0% found this document useful (0 votes)
279 views4 pages

DPT100: Single Phase: Compact, Con Gurable Multiple Measurand Transducers

The DPT100 is a compact, configurable transducer that offers accurate true-RMS measurements with fast response times of 100-220ms. It can measure multiple parameters like voltage, current, frequency, and power. It has two isolated analog outputs that can be configured for different measurement ranges and output curves. The DPT100 has a compact footprint of 45x75x105mm and is designed for demanding industrial and utility applications.

Uploaded by

ajayraam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
279 views4 pages

DPT100: Single Phase: Compact, Con Gurable Multiple Measurand Transducers

The DPT100 is a compact, configurable transducer that offers accurate true-RMS measurements with fast response times of 100-220ms. It can measure multiple parameters like voltage, current, frequency, and power. It has two isolated analog outputs that can be configured for different measurement ranges and output curves. The DPT100 has a compact footprint of 45x75x105mm and is designed for demanding industrial and utility applications.

Uploaded by

ajayraam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

DPT100: single phase

multi-function transducers

compact, con gurable multiple


measurand transducers

Accurate USB Response time Compact size


class 0.2, 0.5 & 1 programming ~100-220 ms

DPT100 is a range of compact, con gurable multiple measurand ! Best in class response time
transducers designed to meet the demanding needs of supply ! Long range, site-con gurable inputs, outputs and
utilities and industrial applications. It o ers accurate true-RMS measurands
measurements for high e ciency and quick response time. It is ! Load-independent accuracy on all outputs
equipped with two load-independent, galvanically-isolated ! 2-in-1 programmable transducers
analogue outputs that can be con gured for di erent ! Diagnostic LEDs
measurands, input range and output curves. ! Compact footprint

M easurement functions Output type Output range No. of Accuracy class


(Measurands) outputs
Voltage, current, frequency, Option for mA or V 0-20 mA, 0-10 mA, 0-5 mA*, 0-2 mA* 2 0.2, 0.5, 1.0
active power 0-5 V, 0-10 V

*available in accuracy class 1.0 only


Frequency accuracy - ± 0.1 Hz
DPT100: single phase
multi-function transducers

Output cuves
Curve A Curve B
Linear Linear with live zero

Output Output

Input Input

Curve C Curve D
Compressed upper region Compressed lower region

Output Output

Input Input

Mechanical dimensions
105 mm
75 mm

45 mm Top view Isometric view


Front view
DPT100: single phase
Technical speci cations

Site-con gurable measurement functions (measurands)

AC voltage
Nominal input (Un) 57.7 to 415 V
Measuring range 0 to 130 % Un (up to 500 V)
Scale factor 0.8 to 1.3 of Un (up to 500 V)
Measurement frequency 50/60 Hz (±5%)
Burden ≤ 0.2 VA
Maximum overload voltage 1.3 x Un continuously (500 V max.)
2 x Un for 1 s, with up to 10 repetitions at 10 s intervals

AC current
Nominal input (In) 1/5 A
Measuring current range 0 to 150 % In
Scale factor 0.6 to 1.5 of In
Burden ≤ 0.2 VA
Maximum overload current 2 x In continuously
20 x In for 1 s, with up to 10 repetitions at 100 s intervals

Frequency
Nominal input voltage (Un) 57.7 to 415 V
Input range 0 to 130 % Un (up to 500 V)
Measurement range 45 Hz to 55 Hz, or 55 Hz to 65 Hz
Accuracy ±0.1 Hz

Active Power
Nominal input voltage (Un) 57.7 to 415 V
Input voltage range 0 to 130 % Un (up to 500 V)
Nominal input current (In) 1/5 A
Input current range 0 to 150 % In
Measurement frequency 50/60 Hz (±5%)
Scale factor 0.5 to 1.5 of Un x In (at unity power factor)

Auxiliary Supply
High auxiliary
Nominal voltage range 80 to 276 V AC/DC (±10 %)
Frequency 50/60 Hz
Maximum burden ≤6VA, 3W with one output at 750 Ω
≤7VA, 3.5W with two outputs at 750 Ω each
Low auxiliary
Nominal voltage range 24 to 80 V DC (±10 %)
Maximum burden ≤3 W with one output at 750 Ω
≤4 W with two outputs 750 Ω each

Analogue outputs
Output type mA or V
Maximum load resistance ≤750 Ω for 20 mA, ≥ 2 k Ω for 10 V(for each output)
Response time 5 cycles measurement (≤100-220 ms)
Ripple <0.4 % peak to peak
DPT100: single phase
Technical speci cations
PT1
Temperature range
Operating range -5 °C to +55 °C
Storage range -25 °C to +70 °C

Mechanical
Dimension (W x H x D) 45 x 75 x 105 mm
Weight 0.4 kg approx.
Material Fire-retardant polycarbonate (PC-FR), UL94 V-0
Mounting DIN (EN 50022)
Connector type Screw terminals
Conductor size for terminals ≤4 mm2

Environmental
Protection class II (double insulation) EN 61010-1
Pollution degree 2
Installation category CAT III
Protection degree Housing: IP 40, front side: IP 20

Standards compliance
Standards IEC 60688, IEC 61010-1, IEC 61010-2-30,
IEC 61326-1, DIN 50022

Communication ports
USB For on-site con guration

Con guration so ware tool


Con gView For on-site con guration of measurement inputs, measurands, output curve and
online parameter reading. It can be freely downloaded from
www.ceweinstruments.se

Ordering key
DPT100 XX1-1XF X X 1 - 1 Y F
Example
DPT100 611-12F
where high auxiliary (6), Output Accuracy
mA output (1), accuracy class 0.2 1: mA 1: Cl 1.0
2: V 2: Cl 0.2
Aux supply 5: Cl 0.5
6: High
7: Low

Cewe Instrument AB
Box 1006 | SE-611 29 Nyköping | Sweden | Tel: +46 (0)155 775 00 | E: [email protected] | Fax: +46 (0)155 775 97 | www.ceweinstrument.se

UK Channel Partner
Secure House, Moorside Road, Winchester, Hampshire, SO23 7RX, England | T: +44 (o) 1962 840048 | F: +44 (o) 1962 841046
E: [email protected] | www.securetogether.com