Power Systems Lab Manual: Department of Electrical Engineering
Power Systems Lab Manual: Department of Electrical Engineering
Power Systems Lab Manual: Department of Electrical Engineering
Name:……………………………………………
Roll no:………………………………………….
Course:B.Tech……..Year…… Semester…………
Branch: ……………………………………………
Experiment No. 1: To study Ferranti effect and determine A, B, C, D parameters of short and medium
transmission line.
Experiment No. 2: To study the characteristics of microcontroller based over current relay.
Experiment No. 3: To perform symmetrical fault analysis in AC network analyser.
Experiment No. 4: To perform symmetrical fault analysis in DC network analyser & perform the
experiment for Unsymmetrical fault analysis on DC network.
Experiment No. 5: To study the characteristics of the operation of Buchholz relay.
Experiment No. 6: To study the characteristics of the microprocessor based DMT/IDMT over current
relay and determines the time current characteristics.
Experiment No. 7: Testing of negative Sequence relay using the negative sequence kit against negative
sequence current balanced and unbalanced load condition.
Experiment No. 8: To study the characteristics of Electromechanical over current relay.
Experiment No. 9: To study microcontroller base over/ under voltage relay.
Experiment No. 10: To study characteristics of microcontroller based earth fault relay.
Experiment No. 11: To study characteristics of electromechanical earth fault relay.
Experiment No. 12: To find out the string efficiency across the string of insulators.
PROGRAM OUTCOMES:
Engineering Graduates will be able to:
1. Apply the knowledge of mathematics, science, electrical engineering
fundamentals, and an electrical engineering specialization to the solution of
complex electrical engineering problems.
2. Identify, formulate, review research literature, and analyze complex electrical
engineering problems reaching substantiated conclusions using first principles
of mathematics, natural sciences, and engineering sciences.
3. Design solutions for complex electrical engineering problems and design
system components or processes that meet the specified needs with appropriate
consideration for the public health and safety, and the cultural, societal, and
environmental considerations.
4. Use research-based knowledge and research methods including design of
experiments, analysis and interpretation of data, and synthesis of the
information to provide valid conclusions.
5. Create, select, and apply appropriate techniques, resources, and modern
engineering and IT tools including prediction and modelling to complex
electrical engineering activities with an understanding of the limitations.
6. Apply reasoning informed by the contextual knowledge to assess societal,
health, safety, legal and cultural issues and the consequent responsibilities
relevant to the professional engineering practice.
7. Understand the impact of the professional electrical engineering solutions in
societal and environmental contexts, and demonstrate the knowledge of, and
need for sustainable development.
8. Apply ethical principles and commit to professional ethics and responsibilities
and norms of the engineering practice.
9. Function effectively as an individual, and as a member or leader in diverse
teams, and in multidisciplinary settings.
10. Communicate effectively on complex engineering activities with the
engineering community and with society at large, such as, being able to
comprehend and write effective reports and design documentation, make
effective presentations, and give and receive clear instructions.
11. Demonstrate knowledge and understanding of the engineering and management
principles and apply these to one’s own work, as a member and leader in a
team, to manage projects and in multidisciplinary environments.
12. Recognize the need for, and have the preparation and ability to engage in
independent and life-long learning in the broadest context of technological
change.
PROGRAM SPECIFIC OUTCOMES (PSOs)
1. To impart State-of-Art knowledge in the field of Electrical Engineering and
hand on application based practical training with regular Academic and
Industry interaction.
2. To incorporate research environment and innovation projects towards
assimilation of global technology in order to meet needs of automation and
articulate a higher education system of ethics and mind set for a realistic
education.
Course Objectives
1. To study Characteristics of different types of electromechanical Relays.
2. To study Characteristics of different types of microprocessor based
Relays.
3. To perform Different types of fault analysis in AC/DC Network
Analyzer.
4. To Study string efficiency across the insulators
5. To study the ABCD parameters and various compensation techniques on
Transmission/Distribution line model.
INDEX
SI.NO: DATE EXPERIMENT SIGNATURE
SI.NO: DATE EXPERIMENT SIGNATURE
STUDY EXPERIMENTS
EXPERIMENT NO-1
AIM: To study Ferranti effect and determine A, B, C, D parameters of short
and medium transmission line.
APPARATUS: -
3 Digital Voltmeter 2
4 Digital Ammeters 2
THEORY:
Transmission line model consists of four sections and each section represents 50 Km long 400KV
transmission line. Parameters of 50 Km long 400KV Transmission line are taken as:
Series Inductance = 80 mH
ABCD parameters are widely used in analysis of power transmission engineering where they will be
9
tuned as “Generalised Circuit Parameters” ABCD parameters are also called as “Transmission
Parameter”. It is conventional to designate the input port as sending end and the output port as receiving
end while representing ABCD parameters.
A long transmission line draws a substantial quantity of charging current. If such a line is open circuited
for a very lightly loaded at the receiving end, the voltage at the receiving end may become higher than
the voltage at the sending end. This is known as ‘FERRANTI EFFECT’ and is due to the voltage drop
across the line inductance (due to the charging current) being in phase the sending end voltage. The both
capacitance and inductance are necessary to produce this phenomenon. The capacitance and charging
current is negligible in short line but significant in medium length lines and appreciable in long lines.
Therefore, phenomenon occurs in medium and long lines.
Is IR
VR
Vs
𝑉 𝐴 𝐵 𝑉𝑅
[ 𝑆 ]= [ ][ ]
𝐼𝑆 𝐶 𝐷 𝐼𝑅
This gives:-
𝑉𝑆
A= Reverse Voltage ratio and is unit less
𝑉𝑅
𝐼𝑆
C= Transfer admittance, unit is mho
𝑉𝑅
𝑉𝑆
B= Transfer impedance and expressed in ohm
𝐼𝑅
𝐼𝑆
D= Reverse current ratio and is unit less
𝐼𝑅
In hybrid parameter representation both short circuit and open circuit terminal conditions are utilized hence
this parameter representation is known as hybrid parameter representation.
10
Here:-
𝑉𝑆 ℎ ℎ12 𝐼𝑆
[ ]= [ 11 ][ ]
−𝐼𝑅 ℎ21 ℎ22 𝑉𝑅
𝐼𝑅
ℎ21 = Forward current gain is a unit less quantity
𝐼𝑆
In a similar way for the sending end open circuited i.e. IS=0
𝑉
ℎ12 = 𝑉𝑆 Reverse voltage gain and has no unit
𝑅
𝐼
ℎ22 = 𝑉𝑅 Output admittance and is expresses in mho
𝑅
In a transmission line, if the impedance at the sending end with Zi2 at receiving end be Zi1 at input port is
Zi2 then Zi1 and Zi2 are termed as the IMAGE IMPEDANCE OF THE NETWORKS.
