TOP BARS: BOTTOM BARS:
Area of Steel 3 As3 0.000 0.000 201.062 4 Layer 1 3 Layer 1
Steel Ratio ρ act 0.007055 0.009406 0.010148 0 Layer 2 0 Layer 2
Reinf. Beam Type Singly R.B. Singly R.B. Singly R.B. 0 Layer 3 1 Layer 3
Stress Block Depth a 37.710 50.280 50.280 4 Total 4 Total
Extreme Comp. Fiber to Neutral Axis c 44.365 59.153 59.153
Nominal Moment Mn 53.610 70.080 65.550 FACTOR OF SAFETY:
Design Moment Mu 48.250 63.080 59.000 FS = 1.22 FS = 3.04

B. Design for Stirrups


• Applied Force Vu max = 61.50 kN • Calculate S = Av Fy d / Vs = -86 mm
• Calculate Vc = 1/6 √fc'bd = 216.11 kN • Check Vs < 1/3 √fc'bd = -143.76 < 129.67 .'. Smax = d/2
• Check Vu < 1/2 ΦVc = 61.50 < 91.85 .'. Not Required • Calculate Smax = d/2= 171 mm
• Calculate Vn = Vu/ф = 72.35 kN • Summary
• Calculate Vs = Vn - Vc = -143.76 kN 1 @ 50 mm 3 @ 150 mm
• Check beam size Vs > 2/3 √fc'bd = -143.76 < 259.33 .'. Adequate 7 @ 100 mm rest @ 170 mm
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE BEAM


Beam: 2FB-5
Location: A'-34
I. BEAM PROPERTIES
Material Properties: Shear and Moment Diagram:
Concrete, fc' = 20.70 MPa Flexure, fy = 275.00 MPa
Shear, fy = 230.00 MPa Mz(kN-m)
Reduction Factor: 40
30.3 32.2 40
Flexure, ф = 0.90 β= 0.85
Torsion, ф = 0.85 steel cover = 0.040 m 20 20
Shear, ф = 0.85 max. agg. size = 0.025 m
1.78
Type of Beam: Continuous Beam 2007 2011
Dimensions: -6.03 1 2 3 3.55
-6.45
Width, b = 0.250 m Length, L = 4.00 m 20 -17.8 20
Height, h = 0.400 m h min. = 0.333 m
Reinf. Steel Bar Diameter: 40 40
Flexure = 16 mm
Shear = 10 mm Fy(kN)
Effective Depth (m): 60 60
47.1
d1' = 0.058 m d1 = 0.342 m
40 40
d2' = 0.099 m d2 = 0.301 m
d3' = 0.140 m d3 = 0.260 m 20 20
3.58
Result Stresses (from Frame Analysis): 2007 2011
Stresses Left Midspan Right -3.44 1 2 3 3.55 20
20
- Mu 30.30 0.00 32.20
40 40
+ Mu 6.03 17.80 6.45
-46.1
Vu 47.10 0.00 46.10 60 60

