Simplex Installation Instructions TrueAlert Power Supply
Simplex Installation Instructions TrueAlert Power Supply
The TrueAlert power supplies are identical to each other with the following exceptions:
If you are wiring Class A circuits, you need to install a 4100-5124 Class A Adapter Card onto the
TrueAlert Power Supply before installing the power supply. Refer to Document # 579-337 for
more information.
This product is compatible with the 4100U and 4100ES Fire Alarm Control Panel (FACP).
READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation manual.
These instructions must be followed to avoid damage to this product and associated equipment.
Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED- Upon unpacking
your Simplex product, inspect the contents of the carton for shipping damage. If damage is
apparent, immediately file a claim with the carrier and notify an authorized Simplex product
supplier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments
or repairs. All repairs should be performed by a representative or authorized agent of your local
Simplex product supplier.
EYE SAFETY HAZARD - Under certain fiber optic application conditions, the optical output of
this device may exceed eye safety limits. Do not use magnification (such as a microscope or other
focusing equipment) when viewing the output of this device.
FCC RULES AND REGULATIONS – PART 15 - This equipment has been tested and found
to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment
in a residential area is likely to cause harmful interference in which case the user will be required
to correct the interference at his own expense.
2
Introduction to the TPS
Three Signaling Line Circuits. The TPS provides uninterruptible power and control to three
separate channels of TrueAlert addressable notification appliances. Each channel is referred to as
a Signaling Line Circuit (SLC) and is power limited, power limited is defined in NFPA 70
(National Electric Code). The SLCs can be either Class B (Style 4) or Class A (Style 6). Class A
requires the installation of a Class A adapter board. All SLCs are monitored for short and open
circuits.
24VDC AUX Power. Provides up to 2 A of 24 VDC auxiliary power for use by the
option cards.
Battery
Trouble Scroll Terminals
Push Button
DIP Switches
LEDs 1, 2, and 3. SW1 to SW8
Each Corresponds
to an SLC
Earth Fault
LEDs AUX Power Jumper
A to E
3
Introduction to the TPS, Continued
Additional Features Full TrueAlert Operation. TrueAlert addressable notification appliances are individually
addressed and receive power, supervision, and control signals over the SLC. Horns sound with
selectable high or low output, using a temporal, march time (60 or 120 beats per minute), or
continuous pattern. Horns are controlled separately from visible appliances installed on the same
two-wire circuit. (Combination speaker/strobe TrueAlert appliances receive audible control from
separate audio circuit wiring.)
Extensive Diagnostic Capabilities. LEDs on the TPS flash codes that identify the nature of
trouble conditions. The TPS also monitors for short and open circuits and positive and negative
Earth fault status.
Depleted Battery Cutout (Canadian Version Only). When AC Power fails, the Depleted
Battery Cutout feature disconnects a battery from the panel when its voltage is approximately
18 VDC.
Visual Synchronization. A maximum of 46 MultiCandela addressable visuals may be
synchronized per SLC. All SLCs are synchronized across a TPS. All TPSs are synchronized
across the FACP.
Input/Output/Battery The following table summarizes the AC Input, DC Output, and Battery Charger specifications of
Specifications the TPS.
Table 1. AC Input, DC Output, Battery Charger Specifications
AC Input Specifications
4 A Maximum
4100-5120/5121
120 VAC @ 60 Hz
2 A Maximum
4100-5122
220/230/240 VAC @ 50 or 60 Hz
DC Output Specifications
Minimum: 19 VDC
Aux Power and
Maximum: 32 VDC
Each SLC
Ripple: 2 VDC, peak to peak @ full load (9A)
Battery Charger Specifications
Input Voltage
21-33 VDC
Range
27.4 VDC ± 500 mV @ 68° F (20° C), temperature compensated
Output Voltage
at –24 mV / deg. C
High Voltage
29.1 V @ 3.3 A
Output
1.4 A (For 6.2 –18 Ah battery)
Output Current
Limit 3.3 A (Default for 18-50 Ah battery [Canada]; 18-110 Ah battery
[United States])
4
Introduction to the TPS, Continued
TPS Current Table 2 lists the battery standby requirements for the TPS. The voltage is 24 VDC, which is the rated
Consumption battery voltage for lead-acid type batteries.