We can conveniently express the image impedance in terms of ABCD constant as:-
𝐴𝐵 𝐵𝐷
Zi1 = √𝐶𝐷 and Zi2 = √ 𝐴𝐶
However image impedance does not completely define a network. We need another parameter which we
shall get from the voltage and current ratio known as image transfer constant and can be calculated as:-
1 𝑉 𝐼 𝐵𝐶
= 2 𝑙𝑛 (𝑉 𝑆 𝐼𝑆 ) = 𝑡𝑎𝑛ℎ−1 √𝐴𝐷
𝑅 𝑅
11
CALCULATIONS & OBSERVATIONS
VR
Vs
IR = 0
Vs
12
IR = 0
Vs
Calculation Table:-
IR
Vs
𝐴𝐵
Zi1 = √𝐶𝐷
13
𝐵𝐷
Zi2 = √𝐴𝐶
𝐵𝐶
= 𝑡𝑎𝑛ℎ−1 √𝐴𝐷
PROCEDURE:
STEP 1:-
(i) To find out A and C parameters connected voltage supply of 220V to sending end (1-1’) and open
circuit (5-5’) receiving end.
(ii) Observe the voltage of Vs, Is and VR with the help of voltmeters and ammeters in the experimental kit.
STEP 2:-
(i)To find out B and D receiving end (5-5’) is short circuited and supply of 220V is given to sending end (1-1’).
(ii)Observe the voltage of Vs, Is and IR.
STEP 3:-
(i) To find out the value of h11 and h21 take the reading of VS, IS and IR from step No.2.
STEP 4:-
(i) To find out the value of h12 and h22 supply the 220V at receiving end terminal (5-5’) and open circuit
the sending end terminal (1-1’).
(ii) To find out the image parameters take the value of A, B, C and D from step No.1 & 2.
14
RESULT: ABCD parameters of medium transmission line (T and PI network) are computed.
15
EXPERIMENT NO- 2
AIM: To study micro controller based Over Current Relay
APPARATUS: -
1 VPL-01 Module 1
THEORY:
The over current relays are used to sense the fault currents and over-load currents and trips off the system.
Micro controller is used for the control operation. The programming is done in such a way that when the fault
current value is above the set value the relay is closed/ opened (depends on connection) and it trips the circuit.
The tripping of the relay is indicated by the LED. The LCD displays the set time, set current, fault current and
tripping time. The following figure show front panel of VPL-01 module.
16
ii. FRONT PANEL DESCRIPTION
Display
LCD – Display the selection, set mode and relay status.
1 - Increment the Current and time settings.
2 – Decrement the Current and time settings.
3 – Cursor movement
4 –Enter the setting values & set to the processor.
RST -Reset the all current setting values.
‘9’ PIN ‘D’ Connector – Its used to interface with PC.
Power- Power N/OFF the Switch.
LED (Indicate the relay tripping action)
LED ‘ON’ – Relay Trip
LED ‘OFF’- Relay is normal condition (not Trip)
Current Sensing – Current sensing output = 5VAC
Banana Connector
P & N (Current coil/input) – Apply input variable current (0-20A)
NO Contact – This terminal indicates the relay is normally in closed condition after relay tripped, this two
terminal is closed with relay contacts.
NC Contact- This terminal indicates the relay is normally closed condition after relay tripped, this two
terminal is opened with relay contacts.
PROCEDURE:
1. Current source is connected to across the banana connector L1 & L2 of VPL-01 module.
2. Power ON the VPL-01 module (Micro controller based Over Current relay). The LCD displays shows
the following with a delay of few seconds between each display.
17
VI MICROSYSTEMS
VI MICROSYSTEMS PRESENTS
The selection between type of relay of relay should be made by pressing the appropriate buttons in the
display. The details of buttons in the display.
1- Selecting and incrementing
2- Selecting and decrementing
3- Cursor movement
4- Enter
RST- Reset the relay system
The type of operation to be carried out is displayed and is selected by the buttons 1 or 2.
Select buttons
1. DMT (Define Minimum Time)
2. IDMT (Inverse Definite Minimum Time)
i. Select IDMT
1. The IDMT operation can be selected by pressing 2.The set current I(s) has to be entered. The LCD
displays the following.
18
ENTER AMP : 00.1A
………. [0.1-15A]……..
………. [0.1-15A]……..
2. The button 4 is pressed. (All the set values are sent to the processor). Now the display shows.
………[0.1-2s]….
………[0.1-2s]….
The Time Multiplier Setting (TMS) value is to be entered. The range of TMS is 0.1 to 2s. This value is
entered by pressing 4.
NOTE:
If the fault current < set Current the LCD displays the Current values by default as
CURRENT: 3
Now press the RST button. Again set the same values and set the fault current is above the set Current.
4. If the fault current > set Current the LCD displays
OVER CURRENT
Time: 1s
The calculate time for relay tripping is obtained from the formula.
𝐾
t = TMS X [ 𝐼 𝛼 ] + 𝐶
−1
𝐼𝑆
The IDMT used is of normal inverse type. So the values of k, α, C are constant and are K=0.14, α=0.02 and
19
C=0. I is the fault Current and Is is the set Current of the relay unit.
5. The time starts to increase from 0.1S to until end of the calculated time in sec, then the relay coil is
energized and trips the relay contacts. At the same time LED glows. After shows the LCD display.
Relay Tripped…
Due to Over Current
6. Now LCD displays the following message one by one continuously until the relay system is reset and LED
is glow.
Set AMP : 5A
Tripped AMP : 10
7. Press the RST button, Reset the processor and Relay tripping action.
………. [0.1-15A]……..
………. [0.1-15A]……..
2. The button 4 is pressed. (All the set values are sent to the processor). Now the display shows.
………[0-300s]….
20
Set the Reset Time value by using 1, 2 & 3 buttons
………[0-300s]….
OVER Tripped…….
SET : 7S T:7S
After the tripping of relay, the following messages are displayed one by one continuously until the system is
reset.
Relay Tripped…….
Due to Over Current
TABULATION:
IDMT
S.NO. Set Current Fault Current Time Multiplier Calculated Relay tripping Time Actual
21
(A) (A) Setting (sec) Relay
(sec) Tripping
Time(sec)
DMT:
S.NO. Set Current Fault Current Set Time Actual Relay Tripping
(A) (A) (sec) Time(sec)
22
EXPERIMENT NO. 3
AIM: To perform symmetrical fault analysis in AC network analyzer.
APPARATUS USED:
1 Network Analyzer 1
2 Ammeter (0-2A) 4
3 Voltmeter (0-2V) 1
THEORY:
SYMMETRICAL FAULT
Fault involving all three phases is called a symmetrical fault (Balanced fault). Three phase short circuit is a
symmetrical fault. When insulation of the system fails at one or more points or a conducting object comes in
contact with live point, a fault occurs. The system must be protected against heavy flow of short circuit by
means of protective equipment.
UNSYMMETRICAL FAULT:
The fault involving only one or two phases is called Unsymmetrical (Unbalanced fault). Single Line to
Ground fault, Line-Line fault. Double line to ground fault are unsymmetrical faults. The majority of system
fault are unsymmetrical fault. The system must be protected against these faults currents by mean of circuit
breaker & relays. For the choice of protective equipment we must estimate the magnitude of current that
would flow under fault condition. Unsymmetrical fault analyses require special tools like symmetrical
components. Network analyzer can be for analysis of any type of unsymmetrical fault. First of all positive,
negative and zero sequence networks are drawn of the system to be analyzed. Depending upon the type of
unsymmetrical fault, these networks are interconnected on the Network analyzer.
For L-G fault, Positive, negative and zero sequence are connected in series.
For L-L fault, positive & negative are connected in parallel.
For LL-G fault, positive sequence N/W is in series with the parallel combination of negative sequence
network N/W & zero sequence N/W.
For symmetrical fault (L-L-L-G) only positive sequence network is required.
