SL 0011 System Bypass Design Considerations 5.21.14
SL 0011 System Bypass Design Considerations 5.21.14
SL 0011 System Bypass Design Considerations 5.21.14
Yes, a bypass is required for any chilled water/evaporator, hot water/condenser (heating load) and
source water side (geothermal, cooling tower or closed circuit cooler) with variable pumping. The
bypass must be piped in such a way that the temperature and differential pressure sensors are still
sensing active flow.
The purpose of the chiller/heater system bypass is to prevent deadheading of the pumps when all of
the internal unit valves go closed as well as allow temperature and differential pressure sensors to
sense active flow.
Yes, modules can be designated for fixed bypass for heating, cooling and source flow, however, this
limits the number of modules remaining for that duty. For instance with an SHC OnDemand® heat
pump system with four (4) modules, if you designate one (1) module for heating bypass and one (1)
module for cooling bypass, the system now only allows a maximum of three (3) modules for heating
or three (3) modules for cooling.
What amount of flow should the chiller/heater system bypass be sized for?
The bypass should be sized for an absolute minimum of one module’s worth of design flow. Refer to
selection software for design flow rates.
Yes, you can purchase a bypass kit from ClimaCool. The kits are inexpensive, easy to install and
controls are integrated with the ClimaCool CoolLogic software.
Yes, the design piping must accommodate one module’s worth of design flow, and be positioned
so that the temperature and differential flow sensors sense active flow in the bypass mode. Refer
to the Water Piping Configuration Drawing, Figure 1, on previous page.
The field supplied piped chiller/heater system bypass must be controlled by others. It may control
the differential pressure across the chiller/heater system, gpm flow meters, etc.
Can the ClimaCool CoolLogic controls via BACnet or other remote interface be utilized to control
a field supplied bypass?
No. There are system communication delays, polling and network conflicts that strictly prohibit the
use of ClimaCool sensors and controls for control of field supplied bypasses or other field installed
items. The recommended method is to control via differential pressure or gpm flow meters across
the chilled water/evaporator, hot water/condenser and source water systems.
The above strictly relates to the bypass at the chiller/heater system. In order to have a stable
operating cooling and/or heating system, consideration must be given to the load side of the
system as well.
Yes, a load system bypass is required for preventing pump deadheading, allowing active flow system
sensing and preventing starving flow from the chiller/heater system.
• Utilize a quantity of 3-way control valves on the largest loads farthest from the
chiller/heater system.
• Field piping with a control valve to provide a bypass across the larger system loads when
their 2-way valves go closed.
What amount of flow should the load side system bypass be sized for?
The system should be sized for an absolute minimum of one module’s worth of design flow. Refer to
selection software for design flow rates.
Is there a required minimum system volume to maintain proper system thermal mass?
Yes, a minimum of six (6) gallons per nominal system ton are required to maintain proper system
thermal inertia. This is to avoid short cycling of compressors in the chiller/heater system as well
as prevent nuisance alarms.