MX Fire Alarm Fault Finding 1
MX Fire Alarm Fault Finding 1
MX Fire Alarm Fault Finding 1
PUBLICATION: 17A-04-FF4
ISSUE No. & DATE: 1 9/03
The states monitored are the RAM and the firmware checksum.
Assigned Group 104 - Gen. Purpose Fault I/P
PAGE 2 of 16
EQUIPMENT:
MX
17A-04-FF4
PUBLICATION:
1 9/03
ISSUE No. & DATE:
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-FF4
1 9/03
PAGE 4 of 16
EQUIPMENT:
MX
17A-04-FF4
PUBLICATION:
1 9/03
ISSUE No. & DATE:
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-FF4
1 9/03
Note:
1) This section refers to faults reported from a node, not the higher level monitoring which detects presence of
absence of complete nodes.
2) Some personalities will not have some of these faults configured.
PAGE 6 of 16
EQUIPMENT:
MX
17A-04-FF4
PUBLICATION:
1 9/03
ISSUE No. & DATE:
Note:
1) This section refers to faults regarding presence or absence of complete nodes, It is NOT an indication of
faults held by the node but the node itself.
2) This set of points are exceptions to the normal address where the first point address is ‘One’ instead here
as the RBUS units can be addressed from 0-15 the first address is ‘Zero’
Note: This section refers to faults assigned to the network card. The configuration is controlled by the use of the
options in the ‘Network Card’ dialog within Consys
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-FF4
1 9/03
PAGE 8 of 16
EQUIPMENT:
MX
17A-04-FF4
PUBLICATION:
1 9/03
ISSUE No. & DATE:
Note: This section refers to faults regarding presence or absence of panel nodes
Note: This section refers a fault regarding presence of absence of a printer connected to COM1
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-FF4
1 9/03
Note: This section refers to faults regarding COM2 which is the configuration or MX remote port.
Note: This section refers to faults regarding COM3 which is used to connect to the network card
PAGE 10 of 16
EQUIPMENT:
MX
17A-04-FF4
PUBLICATION:
1 9/03
ISSUE No. & DATE:
Loop Shutdown This fault is raised on the loop pseudo point 136
if the loop is shutdown. LOOP FAULT SHUTDOWN
Device Fault Used on the MX Digital loop driver for non- 143
specific faults. The device is present and DEVICE FAULT
replying, but the reply indicates a device
error. This is the catchall where a more
meaningful fault can not be raised.
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-FF4
1 9/03
Low Long Term Average This fault is currently valid for the 8xxI and 145
8xxPH/PHEx, 801F/FEx devices. LO L.TERM AVG FAULT
It indicates the device is dirty and requires
changing.
High Long Term Average This fault is valid for 8xxI and 8xxPH/ 146
PHEx devices and indicates the device is HI T.TERM AVG FAULT
dirty and requires changing.
Loop Short Circuit Raised on the loop pseudo point if the AVR 148
processor detects higher than expected loop LOOP S/C FAULT
current.
Power Open Circuit This fault is used for the BDM800 and will 151
be raised if the device detects a supply open POWER WIRING OPEN
circuit.
Power Short Circuit This fault is used for the BDM800 and will 184
be raised if the device detects a supply short POWER WIRING SHORT
circuit.
Contact Open Circuit Raised on the MIM800 and SIO800 devices 185
if the supervised input is open. CONTACT WIRING OPEN
Contact Short Circuit Raised on the MIM800 and SIO800 devices 186
if the supervised input is shorted. CONTACT WIRING SHRT
PAGE 12 of 16
EQUIPMENT:
MX
17A-04-FF4
PUBLICATION:
1 9/03
ISSUE No. & DATE:
Sounder Open Circuit Used to report faults on the LPS800 and 159
SNM800 if the supervised output is open. SOUNDER LINE OPEN
Sounder Short Circuit Used to report faults on the LPS800 and 187
SNM800 if the supervised output is shorted. SOUNDER LINE SHORT
Relay Coil Fault Used for fault reporting on the two sounder 160
circuits and the alarm relay on the FIM. RELAY COIL FAULT
Wiring Fault - Short Circuit This fault applies to CIM800, DIM800, 161
DIO800, GAR800, GARA800 and WIRING S/C FAULT
BDM800 devices and indicates the
supervised input is shorted.
Wiring Fault - Open Circuit As above, indicating the supervised input is 162
open. WIRING O/C FAULT
System Release Line Short Used by the LAV800, it indicates the 202
Circuit supervised output is shorted. RELEASE LINE SHORT
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-FF4
1 9/03
System Release Line Open Used by the LAV800, it indicates the 201
circuit supervised output is open. RELEASE LINE OPEN
System Release Line Stuck Used by the LAV800. It indicates the relay 203
cannot switch to the state which is required RELEASE RELAY STUCK
by the firmware.
PAGE 14 of 16
EQUIPMENT:
MX
17A-04-FF4
PUBLICATION:
1 9/03
ISSUE No. & DATE:
Fault with supervised input If the supervised input on the FIM becomes 143
faulty. DEVICE FAULT
Lost External Power Supply Reported by the DIM if it has problems with 326
its external power source. EXT PSU LOST
Invalid character set Raised by the panel if the OCM does not 386
contain a character set chip which supports WRONG CHAR SET CHIP
the codepage the panel wishes to use.
System Extinguishing Fault The control line used to control or monitor 388
extinguishing equipment is in fault. SYS EXTINGUISH. FLT
Loop Loading Fault The load on the loop has passed a threshold. 389
The loop is still working but the system may LOOP LOADING FAULT
not have the current to handle further large
scale point activations.
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-FF4
1 9/03
Polling Error This fault is linked to the ‘Late Poll’ fault 421
described above. POLLING ERROR
The background monitor also scans the last
poll time of all points. If a point has not
been polled within a time window this fault
is raised.
It is not expected this fault will ever be
announced, it is a required background
process for approvals.
Window Fault The S271I+ and S271F+ devices can 433
monitor the state of their ‘window’. If this WINDOW FAULT
is found to be dirty and requires cleaning,
this fault is raised.
It is expected that dealing with this fault
will not require Tyco level service and can
be handled by the end user.