0% found this document useful (0 votes)
469 views76 pages

Desigo PX PXM20 Operator Unit: User's Guide

Uploaded by

Eng M Elseaidy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
469 views76 pages

Desigo PX PXM20 Operator Unit: User's Guide

Uploaded by

Eng M Elseaidy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 76

DESIGOä PX

PXM20 operator unit


User's Guide
Version 2.1

CA1U9231en
08.2002
Siemens Building Technologies
Building Automation
2/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation 08.2002
Contents

1 About this manual.................................................7

1.1 Target readers......................................................7


1.2 Contents ...............................................................7
1.3 Printing conventions .............................................8

2 Display and control elements ...............................9

2.1 Housing ................................................................9


2.1.1 Alarm LED ............................................................9
2.1.2 Audible signal .....................................................10
2.1.3 Keys ...................................................................10
2.2 The display panel ...............................................12
2.2.1 Title line ..............................................................12
2.2.2 Working area ......................................................13
2.2.3 Symbols .............................................................15

3 Settings ..............................................................17

3.1 System ...............................................................18


3.1.1 Set date & time (system time) ............................18
3.1.2 Set daylight savings ...........................................19
3.2 PXM20 operator unit ..........................................20
3.2.1 Language ...........................................................21
3.2.2 Date & time format .............................................21
3.2.3 Contrast..............................................................21
3.2.4 Buzzer ................................................................21
3.2.5 Alarm pop-up......................................................21
3.2.6 Alarm text mode .................................................21
3.2.7 Relogin ...............................................................22
3.2.8 Display saver on.................................................22
3.2.9 Main value ..........................................................22
3.2.10 Welcome window ...............................................22
rd
3.2.11 3 party site........................................................22
3.2.12 Domain ID ..........................................................23
3.2.13 Network scope....................................................23

3/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Contents 08.2002
4 Login and logout.................................................25

4.1 Connecting to the network..................................26


4.2 Login ..................................................................27
4.3 Logout ................................................................28

5 Navigation ..........................................................29

6 Reading and editing values ................................31

6.1.1 Example: Setting a setpoint................................33


6.1.2 Example: Modifying a heating curve...................33
6.1.3 Forced control ....................................................35

7 Alarms ................................................................37

7.1 Occurrence of alarms and events.......................37


7.2 Alarm acknowledgement ....................................38
7.2.1 Displaying the Alarm viewer ...............................38
7.2.2 Selecting an event or alarm................................39
7.2.3 Alarm acknowledgement / Alarm & event details ..
......................................................................40
7.3 Alarm & event history .........................................41

8 Access rights ......................................................43

8.1 Introduction.........................................................43
8.2 Password............................................................43
8.3 Add new user .....................................................43
8.4 Remove user ......................................................45
8.5 Change password ..............................................45
8.6 Edit user .............................................................46

9 Setting time schedules .......................................47

9.1 7-day schedule ...................................................47


9.1.1 Editing the switching points ................................48
9.2 Exception schedules ..........................................50
9.2.1 Listing the exceptions for a given day ................50
4/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Contents 08.2002
9.2.2 Listing all the exceptions ....................................51
9.2.3 Create new local exception ................................52
9.2.4 Editing a local exception.....................................52
9.2.5 Editing a calendar entry......................................54

10 Trend function and trend settings .......................55

10.1 Setting up a new trend .......................................55


10.2 Displaying an existing trend................................56
10.3 Main trenddialog box ..........................................57
10.3.1 Trend configuration ............................................57
10.3.2 Graphic view.......................................................59
10.3.3 Graphic view online ............................................61
10.3.4 List view..............................................................62

11 Service support ..................................................63

11.1 Wiring test ..........................................................63


11.2 Debug information ..............................................65

Index ...........................................................................67

5/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Contents 08.2002
6/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Contents 08.2002
1 About this manual
1.1 Target readers

This user guide is intended for those responsible for the


HVAC plant in a building and for other qualified staff
including commissioning and service engineers. It is
assumed that the users of this manual already have the level
of knowledge required before carrying out the tasks
described.

1.2 Contents

The manual starts with a description of the display and


control panel of the PXM20 operator unit and introduces the
generally applicable procedures for navigation and for editing
values. The second part of the manual leads you step by
step through the various activities involved in commissioning
and maintaining the plant.
As there may be significant differences between one plant
and another, and between the read and write access of one
user and another, it follows that it is not possible to provide a
description which is generally valid for every individual case.
"Favorite" objects, for example, are special objects
containing important values, which can be accessed with a
short-cut operation. The question of exactly which objects
and which values these are, is determined in the engineering
phase according to the individual needs of the plant operator.
Important For this reason, the steps described in this manual are
intended as examples, designed to clarify the basic
operating principles of the PXM20 operator unit.

7/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation About this manual 08.2002
1.3 Printing conventions

Text Bold text is used for text exactly as it appears in the display,
e.g. START, ACKNOWLEDGE, Settings etc.

Keys Key names are indicated as follows:


• Brackets < > indicate that the description appears on the
key itself. This convention is used for the <?> key (Info),
the <–> key and the <+> key.
Example: Press the <?> key.
• The OK key and ESC key are referred to without brackets;
their name is marked on the unit housing.
Example: Press the ESC key or: Acknowledge with OK.
• The "direct access" keys are referred to as such. These
keys have no names, either on the keys themselves, nor
on the housing. Example: Use the direct access key to go
to the next value.
• The same applies to the Page Up and Page Down keys.
Example: Go to the next dialog box using the Page Up
key.

8/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation About this manual 08.2002
2 Display and control
elements
2.1 Housing

1 2
00262

OK ESC

? – + Landis & Staefa


PXM20
PXM20

7 5 6
Figure 2-1 Housing
Key:
1. Display panel (Section 2.2)
2. Direct access keys (Section 2.1.3.1)
3. Alarm LED (Section 2.1.1)
4. Page Up & Page Down keys (Section 2.1.3.2)
5. OK key, <+> and <–> editing keys (Section 2.1.3.3)
6. ESC key (Section 2.1.3.4)
7. <?> key (Section 2.1.3.5)

2.1.1 Alarm LED

The alarm LED lights up or flashes when an alarm is tripped


in the system. As soon as all alarms have been
acknowledged, the LED stops flashing and remains on
continuously. For further information on alarm signals refer to
Section 5.
Exception The LED does not flash in response to an event.