Symmetrical fault analysis is performed on the following sample problems.
23
PANEL VIEW
PROCEDURE:
1. Draw the single line diagram of the system indicating the fault point as per Figure-1.
Figure 1
2. Draw the positive sequence network, negative sequence network and zero sequence network of the system
24
as the case may be.
In the present sample problem the negative sequence network is as shown in Figure-2
Figure 2
3. Redraw the positive sequence network by replacing the voltage source with per unit voltage source and by
multiplying the inductances by a suitable factor so that sequence network can be simulated on the network
analyzer. In the present case multiplication factor is as 31.4 (Reason for taking multiplication factor as 31.4 is
that 0.05 Ohms reactance into 5mH inductance as shown below)
If XL=0.05
2пfL =0.05
0.05 5
L= * 100Mh = 31.4 mH
314
And the positive sequence network is redrawn as shown in figure 3.
25
Figure 3
1. Simulate the system as shown in Figure-3 on the network analyzer (for the convenience of simulating the
system on the network analyzer it preferred to mark positions of nodes on figure-3 and corresponding making
shall be done with a marker on the front accordingly for different setups).
2. Keep the variac in the minimum position and switch on the supply of the network analyzer.
3. Adjust the voltage of the source as one volt with the help of variac.
4. Record the reading of the currents I1, I2, I3 and I4 as under:-
Source Voltage I1 I2 I3 I4
5. Calculate the total fault current and fault current contributed by each generator. For the sample problem
Current contributed by
Generator G1= I1 *multiplication factor * Base Current
Generator G2= I2 *multiplication factor * Base Current
Generator G3= I3 *multiplication factor * Base Current
Total Fault Current = I4 * multiplication factor * Base Current
𝐵𝑎𝑠𝑒 𝑀𝑉𝐴 50
Base Current (in KA) = 𝐵𝑎𝑠𝑒 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 (𝐾𝑉) = = 2.62 KA
√3∗11
26
EXPERIMENT NO. 4
AIM: To perform symmetrical fault analysis in DC network analyzer & to perform the experiment for
unsymmetrical fault analysis on DC network.
APPARATUS USED:
1 DC Network Analyzer 1
Ammeter (0-2A) 4
Voltmeter (110 V) 1
Resistance 1,2,3,4,5,10
ohm
2 Dc Supply 1
3 Connecting Wires
THEORY:
Case (i) SYMMETRICAL FAULT
Fault involving all the three phase (balance fault) is called symmetrical fault. Three phase short circuit is a
symmetrical fault. Three phase short circuit is a symmetrical fault. When the insulation of the system fails at
one or more point of a conduction object comes in contact with live point a fault occurs. The system must be
protected again heavy flow of short circuit currents by means of protection equipments.
For the proper choice of the circuit breakers and protective equipment, we must estimate the magnitude of the
current that would flow under short circuit condition.
For finding out the short circuit current, DC and AC Network analyzer are used. The circuit of the system to
be analyzed is made on the network analyser. The problem to be solved is simulated on the analyzer. The fault
is created and fault current is measured. This fault current when multiplied with base current gives the actual
fault under fault conditions in the actual system.
SAMPLE PROBLEM
27
In case the generators and lines have different MVA values then for making calculations, the reactance are
converted to some base MVA, normally the highest values is taken as base MVA.
𝑁𝑒𝑤𝑀𝑉𝐴 𝑂𝑙𝑑𝐾𝑉 2
𝑍𝑛𝑒𝑤 = 𝑍𝑜𝑙𝑑 ∗ ∗ (𝑁𝑒𝑤𝐾𝑉)
𝑂𝑙𝑑𝑀𝑉𝐴
𝐵𝑎𝑠𝑒𝑀𝑉𝐴
Base Current IB = 𝐵𝑎𝑠𝑒𝑀𝑉𝐴 KV
In our problem:-
(50/3)∗106
𝐼𝐵 = (11/ A
√3)∗103
Reactance diagram of the system is as under:
Replacing the generator with p.u. voltage source and further these voltage sources are in parallel so can be
represented by a single voltage source of 1V DC. In case of DC network analyzer, the reactance of the
generators and transmission lines are replaced with the resistance values.
28
Multiplying the resistance values with multiplying factor of 100, we get the circuit as under:-
29
OBSERVATIONS:
V I1 I2 I3 I4
30
31
32
Reducing the Sequence Networks with series parallel combination & Inter connecting we get
Procedure:
i. Take multiplication factor of 100.
ii. Make the connections as shown in fig 3
iii. Connect the DC voltage Source.
iv. Note down the Ammeter readings.
v. It gives the fault current.
Formula Used:
𝐸𝑎 𝑍2 𝑍0
𝐼𝐹 = +( + 𝑍0 )
𝑍1 𝑍2
Conclusion:
Theoretical fault current =
Practical fault Current =
𝑇ℎ𝑒𝑜𝑟𝑖𝑡𝑖𝑐𝑎𝑙 𝑓𝑎𝑢𝑙𝑡 𝐶𝑢𝑟𝑟𝑒𝑛𝑡−𝑃𝑟𝑎𝑐𝑡𝑖𝑐𝑎𝑙 𝑓𝑎𝑢𝑙𝑡 𝑐𝑢𝑟𝑟𝑒𝑛𝑡
% age error = ∗ 100
𝑇ℎ𝑒𝑜𝑟𝑡𝑖𝑐𝑎𝑙 𝑓𝑎𝑢𝑙𝑡 𝑐𝑢𝑟𝑟𝑒𝑛𝑡
34
EXPERIMENT NO.5
AIM: To study the operation of Buchholz relay.
APPARATUS USED:
THEORY:
Buchholz relay function is based on very simple mechanical phenomenon. It is mechanically actuated.
Whenever there will a minor internal fault in the transformer such as an insulation faults between turns, break
down of core of transformer, core heating, the transformer insulating oil will be decomposed in different
hydrocarbon gases, CO2 and CO. The gases produced due to decomposition of transformer insulating oil will
accumulate in the upper part the Buchholz container which causes fall of oil level in it.
Fall of oil level means lowering the position of float and thereby tilting the mercury switch. The contacts of
this mercury switch are closed and an alarm circuit energized. Sometime due to oil leakage on the main tank
air bubbles may be accumulated in the upper part of the Buchholz container which may also cause fall of oil
level in it and alarm circuit will be energized. By collecting the accumulated gases from the gas release
pockets on the top of the relay and by analyzing them one can predict the type of fault in the transformer.
More severe type of faults, such as short circuit between phases or the earth and faults in the tap changing
environment, are accompanied by surge of oil which strikes the baffle plate and causes the mercury switch of
the lower element to close. This switch energized the trip circuit of the circuit breakers associated with the
transformer and immediately isolates the faulty transformer from the rest of the electrical power system by
inter tripping breakers associated with both LV and HV sides of the transformer. This is how Buchholz relay
functions.
35
PROCEDURE:
i. Close all the balls.
ii. Press the air compressor in order to increase the pressure.
iii. Immediately open the valve number 1.
iv. Oil from the tank rushes into the Buchholz relay & fill it completely.
v. Open the output valve of Buchholz relay.
vi. Oil will rush out from the Buchholz relay into tank.
vii. When the oil reaches at the half level, the buzzers starts ringing to show that the low recipient fault
has occurred.
