Lit Quick Start Guide
Lit Quick Start Guide
Lit Quick Start Guide
00825-0100-4530, Rev HA
February 2019
Contents
About this guide............................................ 3 Configure.....................................................22
®
Confirm system readiness (HART only).........5 Safety Instrumented Systems (4-20 mA only)..
25
Mount transmitter on tank.............................6
Adjust probe length..................................... 26
Prepare the electrical connections............... 11
Product certifications...................................29
Connect wiring and power up...................... 19
WARNING
Failure to follow safe installation and servicing guidelines could result in death
or serious injury.
• Make sure the transmitter is installed by qualified personnel and in
accordance with applicable code of practice.
• Use the equipment only as specified in this Quick Start Guide and the
Reference Manual. Failure to do so may impair the protection provided by
the equipment.
• Any substitution of non-recognized parts may jeopardize safety. Repair,
e.g. substitution of components etc., may also jeopardize safety and is
under no circumstances allowed.
Explosions could result in death or serious injury.
• Verify that the operating atmosphere of the transmitter is consistent with
the appropriate hazardous locations certifications.
• To prevent ignition of flammable or combustible atmospheres, disconnect
power before servicing.
• Before connecting a handheld communicator in an explosive atmosphere,
ensure the instruments are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
• To avoid process leaks, only use the O-ring designed to seal with the
corresponding flange adapter.
Electrical shock could cause death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
• Make sure the mains power to the transmitter is off and the lines to any
other external power source are disconnected or not powered while
wiring the transmitter.
• Ground device on non-metallic tanks (e.g. fiberglass tanks) to prevent
electrostatic charge build-up.
WARNING
Probes with non-conducting surfaces
• Probes covered with plastic and/or with plastic discs may generate an
ignition-capable level of electrostatic charge under certain extreme
conditions. Therefore, when the probe is used in a potentially explosive
atmosphere, appropriate measures must be taken to prevent electrostatic
discharge.
Eliminate the risk of ESD discharge prior to dismounting the transmitter head
from the probe.
• Probes may generate an ignition-capable level of electrostatic charge
under extreme conditions. During any type of installation or maintenance
in a potentially explosive atmosphere, the responsible person should
make sure that any ESD risks are eliminated before attempting to separate
the probe from the transmitter head.
2F0 or later 7 4
5 3
2A2 - 2E0 5 3
(1) Firmware version is printed on the transmitter head label, e.g. SW 2E0 or can
be found in Rosemount Radar Master (select Device > Properties).
(2) Device revision is printed on the transmitter head label, e.g. HART Dev Rev 4.
Procedure
1. Locate the “Message” field.
2. In the Message field, enter HART5 or HART7 and then 27 trailing
spaces.
&
A. NPT
B. Flange
C. Gasket
$ %
& &
A. Tri-Clamp
B. BSP/G
C. Gasket
A. Gasket
4X
%
A. Horizontal pipe
B. Vertical pipe
3X
4X
%
A. Horizontal pipe
B. Vertical pipe
On wall:
4X
3X
&
' )
- - -
+ + +
(
%
A. Handheld communicator
B. Approved IS barrier (for Intrinsically Safe installations only)
C. HART modem
D. Current meter
E. Load resistance (≥250 Ω)
F. Power supply
Note
Rosemount 5300 Level Transmitters with flameproof/explosion-proof output
have a built-in barrier; no external barrier needed.
$
&
%
$
&
%
Note
For the Ex d case, the diagram is only valid if the load resistance is at the + side
and if the - side is grounded, otherwise the maximum load resistance is
limited to 435 Ω.
&
+ + + '
- - -
A. Handheld communicator
B. Approved IS barrier (for Intrinsically Safe installations only)
C. FOUNDATION Fieldbus modem
D. Power supply
Note
Rosemount 5300 Level Transmitters with flameproof/explosion-proof output
have a built-in barrier; no external barrier needed.
)
*
+
- (
$
& ' &
%
A. “A” line
B. “B” line
C. 120 Ω
D. RS-485 Bus
E. Power supply
F. HART -
G. HART +
H. If it is the last transmitter on the bus, connect the 120 Ω termination
resistor.
