PAVA Catalog en V5

Download as pdf or txt
Download as pdf or txt
You are on page 1of 66

Public Address - Voice Alarm

ATEI Audio Distribution over IP


Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

Public Address & Voice Alarm

D ELIVERING Y OUR M ESSAGE


Ver. 5
ATEIS which boosts 30-years of experience in the
research and development of Public Address and
Voice Evacuation Systems now introduces a new
system that perfectly integrates Fire-Alarm with
Voice-Alarm according to EN 54-16(VACIE&FACIE),
BS 5839-Part 8 and ISO 7240-16, compliance
for large installations and installations with specific
purpose.

IDA8 Digital Public Address and Voice Alarm series is


a 3rd generation modular system that complies with
current architectural demands that required IP-
and/or Fiber-optics Networking to cover for any
complex design possible.

ATEIS has developed and will continue developing


dedicated system for Digital Public Address and
Voice-Alarm applications.

ATEI

D ELIVERING Y OUR M ESSAGE


IDA8 system Index ATEI
Networkable PAVA System Controller–Matrix Mode
IDA8C 6
Networkable PAVA System–Slave Unit–Matrix Mode
IDA8S 9
Networkable PAVA System–Slave Unit–A/B-zoning–Matrix Mode
IDA8SAB 11
Networkable PAVA System–Lo-Z Slave Unit–Matrix Mode
IDA8SL 14
Networkable PAVA System–Controller / Slave Unit–Switch Mode
IDA8C-SW / IDA8SAB-SW 16
IDA8 Full-Redundancy Switching Unit
RU-MAIN / CTL / PDC 24
ATEÏS Net Secured Audio Network Card / Optional Boards
NET-CX / Optional Boards 26 Public Address
IDA8 System Voice Alarm
Ordering Information 29
ATEÏS Studio
Integrated Operation Software
ATEÏS Studio 30
DIVA8G2 System
Compact PAVA system–Master Unit–Switch Mode
DIVA8MG2 33
Compact PAVA system–Slave Unit–Switch Mode
DIVA8SG2 36
Amplifiers
Digital Power Amplifiers
DPAfour 41
Security Power Amplifiers
SPA 43
Bridging Power Amplifiers
BPA 45
Battery Charger
Charger and Monitoring Unit - EN 54-4
SONAES 47
Consoles & Accessories
Color Touch-Screen Secure Paging Console
PSS AS / PSS G2 / PSS G2E / PPM-IT5 51
Desktop Paging Consoles
PPM AS / PSM 53
Wall-mounted Monitored Touch-screen Paging Console
CD-Touch 56
Wall-mounted Monitored Paging Console
CD8 / CD16 / CDPM / PCP 57
Programmable Remote Controller with Display
URC-AS / URC200 61
Digital Noise Sensing Microphone
DNM 61
Touch Dial Controller / Wireless Transceiver for IDA8 system
DialPad / Wireless Transceiver 62
Alarm Input Interface for IDA8 System and DIVA8G2 System
URGP32in / URGP 16I160 63
Enclosure
List of Peripherals 64
DIVA8 G2 System / Amplifiers / Batter y Charger/Remote Controller
/Alarm Input Interface /Accessories
Ordering Information 65
Public Address - Voice Alarm
Audio Distribution over IP ATEI
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers IDA8C

Networkable PAVA System


Controller – Matrix Mode

IDA8 is a third-generation modular


system that complies with current
IDA8C-SW architectural demands requiring IP
Networkable PAVA System
Controller – Switch Mode
and/or fiber-optic networking to
Pending
allow for even the most complex
of system designs.

IDA8 responds to Public Address


and Voice Alarm requirements as
stated in EN54-16, ISO 7240- 16,
UL60065 and BS5839/8, with
specific attributes for compliance
in large installations.
Public Address - Voice Alarm
ATEI Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

IDA8S

Networkable PAVA System


Slave Unit – Matrix Mode
IDA8SAB

Networkable PAVA System


Slave Unit – A/B-zoning – Matrix Mode

IDA8SAB - SW
IDA8SL
Networkable PAVA System
Networkable PAVA System
Slave Unit – Switch Mode
Lo-Z Slave Unit – Matrix Mode
Pending Pending
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

IDA8C
NETWORKABLE PAVA SYSTEM CONTROLLER – MATRIX MODE

IDA8 is a third-generation modular system that complies with current


architectural demands requiring IP and/or fiber-optic networking to
allow for even the most complex of system designs. IDA8C responds
to Public Address and Voice Alarm requirements as stated in EN54-16,
UL60065, ISO 7240-16 and BS5839/8, with specific attributes for
compliance in large installations.