36
EXPERIMENT NO.6
AIM: To study the characteristics of microprocessor based DMT/IDMT over current relay and
determines the time current characteristics.
APPARATUS USED:
THEORY:
There are several over current protection such as fuse, thermal relay & IDMT Relay. IDMT (Inverse
Definite Minimum Time) Relay is high accuracy over current relay. The over current relay are used to sense
the current and over-load currents and trips off the system. Micro controller is used for the control
operation. The programming is done in such a way that when the fault current value is above the set value
the relay is closed/ opened (depends on connection) and it trips the circuit. The tripping of the relay is
indicated by the LED. The LCD displays the set time, set current, fault current and tripping time.
CIRCUIT DIAGRAM:
FRONT PANEL VIEW
37
PROCEDURE: MICRO CONTROLLER BASED OVER CURRENT RELAY
i. Current source is connected across the banana connector L1 & L2 of VPL-01 module.
ii. Power ON the VPL-01 module (Micro controller based Over Current relay). The LCD display shows
the following with a delay of few seconds between each display.
iii.
VI MICROSYSTEMS
VI MICROSYSTEMS PRESENTS
The selection between types of relay should be made by pressing the appropriate buttons in the display.
The details of buttons in the display.
1-Selecting and incrementing
2-Selecting and decrementing
3-Cursor movement
4-Enter RST-Reset the relay system.
The type of operation to be carried out is displayed and is selected by the buttons 1 or 2.
Select buttons
1. DMT (Definite Minimum Time)
2. IDMT(Inverse Definite Minimum Time)
I. SELECT IDMT
1. IDMT is selected by pressing 2, then the set Current (Is) of the relay unit is to be entered.
The LCD displays,
38
ENTER AMP : 00.1 A
……………[0.1-15A]
……………[0.1-15A]
2. The button 4 is pressed. (All the set values are sent to the processor). Now the display shows.
……………[0.1-2s]
……………[0.1-2s]
The Time Multiplier Setting (TMS) value is to be entered. The range of TMS is 0.1 to 0.2s. This value is
entered by pressing 4.
If the fault Current< Set current the LCD displays the current values by default as
CURRENT :3
Now press the RST button. Again set the same values and set the fault current is above the set Current.
39
4. If the fault Current > set Current then the LCD displays
OVER CURRENT
Time: 01.0s
K
t = TMS * [ 1 ∝ ] +C
(Is) −1
5. The time starts to increase from 0.1s to until end of the calculated time in sec, then the
relay coil is energized and tips the relay contacts. At the same time LED glows. After
shows the LCD display.
Relay Tripped
6. Now LCD displays the following one by one continuously until the relay system is reset and
LED is glow.
7. Press the RST button, reset the processor and relay tripping action.
40
II. SELECT DMT
1. The DMT operation tab is selected by pressing 1. The LCD displays the following.
……………[0.1-15A]
……………[0.1-15A]
2. The button 4 is pressed. (All the set values are sent to the processor). Now the display shows.
……………[0-300s]
……………[0-300s]
OVER Tripped
Set : 7s T:7s
After the tripping of relay, the following messages are displayed one by one continuously until the system is
41
reset.
Relay Tripped
Tripped Time: 7
OBSERVATION TABLE:
IDMT
S.NO.
DMT
S.NO.
RESULT: Characteristics of IDMT relay are drawn after performing the test.
42
EXPERIMENT- 7
AIM: Testing of negative sequence relay using the negative sequence kit against negative sequence
current under balanced and unbalanced load condition.
APPARATUS USED:
1 VPL-04mcl 2
2 3-Phase load 1
3 3-Phase Variac 1
4 Patch Chords 1
THEORY: The negative relays are also called unbalanced relays because these relays provide protection
against negative sequence component of unbalanced currents existing due to unbalanced loads or phase-
phase faults. The unbalanced currents are dangerous from generators and motors point of view as these
currents can cause overheating. Negative sequence relays are generally used to give protection to
generators and motors against unbalanced currents.
A negative sequence relay has a filter circuit which is operative only for negative sequence components.
Low order of over current also causes dangerous situations hence a negative sequence relay has low
current settings. The earth relay provides protection for phase to earth fault but not for phase to phase fault.
A negative sequence relay provides protection against phase to phase faults which are responsible to
produce negative sequence components.
PROCEDURE:
a) Balanced Load Condition
1. Initially keep the MCB and switches in the test kit in OFF condition.
2. Connect Power chord at the back of the module.
3. Give 3-Phase positive sequence supply to the input terminals of Variac.
4. Output of the variac should be connected to the R, Y, B and N terminals which is given along the
side panel of the test kit.
5. Connect terminal U1 to U2, V1 and V2 and W1 &W2 as per the connection diagram.
6. Connect R, Y and B terminals which are given in the front panel of test kit to the 3-phase load
terminal.
7. Now switch on the three phase mains.
8. Switch on the three phase MCB and ON/OFF switch in the front panel of the negative sequence test
kit.
9. Switch on the 3-phase load.
10. Switch on the supply on the negative sequence panel.
43
11. Reset the digital timer using the reset switch given in the front panel.
12. Now increase the 3-phase input voltage. So that the current through the relay should be more than
the relay coil rating.
13. Measure the three phase current.
14. The negative sequence relay will trip according to internal time setting of the relay, when current
through the relay coil reaches the coil current rating.
15. The similar experiment can be performed by reversing the input phase supply terminals fron RYB
to RBY or BYR.
CIRCUIT DIAGRAM:
44
RESULT:
Thus the testing of negative sequence relay using the negative sequence kit under both balanced and
unbalanced load condition has been performed.
45
EXPERIMENT NO. 8
AIM: To study and test the Electromechanical Over Current Relay at different current setting in
IDMT mode.
APPARATUS USED:
1 VPL-102A Module 1
2 PC Power Chord 1
THEORY:
In a power system consisting of generators, transformers, transmission and distribution circuits, it is
inevitable that some failure will occur somewhere in the system. When a failure occurs in any part of the
system, it must be quickly detected and disconnected from the system. There are two principal reasons for
it. Firstly, if the fault is not cleared quickly, it may cause unnecessary interruption of service to the
customers. Secondly, rapid disconnection of faulted apparatus limits the amount of damage to it and
prevents the effect of fault from spreading into the system.
The detection of a fault and disconnection of a faulty section or apparatus can be achieved by using fuses
or relays in conjunction with circuit breakers. A fuse performs both detection and interruption functions
automatically but its use is limited for the protection of low-voltage circuits only. For high voltage circuits,
relays and circuit breakers are employed to serve the desired function of automatic protective gear. The
relays detect the fault and supply information to the circuit breaker, which performs the function of circuit
interruption.
A Protective relay is a device that detects the fault and initiates the operation of the circuit breaker to
isolate the defective element from the rest of the system. The relays detect the abnormal conditions in the
electrical circuits by constantly measuring the electrical quantities, which are different under normal and
fault conditions. The electrical quantities which may change under fault conditions are voltage, current,
frequency and phase angle. The over current relay is a type of relay which operates when the current
exceeds above the set value.