Table 2. Battery Standby
Conditions Current
Standby – no alarms, SLCs normal 88 mA
Standby – 3 SLCs ON 100 mA
Class A option (Standby or Alarm) 10 mA
Environmental The TPS operates normally within the following temperature range: 32° F (0° C) and 120° F (49° C).
Requirements
Humidity: 90°F (32° C) degrees at 93% Relative Humidity (non-condensing).
Note: Add auxiliary and card power currents to standby current. For each TrueAlert appliance, add
0.2 mA standby current. The maximum auxiliary current is 2A. The maximum card power is 2A.
Deduct card power and auxiliary currents from 9A total power supply capacity.
5
Mounting
Overview The TPS mounts onto the right side of an expansion box, and connects to the Power Distribution
Interface (PDI).
Mounting Procedure 1. Slide the two tabs on the bottom of the TPS into the rightmost two slots on the expansion bay.
2. Push the TPS assembly against the back of the expansion bay.
3. Use two #6 torx screws to secure the assembly to the expansion bay.
6
Configuring the TPS
Setting Earth Fault The Earth Fault Enable/Disable jumper allows you to enable or disable positive and negative Earth
Enable/Disable Fault detection.
Jumper
Place the jumper block on Pins 1 and 2 to enable Earth fault detection. Place the jumper block on
Pins 2 and 3 to disable Earth fault detection. See below.
FigureTag FD9-336-01
3
3 22 11 33 22 11
Disabled Enabled
Note: When one or more TPS unit resides in a system sharing a common “0V” with any other type
power supply (SPS/RPS/XPS), jumper only one of the TPS units to enable Earth Fault
Detection. All other power supplies must be jumpered to disable Earth Fault Detection.
Ensure that the Slave Exec firmware, later than Revision 1.04, is loaded on this TPS.
Setting Address The TPS device address is set via DIP switch SW1, which is a bank of eight switches. From left to
Switch right (see figure below), these switches are designated as SW1-1 through SW1-8. The function of
these switches is as follows:
SW1-1. This switch sets the baud rate for the internal FACP communications line running between
the card and the FACP CPU. Set this switch to ON.
SW1-2 through SW1-8. These switches set the card’s address within the FACP.
Note: You must set these switches to the value assigned to the card by the Programmer.
ON
OFF
1 2 3 4 5 6 7 8
7
Configuring the TPS, Continued
Setting Address
Switch
Table 3. Card Addresses
Address SW 1-2 SW 1-3 SW 1-4 SW 1-5 SW 1-6 SW 1-7 SW 1-8 Address SW 1-2 SW 1-3 SW 1-4 SW 1-5 SW 1-6 SW 1-7 SW 1-8
1 ON ON ON ON ON ON OFF 61 ON OFF OFF OFF OFF ON OFF
2 ON ON ON ON ON OFF ON 62 ON OFF OFF OFF OFF OFF ON
3 ON ON ON ON ON OFF OFF 63 ON OFF OFF OFF OFF OFF OFF
4 ON ON ON ON OFF ON ON 64 OFF ON ON ON ON ON ON
5 ON ON ON ON OFF ON OFF 65 OFF ON ON ON ON ON OFF
6 ON ON ON ON OFF OFF ON 66 OFF ON ON ON ON OFF ON
7 ON ON ON ON OFF OFF OFF 67 OFF ON ON ON ON OFF OFF
8 ON ON ON OFF ON ON ON 68 OFF ON ON ON OFF ON ON
9 ON ON ON OFF ON ON OFF 69 OFF ON ON ON OFF ON OFF
10 ON ON ON OFF ON OFF ON 70 OFF ON ON ON OFF OFF ON