9/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Display and control elements 08.2002
2.1.2 Audible signal

If the Buzzer is set to On under Settings (Section 3.2.4), an


incoming alarm will be accompanied by an audible alarm
signal.

2.1.3 Keys
2.1.3.1 Direct access keys

An arrowhead symbol at the end of a line indicates that you


can use the direct access key adjacent to that line to carry
out a number of actions:
The direct access keys have a dual function.
• Navigation:
Direct access to the view at the next level down.
Refer to Section 5 for detailed instructions on navigating
in the PXM20.
• Editing a value
Your user rights determine whether you can edit values,
or only read them. Refer to Section 6 for detailed
instructions on navigating in the PXM20.

2.1.3.2 Page Up and Page Down key

If there are several pages in one display, use the Page Up


and Page Down keys to change to the next or previous page.
In addition to the <+> and <–>keys you can use the Page Up
and Page Down keys to edit numerical values.

10/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Display and control elements 08.2002
2.1.3.3 The OK key and editing keys <+>and <–>

As soon as you access a value with the direct access key,


the value concerned begins to flash, indicating that it can be
edited with the <+> and <–> keys. Confirm each change by
pressing OK. In addition to the <+> and <–> keys you can
use the Page Up and Page Down keys to edit numerical
values.
The step-by-step procedure for editing is described in
Section 6.

2.1.3.4 The ESC key

By pressing the ESC key, you can cancel a current process


(e.g. the editing of a value) at any time, switch to the view at
the next higher level, or close a pop-up window..

Holding the ESC key down for more than 2 seconds ("Long
ESC") closes all the active pop-up windows.

2.1.3.5 The <?> key (Info key)

Info mode Pressing the <?> key once takes you into "Info" mode. A
question mark at the end of a line indicates that you can
display information about this line. To do this, press the
associated direct access key.

Pressing the <?> key again, displays a dialog box with


general information about the associated window.

11/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Display and control elements 08.2002
2.2 The display panel

All the elements of a plant are shown in the display, with


values or information which you can read or overwrite,
depending on your user rights. Figure 2-2 shows the layout
of the display. The next section describes the areas of the
display and the symbols used.

The keys used for navigation and editing are outside the
display panel, and set into the housing itself. These keys are
also described below in more detail.

Title line
Line of text

Working area
Button

Figure 2-2 Display layout

2.2.1 Title line

The current level within the tree structure is shown at the top
à
left in the display panel and is marked with an arrow . The
current page and the total number of pages is shown on the
right. The title line is separated from the rest of the display
with a horizontal line.

In the example above, you are in the Schedule exception


list dialog box, on page 1 of 1.

12/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Display and control elements 08.2002
2.2.2 Working area

Below the title line is the working area, which may contain
either several lines of alphanumerical text, or a graph.
Text lines A maximum of six lines of text can be displayed in the
working area. If there are more than this, the remaining lines
appear on the next page.

An ellipsis (…) indicates that the text is too long to fit on the
line.

To see the rest of the information, use the <?> key followed
by the direct access key.

Each line comprises the following elements from left to right:


• Symbol
• Values, alarms, events, entries, functions, hierarchical
elements etc.
• An arrowhead symbol, for values which you can edit.

Graphs Trends and heating curves are displayed in graph form.

Figure 2-3 Heating curve graph

13/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Display and control elements 08.2002
Buttons The "Button" field provides access to other functions or
dialog boxes; you can gain access to these by pressing the
associated direct access key. Buttons are always displayed
in upper case text in a box.

Pop-up A "pop-up" window is a dialog box used to display an alarm


or an event. The ALARM VIEWER button provides direct
access to the list of active alarms.

Figure 2-4 Pop-up

Dialog box A dialog box is displayed after an action, for example, a


dialog box will appear with a prompt which must be
acknowledged before the required action is carried out or
cancelled. Dialog boxes with the relevant information are
also displayed when you press the <?> key.

Figure 2-5 Dialog box with confirmation prompt

14/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Display and control elements 08.2002
2.2.3 Symbols

The following is a list of all the symbols used in the display,


and their meanings. The same symbol may represent
different entries, or have a different meaning, depending on
the context.

Symbols Description
Arrowhead symbol. Values on this line can be accessed
with the direct access key directly to the right of the line.
This line contains additional information about the
highlighted object. The information appears when you press
the Info key <?>. Refer also to Section 2.1.3.5.
Parameter
Input
Output
Calendar / Calendar entry
Forced control symbol

− Alarm for "Off Normal" or fault state; flashing indicates


unacknowledged alarm
1 Alarm viewer
2 Alarm & event history

Acknowledged alarm state

Alarm for "Normal" state; flashing indicates unacknowledged


state.

Normal state not reset

System event

Site

Hierarchical element

Device

Interface variable

15/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Display and control elements 08.2002
Symbols Description
Acknowledged alarm or event in Alarm & event history

Reset alarm or event in Alarm & event history

Alarming & functions

Trend

Logout

Edit user

Add new users

Delete user

Change password

Wiring test (commissioning and service engineers only)

1. Time schedules
2. Set date and time
Set daylight savings

Settings

Debug information (commissioning and service engineers


only)

Global objects. Contain data which is globally available


(within a given site, across controllers)

Favorites. These are defined in the engineering phase and


contain frequently interrogated elements with short-cuts for
operator access.

Page(s)

Page n of total n pages.

16/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Display and control elements 08.2002
3 Settings
To be able to carry out settings and modifications, you must
be in a site (see Section 4).

In the Site dialog box, select the entry Alarming &


functions.

Figure 3-1 Site overview

This is where you will find all the entries via which you can
modify settings in the system with your PXM20 operator unit.

Figure 3-2 Alarm list

17/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Settings 08.2002
3.1 System

Note You can only make system settings if a primary server has
been defined in the network.