46
FIGURE
47
PROCEDURE:
Connection Procedure
1. Keep all the switches in OFF position.
2. Keep the current adjustment knob in minimum position.
3. Plug the plug setting at desired current value.
4. Connect desired relay contact that may be NO (or) NC Contact to the load terminal.
Experimental Procedure
1. Switch ON the power supply.
2. Switch ON the MCB ON/OFF switch.
3. Press the start button S1. Now start LED glows.
4. Set the fault current value using current adjustment knob provided on the front panel before the
relay will trip. Now the stop clock also in running condition.
5. After setting the fault current then press the stop button S2 and also press the stop clock reset
button to calculate the relay tripping time correctly.
6. Now press the start button S1. The stop clock starts counting and when relay trips, it stops
counting. During the interval the disc in the relay will rotate.
7. When the relay coil trips, the disc returns to the normal (original) position. Note down the relay
current from the RELAY-CURRENT meter and trip time from the stop clock.
8. To repeat the above experiment for the various fault current values do the above procedure.
9. Take the different readings by applying the different fault current values and tabulate all the
readings and draw the graph between different fault current value and the corresponding actual
tripping time.
S.NO. Plug setting value Fault current value Theoretical tripping Actual
time tripping
time
48
Figure 1, Inverse Time Characteristics of Electromechanical Type Over Current Relay
RESULT:
The Electromechanical Type Over Current Relay at different current setting in IDMT mode are studied.
49
EXPERIMENT NO. 9
1 VPL-05 Module 1
THEORY:
Over/Under voltage relays are provided in AC circuits, bus bars, motors, rectifiers, and transformers etc., for
voltage control and reactive power control of network buses and load buses. These relays can have
instantaneous characteristics or inverse characteristics depending upon the construction and design. A define
minimum time delay is provided in both types because the electrical apparatus must be capable of
withstanding overload. Time delay is achieved by programming in the microcontroller which depends upon
the amount of fault current.
50
ii. FRONT PANEL DESCRIPTION
Display
LCD – Display the selection, set mode and relay status.
1- Increment the Current and time settings.
2– Decrement the Current and time settings.
3– Cursor movement
4–Enter the setting values & set to the processor.
RST -Reset the all current setting values.
‘9’ PIN ‘D’ Connector – Its used to interface with PC.
Power- Power N/OFF the Switch.
LED (Indicate the relay tripping action)
LED ‘ON’ – Relay Trip
LED ‘OFF’- Relay is normal condition (not Trip)
Current Sensing – Current sensing output = 5VAC
Banana Connector
P & N (Voltage Coil) – Apply input Voltage(0-400V)
NO Contact – This terminal indicates the relay is normally in closed condition after relay tripped, this two
terminal is closed with relay contacts.
NC Contact- This terminal indicates the relay is normally closed condition after relay tripped, this two
terminal is opened with relay contacts.
PROCEDURE:
1. Initially auto transformer is in minimum position.
2. Connect Power card to auto transformer primary and secondary is connected to primary of step up
transformer (230/400V).
3. Step up transformer secondary is connected to banana connector P & N (Voltage coil input) of VPL-05
module.
4. Power ON the Auto transformer.
5. Adjust the auto transformer at 50% of voltage.
6. Power ON the VPL-05 module. The LCD display shows the following with a delay of few seconds
between each display.
51
VI MICROSYSTEMS PRESENTS
7. The selection between type of relay of relay should be made by pressing the appropriate buttons in the
display.
The details of buttons in the display
1-Selecting and incrementing
2- Selecting and incrementing
3- Cursor movement
4-Enter
RST- Reset the relay system
8. The LCD display shows the two relay system. First select over voltage relay and then afterwards select
under voltage relay.
9. Then select from DMT (Define Minimum Time) and IDMT (Inverse Definite Minimum Time)
1. The IDMT operation can be selected by pressing 2.The set Voltage V(s) has to be entered. The LCD
displays the following.
………. [10-375V]……..
52
ENTER VOLTAGE :100V
………. [10-375V]……..
2. The button 4 is pressed. (All the set values are sent to the processor). Now the display shows.
………[0.1-2s]….
………[0.1-2s]….
The Time Multiplier Setting (TMS) value is to be entered. The range of TMS is 0.1 to 2s. This value is
entered by pressing 4.
NOTE:
If the fault current < set Current the LCD displays the Current values by default as
Voltage: 25 V
Now press the RST button. Again set the same values and set the fault voltage is the set Voltage.
4. If the fault voltage > set voltage the LCD displays
OVER VOLTAGE
Time: 1s
The calculate time for relay tripping is obtained from the formula.
𝐾
t = TMS X [ 𝑉 𝛼 ] + 𝐶
𝑉𝑆
−1
The IDMT used is of normal inverse type. So the values of k, α, C are constant and are K=0.14, α=0.02 and
C=0. I is the fault Voltage and Vs is the set Voltage of the relay unit.
5. The time starts to increase from 0.1S to until end of the calculated time in sec, then the relay coil is
energized and trips the relay contacts. At the same time LED glows. After shows the LCD display.
53
Relay Tripped…
Due to Over Voltage
6. Now LCD displays the following message one by one continuously until the relay system is reset and LED
is glow.
Calc Time : 4s
Trip Time: 4s
7. Press the RST button, Reset the processor and Relay tripping action.
………. [10-375V]……..
………. [10-375V]……..
2. The button 4 is pressed. (All the set values are sent to the processor). Now the display shows.
………[0-300s]….
………[0-300s]….
54
3. Press the button 4.
4. The time starts to increase from 1S to until 007S. After 007S the relay coil is energized and trips the replay
contacts. At the same time LED glows. After relay is tripped the LCD displays it as.
OVER Tripped…….
SET : 7S T:7S
After the tripping of relay, the following messages are displayed one by one continuously until the system is
reset.
Relay Tripped…….
Due to Over Voltage
TABULATION:
IDMT
S.NO. Set Voltage Fault Voltage Time Multiplier Calculated Relay tripping Time Actual
(V) (V) Setting (sec) Relay
(sec) Tripping
Time(sec)
55
DMT:
S.NO. Set Voltage Fault Voltage Set Time Actual Relay Tripping
(V) (V) (sec) Time(sec)
1. The IDMT operation can be selected by pressing 2.The set Voltage V(s) has to be entered. The LCD
displays the following.
………. [10-375V]……..
………. [10-375V]……..
2. The button 4 is pressed. (All the set values are sent to the processor). Now the display shows.
………[0.1-2s]….
………[0.1-2s]….
The Time Multiplier Setting (TMS) value is to be entered. The range of TMS is 0.1 to 2s. This value is
entered by pressing 4.
NOTE:
If the fault current < set Current the LCD displays the Current values by default as
Voltage: 200 V
Now press the RST button. Again set the same values and set the fault voltage is the set Voltage.
4. If the fault voltage > set voltage the LCD displays
UNDER VOLTAGE
Time: 1s
The calculate time for relay tripping is obtained from the formula.
𝐾
t = TMS X [ 𝑉 𝛼 ] + 𝐶
𝑉𝑆
−1
The IDMT used is of normal inverse type. So the values of k, α, C are constant and are K=0.14, α=0.02 and
C=0. I is the fault Voltage and Vs is the set Voltage of the relay unit.
5. The time starts to increase from 0.1S to until end of the calculated time in sec, then the relay coil is
energized and trips the relay contacts. At the same time LED glows. After shows the LCD display.
Relay Tripped…
Due to Under Voltage
6. Now LCD displays the following message one by one continuously until the relay system is reset and LED
is glow.