11 ON ON ON OFF ON OFF OFF 71 OFF ON ON ON OFF OFF OFF
12 ON ON ON OFF OFF ON ON 72 OFF ON ON OFF ON ON ON
13 ON ON ON OFF OFF ON OFF 73 OFF ON ON OFF ON ON OFF
14 ON ON ON OFF OFF OFF ON 74 OFF ON ON OFF ON OFF ON
15 ON ON ON OFF OFF OFF OFF 75 OFF ON ON OFF ON OFF OFF
16 ON ON OFF ON ON ON ON 76 OFF ON ON OFF OFF ON ON
17 ON ON OFF ON ON ON OFF 77 OFF ON ON OFF OFF ON OFF
18 ON ON OFF ON ON OFF ON 78 OFF ON ON OFF OFF OFF ON
19 ON ON OFF ON ON OFF OFF 79 OFF ON ON OFF OFF OFF OFF
20 ON ON OFF ON OFF ON ON 80 OFF ON OFF ON ON ON ON
21 ON ON OFF ON OFF ON OFF 81 OFF ON OFF ON ON ON OFF
22 ON ON OFF ON OFF OFF ON 82 OFF ON OFF ON ON OFF ON
23 ON ON OFF ON OFF OFF OFF 83 OFF ON OFF ON ON OFF OFF
24 ON ON OFF OFF ON ON ON 84 OFF ON OFF ON OFF ON ON
25 ON ON OFF OFF ON ON OFF 85 OFF ON OFF ON OFF ON OFF
26 ON ON OFF OFF ON OFF ON 86 OFF ON OFF ON OFF OFF ON
27 ON ON OFF OFF ON OFF OFF 87 OFF ON OFF ON OFF OFF OFF
28 ON ON OFF OFF OFF ON ON 88 OFF ON OFF OFF ON ON ON
29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF
30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON
31 ON ON OFF OFF OFF OFF OFF 91 OFF ON OFF OFF ON OFF OFF
32 ON OFF ON ON ON ON ON 92 OFF ON OFF OFF OFF ON ON
33 ON OFF ON ON ON ON OFF 93 OFF ON OFF OFF OFF ON OFF
34 ON OFF ON ON ON OFF ON 94 OFF ON OFF OFF OFF OFF ON
35 ON OFF ON ON ON OFF OFF 95 OFF ON OFF OFF OFF OFF OFF
36 ON OFF ON ON OFF ON ON 96 OFF OFF ON ON ON ON ON
37 ON OFF ON ON OFF ON OFF 97 OFF OFF ON ON ON ON OFF
38 ON OFF ON ON OFF OFF ON 98 OFF OFF ON ON ON OFF ON
39 ON OFF ON ON OFF OFF OFF 99 OFF OFF ON ON ON OFF OFF
40 ON OFF ON OFF ON ON ON 100 OFF OFF ON ON OFF ON ON
41 ON OFF ON OFF ON ON OFF 101 OFF OFF ON ON OFF ON OFF
42 ON OFF ON OFF ON OFF ON 102 OFF OFF ON ON OFF OFF ON
43 ON OFF ON OFF ON OFF OFF 103 OFF OFF ON ON OFF OFF OFF
44 ON OFF ON OFF OFF ON ON 104 OFF OFF ON OFF ON ON ON
45 ON OFF ON OFF OFF ON OFF 105 OFF OFF ON OFF ON ON OFF
46 ON OFF ON OFF OFF OFF ON 106 OFF OFF ON OFF ON OFF ON
47 ON OFF ON OFF OFF OFF OFF 107 OFF OFF ON OFF ON OFF OFF
48 ON OFF OFF ON ON ON ON 108 OFF OFF ON OFF OFF ON ON
49 ON OFF OFF ON ON ON OFF 109 OFF OFF ON OFF OFF ON OFF
50 ON OFF OFF ON ON OFF ON 110 OFF OFF ON OFF OFF OFF ON
51 ON OFF OFF ON ON OFF OFF 111 OFF OFF ON OFF OFF OFF OFF
52 ON OFF OFF ON OFF ON ON 112 OFF OFF OFF ON ON ON ON
53 ON OFF OFF ON OFF ON OFF 113 OFF OFF OFF ON ON ON OFF
54 ON OFF OFF ON OFF OFF ON 114 OFF OFF OFF ON ON OFF ON
55 ON OFF OFF ON OFF OFF OFF 115 OFF OFF OFF ON ON OFF OFF
56 ON OFF OFF OFF ON ON ON 116 OFF OFF OFF ON OFF ON ON
57 ON OFF OFF OFF ON ON OFF 117 OFF OFF OFF ON OFF ON OFF
58 ON OFF OFF OFF ON OFF ON 118 OFF OFF OFF ON OFF OFF ON
59 ON OFF OFF OFF ON OFF OFF 119 OFF OFF OFF ON OFF OFF OFF
60 ON OFF OFF OFF OFF ON ON
8
Power Distribution Module/Battery Connections
Overview The TPS gets its power from the Power Distribution Module (PDM). The PDM takes power directly
from a dedicated AC line and the two backup batteries, and distributes power to each bay in the
cabinet.