3.1.1 Set date & time (system time)

The system time is always applicable to one site. To change


the system time, proceed as follows:
1. Select Set date & time.

2. Set the required time using the direct access key


adjacent to the numerical time display.
3. Confirm your input.

18/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Settings 08.2002
3.1.2 Set daylight savings

This option is used to define the requirements for an


automatic daylight savings time change.
1. Select Set daylight savings

2. You can start by accepting or rejecting the current


automatic summer time change.
3. You then define the date and time at which summer time
is to begin and end. The basic settings are the last
Sunday in March at 0200 hours for the start of summer
time and the last Sunday in October at 0300 hours for
the end of summer time.

19/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Settings 08.2002
3.2 PXM20 operator unit

Note The procedure for defining or modifying settings in the


PXM20 is always the same. It is therefore described here
once only. The same procedure applies to Sections 3.2.1 …
0.

1. Select Alarming & functions/Settings on the current


site.

2. Select the required entry; the value will start flashing.


3. Configure the value as required.
4. Confirm your entries.

20/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Settings 08.2002
3.2.1 Language

Select the language here. The basic setting is English.

3.2.2 Date & time format

Select either the American or the European date and time


format.

3.2.3 Contrast

The display contrast can be set here:

3.2.4 Buzzer

Use this option to specify whether or not alarms are to be


indicated with an audible signal. This is only possible,
however, provided that the alarms are displayed in pop-up
windows.

3.2.5 Alarm pop-up

Here, you can determine whether or not alarms and events


are to be displayed in an alarm pop-up window.

3.2.6 Alarm text mode

This allows you to specify how alarms and events are to be


displayed in the Alarm viewer and Alarm & event history.
1. If you select Message text, the text of notifications will
be displayed in the overview.
2. If you select Description, the generic description of the
object will be displayed.

21/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Settings 08.2002
3.2.7 Relogin

This setting enables you to specify that a user must log in


again after the display saver has been activated.

3.2.8 Display saver on

Use this option to specify the time period (5 – 60 mins in


5-minute increments) after which the display saver is to be
activated.

3.2.9 Main value

This setting lets you specify that when operating the plant,
the main value is to be displayed at the end of the line for the
object concerned.

3.2.10 Welcome window

Here you can define whether a "Welcome" window is to


appear when a user logs in.

3.2.11 3rd party site

Use this option to specify whether or not third-party devices


are to be operated with the PXM20.

22/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Settings 08.2002
3.2.12 Domain ID

Set the Domain ID for the PXM20 here.

Figure 3-3 Domain ID

Important This setting should be modified by fully qualified


personnel only.

3.2.13 Network scope

Specify here whether the PXM20 is to allow connections


beyond the LON network.

Important This setting should be modified by fully qualified


personnel only.

23/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Settings 08.2002
24/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Settings 08.2002
4 Login and logout
As soon as you connect the PXM20 operator unit to an
automation and control station or to a connection point in the
LON network, the "Start" window will appear in the display
panel.

Figure 4-1 "Start" window

Press the direct access key adjacent to START.

25/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Login and logout 08.2002
4.1 Connecting to the network

A connection is established with the network. The PXM20


starts by looking for an automation and control station
defined as the primary server.

The login procedure is in two steps:


1. Select a site.

If no sites are listed, this means that no automation and


control station in the network has been defined as the
primary server.

Use RESCAN NETWORK to scan all the devices in the


network. In this case, access to the system will be via an
automation and control station defined as the back-up
server.
Commissioning and service engineers can carry out a
wiring test with the WIRINGTEST option (see
Section 11)

26/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Login and logout 08.2002
4.2 Login

1. Log in to the selected site with your user name.

2. You will then be asked to enter your password.

3. Select the required letters, numbers or characters, using


the <+> key to enter them in the password field. These
inputs can be deleted using the <–> key.
Note Note that wildcard characters (*) are used to represent the
password in the password field. You can cancel password
entry at any time by pressing ESC.
4. Press OK to confirm the password entered.

Logging in to Before you can log in to a new site, you must first log out
another site from the current site (see the next section).

27/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Login and logout 08.2002
4.3 Logout

Note If you disconnect the PXM20 from the network without first
logging out, this can temporarily impair the performance of
the plant (e.g. by delaying the transfer of alarms). You
should therefore always log off properly as described
below.

1. Within the site, go to Alarming & functions.

2. Select Logout.
3. Confirm that you really do want to log out.
4. The site overview appears again (Figure 3-1 ).

28/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Login and logout 08.2002
5 Navigation
Tree structure The structure for navigating with the PXM20 operator unit is
displayed as a tree structure.

Down one level The arrowhead symbol at the end of a line indicates that you
can move to a dialog box at the next level down by pressing
the associated direct access key.

Up one level Press ESC to leave the current dialog box and move to a
dialog box at the next higher level.

Closing windows Press ESC to close pop-up windows or dialog boxes.

Moving from If there are several pages in one display, use the Page Up
page to page and Page Down keys to change to the next or previous page.
The total number of pages is shown in the top right corner of
the display:

29/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Navigation 08.2002
30/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Navigation 08.2002
6 Reading and editing
values
In order to edit values, you must have Write access rights. If
you only have Read access, you can view a value, but not
modify it.

In the example below, the values which you can edit are
indicated as follows:

Figure 6-1

Key:
Arrowhead The arrowhead symbol at the end of the first line in the
example indicates that you have the necessary Write
access rights to edit this value. Press the direct access key
to switch to edit mode. There is no arrowhead symbol
adjacent to any of the other values; this means that you
have no access to these values.

Direct To edit a value to which you have Write access, press the
access key direct access key adjacent to the line concerned.

31/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Reading and editing values 08.2002
Note As the procedure described below is applicable to all cases,
it is described once only, in order to keep this manual as
easy to read as possible. If you are required to edit a value
in any subsequent routines, the procedure referred to is the
one described here.

To keep the manual as clear as possible, the instruction


"Press the direct access key" is not repeated.
Example: "Select the month and the year".