7. Press the RST button, Reset the processor and Relay tripping action.
………. [10-375V]……..
………. [10-375V]……..
2. The button 4 is pressed. (All the set values are sent to the processor). Now the display shows.
………[0-300s]….
………[0-300s]….
OVER Tripped…….
SET : 7S T:7S
After the tripping of relay, the following messages are displayed one by one continuously until the system is
reset.
Relay Tripped…….
Due to Over Voltage
58
Set voltage: 100V
Tripped VOLTAGE : 200
TABULATION:
IDMT
S.NO. Set Voltage Fault Voltage Time Multiplier Calculated Relay Actual Relay
(V) (V) Setting tripping Time Tripping
(sec) (sec) Time(sec)
DMT:
S.NO. Set Voltage Fault Voltage Set Time Actual Relay Tripping
(A) (A) (sec) Time(sec)
59
EXPERIMENT NO. 10
AIM: To study Micro Controller Based Earth fault relay.
APPARATUS: -
1 VPL-04 Module 1
THEORY:
The earth fault relay is used to provide protection against any earth fault in the windings of the transformer.
The earth relay does not get actuated when there is a balanced flow of current in the windings of transformer.
Hence no current spills into the earth fault relay. But, when there is an earth fault in the protected zone, (i.e.
when phase is connected to earth) no longer the balanced current flows in the transformer windings. Now the
earth fault relays is energized and the circuit breaker is opened. The earth fault is of two types.
1. Electro mechanical type relay
2. Static relay
PROCEDURE:
1. Current source is connected to across the banana connector L1& L2 of VPL-04 module.
2. Power ON the VPL-04 module. The LCD display shows the following with a delay of few seconds
between each display.
VI MICROSYSTEMS PRESENTS
61
3. The selection between type of relay of relay should be made by pressing the appropriate buttons in the
display.
The details of buttons in the display
1-Selecting and incrementing
2- Selecting and incrementing
3- Cursor movement
4-Enter
RST- Reset the relay system
The type of operation to be carried out is displayed and is selected by buttons 1 and 2. Select from DMT
(Define Minimum Time) and IDMT (Inverse Definite Minimum Time)
i. Select IDMT
1. The IDMT operation can be selected by pressing 2.The set Current I(s) has to be entered. The LCD
displays the following.
………. [0.01-1.5A]……..
………. [0.01-1.5A]……..
2. The button 4 is pressed. (All the set values are sent to the processor). Now the display shows.
………[0.1-2s]….
………[0.1-2s]….
62
The Time Multiplier Setting (TMS) value is to be entered. The range of TMS is 0.1 to 2s. This value is
entered by pressing 4.
NOTE:
If the fault current < set Current the LCD displays the Current values by default as
Current: 0.30
Now press the RST button. Again set the same values and set the fault current is the set Current.
4. If the fault current > set current the LCD displays
OVER CURRENT
Time: 1s
The calculate time for relay tripping is obtained from the formula.
𝐾
t = TMS X [ 𝐼 𝛼 ] + 𝐶
𝐼𝑆
−1
The IDMT used is of normal inverse type. So the values of k, α, C are constant and are K=0.14, α=0.02 and
C=0. I is the fault Voltage and Vs is the set Voltage of the relay unit.
5. The time starts to increase from 0.1S to until end of the calculated time in sec, then the relay coil is
energized and trips the relay contacts. At the same time LED glows. After shows the LCD display.
Relay Tripped…
Due to Over Voltage
6. Now LCD displays the following message one by one continuously until the relay system is reset and LED
is glow.
Calc Time : s
Trip Time: s
63
7. Press the RST button, Reset the processor and Relay tripping action.
………. [0.1-1.5A]……..
………. [0.1-1.5A]……..
2. The button 4 is pressed. (All the set values are sent to the processor). Now the display shows.
………[0-300s]….
………[0-300s]….
OVER Tripped…….
SET : 7S T:7S
After the tripping of relay, the following messages are displayed one by one continuously until the system is
reset.
Relay Tripped…….
Due to Over Current
TABULATION:
IDMT
S.NO. Set Current Fault Current Time Calculated Relay tripping Actual
(A) (A) Multiplier Time Relay
Setting (sec) Tripping
(sec) Time(sec)
DMT:
S.NO. Set Current Fault Current Set Time Actual Relay Tripping
(A) (A) (sec) Time(sec)
65
EXPERIMENT NO. 11
AIM: To study the Earth fault Relay for AC Motor Phase to Earth fault protection using Earth fault
relay test setup trainer module (VPL-04A).
APPARATUS: -
1 VPL-04 Module 1
2 0.5 HP AC motor 1
5 Patch Chords 1
THEORY:
In electrical engineering, a protective relay is a relay device designed to trip a circuit breaker when a fault
is detected. The first protective relays were electromagnetic devices, relying on coils operating on moving
parts to provide detection of abnormal operating conditions such as over-current, over-voltage,
reverse power flow, over-frequency, and under-frequency.
The relays detect the abnormal conditions in the electrical circuits by constantly measuring the electrical
quantities, which are different under normal and fault conditions. The electrical quantities which may
change under fault conditions are voltage, current, frequency and phase angle. The earth fault relay is a
type of relay which operates when the earth current exceeds the set value.
66
67
CONNECTIONS:
1. Give 1ф supply to module setup, connect 3ф AC input supply R,Y and B to test setup through the
terminals provided on the right side of the module. Black connector is the earth terminal.
2.Connect motor input R, Y, B and Neutral terminals to the 3 ф AC output terminals provided on the left
side of the module (Black terminal is neutral).
3. Connect desired relay contact (may be NO or NC contacts) to the Load terminal.
4. Connect one of the phase terminal of the motor to the earth through rheostat and portable ammeter to the
machine body. Machine body should be earthed.
PROCEDURE:
1. Set the earth fault relay plug setting value in any of the values.
2. Switch ON the power supply to the module.
3. Switch ON the power ON/OFF switch in the test set-up. And reset the circuit breaker.
4. Switch ON the 3ф power supply.
5. Switch ON the MCB ON/OFF switch.
6. Apply 3 ф AC voltage gradually to the module. The motor starts to rotate.
7. Digital Ammeter shows the neutral current of the motor which is the fault current for relay.
8. When the earth fault current reaches the set value the relay trips according to the fault current.
9. Ammeter displays the fault current at which the relay trips.
10. To apply the various fault current value adjust the rheostat and watch the current through the
rheostat in the ammeter which should not exceed the rheostat current rating.
11. After the relay trip the circuit breaker will break the main supply. And the motor will stop rotate.
12. To repeat the above experiment for the various fault current values first switch of the MCB and
make the rheostat at the maximum position. Then reset the Circuit Breaker.
RESULT:
The Earth fault relay for AC Motor Phase to earth fault protection using earth fault relay test setup trainer
module (VPL-04A)
68
EXPERIMENT NO. 12
AIM: To determine the voltage distribution and string efficiency across the string of insulators with
and without guard ring.
APPARATUS: -
FIGURE 1
69
FIGURE 2
PROCEDURE:
1. Figure 2 represents the string of five suspension insulators and capacitance of each insulators Cs as
2.2microF and stray capacitance to ground/ tower Ce as 0.22 microF.