Power Distribution The Power Distribution Module (PDM) connects to every power supply in each back box. Connect the
Module Connections 734-012 Harness from the top connector on the PDM to the TPS.
1. Wire 120 VAC to the PDM, keeping AC wires at least one inch away from all other wires.
AC power must be kept to the right side of the cabinet, in the non-power-limited area.
2. Connect batteries to P5 on the PDM using Harness 734-015.
3. Connect the PDM to the TPS using Harness 734-012.
Connect the separate Red and Black wires (with Yellow female terminations) to Plugs P5
(Black) and P4 (Red) on the TPS.
Connect the White and Black wires, which terminate together in a White snap-on
connector, to the bulkhead connector at the bottom of the TPS assembly, as shown below.
9
Compatible TrueAlert Devices
Compatible The following table lists compatible TrueAlert devices. All devices are rated one unit load, with the
TrueAlert Devices exception of the Isolator Module (4905-9929) that is rated three unit loads.
Note: If you are connecting devices to the 4100-5121 (Canadian) TPS, you must only attach
TrueAlert compatible, ULC listed devices.
Table 4. Compatible TrueAlert Devices
Installation
Device PID
Document #
Horn -- Red 4901-9850 574-764
Horn – White 4901-9853 574-764
Strobe (15 cd) – Red 4904-9350 574-767
Strobe (15 cd) – White 4904-9353 574-767
Strobe (75 cd) – Red 4904-9351 574-767
Strobe (75 cd) – White 4904-9354 574-767
Strobe (110 cd) – Red 4904-9352 574-767
Strobe (110 cd) – White 4904-9355 574-767
Strobe (15 cd), Ceiling – Red 4904-9356 574-928
Strobe (15 cd), Ceiling – White 4904-9359 574-928
Strobe (75 cd), Ceiling – Red 4904-9357 574-928
Strobe (75 cd), Ceiling – White 4904-9360 574-928
Strobe (110 cd), Ceiling – Red 4904-9358 574-928
Strobe (110 cd), Ceiling – White 4904-9361 574-928
A/V (15 cd) – Red 4903-9450 574-768
A/V (15 cd) – White 4903-9453 574-768
A/V (75 cd) – Red 4903-9451 574-768
A/V (75 cd) – White 4903-9454 574-768
A/V (110 cd) – Red 4903-9452 574-768
A/V (110 cd) – White 4903-9455 574-768
A/V (15 cd), Ceiling – White 4903-9459 574-929
A/V (75 cd), Ceiling – White 4903-9460 574-929
A/V (110 cd), Ceiling – White 4903-9461 574-929
Isolator Module 4905-9929 574-769
25V/70V Speaker /V (15 cd) – Red 4903-9350 574-766
25V/70V Speaker /V (15 cd) – White 4903-9353 574-766
25V/70V Speaker /V (75 cd) – Red 4903-9351 574-766
25V/70V Speaker /V (75 cd) – White 4903-9354 574-766
25V/70V Speaker /V (110 cd) – Red 4903-9352 574-766
25V/70V Speaker /V (110 cd) -- White 4903-9355 574-766
10
Compatible TrueAlert Devices, Continued
11
General Wiring Guidelines
General Wiring Use only copper conductors for all wiring applications. All equipment must be installed in
Guidelines accordance with the manufacturer’s recommendations and the specifications and standards of the
authority having jurisdiction (AHJ). The installation of all wiring, cable, and equipment must be
in accordance with NFPA 70 and the National Electrical Code (NEC), specifically Article 760
(Fire Alarm Systems), Article 800 (Communications Circuits).