When editing always proceed as follows:


1. Press the direct access key adjacent to the required line.
The first value to be edited will now start flashing.
(Optional: Repeated operation of the direct access key
allows you to jump from one input field to the next.)
2. Edit the required value with the <+> and <–> keys.
Numerical values can also be edited using the Page Up
and Page Down keys.
3. Acknowledge the changes you have made by pressing
the OK key.
4. You can also acknowledge an input by pressing the
direct access key itself.
5. If there are several values on one line, press the key
repeatedly until all the values stop flashing.

32/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Reading and editing values 08.2002
6.1.1 Example: Setting a setpoint

Navigate to the value that you want to edit. Set the required
value.

Figure 6-2 Setting a manual setpoint

6.1.2 Example: Modifying a heating curve

The heating curve is used to determine the flow temperature


setpoint for weather-compensated flow temperature control.

Two display There are two ways of setting the heating curve values using
formats the PXM20 operator unit. Either the main parameters can be
displayed in graph form, or all the parameters, inputs and
outputs can be displayed in list form.

Figure 6-3 Graphic view of heating curve

33/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Reading and editing values 08.2002
List view of Select LIST VIEW for access to a list of all parameters,
heating curve inputs and outputs.

Figure 6-4 Heating curve: list view, page 1

Figure 6-5 Heating curve: list view, page 2

Select GRAPHIC VIEW to return to the graph.

34/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Reading and editing values 08.2002
6.1.3 Forced control

"Forced control" refers to the process of setting inputs and


outputs manually to a given value.
The inputs and outputs are edited in the normal way. As
soon as you select the required value you will be prompted in
a dialog box to confirm that you want to force this value.

Figure 6-6 Prompt for acknowledgement of forced control

You can use the direct access key to cancel the forced
control in the dialog box again.

Forced control The forced control symbol is displayed after the input or
symbol output has been forced.

35/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Reading and editing values 08.2002
36/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Reading and editing values 08.2002
7 Alarms
7.1 Occurrence of alarms and
events

Signals Attention is drawn to the presence of alarms and events by


use of pop-up windows (Figure 7-1 ); in the case of alarms,
there is also an audible signal and the LED display starts
flashing. The use of pop-up windows and audible signals for
this purpose is optional and can be enabled in Settings
(Section 3.2.5).

Info in pop-up The main information on the current event is displayed in a


windows pop-up window:

Figure 7-1 Alarm pop-up with unacknowledged alarm

The display shows a time stamp, the object name, the


notification text and the alarm priority. In the case of alarm
messages, you can display the Alarm viewer directly (see
Section 7.2.1).

Symbols in an alarm pop-up window


Unacknowledged alarm

Alarm state acknowledged

Normal state; existing alarm unacknowledged

Normal state, unreset


(only used for Extended alarms. In such cases, reset
the alarm.)

System event

37/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Alarms 08.2002
Deleting a pop- Press ESC to delete a pop-up window without affecting the
up window alarm or event.

Canceling the An audible signal can also be cancelled by deleting the


audible signal associated pop-up window with ESC.

7.2 Alarm acknowledgement

All alarms still requiring acknowledgement are listed in the


Alarm viewer.

7.2.1 Displaying the Alarm viewer

Go to the Alarm viewer in the Alarming & Functions dialog


box..

Figure 7-2 Alarm viewer

The Alarm viewer displays all the most recently received


alarms.
Each line consists of an alarm symbol, the object name or
notification text, and the date and time.

Tracking the The Alarm viewer tracks the alarm state as follows: If the
alarm state alarm state changes (e.g. an alarm is acknowledged) the
associated entry also changes.

Note Note that for each object, only the current alarm, i.e. the last
alarm received, is displayed.

When a fault has been cleared and acknowledged the


relevant entry disappears from the list.

38/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Alarms 08.2002
7.2.2 Selecting an event or alarm

1. Select the alarm which you wish to acknowledge. The


Alarm message dialog box opens.
2. You can now select either ACKNOWLEDGE or
DETAILS.

Figure 7-3 Alarm message

The procedure for events is basically the same as for


alarms. Unlike alarms, however, you do not need to
acknowledge events.

Figure 7-4 Event message

39/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Alarms 08.2002
7.2.3 Alarm acknowledgement /
Alarm & event details

Use ACKNOWLEDGE to acknowledge the alarm. The


Alarm viewer dialog box will re-appear (Figure 7-2 ).

By selecting DETAILS you can switch to a dialog box which


provides more information about the object responsible for
triggering the alarm or event, and which displays the priority
of the alarm message.

Figure 7-5 Alarm details

Figure 7-6 Event details

40/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Alarms 08.2002
Extended alarm After acknowledgement, Extended alarms will also need to
be reset with the RESET option. You cannot do this until the
object has returned to normal.

Figure 7-7 Example of Extended alarm

After the reset, the display reverts to the Alarm viewer


dialog box.

7.3 Alarm & event history

Select Alarm & event history from the Alarming &


functions dialog box.

Figure 7-8 Alarm & event history

The Alarm & event history dialog box displays not only the
current alarm, but all alarms which have occurred in relation
to the selected object.
As with the Alarm viewer, a line consists of a symbol, the
object name and the date and time.
The following information is displayed for a maximum of 30
entries:

41/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Alarms 08.2002
3 All the most recently received alarms
4 The most recent alarm acknowledgements
5 The most recent events

Note Note that it is not possible to acknowledge or reset alarms in


the Alarm & Event history.

Unlike the Alarm viewer, the Alarm & event history only
logs incoming alarms, but does not update the entries with
any changes.

As with Alarm viewer, you can invoke an individual alarm or


event here, and view the details.

Symbols in the Alarm & event history

Unacknowledged alarm

Normal state; existing alarm unacknowledged

System event

Acknowledged

Reset

42/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Alarms 08.2002
8 Access rights
8.1 Introduction

There are seven user levels in the system. In the engineering


process, each user group is defined with the associated
Read and Write access rights (user level). Individual users
are then assigned to one of these user groups.

8.2 Password

When the plant is handed over, you will be informed about


which users have been set up, and notified of the associated
passwords. Users can then change their own passwords to
suit their own preferences. The procedure is as described in
Section 8.5.

