Cerberus® PRO

Modular system
Device Loop Card
Model XDLC

Architect & Engineer Specifications Product Overview


 Supports up to 252 addressable points The Siemens – Fire Safety `Class X’ Device Loop Card (Model XDLC) is the interface
used for connecting Siemens addressable, intelligent `X’ as well as `H’-series devices.
 Operates and maintains all devices
residing on up to four (4) `Class A’, Each Model XDLC plugs into one (1) slot of the Model CC-2 or Model CC-5 card cage.
eight (8) `Class B’ addressable circuits Programming for Model XDLC is accomplished via the Cerberus PRO Modular system
 Compatible with Siemens intelligent, custom-configuration tool, Zeus-C. Model XDLC takes one (1) address on the
addressable ‘X’ and ‘H’-series devices: network, communicating up to a total 252 detectors and devices. Model XDLC has
- Multi-criteria / Carbon Monoxide (CO) 16 LEDs for diagnostic purposes, and provides ground-fault detection and zone-
Detector with ASAtechnology TM isolation circuitry.
- Multi-criteria Detector
with ASAtechnology TM
- Multi-criteria Detector Specifications
- Thermal (Heat) Detector The `Class X’ Device Loop Card (Model XDLC) initializes, operates and maintains all
- Input / Output Interface Module devices residing on up to four (4) `Class A’, eight (8) `Class B’ addressable circuits.
 Polarity insensitive (in non-isolation Model XDLC communicates all relevant device and event data (`Alarm’, `Trouble’ and
mode) via SureWire™ technology: `Supervisory’ commands) to a Cerberus PRO Modular fire-alarm control panel (FACP),
- Modern technology supports and supervises the device loop circuit.
comprehensive system and
interface communication Model XDLC is polarity insensitive via SureWire technology, which greatly reduces
commissioning time normally spent tracing down crossed-field wiring. Model XDLC
 Quantity 16 diagnostic light-emitting
diodes (LEDs) for easy circuit diagnosis communicates detector data, such as sensitivity of intelligent fire detectors and logic-
function information, to the Cerberus PRO Modular Operating Unit (Model FCM2041-
 Microchip controls on-board isolators U3), which is located within a given Cerberus PRO Modular system.
 Device Programmer / Tester
(Model DPU) programs and
Each device loop card supports four (4) `Class A’, eight (8) `Class B’ circuits for up to a
verifies device’s address: total of 252 addressable devices – as well as relay and audible bases, remote lamps
- programming capabilities include and duct-detector housings in any combination.
testing a duct detector, as well as
other Siemens addressable devices
The microprocessor in a Model XDLC controls the
on-board isolation, in case there is a fault (short) in
 Supports `Class B’ | `Class A’ any of the circuits, thus allowing the other circuit to
| `Class X’ wiring
continue operating. For continuous protection, the
 Supports T-Tapping on-board microprocessor continues to operate even
 Degrade mode in the event of a CPU failure.
 UL864 | CAN / ULC Listed
NOTE: Refer to installation manual: P/N –
A6V101040156 to ensure Model XDLC
compatibility with the Siemens FA CPs
intended for use in the given application .

Model XDLC d

Side View
Model d

XDLC d

Front View
Siemens Data Sheet 8312
Building Technologies Division usa.siemens.com/cerberus-pro
Model XDLC-
Diagram of an `Class X’ Device Loop Card
mounted to a Siemens Card Cage

Temperature and Humidity Range


`Class X’ Device Loop Cards are UL Listed | ULC Listed for indoor dry locations within a temperature range of 120+/-3°F
(49+/-2°C) to 32+/-3°F (0+/-2°C) and a relative humidity of 93+/-2% at a temperature of 90+/-3°F (32+/-2°C).

Technical Data Details for Ordering


24V CURRENT DRAW: MODEL PART
0 PRODUCT
[Back Plane] OR TYPE NUMBER
24V CURRENT DRAW: 100mA + 1.4mA
`Class X’
[Screw Terminal] per device XDLC S54430-B8-A1 Device Loop Card
6.2V CURRENT DRAW: 1mA, max.
[Back Plane]
24V CURRENT DRAW: 100mA + 1.4mA
[Standby] per device

DEVICE LOOP: 500mA, max.


[@ 30 VDC Max.] (power limited)

NOTICE – The information contained in this data-sheet document is intended only


as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install-type, instruction sheets – as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire-safety professional before specifying or using the product.

Any further questions or assistance concerning


particular problems that might arise, relative to the
proper functioning of the equipment, please contact
Cerberus® PRO
Siemens Industry, Inc.
the Manufacturer.
Building Technologies Division
8 Fernwood Road • Florham Park, NJ 07932
Tel: (973) 593-2600
August 2018 ─ Supersedes sheet dated 10/2017
(Rev. 2)