If applicable, the installation must be in accordance with the Canadian Building Code, and any
provincial and/or local requirements.
Each TrueAlert channel is limited to 0.60uF maximum capacitance. This includes conductor to
conductor and conductor to shield capacitance (if shield wire is used).
TPS wiring must use ferrite beads in order to comply with the RF Immunity test specified in
UL864
If shielded wire is used, the following must be observed.
Metallic continuity of the shield must be maintained and insulated throughout the entire
length of the cable.
The entire length of the cable must have a resistance greater than 1 Mega ohm to Earth.
Underground wiring must be free of all water.
Wiring other than that connected to elevator cabs must not be run in elevator shafts
(reference NFPA 70, Article 620).
Wiring in ducts, plenums, and other air handling spaces must be installed in accordance with
NFPA 70, Article 300.
Splicing is permitted in accordance with NFPA 70. All junctions must be insulated as soundly as
the original jacket. Continuity of shields (where used) must be maintained.
A system ground must be provided for Earth detection and lightning protection devices. This
connection shall be made to an approved, dedicated Earth connection, per NFPA 70, Article 250.
Only system wiring can be run in the same conduit.
Field wiring circuits shall not leave the building of origin unless all of the following conditions are
met.
Circuits are protected from lightning by utilization of either the Model 2081-9044 or the
Model 2081-9028 listed isolated loop circuit protectors.
One isolated loop circuit protector is inserted into the circuit where the wiring leaves the
building. A second isolated loop circuit protector is inserted into the circuit where the wiring
enters the next building.
Underground wiring circuits are run in a parallel wiring trough separate from any commercial
power distribution wiring.
Overhead circuit wiring is run in parallel with relation to the commercial power distribution
wiring. Overhead circuit wiring is separated from the commercial power distribution wiring
by a minimum distance equal to the maximum span between two adjacent poles of either the
system’s circuit or the commercial power distribution circuit, or 100 feet (30 m), whichever is
greater. Outside plant wiring is limited to one contiguous property and the total wire length
may not exceed 3,270 feet (997 m).
12
General Wiring Guidelines, Continued
Power-Limited/Non- Adhere to these guidelines when wiring power limited and non-power limited wiring within the FACP.
Power Limited
Wiring Guidelines
Non-power limited field wiring (AC power, batteries) must be installed and routed in the
shaded areas shown in the figure below.
Power-limited field wiring must be installed and routed in the non-shaded areas shown in
the figure below.
Excess slack should be kept to a minimum inside the back box enclosure. The wiring
should be neatly dressed and bundled together using the wire ties provided with the
equipment. Anchor power-limited wiring to tie points, as shown in the figure below.
Tie the wiring located between bays to the internal wiring troughs, if applicable.
When powering remote units or switching power through relay contacts, power for these
circuits must be provided by a power-limited power supply that is UL listed for fire-
protective signaling use. A UL listed EOL relay must be used to supervise the auxiliary
power circuit.