8.3 Add new user

Members of a group are authorized to add new users to


groups at a lower hierarchical level.

1. Within the current site, go to Alarming & functions and


select User definition.
2. Select Add new user.

Figure 8-1 User definition

43/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Access rights 08.2002
3. You will be prompted in the next dialog box to enter the
user name:
Please enter the USERNAME.
Select the required characters and use the <+> key to
enter them in the field. Use the <–> key, if required, to
delete characters.
4. Acknowledge the user name with OK.
5. You will then be prompted to enter the password:
Please enter the PASSWORD
6. Enter the required password and confirm with OK. A list
of all the information describing the newly defined user
will now appear. You now have the option of modifying
or adding to the information or settings:

User Group
7. Select the required user group.
User visa
8. Select initials for the user you have defined.
User scope number
9. Scopes are not yet supported in Version 2.1.
10. Answer the prompt to save the new user entry:
SAVE USER
The display will revert to the User definition dialog box
(Figure 8-1 ).

44/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Access rights 08.2002
8.4 Remove user

To remove a user, proceed as follows:

Note You can only remove users at a lower level in the hierarchy.

1. In the current site, select Alarming & Functions (Figure


8-1 ).
2. Select Remove user. The next dialog box displays a list
of all the users which your access rights entitle you to
delete.

3. Select the user which you want to delete.


4. In the next pop-up window, confirm that you want to
delete this user.

8.5 Change password

To change your own password, proceed as follows:

1. In the current site, select Alarming & functions / User


definition (Figure 8-1 ).
2. Select Change password.
You will be prompted as follows:
Enter OLD password:
3. Enter your old password and confirm with OK.
The following prompt will then appear:
Enter NEW password:
4. Enter your new password and confirm with OK.
5. The change of password is confirmed in a pop-up
window.

45/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Access rights 08.2002
8.6 Edit user

Proceed as follows to change the data for a given user:

1. In the current site, select Alarming & functions / User


definition (Figure 8-1 ).
2. Select Edit user.
The next dialog box displays a list of all the users which
your access rights entitle you to modify or delete.
3. Select the user, for which you want to edit the data.
4. Make the required changes and confirm them by
selecting SAVE USER.

46/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Access rights 08.2002
9 Setting time schedules
The time schedules consists of a 7-day schedule and an
exception schedule. You can use the time schedules to
program the following:
− Time-dependent on/off switch control
and/or
− Time-dependent setpoint adjustment

In the 7-day schedule, you can define daily profiles which are
repeated week after week. In the exception schedule, you
define days which deviate from those defined in the 7-day
schedule.

The names and locations of these time schedules are


defined on a plant-specific basis. The following illustrations
are examples only.

9.1 7-day schedule

It is possible to define a particular profile for each day of the


week within the 7-day program.
1. Navigate to the required time schedule.

47/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Setting time schedules 08.2002
2. In this example, select Zeitschaltuhr Lüf… / Stufe 2
(Time switch Ventila… / Stage 2)

3. Use the direct access key to select the required day of


the week. The selected day is marked with a rectangle
(Monday in the example above).
A graphics-based display of the selected day appears
on the second line. You can select the individual
switching points with the associated direct access key.
The next line displays the values for the selected
switching point.

9.1.1 Editing the switching points

The exact time and the state which comprise the entry are
shown on the next line, and can be selected for editing.
Confirm your entry by pressing OK.

1. To change the schedule for this day, select CHANGE


PROGRAM.

Figure 9-1 24-hour profile

48/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Setting time schedules 08.2002
2. Move from one entry to the next within the 24-hour
schedule. The selected entry is marked by a small black
arrowhead above the 24-hour schedule.

9.1.1.1 Editing an existing entry

Edit existing entries in the normal way, using the associated


direct access keys (the procedure is described in Section 6).

9.1.1.2 Copy 24-hour profile

To copy a 24-hour profile to other days, navigate to the day


which is to be used as a template.
Then go to the line Day copy to and select the days to which
you want to copy the profile, acknowledging with OK for each
day.

9.1.1.3 New entry

To add an entry select NEW ENTRY and edit the new entry.

9.1.1.4 Delete entry

To delete an entry, first select the entry to be deleted, and


then select DELETE ENTRY.

49/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Setting time schedules 08.2002
9.2 Exception schedules

The exception schedule contains two kinds of exception:


• Exceptions which are stored locally in the time schedule
and apply only to that specific time schedule; these are
identifiable by the date information.
• Exceptions which are stored in a calendar object and
used by various time schedules. These are recognizable
by their names, e.g. holidays without date information.
Identification of exceptions in lists:
Symbol for an exception with a 24-hour profile and a date
period

There are two ways of invoking exceptions in a list:


• Via an individual day in the Exceptions overview (see
Section 9.2.1)
• Via the EXCEPTIONS button (see Section 9.2.2).

9.2.1 Listing the exceptions for a given day

In the 7-day schedule, navigate to the exceptions overview


via EXCEPTIONS OVERVIEW.

Figure 9-2 Exceptions overview

Select the month and the year from the top line. All the days
of the selected month will then be displayed. Days on which
exceptions are programmed appear on a black background.
50/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Setting time schedules 08.2002
Select the required day and confirm with OK. A list of all the
exceptions for the selected day is displayed. You can edit
this display directly.

Figure 9-3 Schedule exception list

9.2.2 Listing all the exceptions

Use the EXCEPTIONS button in the Exceptions overview


(Figure 9-2 ) to display a list of all the exceptions defined in
the selected time schedule. You can access these with the
associated direct access keys.

Figure 9-4 Schedule exception list

Wildcards You can use wildcards (*) to enter the date period. Note the
wildcards used in the illustration above.

51/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Setting time schedules 08.2002
9.2.3 Create new local exception

NEW LOCAL EXCEPTION allows you to create a standard


exception with the current date and add it to the Schedule
exception list (Figure 9-4 ). The next section describes how
to adapt this exception to your own particular needs.

9.2.4 Editing a local exception

From the Figure 9-4 and Figure 9-3 select a date entry. A
dialog box will appear (Figure 9-5 ), from which you can
select all the required editing functions.