2. Connect link L1, L2, L3 & L4.
3. Connect link Ph1 & N1 and switch ON the supply.
4. Record the voltage between ab, bc, cd, de, ef and af in table 1.
Table1: Voltage distribution and string efficiency without guard ring
VaVab Vbc Vcd Vde Vef Vaf String Efficiency=Vab/(5*Vaf)
RESULT: String efficiency without guard ring is ---------- and with guard ring is ----------.
70
EXPERIMRNT NO. 13
A) AIM: To demonstrate the concepts of Ferranti effect for a transmission line
Apparatus Required:
Sr. No. Considerations/Equipment Required Specification
Type of conductor Twin Moose
Voltage level 110 V (simulating 400 kV line)
Resistance R in ohm per km 0.009347
Inductive reactance X in ohm per km 0.04488
Half of capacitive susceptance B/2 in µƱ per km 10.8968
Line length in km 350
Number of pi sections: 1
Theory
A long transmission line draws a substantial quantity of charging current. If such a line is
open circuited or very lightly loaded at the receiving end the voltage at receiving end may
become greater than voltage at sending end. This is known as Ferranti Effect and is due to
the voltage drop across the line inductance being in phase with the sending end voltages.
Therefore both capacitance and inductance is responsible to produce this phenomenon. The
capacitance and charging current is negligible in short line but significant in medium line
and appreciable in long line by equivalent π model. Due to high capacitance, the Ferranti
effect is much more pronounced in underground cables, even in short lengths.
Figure below shows the equivalent pi modeling of transmission line used to demonstrate
Ferranti effect and the phasor diagram showing relation between sending end and receiving
end voltage.
71
Figure: Pi-model of transmission line at no load and its Phasor diagram
Procedure
Calculations:
1. Mainly two pi sections are there, which can be connected in series or parallel and
hence accordingly R, L, and C parameter changes. The calculated parameters of each pi-
section (for 350km) is as follows,
Resistance: 3.27 Ω
Inductance: 50 mH Capacitance
(C/2): 12.14 µF
To compute the receiving end voltage of the entire line, equation 1 is used.
respectively
A = D = (ZY/2) + 1 B
=Z
72
C = Y (1 + (ZY/4))
= Vs/A
Ztotal = 3.27+j15.7079 Ω
= 117.55 V
Results:
73
B) AIM : To demonstrate the concepts of shunt reactor compensation as a solution for over
voltage due to unloaded line.
Procedure:
4. Increase inductive load till the receiving end voltage is equal to sending voltage.
5. Note down the sending end and receiving end current and power
factor. Calculations:
As discussed in Ground Work 2, the receiving end voltage and current data from TLS
is used to compute the sending end voltage and current so as to verify the TLS results.
compensation Vr = 110.56 V, Ir
= 0.18 A, pf = 0.32
We have,
Vs = A*Vr + B*Ir Is
= C*Vr + D*Ir
A = D = 1 + (YZ/2) = 0.94009+j0.01247 B
= Z = 3.27145+j15.70796 ohm
74
Results:
75
C) AIM: To determine the various electrical parameters at sending and receiving end for a
loaded line
THEORY
When a transmission line is loaded, it either generates or absorbs reactive power based on
the level of loading. A line which is loaded above its SIL will experience a drop is voltage at
its receiving end. The sending end power factor depends on the load power factor and also
the line parameters and loading level. Further owing to certain resistance present in the line,
the sending end real power is a summation of the line losses and the load power. The aim of
this experiment is to observe the changes in various electrical parameters at the two ends
during various loading condition.
PROCEDURE
Inductance: 50 mH
Capacitance (C/2):
76
12.14 µF
The relation between the sending end and receiving end voltage and currents is
given by:
Vs =
A*Vr +
B*Ir Is =
C*Vr +
D*Ir
A = D = 1 + (YZ/2) =
0.94009+j0.01247 B = Z =
3.27145+j15.70796 ohm
The above equation is used to compute the voltage and currents at any one end, having the
data of the other end.
Results:
2 0.3 0.999 111.84 0.3 109.24 107.6207 0.5 0.5456 -2.3801 -3.9205
3 0.6 0.999 107.6 0.6 108.61 106.7244 0.69 0.7141 0.9299 -0.8204
4 0.9 0.999 102.51 0.9 106.46 105.6839 0.93 0.9379 3.7103 3.0032
5 0.3 0.96 109.31 0.3 108.34 107.0348 0.45 0.4750 -0.8953 -2.1257
77
6 0.6 0.95 102.58 0.6 107 105.9354 0.59 0.5992 4.9833 3.1674
.96
7 0.8 0.95 95.95 0.88 107 104.8 0.81 0.8 10.3 8.4732
8 .08 326 032 941
2 0.3 0.999 60.63 59.4693 58.68 58.0557 1.95 1.4137 -69.39 -82.4919 6.06 2.5983
3 0.6 0.999 115.77 115.6687 111.3 111.709 4.38 3.9593 51.54 -63.5862 6.09 4.9995
9 4
4 0.9 0.999 167.85 167.9089 159.9 159.637 7.95 8.2714 -24.24 -35.8151 5.85 7.1446
5
5 0.3 0.96 59.64 55.5822 55.86 54.5272 3.78 1.0550 -59.91 -68.2949 16.5 15.903
3 8
6 0.6 0.95 105.99 104.4773 101.9 101.274 4.08 3.2032 -24.57 -34.2651 33.7 33.287
1 0 8 2
7 0.88 0.95 145.86 145.8339 139.0 138.935 6.78 6.8988 15.39 1.7643 47.9 45.665
8 1 7 7
78
D) AIM: Transmission line loading with load side shunt capacitive compensation to improve
the voltage profile
Theory:
The transmission line loading depends on the quantum and power factor of the load, which
directly impacts the system voltages. At surge impedance loading of the line, the receiving end
voltage is equal to the sending end voltage for a loss less line. For the higher loadings, the
receiving end voltage will be much less compared to the sending end voltage. The voltage drop in
the EHV transmission line is negligible at unity power factor as the line resistance of the line is
much less compared to series reactance value of the line. When the transmission line is loaded
with reactive power or when the line is loaded beyond the surge impedance loading, the receiving
end voltage drops. The receiving end voltage can be improved by shunt capacitive compensation
at the load point which reduces the reactive power loading on the line and there by reduces the
reactive drop.
Procedure
1) Set up the TLS as explained in Ground Work 1.
2) Ensure that the load end contactor is off.
3) Switch on the main supply.
4) Switch on the line input supply.
5) Slowly increase and adjust the sending end voltage to measure 110V, line to line.
6) Switch on the load side contactor.
7) Connect the resistive load.
8) Connect the inductive load.
9) Vary the load side dimmer to maintain load side power factor at 0.90
10) Take the reading at different loading values.
11) Switch on the shunt capacitor bank to bring back the receiving voltage to above 0.95 pu.
12) At each step, adjust the sending end voltage to be 110 V
79
Calculations:
1. Using the steps given in ground work 2, the calculated parameters of each pi-section is as
follows
Resistance: 3.27 Ω
Inductance: 50 mH Capacitance
(C/2): 12.14 µF
The relation between the sending end and receiving end voltage and currents is given in equation
1 and 2.
= 3.27+j15.7079 Ω
A = D = 1 + (YZ/2) = 0.94009+j0.01247 B = Z
= 3.27145+j15.70796 ohm
Results:
Readings can be taken up for various loadings as per the procedure and verified using given calculation steps.