IMPORTANT: If the TPS is powered up with zero devices connected, the TPS
indicates channel failure for those channels that are programmed to
support devices. The TPS does not sense devices as they are
connected when the TPS has been powered up with zero devices
connected. After at least one valid device is connected, the unit must
be reset by toggling the DIP Switch SW1-1 OFF and then ON. The TPS
then communicates with devices as they are added.
Conduit Entrance for
Non-Power Limited
Conduit Entrance for Wiring
Power-Limited Wiring
Non-Power Limited
Wiring (Route in
Power-Limited Wiring Shaded Area Only)
Tie Point
(Location
May Vary)
13
Wiring Class A Circuits
Class A Guidelines Class A wiring requires purchase of 4100-5124 Class A Adapter Module
Only TrueAlert appliances and accessories (“devices”) are allowed on these signaling line circuit
(SLC) channels. Refer to Table 4 for a list of compatible TrueAlert devices and to the TrueAlert
device installation instructions for connection details.
Maximum of 63 devices or 75 unit loads per channel. Refer to Table 4 for unit load ratings of
TrueAlert compatible devices. The maximum number of visuals that can be synchronized on one
circuit is 43 for fixed candela and 46 for multi-candela devices. The maximum resistance between
any two visuals is 30 Ohms.
All wiring is supervised and power limited.
All wiring to be twisted pair. Wire must be minimum of 18 AWG (0.82 mm2) and maximum
12 AWG (3.31 mm2). If shielded pair is used, then the cable shield drain wire must be attached
back to the (–) Terminal at both Class A and Class B ends of this circuit. Only one wire per
terminal position.
Maximum alarm current is 3.0 A per SLC channel. Use alarm current for lowest rated appliance
nameplate voltage. Total alarm current for all 3 channels plus all current draw from AUX power
and option cards must not exceed 9 A.
Supervisory current is 0.20 mA per unit load.
Maximum length of all wire segments added together is 10,000 feet (3,048 m) per channel.
Maximum wire length from panel to any device is 2,500 feet (762 m).
T-Tapping is NOT allowed. Maximum wire distance from panel to appliance farthest from the
panel is the smaller of the values obtained from Table 5 and Table 6. Add the alarm loads of all
the devices on an SLC wire loop and apply to Table 5.
Voltage rating is 24 VDC nominal, 2 V peak-to-peak ripple, maximum.
Overvoltage suppressors are required when wiring leaves the building. Use Simplex Model
2081-9028 for wire distances of up to 1,000 feet (305 m). Use Simplex Model 2081-9044 for long
wire distances and light alarm loads. Note that the 6 Ohm line resistance of Simplex Model
2081-9044 will decrease the distances given in Table 5. Maximum two suppressors between any
device and SLC channel terminals (A or B). See the previous “General Wiring Guideline” section
for information regarding wiring that leaves a building.
14
Wiring Class A Circuits, Continued
Class A Guidelines
The table below shows the maximum SLC wire lengths based on wire gauge and appliance
current load.
Table 5. Maximum SLC Wire Length to Farthest Appliance Based on Appliance Current Load
Distance in Feet (Meters) to the Last Appliance
Alarm Current 18 AWG (0.82 mm2) 14 AWG (2.08 mm2) 12 AWG (3.31 mm2)
0.11 A 638 ft (194 m) 1,614 ft (492 m) 2,500 ft (762 m)
0.25 A 281 ft (86 m) 710 ft (216 m) 1,129 ft (344 m)
0.60 A 117 ft (36 m) 296 ft (90 m) 471 ft (144 m)
0.80 A 88 ft (27 m) 222 ft (68 m) 353 ft (108 m)
1.0 A 70 ft (21 m) 178 ft (54 m) 282 ft (86 m)
1.3 A ― 137 ft (42 m) 217 ft (66 m)
2.2 A ― 81 ft (25 m) 128 ft (39 m)
3.0 A ― ― 113 ft (34 m)
Distances based on 2.0 V line drop
If notification appliances on a given circuit are to be used for multiple notification zones for partial
evacuation (selective signaling), then either a Class A loop circuit configuration and isolators must be
used, with isolators bounding any wire segment that services a notification zone; or, the NAC riser
must be installed in accordance with Survivability From Attack by Fire Requirements in NFPA 2002
ED. Section 6.9.4, using one or more of the following:
2 hour rated cable assembly
a 2 hour rated shaft or enclosure
2 hour rated stairwell in building fully sprinklered in accordance with NFPA 13
The table below shows the maximum SLC wire length based on wire type and supervision
communications.