Figure 9-5 Editing functions

Select CHANGE DATE to display the following dialog box:

Figure 9-6 Changing the date of an exception

Enter the required information and return to the editing


functions via SAVE & EXIT (Figure 9-5 ).

52/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Setting time schedules 08.2002
Select EDIT PROFILE for access to the 24-hour profile of an
exception. In this dialog box, you can select whether you
want to modify the program or to delete all entries.

Figure 9-7 Changing the profile of an exception

Select CHANGE PROGRAM to invoke the editing mode.


Select New entry to add a new line, in which you can specify
the required values. Modify the priority to suit your
requirements.

Warning The priority should only be modified by fully-qualified


personnel.

Select DELETE ALL ENTRIES. Acknowledge the data


protection prompt. All entries will be deleted from the system.

This button is used to delete the selected exception.

Use this button to revert to the Schedule exception list


(Figure 9-4 ).

53/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Setting time schedules 08.2002
9.2.5 Editing a calendar entry

Select a calendar object from the Schedule exception list.

Figure 9-8 Editing the calendar object

You can edit the date and profile as described in


Section 9.2.4.

54/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Setting time schedules 08.2002
10 Trend function and
trend settings
The PXM20 operator unit provides the user with five
channels for trend logging, enabling 5 data points to be
logged.
The same dialog is used for basic trend settings in all types
of trend view (refer to Section 10.3). This dialog box is
invoked when you set up a new data point (see Section
10.1). For channels which have already been set up, it can
also be invoked by selecting Alarming & functions / Online
Trend (see Section 10.1).
There are three separate ways of viewing the trend data:
6 Graphical view (Section 10.3.2)
7 Online graphical view (Section 10.3.3)
8 List (Section 10.3.4)

10.1 Setting up a new trend

Navigate to the data point for which you want to log a trend.
Display the "Info" pop-up window.

Figure 10-1 "Info" pop-up window

55/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Trend function and trend settings 08.2002
Use the LOG DATA POINT button to set up the required
trend. The dialog box with the trend settings opens (Figure
10-3 ). Section 10.3 describes how to set the trend
parameters and define the type of view required.

The data point is automatically assigned to the first free


channel.

10.2 Displaying an existing trend

Select the required channel via Alarming & functions /


Online trend. The flashing symbol indicates that trend
logging is in progress.

Figure 10-2 Overview of active trend logging and spare channels.

Select the required channel. The main dialog box for the
trend channel will appear (Figure 10-3 ). From here, you can
view graphs and edit parameters.
The next section describes how to set the trend parameters
and define the type of view required.

This button allows you to stop all trend logging and delete all
configured trend charts.

56/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Trend function and trend settings 08.2002
10.3 Main trenddialog box

The main trend dialog box gives you access to the Trend
configuration dialog box and to the various trend data
views.

Figure 10-3 Setting trend parameters and defining the view

RELEASE CHANNEL stops trend logging and deletes the


trend configuration.

10.3.1 Trend configuration

In the main trend dialog box (Figure 10-3 ) select Trend


configuration. You can now modify the parameters for the
required trend logging.

Figure 10-4 Trend configuration, Pages 1 and 2

57/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Trend function and trend settings 08.2002
The individual parameters have the following meanings:

Log Enable On/Off


Start time Here, you should define the length of time over which the
Stop time trend values are to be logged.
Logging interval Enter the sampling rate (logging interval) in days, hours,
minutes and seconds.
A logging interval of 0 results in COV logging (Change of
Value).
Stop when full Define here what should happen to the trend logging when
the memory is full.
If you select No, the first values will be overwritten by new
values. With Yes, trend logging will stop.
Buffer size Number of values that can be stored
Clear record buffer Delete all logged values
Record count Number of sampled values in the current trend log
Total record count Total number of logged values

SAVE TREND SETTINGS lets you save your inputs, after


which the PXM20 will start logging these values. The display
reverts to the main dialog box.

Note The flashing symbol at the beginning of the line in the


Online Trend dialog box indicates that trend logging is
actually running. If Log enable is set to On, but the symbol
is not flashing despite this, you should check your settings
(start time, stop time and referenced data point).

You can display the trend data in three different views, as


described in the next section.

58/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Trend function and trend settings 08.2002
10.3.2 Graphic view

The Graphic view displays a graph of all the values in the


PXM20 for the logged data point.

Note The graph which is displayed represents the past. To view


the values in real time, select Graphic view online (Section
10.3.3).

Before displaying the sampled values in a graph, you can


adapt their display in Graphic view to your requirements, by
modifying the following parameters in the Trend
configuration dialog box (Figure 10-3 ).

Figure 10-5 Parameters for the Graphic view

The two parameters Graphic start time and Graphic stop


time can be used to reduce the display window to a time-
window of particular relevance to you. As default values for
the Graphic start time and Graphic stop time, enter the
start and end of logging.
Use Compare with channel to compare the selected trend
with another trend you have set up (see Figure 10-9 ).

59/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Trend function and trend settings 08.2002
Select GRAPHIC to confirm your settings and display the
trend.

Figure 10-6 Graphic view with a single channel

Figure 10-7 Graphic view with two channels

Setting guides A guide line can be set and moved by use of the <+> and
<-> keys. The data display is also refreshed.

60/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Trend function and trend settings 08.2002
10.3.3 Graphic view online

The Graphic view online displays the required value


dynamically, i.e. in real time.

Note To view all the values so far stored in the PXM20, select
Graphic view (Section 10.3.2).

Here, you can define the duration and the high and low
range limits for the value.

Figure 10-8 Settings in the Graphic view.

Under Record time you can define the period of time over
which you want to this dynamic trend to be displayed.
Low limit and High limit represent the upper and lower
limits for the value range to be displayed.

The trend is displayed soon as you confirm your entries via


GRAPHIC.
You can reset the graphic display by pressing OK.

Figure 10-9 Online trend display

61/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Trend function and trend settings 08.2002
Setting guides A guide line can be set and moved by use of the <+> and
<-> keys. The value corresponding to the guide line is also
displayed.

