0% found this document useful (0 votes)
733 views5 pages

Jeric Lim

This document contains three power system calculation problems involving unity power factor correction, motor input power, and load calculations on a wye-delta system. For the first problem, the reactance required for unity power factor on a 132kV system with 70.7% power factor is calculated to be 348.473 ohms. The second problem determines the input power to a 460V, 208A motor with 0.9 power factor is 149.15 kW. The third and longest problem involves calculating line and phase currents, power, reactive power, and apparent power for a wye-connected load supplied from a delta source.

Uploaded by

Mark Baldado
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
733 views5 pages

Jeric Lim

This document contains three power system calculation problems involving unity power factor correction, motor input power, and load calculations on a wye-delta system. For the first problem, the reactance required for unity power factor on a 132kV system with 70.7% power factor is calculated to be 348.473 ohms. The second problem determines the input power to a 460V, 208A motor with 0.9 power factor is 149.15 kW. The third and longest problem involves calculating line and phase currents, power, reactive power, and apparent power for a wye-connected load supplied from a delta source.

Uploaded by

Mark Baldado
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 5

JERIC LIM

1. A 132-KV line, 3-phase system delivers 70.7 MVA of a balanced


WYE load of power factor 70.7%. Determine the reactance
necessary to attain unity power factor.
P.F=cos o
o = cos−1 (.707)
= 45.009 degrees
Qr= sino Sp
= sin(45.009 degrees)(70.7)
= 50 MVAR
Qp= Qt
3
= 50
3
= 16.667 MVAR
VLL=√3xVp
Vp= VLL
√3
= 132 KV/√3
= 44√3

Xp= Vp^2
Qp
= (44√3x10^3)^2
16.667x10^6
= 348.473 ohms
2. A 460-volt, 3-phase motor draws 208 A with a power factor of
0.90 lagging. Calculate the KW input to the motor.

GIVEN: V= 460 v
I= 208 A
P.F= 0.90

Pi = V x I x PF x √3
1000

Pi= 460x208x.90x√3
1000

Pi= 149.150 KW
3. A balanced WYE connected load load having impedance per phase of 20/36.87
degrees ohms is supplies from balanced DELTA-connected, 3-phase 240-volt
source. Determine the following:
A. Line Currents
B. Phase Currents
C. Power per phase
D. Total Power
E. Total Reactive Power
F. Total Apparent Power

ZAn=ZBn=ZCn= 20 /36.87 degrees

VAB= 240 ∠0 degrees Van=∠-30 degrees


VBC= 240 ∠-120 degrees VBn=∠-150 degrees
VCA= 240∠+120 degrees VCn=∠+90 degrees
VLL=√3 VO

VAn= 240 ∠-30 degrees


√3
= 138. 564 ∠-30 degrees

VBn= 240 ∠-150 degrees


√3
= 138. 564 ∠-150 degrees
VCn= 240 ∠+90 degrees
√3
= 138. 564 ∠+90 degrees
A. IBn= VAn = 138.564 ∠-30 degrees
ZAn 20 ∠36.87 degrees
= 6.928 ∠-66.87 degrees A
IBn= VBn = 138.564 ∠-150 degrees
ZBn 20 ∠36.87 degrees
= 6.928 ∠-186.87 degrees A
ICn= VCn = 138.564 ∠90 degrees
ZCn 20 ∠36.87 degrees
= 6.928 ∠53.13 degrees A
B. IL=IO
IA=IAn= 6.928 ∠-66.87 degrees A

IB=IBn=6.928 ∠-186.87 degrees A

IC=ICn=6.928 ∠53.13 degrees A

C. PAn= VAnIAn cos o


= (138.564)(6.928) cos(36.87)
= 767.976 watts
PBn= VBnIBn cos o
= (138.564)(6.928) cos(36.87)
= 767.976 watts
PCn= VCnICn cos o
= (138.564)(6.928) cos(36.87)
= 767.976 watts
D. PT= 3 Po
= 3(767.976)
= 2303.928 watts
E. QAn= VAnIAn sino
= (138.564)(6.928) sin(36.87)
= 575.984 vars
QBn= VBnIBn sino
= (138.564)(6.928) sin(36.87)
= 575.984 vars
QCn= VCnICn sino
= (138.564)(6.928) sin(36.87)
= 575.984 vars
QT= 3 Qo
= 3(575.984)
= 1727.952 vars

F. ST= 3 VLLIL
= 3(138.564)(6.928)
= 2879.914 VA