III. DETAILED CALCULATION


A. Design for Flexure
If pmin < pact < pmax, Singly Reinforced Beams (SRB) LEFT SUPPORT
If pact > pmax, Doubly Reinforced Beams (DRB) TOP BARS: BOTTOM BARS:
• Calculate ρ bal = 0.85fc'β600 / fy(600+fy) = 0.037292 4 Layer 1 3 Layer 1
• Calculate ρ min = 1.4 / fy = 0.005091 0 Layer 2 0 Layer 2
• Calculate ρ max = 0.75 p bal = 0.027969 0 Layer 3 0 Layer 3
Top Bar Reinforcements 4 Total 3 Total
Negative Moment (-Mu) Left Support Midspan Right Support
Area of Steel 1 As1 804.248 603.186 804.248 FACTOR OF SAFETY:
Area of Steel 2 As2 0.000 0.000 0.000 FS = 2.08 FS = 8.00
Area of Steel 3 As3 0.000 0.000 0.000 MIDSPAN
Steel Ratio ρ act 0.009406 0.007055 0.009406 TOP BARS: BOTTOM BARS:
Reinf. Beam Type Singly R.B. - Singly R.B. 3 Layer 1 4 Layer 1
Stress Block Depth a 50.280 37.710 50.280 0 Layer 2 0 Layer 2
Extreme Comp. Fiber to Neutral Axis c 59.153 44.365 59.153 0 Layer 3 0 Layer 3
Nominal Moment Mn 70.079 53.602 70.079 3 Total 4 Total
Design Moment Mu 63.080 48.250 63.080
Bottom Bar Reinforcements FACTOR OF SAFETY:
Positive Moment (+Mu) Left Support Midspan Right Support FS = - FS = 3.54
Area of Steel 1 As1 603.186 804.248 603.186 RIGHT SUPPORT
Area of Steel 2 As2 0.000 0.000 0.000 TOP BARS: BOTTOM BARS:
Area of Steel 3 As3 0.000 0.000 0.000 4 Layer 1 3 Layer 1
Steel Ratio ρ act 0.007055 0.009406 0.007055 0 Layer 2 0 Layer 2
Reinf. Beam Type Singly R.B. Singly R.B. Singly R.B. 0 Layer 3 0 Layer 3
Stress Block Depth a 37.710 50.280 37.710 4 Total 3 Total
Extreme Comp. Fiber to Neutral Axis c 44.365 59.153 44.365
Nominal Moment Mn 53.610 70.080 53.610 FACTOR OF SAFETY:
Design Moment Mu 48.250 63.080 48.250 FS = 1.96 FS = 7.48

B. Design for Stirrups


• Applied Force Vu max = 47.10 kN • Calculate S = Av Fy d / Vs = -77 mm
• Calculate Vc = 1/6 √fc'bd = 216.11 kN • Check Vs < 1/3 √fc'bd = -160.70 < 129.67 .'. Smax = d/2
• Check Vu < 1/2 ΦVc = 47.10 < 91.85 .'. Not Required • Calculate Smax = d/2= 171 mm
• Calculate Vn = Vu/ф = 55.41 kN • Summary
• Calculate Vs = Vn - Vc = -160.70 kN 1 @ 50 mm 3 @ 150 mm
• Check beam size Vs > 2/3 √fc'bd = -160.70 < 259.33 .'. Adequate 7 @ 100 mm rest @ 170 mm
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE BEAM


Beam: RB-1
Location: A-34
I. BEAM PROPERTIES
Material Properties: Shear and Moment Diagram:
Concrete, fc' = 20.70 MPa Flexure, fy = 275.00 MPa Mz(kN-m)
Shear, fy = 230.00 MPa
30 30
Reduction Factor: 22.1 20.8
Flexure, ф = 0.90 β= 0.85 20 20
Torsion, ф = 0.85 steel cover = 0.040 m 10 10
Shear, ф = 0.85 max. agg. size = 0.025 m 2.06
3008 3011
Type of Beam: Continuous Beam
10 -6.9 1 2 3 3.54 10
Dimensions: -9.12 -7.46
Width, b = 0.200 m Length, L = 4.00 m 20 20
Height, h = 0.300 m h min. = 0.333 m
30 30
Reinf. Steel Bar Diameter:
Flexure = 16 mm Fy(kN)
Shear = 10 mm 29.5
30 30
Effective Depth (m):
d1' = 0.058 m d1 = 0.242 m 20 20
d2' = 0.099 m d2 = 0.201 m 10 4.06 10
d3' = 0.140 m d3 = 0.160 m
3008 3011
Result Stresses (from Frame Analysis):
10 -4.06 1 2 3 3.54 10
Stresses Left Midspan Right
- Mu 22.10 0.00 20.80 20 20
+ Mu 6.90 9.12 7.46
30 -28.3 30
Vu 29.50 0.00 28.30

