Energy Conservation &management in Lightining System

The document discusses energy conservation and auditing of lighting systems. It provides information on calculating the installed load efficiency ratio (ILER) to assess lighting systems and determine where improvements can be made. An energy audit was conducted of the lighting system at a sugar industry plant. By replacing existing lamps with more efficient options, the plant's lighting load was reduced from 83.69 kW to 55.394 kW, saving over 83043.7 kWh per season and Rs. 3.321 lakhs in energy costs annually. The audit demonstrated that significant energy and cost savings can be achieved through upgrading lighting systems.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views5 pages

Energy Conservation &management in Lightining System

The document discusses energy conservation and auditing of lighting systems. It provides information on calculating the installed load efficiency ratio (ILER) to assess lighting systems and determine where improvements can be made. An energy audit was conducted of the lighting system at a sugar industry plant. By replacing existing lamps with more efficient options, the plant's lighting load was reduced from 83.69 kW to 55.394 kW, saving over 83043.7 kWh per season and Rs. 3.321 lakhs in energy costs annually. The audit demonstrated that significant energy and cost savings can be achieved through upgrading lighting systems.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 5

ENERGY CONSERVATION &MANAGEMENT IN

LIGHTINING SYSTEM

INTRODUCTION:
Now a days industries as well as we are facing the problem of load shading i.e.
energy crisis. Systematic energy conservation and energy audits are mandatory for
various industrial sector by bridging the gap between demand and supply through
energy saving.

ENERGY CONSERVATION:
Energy conservation means reduction in energy consumption but without affecting
the quality and quantity of product. It includes that avoiding wastage of energy and
adopting new methods to conserve the energy without affecting productivity and
comfort

ENERGY AUDITY:
Energy audit is a study of energy consumption related with an organization,
system, process, plant, equipment. In energy audit first step is to understand how
the energy is used in a given industry or organization. The study involves mass
and energy balance of major energy consuming equipment .As a result of energy
audit, we can consume the energy and reduce the bill of energy

ENERGY AUDIT OF LIGHTING SYSTEM INCLUDES:


► Assessment of lighting system.

►Lighting load and lighting consumption.

►Lighting performance test.


PROCEDURE FOR ASSESMENT OF LIGHTING
SYSTEM:
1.calculate the room index(RI):
L= length of interior.
W=width of interior.
Hm=The mounting height, which is the height of lighting and fitting above
the horizontal working plane.

2. calculation of the installed load efficiency


ratio(ILEAR):
Step 1 Measure the floor area of Area=………..m2
interior
Step 2 Calculate the Room R I=……….
index
Step 3 Determine the total Total ckt.watts=……
circuit watt
Step4 Calculate watts per sq. w/m=…..
meter(step3/step1)
Step 5 Ascertain the average. E(AVG .MAINTAINED) =…
Maintain illuminance
by using lux meter
Step6 Calculate lux per watt Lux/watt=…..
per sq . meter
(step5/step4)
Step7 Obtain target lux/watt Target lux/ watt=…..
for type of the type of
interior/application.
Step8 Calculate installed load ILER=….
efficiency ratio
(step6/step7)

3. ILER Assessment :
Compare the calculated ILER with the following table

ILER Assessment
0.75 or above Satisfactory to good
0.51 – 0.74 Review suggested
0.5 or less Urgent action is required

For a given installation,

Annual energy wastage (kwh) =(1-ILER) *Total load (kw) *annual


operating hours

PERFORMANCE TEST :
The audit is done at sugar industry. The replacement for various lamps is
suggested. By replacing the existing lamps by energy saving lamp, the sugar
industry plant load is to be reduced from 83.69 kw to 55.394 kw. The
details are given below .

1. Wattage of existing lamps including chokes:


Lamp watts CHOKE TOTAL nos Total kw
Type RATING(W) wattage watts
GLS 40 16 56 0 0 0
GLS 25 10 35 26 910 0.910
GLS 100 25 125 80 10000 10
GLS 200 40 240 37 8880 8.88
FTP 40 16 56 369 20664 20.66
FTP 25 10 35 1 35 0.035
HPMV 250 16 266 31 8246 8.246
HPMV 400 25 425 64 27200 27.2
HPSV 400 40 440 7 3080 3.08
LAMP 400 25 425 11 4675 4.675
TOTAL 83690
83.69
2. WATTAGE OF REPLACED LAMPS INCLUDING
CHOKES:
Lamp type Wattage(w Choke Total Nos Total kw
) rating wattage watts
CFL 18 0 18 0 0 0
CFL 14 0 14 26 364 0.364
CFL 25 0 25 80 1000 10
ML 160 20 180 37 6660 6.66
TLD 36 16 52 369 19188 19.188
CFL 14 0 14 1 14 0.014
HPSV 150 20 170 31 5270 52.7
HPSV 250 20 270 64 17280 17.289
HPSV 250 25 275 7 1925 1.925
SUPER
HPSV 250 20 270 11 2970 2.97
Total 5567155.671

ENERGY SAVING CALCULATION:


LIGHTING LOAD=83.69KW LIGHTING LOAD=54.40KW
DAILY LIGHTING DAILY LIGHTING
CONSUMPTION=1351.12KWH CONSUMPTION=889.766KWH
LIGHTINGCONSUMPTION/SEASON=135 LIGHTING
1.12X180=243201.6KWH CONSUMPTION/SEASON=889.766
X180=160157.9KWH
SAVED KWH/SEASON=243201.6-160157.9=83043.7KWH
SAVING/SEASON=83043.7XRS4 =RS332174.8=3.321LAKHS

conclusion
1. Energy audit of the lighting system has shows that there is a large
energy savings.
2. Energy saved is energy produced,so it helps to reduce the bill of
energy and save the fuel .
3. The saved energy will be made available for the use in the future.
REFERENCES:
1. ‘NATIONAL RENEWABLE ENERGY MISSION’BY
SURESHPRABHU, Vanarai,2004.
2. ENERGY CONSERVATION’ by .S.A.PATIL,
A.G. AWATE COLLEGE MAGAGINE 2008.
3. ENERGY SAVING IN LIGHTING SYSTEM’ by Mane’trends in
mechanical engg ;10
4. WWW.EN.WIKIPEDIA.ORG/WIKI/COMPACT-FLUORESCENT-
LAMP