Note
Rosemount 5300 Level Transmitters with Flameproof/Explosion-proof output
have a built-in barrier; no external barrier needed.(1)
4.6 Grounding
Make sure grounding is done (including IS ground inside Terminal
compartment) according to Hazardous Locations Certifications, national and
local electrical codes.
Note
Grounding the transmitter via threaded conduit connection may not provide
sufficient ground.
Note
In the explosion-proof/flameproof version, the electronics is grounded via the
transmitter housing. After installation and commissioning make sure that no
ground currents exist due to high ground potential differences in the
installation.
%
%
$
&
& &
'
A. Insulate shield
B. Minimize distance
C. Trim shield and insulate
D. Connect shield back to the power supply ground
5. Connect the cable wires (see Figure 4-1, Figure 4-5, and Figure 4-6).
6. Ensure proper grounding (see Grounding).
7. Use the enclosed metal plug to seal any unused port.
Note
Apply PTFE tape or other sealant to the threads.
Note
Make sure to arrange the wiring with a drip loop.
9. Mount the cover making sure the cover is secure to meet explosion-
proof requirements.
10. Turn the jam screw counterclockwise until it contacts the cover.
Required for Flameproof installations only.
6 Configure
Basic configuration can easily be done either with Rosemount Radar Master, a
handheld communicator, AMS Device Manager, DeltaV™, or any other DD
(Device Description) or DTM™ compatible host system. For advanced
configuration features, Rosemount Radar Master is recommended.
FOUNDATION™ Fieldbus
Procedure
1. Select Configure > Guided Setup.
2. Select Level Measurement Setup and follow the instructions.
3. (Optional) Select Volume Calculation Setup.
4. Select Device Specific Setup.
5. Select Restart Measurement.
Function Parameter
Tank diameter (only for ideal tank shapes) TRANSDUCER 1300 >
VOL_IDEAL_DIAMETER
(1) Applicable to “Liquid Product Level” and “Solid Product Level” measurement
modes.
(2) Applicable to “Interface Level with submerged” and “Product Level and Interface
Level” measurement modes.
Procedure
1. Measure tank height.
/727
0
1
2
3
4
5
6
7
8
4. Slide the weight up.
Stainless steel 5
9 Product certifications
Rev 9.17
9.5 USA
9.5.1 E5 Explosionproof (XP), Dust-Ignitionproof (DIP)
Certificate FM16US0444X
Standards FM Class 3600 – 2011; FM Class 3610 – 2010; FM Class 3611 –
2004; FM Class 3615 – 2006; FM Class 3810 – 2005; ANSI/ISA
60079-0 – 2013; ANSI/ISA 60079-11 – 2012; ANSI/NEMA® 250
– 2003;
Markings XP CL I, DIV 1, GP B, C, D; DIP CLII/III, DIV 1, GP E, F, G; T4; -50 °C
≤ Ta ≤ 60 °C / 70 °C; Type 4X
Ui Ii Pi Ci Li
9.5.3 IE FISCO
Certificate FM16US0444X
Standards FM Class 3600 – 2011; FM Class 3610 – 2010; FM Class 3611 –
2004; FM Class 3615 – 2006; FM Class 3810 – 2005; ANSI/ISA
60079-0 – 2013; ANSI/ISA 60079-11 – 2012; ANSI/NEMA 250 –
2003;
Markings IS CL I, II, III, DIV 1, GP A, B, C, D, E, F, G; T4; in accordance with
control drawing 9240030-936; IS CL I, Zone 0 AEx ia IIC T4 in
Ui Ii Pi Ci Li
9.6 Canada
9.6.1 E6 Explosionproof, Dust-Ignitionproof
Certificate 1514653
Standards CSA C22.2 No.0-M91, CSA C22.2 No.25-1966, CSA C22.2
No.30-M1986, CSA C22.2 No.94-M91, CSA C22.2 No.142-
M1987, CSA C22.2 157-92, CAN/CSA C22.2 No. 60529:05,
ANSI/ISA 12.27.01-2003
Markings Explosionproof CL I, DIV 1, GP B, C, D; Dust-Ignitionproof CL II,
DIV 1 and 2, GP E, F, G and coal dust, CL III, DIV 1, Type 4X/IP66/
IP67
Ui Ii Pi Ci Li
9.6.3 IF FISCO
Certificate 1514653
Standards CSA C22.2 No.0-M91, CSA C22.2 No.25-1966, CSA C22.2
No.30-M1986, CSA C22.2 No.94-M91, CSA C22.2 No.142-
M1987, CSA C22.2 157-92, CAN/CSA C22.2 No. 60529:05,
ANSI/ISA 12.27.01-2003
Markings CL I, DIV 1, GP A, B, C, D, T4 see installation drawing
9240030-937; Non-Incendive Class III, DIV 1, Haz-loc CL I DIV 2,
GP A, B, C, D, Maximum Ambient Temperature +60 °C, T4, Type
4X/IP66/IP67, Maximum Working Pressure 5000 psi, Dual Seal.