10.3.4 List view

Instead of displaying the logged values in graph form, you


can view them in list form.

Figure 10-10 List view of trend values

62/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Trend function and trend settings 08.2002
11 Service support
11.1 Wiring test

Note The wiring test must be carried out only by service and
commissioning engineers when commissioning the system.

Prerequisite The automation and control station which is the subject of


the test must not be integrated into a site and must not be
loaded with application software.

Procedure A. No site exists yet, i.e. no program has yet been loaded
by an automation and control station.
– Start the PXM20 operator unit and select Wiring
test from the dialog box.
B. A site already exists and you want to extend the network
by one automation and station:
– Log in to the required site.
– Go to Alarming & functions and choose Wiring
test.

Figure 11-1 Instruction to press the Service pin.

– Follow the instructions in the display, and press the


service pin of the required automation and control
station.

63/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Service support 08.2002
00242

Position of
service pin Lithium battery

Service pin

Figure 11-2 Position of service pin in a


PX compact automation station
00256

Service pin

COM1 COM2

RUN STA ERR TX SERVICE TX SERVICE

Figure 11-3 Position of the service pin in a


PX modular automation station

The wiring test is complete.

List of all inputs For your information, the PXM20 operator unit displays a list
and outputs of all inputs and outputs of the tested automation and control
stations, grouped according to signal type (analog, binary or
multi-state, see Figure 11-4 .

Module No.

Signal:
AI= analog input
AO= analog output
BI= binary input
etc.

Figure 11-4 List of analog signals

From here you can select the various inputs and outputs and
also display further information.

64/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Service support 08.2002
11.2 Debug information

Debug information is helpful for troubleshooting, and is


intended exclusively for development engineers. The latest
entries are always displayed at the end of the list.

Note The time entry is only valid once a PXC automation and
control station has been identified.

Select Debug information from the Alarming & functions


dialog box.

Figure 11-5

This dialog box contains the following information:


Error category Error category (letter at the beginning of the line):
I: Information E Error
F: Fatal error B: Reboot

Message text The following is an example of message text:


PXM20 application started

Address in This address indicates where the error occurred. This


the program information can be useful for troubleshooting.
Example:
Addr: 0x8C6434

Time of The time at which the error occurred. The format is as


occurrence follows:
Day, month, minute, second and millisecond since
01.01.1970 00:00.
Example:
11801 DAYS 09:25:06.000
65/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Service support 08.2002
66/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Service support 08.2002
Index
<?> key ........................................................................................... 8
<?> key ......................................................................................... 11
24-hour schedule........................................................................... 49
Edit entry ................................................................................... 48
7-day schedule .............................................................................. 47
Day copy ................................................................................... 49
DELETE ENTRY ....................................................................... 49
NEW ENTRY............................................................................. 49
Access rights................................................................................. 43
Adjust setpoint............................................................................... 47
Alarm
ACKNOWLEDGE ................................................................ 39, 40
Acknowledgement ..................................................................... 38
Audible signal ............................................................................ 10
DETAILS ............................................................................. 39, 40
RESET ...................................................................................... 41
Select ........................................................................................ 39
Alarm & event history .................................................................... 41
Alarm LED....................................................................................... 9
Alarm pop-up........................................................................... 21, 37
Alarm text mode ............................................................................ 21
Alarm viewer ................................................................................. 38
Alarming & functions...................................................................... 17
Alarms........................................................................................... 37
Audible signal.................................................................... 10, 21, 37
BACK TO EXCEPTION LIST......................................................... 53
Buzzer..................................................................................... 10, 21
Cancel audible signal .................................................................... 38
CHANGE DATE ............................................................................ 52
CHANGE PROGRAM.................................................................... 48
Contrast ........................................................................................ 21
Date format ................................................................................... 21
Day copy ....................................................................................... 49
Debug information ......................................................................... 65
Address in the program ............................................................. 65
Error category............................................................................ 65
Message text ............................................................................. 65

67/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Index 08.2002
Time of error.............................................................................. 65
Dialog box ..................................................................................... 14
Direct access keys .................................................................... 8, 10
Display .......................................................................................... 12
Buttons...................................................................................... 14
Dialog box ................................................................................. 14
Graphs ...................................................................................... 13
Pop-up ...................................................................................... 14
Symbols .................................................................................... 15
Title line..................................................................................... 12
Working area ............................................................................. 13
Display format
Graph ........................................................................................ 33
List view .................................................................................... 34
Display saver................................................................................. 22
Domain ID ..................................................................................... 23
Edit keys ......................................................................................... 8
Edit profile
CHANGE PROGRAM................................................................ 53
DELETE ALL ENTRIES............................................................. 53
EDIT PROFILE.............................................................................. 53
Editing procedure .......................................................................... 32
Editing the switching points ........................................................... 48
Entry
Delete........................................................................................ 49
New........................................................................................... 49
ESC key .................................................................................... 8, 11
Event
DETAILS ............................................................................. 39, 40
Events ........................................................................................... 37
Select ........................................................................................ 39
Exception schedule ....................................................................... 50
EXCEPTIONS OVERVIEW ....................................................... 50
Schedule exception list.............................................................. 51
EXCEPTIONS ............................................................................... 51
EXCEPTIONS OVERVIEW ........................................................... 50
Extended alarm ............................................................................. 41
FORCE ......................................................................................... 35
GRAPHIC................................................................................ 60, 61