The readings can be noted down as
loading Vr Ir Compensatio Vs Is Loss
Case n
no hand hand hand
Amp pf (V) (A) (Var) TLS TLS TLS
cal cal cal
1
80
For verifying the results with hand calculation, the receiving end data from TLS is used to
compute the expected sending end data. The loading current is the load current which is held
constant during a particular case. The receiving end current (Ir) is the current at the receiving end
of the line which comprises of effect of load current and current due to shunt compensation.
81
E) AIM : Simulation of parallel operation of transmission line.
Theory
The performance of transmission line depends on the current flowing through it. When a
transmission line is operated in parallel, the performance of the line improves owing to the fact
that the current now gets divided. Further a double circuit also provides redundancy in operation.
Procedure
9. Vary the load side dimmer to maintain load side to adjust the loading to the required power
factor.
10. Record the various electrical parameters at the two ends.
11. Take the reading at different loading values.
Results:
The results are tabulated as given in Table below.These values can be verified using hand
calculations.
loading loss (W) % Vol drop
Case Parallel Single Parallel Single
no Amp pf
circuit circuit circuit circuit
(2x350 (1x350 (2x350 (1x350
km) km) km) km)
0.6 0.999 3.87 4.38 -2.8148 0.9299
1
0.9 0.999 12.66 7.95 -0.5723 3.7103
2
0.6 0.95 3.81 4.08 -0.4181 4.9833
3
0.9 0.95 4.89 6.78 2.6338 10.3941
4
82
F) AIM:Simulation of 3-Phase fault
Procedure
1. Set up the TLS as explained in Ground Work 1.
2. Set the relay to the following setting. Procedure to set relay is provided in the relay catalogue.
Phase Hi-set pick up = 1.5A. Phase Hi-set operating time = 0.1s. Earth
6. Slowly increase and adjust the sending end voltage to measure 110V, line to line.
8. Create three phase fault at end of pi-section and note down the fault current from the relay.
Table below shows the results of simulation of three phase fault at different locations.
Initially only one pi section is considered and three phase fault is created at the end of line that is
at 350 km. Corresponding readings are:
Secondly, two pi sections are connected in series and three phase fault is created at the end of line
that is at 700 km. Corresponding readings are:
Fault current, If = 1.8 A, fault voltage, Vf = 65.3. V, and reactance, X = 36.3 Ohm
Finally two pi sections are connected in series and three phase fault is created at the center of line
that is at 350 km. Corresponding readings are:
Fault current, If = 4.3 A, fault voltage, Vf = 64.1 V, and reactance, X = 14.9 Ohm
83
Fault Type Fault Distance (km) Fault Current (A) Fault Voltage (V)
84
G) AIM: Simulation of SLG, LLG, LL fault
Procedure
:
2. Set the relay to the following setting. Procedure to set relay is provided in the relay
catalogue.
Phase Hi-set pick up = 1.5 A. Phase Hi-set operating time = 0.1s. Earth
Hi-set pick up = 1.5 A. Earth Hi-set operating time = 0.1s.
6. Slowly increase and adjust the sending end voltage to measure 110V, line to line.
8. Create R-N fault at end of each pi-section and note down the fault current (Ir-n) from the
relay.
9. Reset the relay after each fault creation.
Result
Similar to simulation of three phase fault, other type of faults can be created and corresponding
readings can be noted.
All the unsymmetrical types of faults can be created here; SLG fault can be on R or Y or B phase;
similarly LLG can be RYG or YBG or BRG, and LL can be RY or YB or BR. Hence total nine
types of faults can be created.
Fault Type Fault Distance (km) Fault Current (A) Fault Voltage (V)
86
H) AIM: Effect of parallel line on fault current
Procedure:
2. Set the relay to the following setting. Procedure to set relay is provided in the relay
catalogue.
Phase Hi-set pick up = 1.5 A. Phase Hi-set operating time = 0.1s. Earth
8. Slowly increase and adjust the sending end voltage to measure 110V, line to line.
10. Create R-Y and R-N fault at end of the line and note down the fault current from the relay.
Results
As per the procedure explained, different types of faults can be created and its effect can be
compared for both single and parallel line.
The results are tabulated in table below
Results for fault on parallel line
87
APPENDIX
Ground Work 1: PU modeling of the given transmission line on given base and
computation of TLS values
Input data:
The Table 5.1 shows the input details for 400 kV Twin Moose, 110 kV Zebra and
11 kV Dog conductors.
Table : Input data for different conductor types
Type of conductor Twin Moose Zebra Dog
Voltage level (kV) 400 110 11
Resistance R in Ω per km 0.05887 0.06626 0.2572
Inductive reactance X in Ω per km 0.28266 0.38815 0.34482
Half of capacitive susceptance (B/2) in µƱ per km 1.7292 1.49686 18.137
Line length in km 350 150 10
Theoretical background:
In the pu value computation, the base MVA and the base voltage are defined.
Three phase line to line voltage is selected as base kV. Here for the simplifying
88
the calculation base MVA is taken as 400 MVA for 400 kV, 110 MVA for 110
kV and 11 MVA for 11 kV.
Once these two base quantities are defined, the current and impedance base
values are computed as per the procedure given below.
In the simulator, the given transmission line voltage is mapped to 110V, as the
rated voltage of the simulator is 110V. Further, the power base is selected
close to rated power of the line.
= 577.350527 A.
simulator.
Procedure:
89
for 110 kV, 110 MVA and so on.
5. Determine the PU impedance and susceptance values on the selected base
voltage (kV) and selected MVA, the procedure to calculate the pu values is as
follows
Base impedance= (kV*kV)/MVA
Similar calculations can be done for other types of conductor by using above
formulations and actual values given in Table 1. Table 2 gives the calculated
base and respective pu values for all the conductor types.
91
Calculated value
Description Units
400 kV Twin Moose 110 kV Zebra 11 kV Dog
Calculated value
Description Units
400 kV Twin Moose 110 kV Zebra 11 kV Dog
92
Simulator pi section X Ω 15.7079 33.615 19.90827
93
Ground Work 2: Long hand calculation to verify TLS results
Input data:
• R, X and B/2 of line referred to TLS base
• Receiving end voltage and current
• Stray resistance (Rs)
Theoretical background:
The sending end or receiving end voltage and current can be computed using
ABCD parameters provided the other end voltage and current data is available.
The equation used in ABCD parameters is given in (1) and (2).
current respectively
A = D = (ZY/2) + 1 (Z and Y
C = Y (1 + (ZY/4))
Z = (R + Rs) + j X
94
After solving (1) and (2), the complex sending and receiving end
voltage and currents are known. Compute
φs = difference between sending end voltage angle and sending end current angle.
φr = difference between sending end voltage angle and sending end current angle.
Thus
Ps = √3 *Vr*Ir * cos φs
Qs = √3 *Vrl*Ir * sin φs
Pr = √3 * Vrl * Ir * cos φr
Qr = √3 * Vrl * Ir * sin φr
Where Vrl and Vsl is the receiving end and sending end line to line voltage.
In the ABCD parameter method both voltage and current known must
be of the same end, if one end voltage and the other end current is
known the solution must be obtained by iterative methods. Hence for
the purpose of verifying the TLS results, it is suggested that Vr and Ir
values obtained from the TLS meter is taken and then calculate the
expected Vs and Is for the considered case.
95
96