Table 6. Maximum SLC Wire Length to Farthest Appliance Based on Supervision Communications
15
16
Wiring Class A Circuits, Continued
Ferrite
Bead
Ferrite
Bead
PORT
1 4905-9929
ISOLATOR
PORT Ferrite PORT
4905-9929 2 Bead 2
ISOLATOR
PORT
1
Ferrite
Bead
17
Wiring Class B Circuits
Class B Guidelines Only TrueAlert appliances and accessories (“Devices”) are allowed on these SLCs. Refer to
Table 4 for a list of compatible TrueAlert devices and to the TrueAlert Device Installation
Instructions for connection details.
Maximum 63 devices or 75 unit loads per channel, whichever comes first. See Table 4 for unit
load details. The maximum number of visuals that can be synchronized on one circuit is 43 for
fixed candela and 46 for multi-candela devices. The maximum resistance between any two visuals
is 30 Ohms.
All wiring is supervised and power limited.
All wiring to be twisted pair – minimum 18 AWG (0.82 mm2), maximum 12 AWG (3.31 mm2).
If shielded pair is used, the cable shield drain wire from all connected branches and taps must
attach back to the (--) terminal of the circuit. Maximum two wires per terminal position.
Maximum alarm current is 3 A per SLC. Use alarm current for lowest rated appliance nameplate
voltage. Total alarm current for all three SLCs plus all current draw from AUX power and option
cards must not exceed 9 A.
Supervisory current is 0.20 mA per unit load.
Maximum length of all wire segments added together is 10,000 feet (3,048 m) per SLC.
Maximum wire length from panel to any device is 2,500 feet (762 m).
The maximum wiring capacitance is 0.6 uF per channel. If shielded wire is used, you must add the
capacitance of the drain wire to the conductor.
Voltage rating is 24 VDC, 2 V, peak-to-peak ripple maximum.
Maximum of six isolators between any appliance and SLC terminals. Maximum 12 isolators per
SLC. Maximum 30 devices connected directly to any isolator terminal pair.
If notification appliances on a given Class B circuit are to be used for multiple notification zones for
partial evacuation (selective signaling), then the NAC riser must be installed in accordance with the
Survivability From Attack by Fire Requirements in NFPA 2002 ED. Section 6.9.4. One or more of the
following should be used:
2 hour rated cable assembly
A 2 hour rated shaft or enclosure
2 hour rated stairwell in building fully sprinklered in accordance with NFPA 13
The table below shows the maximum wire branch lengths for various alarm loads.
Table 7. Maximum SLC Wire Branch Length Based on Appliance Current Load
18
Continued on next page
19
Wiring Class B Circuits, Continued
Class B Guidelines The table below shows the maximum SLC wire branch length based on supervision communications.
Class B For Class B wiring with no isolators, T-Tapping is allowed. SLC wiring may be split multiple times to
Wiring Diagram form SLC wiring branches. Maximum wire distance of each of these SLC branches from the panel to
(No Isolators) any device is the smaller of the values obtained from Table 7 and Table 8. Add the alarm loads of all
of the devices on an SLC branch and apply to Table 7. Add the unit loads (see Table 4) of all the
devices on an SLC branch and apply it to Table 8. Use of Table 7 and Table 8 requires all SLC wire
branches join within 10 feet (3 m) of the panel. T-tap wire stubs are allowed on the SLC wire
branches, but each tap must be less than 100 feet (30 m).