III. DETAILED CALCULATION


A. Design for Flexure
If pmin < pact < pmax, Singly Reinforced Beams (SRB) LEFT SUPPORT
If pact > pmax, Doubly Reinforced Beams (DRB) TOP BARS: BOTTOM BARS:
• Calculate ρ bal = 0.85fc'β600 / fy(600+fy) = 0.037292 2 Layer 1 2 Layer 1
• Calculate ρ min = 1.4 / fy = 0.005091 2 Layer 2 0 Layer 2
• Calculate ρ max = 0.75 p bal = 0.027969 0 Layer 3 0 Layer 3
Top Bar Reinforcements 4 Total 2 Total
Negative Moment (-Mu) Left Support Midspan Right Support
Area of Steel 1 As1 402.124 402.124 402.124 FACTOR OF SAFETY:
Area of Steel 2 As2 402.124 0.000 402.124 FS = 1.71 FS = 3.27
Area of Steel 3 As3 0.000 0.000 0.000 MIDSPAN
Steel Ratio ρ act 0.018311 0.008308 0.018311 TOP BARS: BOTTOM BARS:
Reinf. Beam Type Singly R.B. - Singly R.B. 2 Layer 1 2 Layer 1
Stress Block Depth a 62.850 31.425 62.850 0 Layer 2 2 Layer 2
Extreme Comp. Fiber to Neutral Axis c 73.941 36.971 73.941 0 Layer 3 0 Layer 3
Nominal Moment Mn 42.039 25.024 42.039 2 Total 4 Total
Design Moment Mu 37.840 22.530 37.840
Bottom Bar Reinforcements FACTOR OF SAFETY:
Positive Moment (+Mu) Left Support Midspan Right Support FS = - FS = 4.15
Area of Steel 1 As1 402.124 402.124 402.124 RIGHT SUPPORT
Area of Steel 2 As2 0.000 402.124 0.000 TOP BARS: BOTTOM BARS:
Area of Steel 3 As3 0.000 0.000 0.000 2 Layer 1 2 Layer 1
Steel Ratio ρ act 0.008308 0.018311 0.008308 2 Layer 2 0 Layer 2
Reinf. Beam Type Singly R.B. Singly R.B. Singly R.B. 0 Layer 3 0 Layer 3
Stress Block Depth a 31.425 62.850 31.425 4 Total 2 Total
Extreme Comp. Fiber to Neutral Axis c 36.971 73.941 36.971
Nominal Moment Mn 25.030 42.040 25.030 FACTOR OF SAFETY:
Design Moment Mu 22.530 37.840 22.530 FS = 1.82 FS = 3.02

B. Design for Stirrups


• Applied Force Vu max = 29.50 kN • Calculate S = Av Fy d / Vs = -100 mm
• Calculate Vc = 1/6 √fc'bd = 122.34 kN • Check Vs < 1/3 √fc'bd = -87.63 < 73.40 .'. Smax = d/2
• Check Vu < 1/2 ΦVc = 29.50 < 51.99 .'. Not Required • Calculate Smax = d/2= 121 mm
• Calculate Vn = Vu/ф = 34.71 kN • Summary
• Calculate Vs = Vn - Vc = -87.63 kN 1 @ 50 mm 0 @ 0 mm
• Check beam size Vs > 2/3 √fc'bd = -87.63 < 146.80 .'. Adequate 5 @ 100 mm rest @ 125 mm
Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF STEEL


DESIGN ANALYSIS OF PURLIN
I. MATERIAL PROPERTIES
Section: LC 100 x 50 x 15 x 2.0mm thk. Cee Purlins
Weight, Wt = 3.51 kg/m Bay Length = 4.00 m
Section Modulus, Sx = 16.20 x 10³ mm³ Spacing = 0.70 m
Sy = 5.20 x 10³ mm³ Roof Slope = 5.47 degree
Flexural Stress, Fy = 248.00 MPa Roof Dead Load = 0.10 kPa
Allowable Stresses: Fbx = 0.66 Fy = 163.68 MPa Roof Live Load = 1.00 kPa
Fby = 0.75 Fy = 186.00 MPa Wind Pressure = 1.60 kPa
II. DESIGN LOAD COMBINATIONS
A. Weight of Purlin
DL = 3.51 x 9.81 = 34.43 N/m Wpn = 34.43 cos 5.47° = 34.27 N/m
Wpt = 34.43 sin 5.47° = 3.28 N/m
B. Roof Loads
DL = 0.70 x 0.10 = 70.00 N/m Wrn = DL + LLR + 0.5WL = 1,330.00 N/m
LLR = 0.70 x 1.00 = 700.00 N/m = 1,330.00 cos 5.47° = 1,323.94 N/m
WL = 0.70 x 1.60 = 1,120.00 N/m Wrt = DL + LLR = 770.00 N/m
= 770.00 sin 5.47° = 73.40 N/m
III. DESIGN MOMENT
Mpx = Wpn L² / 8 = 68.54 N-m Mrx = Wrn L² / 8 = 2,647.88 N-m
Mpy = Wpt L² / 32 = 1.64 N-m Mry = Wrt L² / 32 = 36.70 N-m
IV. RESULT STRESSES
fbpx = Mpx / Sx = 4.23 MPa fbrx = Mrx / Sx = 163.45 MPa
fbpy = Mpy / Sy = 0.32 MPa fbry = Mry / 0.5Sy = 14.12 MPa
V. INTERACTION CRITERION
Note: 1/3 increase in allowable stresses is allowed.
fbpx + fbrx fbpy + fbry
+ ≤ 1.00
Fbx + 1/3 Fbx Fby + 1/3 Fby
4.23 + 163.45 0.32 + 14.12
+ ≤ 1.00
163.68 + 54.56 186.00 + 62.00

