Product Data Sheet: DEHNventil® modular
DV M TNC 255 FM (951 305)
■ Prewired combined spark-gap-based lightning current and surge arrester consisting of a base part and plug-in protection modules
■ Maximum system availability due to RADAX Flow follow current limitation
■ Capable of protecting terminal equipment
Figure without obligation
Basic circuit diagram DV M TNC 255 FM Dimension drawing DV M TNC 255 FM
Modular combined lightning current and surge arrester for TN-C systems
Type DV M TNC 255 FM
Part No. 951 305
SPD according to EN 61643-11 / IEC 61643-1/-11 Type 1 / Class I
Energy coordination with terminal equipment Type 1 + Type 2
Energy coordination with terminal equipment (≤ 5m) Type 1 + Type 2 + Type 3
Nominal a.c. voltage (UN) 230 / 400 V
Max. continuous operating a.c. voltage (UC) 255 V
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal) 75 kA
Specific energy [L1+L2+L3-PEN] (W/R) 1.40 MJ/ohms
Lightning impulse current (10/350 µs) [L-PEN] (Iimp) 25 kA
Specific energy [L-PEN] (W/R) 156.25 kJ/ohms
Nominal discharge current (8/20 µs) (In) 25 / 75 kA
Voltage protection level (UP) ≤ 1.5 kV
Follow current extinguishing capability a.c. (Ifi) 50 kArms
Response time (tA) ≤ 100 ns
Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG
Max. backup fuse (L) for IK > 50 kArms 200 A gL/gG
Max. backup fuse (L-L') 125 A gL/gG
Temporary overvoltage (TOV) (UT) 440 V / 5 sec.
TOV characteristic withstand
Operating temperature range [parallel]/[series] (TU) -40°C...+80°C / -40°C...+60°C
Operating state/fault indication green / red
Number of ports 1
2
Cross-sectional area (L1, L1', L2, L2', L3, L3', PEN, GND) (min.) 10 mm solid/flexible
2 2
Cross-sectional area (L1, L2, L3, PEN) (max.) 50 mm stranded/35 mm flexible
2 2
Cross-sectional area (L1', L2', L3', 9) (max.) 35 mm stranded/25 mm flexible
For mounting on 35 mm DIN rails acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Place of installation indoor installation
Degree of protection IP 20
Capacity 6 module(s), DIN 43880
Approvals KEMA, VDE, UL, VdS
Type of remote signalling contact changeover contact
a.c. switching capacity 250 V/0.5 A
d.c. switching capacity 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
2
Cross-sectional area for remote signalling terminals max. 1.5 mm solid/flexible
Weight 962 g
Customs tariff number 85363030
GTIN 4013364108141
PU 1 pc(s)
We reserve the right to introduce changes in performance, configuration and technology, dimensions, weights and materials in the course of technical progress. The figures are shown without obligation.
© DEHN + SÖHNE GmbH + Co. KG · Hans-Dehn-Str. 1 · Postfach 1640 · D-92306 Neumarkt · Tel. +499181 906-0 · www.dehn.de
3, te
s ted
: Tested ): New (: Discontinued Model