FigureTag FD9-336-05
TRUEALERT TRUEALERT TRUEALERT
APPLIANCE APPLIANCE APPLIANCE
Ferrite
Bead
Class B For Class B wiring with isolators, T-Tapping is allowed. SLC wiring may be split multiple times to
Wiring Diagram form SLC wire branches. Maximum wire distance of each of these SLC branches from panel to any
(With Isolators) device is the smaller of the values obtained from Table 8 and the Equation 1 shown below. Add the
alarm loads of all the devices on an SLC wire branch and apply to Equation 1. Add the unit loads
(see Table 4 for unit loads) for all devices on an SLC wire branch and the number of isolators and
apply to Table 8. Use of Table 8 requires that all SLC wire branches join within 10 feet (3 m) of
the panel. T-tap wire stubs are allowed on the SLC wire branches, but each tap must be less than
100 feet (30 m).
Equation 1: Maximum SLC Wire Branch Length Based on Appliance Alarm Current Load
FigureTag FD9-336-06
TO OTHER TO OTHER
DEVICES DEVICES
PORT PORT
4905-9929 2 4905-9929 2
ISOLATOR ISOLATOR
PORT PORT
1 1
TO OTHER
DEVICES
PORT PORT
4905-9929 2 1 4905-9929
ISOLATOR ISOLATOR
PORT PORT
1 2
TO OTHER
DEVICES
Ferrite
Bead
21
Wiring AUX Power
Wiring Diagram to Supervision must be provided if the auxiliary power circuit is to be wired as a power-limited circuit.
Connect AUX Power In order to connect a circuit using power-limited wiring, the devices being powered must all be
to Power Limited addressable, or a UL Listed EOL relay must be used to supervise the circuit. Refer to the figure below
Wiring
for wiring directions for the EOL relay.
TO AUX POWER
RED BLACK
Note: The 2098-9739 Relay is used as
an example. Other UL Listed
24 VDC EOL relays can be used, 2098-9739
END OF
depending on the application. LINE RELAY
YELLOW
LAST IDC
IDC DEVICE RESISTOR
AUX Compatible The AUX Power output is defined by UL as Special Applications, and is compatible with these
Devices devices:
2088-Series relays and door handlers
2098-Series four-wire smoke detectors
2190-Series monitor and signal ZAMs
4090-Series IDNet ZAMs
4098-Series four-wire smoke detectors and duct detectors
2190-9039 Printer
4190-9050/9051, 4-20 mA ZAMs
4603-9101 LCD Annunciator
22
Troubleshooting
System Trouble The system trouble indicators consist of a bank of five yellow LEDS (refer back to Figure 1 for their
Indicators location on the TPS). These LEDs are used to signal various trouble conditions on the TPS and its
(LEDs A through E) SLCs. Only one trouble at a time is shown. You can step through all of the troubles present on the
TPS or its SLCs using the Trouble Scroll Pushbutton. This pushbutton is shown in Figure 1 and is
located just to the right of LEDs A through E.
Notes:
Any trouble indication that applies to a specific SLC channel has the corresponding
LED (CH1 through CH3) for that channel lit.
The Trouble Scroll Pushbutton allows an operator to scroll through multiple troubles.
= On LED
= Off LED
SYSTEM CODES
A B C D E
AC Fail
Low/Missing Battery
Running on Depleted Battery
Memory Checksum Error
RUI Comm Fail
Hardware Configuration Mismatch
Channel Controller Trouble
Negative Earth
Positive Earth
Hardware Configuration Error
Memory Test Error
Charger Trouble
Field Power Overcurrent
Battery Cutout
Missing Device
Extra Device
Class A Trouble
Earth Trouble
Isolator Trouble
Bad Download
Address Out of Range
SLC Overcurrent
23
579-336
Rev. K