0.83 < 1.00 .'. Adequate

DESIGN ANALYSIS OF TRUSS/RAFTER


I. MATERIAL PROPERTIES
Section: 2 L - LC 150 x 65 x 20 x 2.0mm thk. Cee Purlins
Weight, Wt = 4.76 kg/m Length = 3.60 m
Section Modulus, Sx = 28.60 x 10³ mm³ Tributary Width = 2.00 m
Sy = 8.10 x 10³ mm³ Roof Slope = 6.55 degree
Flexural Stress, Fy = 248.00 MPa Roof Dead Load = 0.10 kPa
Allowable Stresses: Fbx = 0.66 Fy = 163.68 MPa Roof Live Load = 1.00 kPa
Fby = 0.75 Fy = 186.00 MPa Wind Pressure = 1.60 kPa
II. DESIGN LOAD COMBINATIONS
A. Weight of Purlin
Wt = 34.43 x 2.00 x 7 = 482.02 N Wpn = 482.02 cos 6.55° = 478.87 N/m
DLp = 482.02 / 3.60 = 133.89 N/m
B. Weight of Rafter/Truss
DLr/t = 4.76 x 9.81 x 2 = 93.39 N/m Wpn = 93.39 cos 6.55° = 92.78 N/m
C. Roof Loads
DL = 0.10 x 2.00 = 200.00 N/m Wrn = DL + LLR + 0.5WL = 3,800.00 N/m
LLR = 1.00 x 2.00 = 2,000.00 N/m = 3,800.00 cos 6.55° = 3,775.20 N/m
WL = 1.60 x 2.00 = 3,200.00 N/m
III. DESIGN MOMENT
Mpx = Wpn L² / 8 = 926.07 N-m Mrx = Wrn L² / 8 = 6,115.82 N-m
IV. RESULT STRESSES
fbpx = Mpx / 2Sx = 16.19 MPa fbrx = Mpx / 2Sx = 106.92 MPa
V. INTERACTION CRITERION
Note: 1/3 increase in allowable stresses is allowed.
fbx + frx
≤ 1.00
Fbx + 1/3 Fbx
16.19 + 106.92
≤ 1.00
163.68 + 54.56

0.56 < 1.00 .'. Adequate


Project Name: PROPOSED TWO(2) - STOREY RESIDENTIAL BUILDING Owner: JERSON MONTANO

Location: SINDANGAN, ZAMBOANGA DEL NORTE Civil Engineer: JULIE ANNE LAIRE A. LORILLA

DESIGN ANALYSIS OF REINFORCED CONCRETE SLAB


TWO-WAY SLAB DESIGN
Slab: S-1
Location: AB-23
Slab Type: Slab Properties: Span Ratio: 0.75 ≈ 0.75
Short Span = 3.00 m Ca dl = 0.036 Ca ll = 0.049 Ca = 0.061
+ Mu + Mu - Mu
3 One Long Edge Discontiuous Long Span = 4.00 m Cb dl = 0.013 Cb ll = 0.016 Cb = 0.036
Slab thk. = 0.125 m Steel Reinforcements: Temperature Bars:
DSBØ = 10 mm d eff. @ short = 0.100 ρmin = 0.00609 Assumption, ρact As Smax
Material Properties: Unfactored Loads: d eff. @ long = 0.090 ρmax = 0.03525 1/2 of ρmin 0.00305 305.00 258
Concrete, fc' = 20.70 MPa Dead Load = 11.07 kN/m Along Short Span: Along Long Span:
Steel, fy = 230.00 MPa Live Load = 1.90 kN/m Location Mu ρact As Smax Location Mu ρact As Smax
Reduction Factor: Factored Loads: Mid 5.64 0.00277 609.00 129 Mid 2.27 0.00137 548.10 143
Bending, Φ = 0.90 Dead Load = 13.28 kN/m Cont. 8.96 0.00446 609.00 129 Cont. 5.29 0.00322 548.10 143
steel cover, sc = 0.020 m Live Load = 3.04 kN/m Discont. 1.88 0.00091 609.00 129 Discont. 0.76 0.00045 548.10 143