68/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Index 08.2002
GRAPHIC VIEW............................................................................ 33
Graphic view online ....................................................................... 61
Guide line ...................................................................................... 62
Heating curve ................................................................................ 33
LIST VIEW ................................................................................ 34
Housing........................................................................................... 9
Info mode ...................................................................................... 11
Keys
Direct access............................................................................. 10
Edit keys.................................................................................... 11
ESC........................................................................................... 11
Info ............................................................................................ 11
OK............................................................................................. 11
Page Down................................................................................ 10
Page Up .................................................................................... 10
Printing convention ...................................................................... 8
Language ...................................................................................... 21
LED........................................................................................... 9, 37
LIST VIEW
Heating curve ............................................................................ 34
List view, online trend .................................................................... 62
LOG DATA POINT ........................................................................ 56
Login ............................................................................................. 27
START ...................................................................................... 25
Login and logout............................................................................ 26
Logout ........................................................................................... 28
Main value..................................................................................... 22
Navigating ..................................................................................... 29
Network ......................................................................................... 26
Network scope .............................................................................. 23
NEW LOCAL EXCEPTION............................................................ 52
OK key ...................................................................................... 8, 11
Online trend
GRAPHIC.................................................................................. 61
Guide line .................................................................................. 62
Online Trend ........................................................................... 55, 59
OnlineTrend
List view .................................................................................... 62
Page Down key ......................................................................... 8, 10

69/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Index 08.2002
Page Up key.............................................................................. 8, 10
Password ................................................................................ 27, 43
change ...................................................................................... 45
Input .......................................................................................... 27
Pop-up .............................................................................. 14, 21, 37
Pop-up window
Delete........................................................................................ 38
Printing conventions ........................................................................ 8
Read access ................................................................................. 43
RELEASE ALL CHANNELS .......................................................... 56
RELEASE CHANNEL.................................................................... 57
Relogin.......................................................................................... 22
RESCAN NETWORK .................................................................... 26
RESET .......................................................................................... 41
SAVE TREND SETTINGS............................................................. 58
SAVE USER.................................................................................. 45
Schedule exception list.................................................................. 51
BACK TO EXCEPTION LIST..................................................... 53
CHANGE DATE ........................................................................ 52
DELETE ENTRY ....................................................................... 53
Edit calendar obect.................................................................... 54
EDIT PROFILE.......................................................................... 53
NEW LOCAL EXCEPTION........................................................ 51
Service pin .............................................................................. 63, 64
Set date......................................................................................... 18
Set date & time.............................................................................. 18
Set daylight savings ...................................................................... 19
Setting a setpoint........................................................................... 33
Setting values
heating curve............................................................................. 33
Settings ......................................................................................... 17
PXM20 ...................................................................................... 20
System ...................................................................................... 18
START .......................................................................................... 25
Symbols ........................................................................................ 15
acknowledged ........................................................................... 42
Acknowledged alarm ................................................................. 15
Add new user ...................................................................... 16, 43
Alarm acknowledged ........................................................... 16, 37

70/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Index 08.2002
Alarm fault state ........................................................................ 15
Alarm Normal ............................................................................ 37
Alarm Normal state.................................................................... 15
Alarm Off Normal....................................................................... 15
Alarm reset................................................................................ 16
Alarming & functions.................................................................. 16
Arrowhead ................................................................................. 15
Calendar / Calendar entry.......................................................... 15
Change password...................................................................... 16
Debug information ..................................................................... 16
Delete user................................................................................ 16
Device ....................................................................................... 15
Edit user.................................................................................... 16
Event acknowledged ................................................................. 16
Event reset ................................................................................ 16
Extended alarm ......................................................................... 37
Favorites ................................................................................... 16
Forced control ..................................................................... 15, 35
Global objects............................................................................ 16
Hierarchical element.................................................................. 15
Information ................................................................................ 15
Input .......................................................................................... 15
Interface variable....................................................................... 15
Logout ....................................................................................... 16
Output ....................................................................................... 15
Override .................................................................................... 15
Parameter ................................................................................. 15
reset .......................................................................................... 42
Schedule ................................................................................... 16
Set date & time.......................................................................... 16
Set daylight savings............................................................. 16, 19
Settings ..................................................................................... 16
Site............................................................................................ 15
System event ...................................................................... 15, 37
Trend......................................................................................... 16
unacknowledged alarm.............................................................. 37
Wiring test ................................................................................. 16
System time .................................................................................. 18
Third-party site .............................................................................. 22

71/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Index 08.2002
Time
Summer time ............................................................................. 19
Time format ................................................................................... 21
Time schedules ............................................................................. 47
CHANGE PROGRAM................................................................ 48
DELETE ENTRY ....................................................................... 49
NEW ENTRY............................................................................. 49
Title line......................................................................................... 12
Tracking the alarm state ................................................................ 38
Tree structure................................................................................ 29
Trend
Buffer size ................................................................................. 58
Clear record buffer .................................................................... 58
Compare with channel............................................................... 59
Configuring the online view........................................................ 61
display....................................................................................... 56
Function & settings .................................................................... 55
GRAPHIC.................................................................................. 60
Graphic start time ...................................................................... 59
Graphic view.............................................................................. 59
Graphic view online ................................................................... 61
Guide line .................................................................................. 61
Log data point ........................................................................... 55
LOG DATA POINT .................................................................... 56
Log Enable ................................................................................ 58
Logging interval ......................................................................... 58
Main dialog box ......................................................................... 57
Memory limits ............................................................................ 58
Record count............................................................................. 58
RELEASE ALL CHANNELS ...................................................... 56
RELEASE CHANNEL................................................................ 57
SAVE TREND SETTINGS......................................................... 58
Start time................................................................................... 58
Stop time ................................................................................... 58
Total record count ..................................................................... 58
Views ........................................................................................ 55
Trend configuration ....................................................................... 57
User
edit user .................................................................................... 46

72/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Index 08.2002
remove user .............................................................................. 45
User definition ............................................................................... 43
User groups................................................................................... 43
Values
Forced control ........................................................................... 35
Reading and writing................................................................... 31
Welcome window .......................................................................... 22
Wildcards ...................................................................................... 27
Wiring test ..................................................................................... 63
List of inputs and outputs........................................................... 64
WIRING TEST............................................................................... 26
Working area................................................................................. 13
Write access.................................................................................. 43

73/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Index 08.2002
74/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation Index 08.2002
75/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Siemens Building Automation 08.2002
Siemens Building Technologies Ltd.
Siemens Building Automation
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41-724 24 24
Fax +41 41-724 35 22 © 2002 Siemens Building Technologies Ltd.
www.landisstaefa.com Subject to change
76/76

Siemens Building Technologies PXM20 operator unit CA1U9231en


Building Automation 08.2002

You might also like