Ui Ii Pi Ci Li
9.7 Europe
9.7.1 E1 ATEX Flameproof
Certificate Nemko 04ATEX1073X
Standards EN 60079-0:2012, EN 60079-1:2014, EN 60079-11:2012, EN
60079-26:2015, EN 60079-31:2014
Markings II 1/2G Ex db ia IIC T4 Ga/Gb, (-40 °C ≤ Ta ≤ +60 °C /+70 °C)
II 1D Ex ta IIIC T69 °C/T79 °C Da, (-40 °C ≤ Ta ≤ +60 °C /+70
°C)
Um = 250 V
2. Parts of the sensor probes, for type 5300 are non-conducting material
covering metal surfaces. The area of the non-conducting part exceeds
the maximum permissible areas for Group III according to EN
60079-0.2012 clause 7.4:3. Therefore, when the probe is used in a
potentially explosive atmosphere group III, EPL Da, appropriate
measures must be taken to prevent electrostatic discharge.
3. 1/2” NPT threads need to be sealed for dust and water ingress
protection, IP 66, IP 67 or “Ex t”, EPL Da or Db is required.
Ui Ii Pi Ci Li
Ui Ii Pi Ci Li
Ui Ii Pi Ci Li
9.8 International
9.8.1 E7 IECEx Flameproof
Certificate IECEx NEM 06.0001X
Standards IEC 60079-0:2011, IEC 60079-1:2014-06, IEC 60079-11:2011;
IEC 60079-26:2014, IEC 60079-31:2013
Markings Ex db ia IIC T4 Ga/Gb (-40 °C ≤ Ta ≤ +60 °C /+70 °C)
Ex ta IIIC T69 °C/T79 °C Da (-40 °C ≤ Ta ≤ +60 °C /+70 °C)
Um=250 VAC, IP66/IP67
Ui Ii Pi Ci Li
Ui Ii Pi Ci Li
Ui Ii Pi Ci Li
9.9 Brazil
9.9.1 E2 INMETRO Flameproof
Certificate UL-BR 17.0188X
Standards ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-1:2016,
ABNT NBR IEC 60079-11:2013, ABNT NBR IEC 60079-26:2016,
ABNT NBR IEC 60079-31:2014
Markings Ex db ia IIC T4 Ga/Gb (-40 °C ≤ Tamb ≤ +60 °C /+70 °C)
Ex ta IIIC T69 °C/T79 °C Da (-40 °C ≤ Tamb ≤ +60 °C /+70 °C)
Um=250 Vac, IP66/67
Ui Ii Pi Ci Li
Ui Ii Pi Ci Li
9.10 China
9.10.1 E3 China Flameproof
Certificate GYJ16.1095X
Standards GB 3836.1/2/4/20-2010, GB 12476.1/5-2013, GB
12476.4-2010
Markings Ex d ia IIC T4 Ga/Gb (-40 °C ≤ Ta ≤ +60 °C/+70 °C)
Ex tD A20 IP 66/67 T69 °C /T79 °C (-40 °C ≤ Ta ≤ +60 °C/+70 °C)
Ui Ii Pi Ci Li
Ui Ii Pi Ci Li
Ui Ii Pi Ci Li
Ui Ii Pi Ci Li
9.12 Japan
9.12.1 E4 Flameproof
Certificate CML 17JPN1334X
Markings Ex d ia IIC T4 Ga/Gb (-40 °C ≤ Ta ≤ +60 °C/+70 °C)
9.14 India
9.14.1 Flameproof, Intrinsically safe
Certificate P392482/1
Markings Ex db ia IIC T4 Ga /Gb
Ex ia IIC T4 Ga
9.15 Ukraine
9.15.1 Flameproof, Intrinsically Safe
Certificate UA.TR.047.C.0352-13