Slab: S-1
Location: BC-23
Slab Type: Slab Properties: Span Ratio: 0.88 ≈ 0.85
Short Span = 3.70 m Ca dl = 0.036 Ca ll = 0.043 Ca = 0.066
Two Adjacent Edges + Mu + Mu - Mu
4 Long Span = 4.20 m Cb dl = 0.019 Cb ll = 0.023 Cb = 0.034
Discontinuous
Slab thk. = 0.125 m Steel Reinforcements: Temperature Bars:
DSBØ = 10 mm d eff. @ short = 0.100 ρmin = 0.00609 Assumption, ρact As Smax
Material Properties: Unfactored Loads: d eff. @ long = 0.090 ρmax = 0.03525 1/2 of ρmin 0.00305 305.00 258
Concrete, fc' = 20.70 MPa Dead Load = 11.07 kN/m Along Short Span: Along Long Span:
Steel, fy = 230.00 MPa Live Load = 1.90 kN/m Location Mu ρact As Smax Location Mu ρact As Smax
Reduction Factor: Factored Loads: Mid 8.33 0.00414 609.00 129 Mid 4.97 0.00302 548.10 143
Bending, Φ = 0.90 Dead Load = 13.28 kN/m Cont. 14.75 0.00749 749.00 105 Cont. 7.60 0.00468 548.10 143
steel cover, sc = 0.020 m Live Load = 3.04 kN/m Discont. 2.78 0.00135 609.00 129 Discont. 1.66 0.00100 548.10 143

Slab: S-1
Location: BC-23
Slab Type: Slab Properties: Span Ratio: 0.79 ≈ 0.75
Short Span = 3.00 m Ca dl = 0.036 Ca ll = 0.049 Ca = 0.061
+ Mu + Mu - Mu
3 One Long Edge Discontiuous Long Span = 3.80 m Cb dl = 0.013 Cb ll = 0.016 Cb = 0.036
Slab thk. = 0.125 m Steel Reinforcements: Temperature Bars:
DSBØ = 10 mm d eff. @ short = 0.100 ρmin = 0.00609 Assumption, ρact As Smax
Material Properties: Unfactored Loads: d eff. @ long = 0.090 ρmax = 0.03525 1/2 of ρmin 0.00305 305.00 258
Concrete, fc' = 20.70 MPa Dead Load = 11.07 kN/m Along Short Span: Along Long Span:
Steel, fy = 230.00 MPa Live Load = 1.90 kN/m Location Mu ρact As Smax Location Mu ρact As Smax
Reduction Factor: Factored Loads: Mid 5.64 0.00277 609.00 129 Mid 2.27 0.00137 548.10 143
Bending, Φ = 0.90 Dead Load = 13.28 kN/m Cont. 8.96 0.00446 609.00 129 Cont. 5.29 0.00322 548.10 143
steel cover, sc = 0.020 m Live Load = 3.04 kN/m Discont. 1.88 0.00091 609.00 129 Discont. 0.76 0.00045 548.10 143

Slab: S-1
Location: BC-23
Slab Type: Slab Properties: Span Ratio: 0.95 ≈ 0.95
Short Span = 3.60 m Ca dl = 0.030 Ca ll = 0.035 Ca = 0.050
Two Adjacent Edges + Mu + Mu - Mu
4 Long Span = 3.80 m Cb dl = 0.024 Cb ll = 0.029 Cb = 0.045
Discontinuous
Slab thk. = 0.125 m Steel Reinforcements: Temperature Bars:
DSBØ = 10 mm d eff. @ short = 0.100 ρmin = 0.00609 Assumption, ρact As Smax
Material Properties: Unfactored Loads: d eff. @ long = 0.090 ρmax = 0.03525 1/2 of ρmin 0.00305 305.00 258
Concrete, fc' = 20.70 MPa Dead Load = 11.07 kN/m Along Short Span: Along Long Span:
Steel, fy = 230.00 MPa Live Load = 1.90 kN/m Location Mu ρact As Smax Location Mu ρact As Smax
Reduction Factor: Factored Loads: Mid 6.54 0.00323 609.00 129 Mid 5.94 0.00363 548.10 143
Bending, Φ = 0.90 Dead Load = 13.28 kN/m Cont. 10.58 0.00529 609.00 129 Cont. 9.52 0.00591 548.10 143
steel cover, sc = 0.020 m Live Load = 3.04 kN/m Discont. 2.18 0.00106 609.00 129 Discont. 1.98 0.00119 548.10 143

ONE-WAY SLAB DESIGN


Slab: -
Location: -
Material Properties: Unfactored Loads: Slab Properties: Main Bar: Temp. Bar:
Concrete, fc' = 0.00 MPa Dead Load = 0.00 kN/m Short Span = 0.00 m d eff. = 0.000 d eff. = 0.000
Steel, fy = 0.00 MPa Live Load = 0.00 kN/m Slab thk. = 0.000 m Mu = 0.00 Mu = 0.00
DSBØ = 0 mm ρact = 0.00000 ρact = 0.00000
Reduction Factor: Factored Loads: Steel Reinforcements: As = 0.00 Ast = 0.00
Bending, Φ = 0.00 Dead Load = 0.00 kN/m ρmin = 0.00000
Smax = 0 Smax = 0
steel cover, sc = 0.000 m Live Load = 0.00 kN/m ρmax = 0.00000
Project Name: Owner:
Location: Civil Engineer:

DESIGN ANALYSIS OF REINFORCED CONCRETE STAIR


REINFORCED CONCRETE SLAB
Location: Landing to Up Stair Location: Landing to Down Stair
Slab Properties: Slab Properties:
Considering 1m strip, Considering 1m strip,
Length = 3.800 m Rise = 0.200 m Length = 2.200 m Rise = 0.200 m
Slab thk = 0.150 m Tread = 0.250 m Slab thk = 0.150 m Tread = 0.250 m
Steps = 16 set Steps = 4 set
Material Properties: Reduction Factor: Material Properties: Reduction Factor:
Concrete, fc' = 20.70 MPa Bending, Φ = 0.900 Concrete, fc' = 20.70 MPa Bending, Φ = 0.900
Main Steel, fy = 275.00 MPa steel cover, sc = 0.020 m Main Steel, fy = 275.00 MPa steel cover, sc = 0.020 m
Sec. Steel, fy = 230.00 MPa Sec. Steel, fy = 230.00 MPa
Unfactored Loads: Factored Loads: Unfactored Loads: Factored Loads:
Dead Load = 7.23 kN/m Dead Load = 8.68 kN/m Dead Load = 5.79 kN/m Dead Load = 6.95 kN/m
Live Load = 1.90 kN/m Live Load = 3.04 kN/m Live Load = 1.90 kN/m Live Load = 3.04 kN/m
Steel Reinforcements: Steel Reinforcements:
ρ min = 0.005091 ρ max = 0.027969 ρ min = 0.005091 ρ max = 0.027969
Main Bars, Main Bars,
Main RSBØ = 12 mm d eff. = 0.124 m Main RSBØ = 16 mm d eff. = 0.122 m
Negative Moment, Positive Moment, Negative Moment, Positive Moment,
- Mu = 14.10 kN-m + Mu = 21.15 kN-m - Mu = 4.03 kN-m + Mu = 6.04 kN-m
ρ= 0.003819 ρ= 0.005823 ρ= 0.001103 ρ= 0.001661
Ast = 631.28 mm² As = 722.05 mm² Ast = 621.10 mm² As = 621.10 mm²
Smax = 179 mm Smax = 157 mm Smax = 324 mm Smax = 324 mm
Temperature Bars, Temperature Bars,
Sec. RSBØ = 10 mm Sec. RSBØ = 10 mm
ρ = 1/2 of ρ min As = 315.70 mm² ρ = 1/2 of ρ min As = 310.61 mm²
ρ= 0.002546 Smax = 249 mm ρ= 0.002546 Smax = 253 mm