Markings 0 Ex ia IIC T4 X,
1 Ex d ia IIC T4 X
9.16 Uzbekistan
9.16.1 Safety (import)
Certificate UZ.SMT.01.342.2017121
9.17 Combinations
KA Combination of E1, E5 and E6
KB Combination of E1, E5 and E7
KC Combination of E1, E6 and E7
KD Combination of E5, E6 and E7
KE Combination of I1, I5 and I6
KF Combination of I1, I5 and I7
KG Combination of I1, I6 and I7
KH Combination of I5, I6 and I7
KI Combination of IA, IE and IF
KJ Combination of IA, IE and IG
KK Combination of IA, IF and IG
KL Combination of IE, IF and IG
Note
Housing material A, Aluminum, is not to be used on open decks.
Note
Housing material A, Aluminum, is not to be used on open decks.
9.18.3 SDN Det Norske Veritas Germanischer Lloyd (DNV GL) Type Approval
Certificate TAA000020G
Intended Use DNV GL rules for classification – Ships, offshore units, and
high speed and light craft
Location classes
Temperature D
Humidity B
Vibration A
EMC B
Enclosure C
Note
Housing material A, Aluminum, is not to be used on open decks.
Note
Housing material A, Aluminum, is not to be used on open decks.
GOST Kazakhstan
Certificate KZ.02.02.03473-2013
GOST Russia
Certificate SE.C.29.010.A
GOST Uzbekistan
Certificate 02.2977-14
Certificate FM13ATEX0076X
Standards EN60079-0:2012, EN60079-1:2007, IEC60079-7:2007
Markings II 2 G Ex de IIC Gb
½ - 14 NPT ½ NPT
½- 14 NPT ½ - 14 NPT
¾ - 14 NPT ¾- 14 NPT
½ - 14 NPT ½ - 14 NPT
G1/2 G1/2
Electronics
Assembly X O O O O O
䓝⫸乬ẞ
Housing
Assembly O O O O O O
体乬ẞ
This table is proposed in accordance with the provision of SJ/T11364
本表格系依据SJ/T11364的奬⭂侴⇞ἄį
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement
of GB/T 26572.
O: 意ᷢ宍悐ẞ䘬㚱⛯峐㛸㕁ᷕ宍㚱⭛䈑峐䘬⏓慷⛯ỶḶGB/T 26572所奬⭂䘬旸慷天㯪į
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is
above the limit requirement of GB/T 26572.
X: 意ᷢ⛐宍悐ẞἧ䓐䘬㚱⛯峐㛸㕁慴炻军⮹㚱ᶨ䰣⛯峐㛸㕁ᷕ宍㚱⭛䈑峐䘬⏓慷檀ḶGB/T 26572所奬⭂䘬旸慷天㯪į
Asia Pacific Regional Office Middle East and Africa Regional Office
Emerson Automation Solutions Emerson Automation Solutions
1 Pandan Crescent Emerson FZE P.O. Box 17033
Singapore 128461 Jebel Ali Free Zone - South 2
+65 6777 8211 Dubai, United Arab Emirates
+65 6777 0947 +971 4 8118100
[email protected] +971 4 8865465
[email protected]
Linkedin.com/company/Emerson-
Automation-Solutions ©2019 Emerson. All rights reserved.