REINFORCED CONCRETE BEAM


Type of Beam: Simply Supported Beam Steel Reinforcements:
Dimensions: Design for Flexure,
Width, b = 0.200 m Length, L = 1.20 m Main RSBØ = 16 mm ρ min = 0.005091
Height, h = 0.300 m h min. = 0.100 m d eff. = 0.252 m ρ max = 0.027969
Negative Moment, Positive Moment,
Material Properties: Reduction Factor: - Mu = 1.41 kN-m + Mu = 2.11 kN-m
Concrete, fc' = 20.70 MPa Bending, Φ = 0.90 ρ act = 0.000090 ρ act = 0.000134
Main Steel, fy = 275.00 MPa Shear, ф = 0.85 As = 256.59 mm² As = 256.59 mm²
Sec. Steel, fy = 230.00 MPa steel cover, sc = 0.040 m Qty = 2 L - 16mm RSBØ Qty = 2 L - 16mm RSBØ
Design for Shear,
Uniform Distributed Load - 1 (UDL-1): Sec. RSBØ = 10 mm S = AvFyd/Vs = -246 mm
Unfactored Loads, Factored Loads, Vu = 1.00 kN Vs < √fc'bd/3 = -37.04 < 76.44
Dead Load = 7.23 kN/m Dead Load = 8.68 kN/m Vc = √fc'bd/6 = 38.22 kN .'. Smax = d/2
Live Load = 1.90 kN/m Live Load = 3.04 kN/m Vu < 1/2 ΦVc = 1.00 < 16.24 Smax = d / 2 = 126 mm
.'. Not Required Summary:
Uniform Distributed Load - 2 (UDL-2): Vn = Vu/ф = 1.18 kN 1 @ 50 mm
Unfactored Loads, Factored Loads, Vs = Vn - Vc = -37.04 kN 6 @ 100 mm
Dead Load = 5.79 kN/m Dead Load = 6.95 kN/m Vs>2/3 √fc'bd = -37.04 < 152.87 0 @ 150 mm
Live Load = 1.90 kN/m Live Load = 3.04 kN/m .'. Adequate rest @ 120 mm

REINFORCED CONCRETE FOOTING


Design Footing: Design Loads: Steel Requirements:
Length, L = 1.20 m Unfactored Loads, RSBØ = 12 mm ρ min = 0.005091
Width, W = 0.80 m SLC, Pn = 20.82 kN d eff. = 0.169 m ρ max = 0.027969
Depth, d = 0.250 m Ftng. Self Wt. = 5.76 kN Wide Beam Shear,
Fdn. Depth, D = 0.80 m Total, Pn = 26.58 kN Vu = qu A = 6.47 kN
Min. Fdn. Depth = 0.52 m Factored Loads, Vc = 1/6 √fc' W d = 102.52 kN
Column, b = 1.20 m SLC, Pu = 26.72 kN FS = ΦVc / Vu = 13.47 >1 .'. Adequate!
Column, h = 0.15 m Ftng. Self Wt. = 6.91 kN Reinforcing Bars along Width,
Total, Pu = 33.63 kN Mu = qu A = 11.38 kN-m
Material Properties: Ru = Mu/Φ L d² = 0.369 MPa
Concrete, Fc' = 20.70 Mpa Bearing Pressure: ρ act = 0.85fc'/fy [1-√1-(2Ru/0.85fc')] = 0.001356
Steel, Fy = 275.00 Mpa ESBP, qe = 79.94 kN/m² As = ρ L d = 688.30 mm²
USBP, qu = 35.03 kN/m² Qty = As / Ab = 7 L - 12mm RSBØ
Reduction Factor: Reinforcing Bars along Length / Temperature Bar,
Bending, ф = 0.90 Minimum Footing Dimension: ρ = 1/2 of ρ min = 0.002546
Shear, ф = 0.85 Length, L = 1.20 m Ast = ρ W d = 516.33 mm²
steel cover, sc = 0.075 m Width, W = 0.28 m Qty = As / Ab = 5 L - 12mm RSBØ