MAIN CHARACTERISTICS CONNECTIVITY:

Support a maximum up to 31 slave units in ATEÏS Local-Net


Ÿ The IDA8C Controller unit houses advanced audio digital signal processing (DSP),
Up to 256 zones provision via ATEÏS Local-Net
Ÿ matrix control functions and a digital message player, with front panel access for
Up to 8192 zones provision via ATEÏS Global-Net
Ÿ a fully monitored fireman’s microphone and emergency message trigger buttons.
IDA8C also supports amplifier monitoring with hot-swap amplifiers and
Fully digital with 8 audio inputs and 8 audio outputs
Ÿ
loudspeaker line impedance monitoring. It can support up to four PSS-AS
4 dedicated and monitored PDC-ports for paging consoles
Ÿ
monitored microphone consoles and up to eight monitored amplifiers plus two
2 dedicated audio in and outputs for back-up amplifiers
Ÿ
back-up amplifiers, paging into 8 different zones per unit with A/B line detection
Enhanced loudspeaker line surveillance for AB-zoned installation
Ÿ according to BS 5839 part 8. Featuring 8 monitored zones for 25V/70V/100V
Simultaneous control and routing of 48 audio channels over
Ÿ outputs with simultaneous selection, control inputs, and contact outputs. IDA8C
dedicated network provides the zones and audio in & out expansion of the IDA8 systems, using a
secured 48-channel audio and data network over CAT5 or fiber optic, which can
24bit, 48k sampling digital A/D converter, 32bit DSP
Ÿ
be a network of one controller and a maximum up to 31 Slave units via ATEÏS
Each of the 8 zones offers 1000W (MAX.)
Ÿ
local-net, providing with 256 paging zones with priorities (1~99), satisfying with
25 / 70 / 100V selectable outputs
Ÿ
the most complex public address and voice alarm requirements. Two card slots
Up to 100m by using CAT-5 cable with NET-C1
Ÿ are provided for either 4-channel 0dB audio input or 4-channel audio cards.
Optional Fiber-optic cards for links up to 20 km
Ÿ Optional AES/EBU cards are also available.
9 supervised control inputs and 8 control outputs
Ÿ
Each IDA8C input and output channel is fitted with a wide range of pre-and
Modbus Protocol interface via TCP/IP or RS485
Ÿ
post-processing devices such as volume controllers, routing mixers and switches,
Digital storage for up to 100 minutes in WAV format (16k 16 bit) or
Ÿ priority and paging components, equalizers, compressors, limiters and delay-lines.
400 minutes in G.722 format of pre-recorded messages Digital messaging (G.711, G.722, G.726, G.727 and WAV format) can be stored for
4 message players
Ÿ live or pre-recorded playback. Digital audio files are uploaded from a computer to
the IDA8C through the user-friendly ATEÏS Studio GUI. Several messages can be
Programmable Message Scheduler Events
Ÿ
played simultaneously into different zones: up to 4 messages from a single IDA8C
DSP functions of PEQ, GEQ, Delays, Ducker, Gate, AGC, feedback, filter,
Ÿ
Controller or a total of 48 messages across an IDA8 system (controller with
inverter, local echo suppressor, mixer slaves). A built-in loudspeaker on the IDA8C allows selective feedback for all
Ethernet interface for TERRACOM, 3rd party devices, configuration,
Ÿ sources and 100V output signals. One IDA8C can also connect to a maximum up
control, diagnostics and logging to 31 Slave units. The slave units are available as single zone (IDA8S) or with A/B
Incident data record with at least 800 entries (max. 1300)
Ÿ speaker line configurations (IDA8SAB), or for Lo-Z monitoring (IDA8SL).
Programmable of 4 user levels
Ÿ
The IDA8C Controller unit enables operators to see a detailed overview of the
Telephone interface via SIP protocol or telephone line services
Ÿ operational status of the entire PA system at the press of a button. It is able to
1 Fault & 1 EVAC relays outputs
Ÿ run an impedance scan of all components connected to it, covering not only the
Programmable 256 priority paging zones with priority(1~99)
Ÿ input paging consoles but also cabling, processing blocks such as compressors
and limiters, delay lines, the network and loudspeakers.
2U standard 19" rack mounting
Ÿ
Export the incident log
Ÿ The IDA8C Controller operates either on 110VAC or 230VAC mains power supply
EN54-16 certified, UL listed
Ÿ or on a 24V battery power supply for emergency back-up, with automatic switch-
To cooperate with RU devices to do redundancy, external power is
Ÿ over. Both power supplies are securely monitored. IDA8C is easily configured
using the PC-based ATEÏS Studio global software. Once programmed, the system
requested
will operate independently (off-line) without a PC having to be connected.

ATEI
6
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

IDA8C
INSTALLATION NOTES

SECURITY:

In accordance with EN54-16, UL60065, ISO 7240-16 and BS5839/8, all IDA8 system components and
peripherals are monitored. This monitoring extends from the capsule of a paging station microphone to the
end of a loudspeaker line. The external cables connected to the control inputs are monitored for short and
open circuit and an internally-generated pilot tone is available for monitoring impedance on the
loudspeaker lines.

The system can handle 256 paging zones with priority(1~99), satisfying with the most complex public
address and voice alarm requirements. The controller monitors the status of all the equipment in the
ATEÏS STUDIO system, reports status changes and logs the last 1300 fault messages in the system. The log can be
Design Software For IDA8 accessed on the front-panel IDA8C display or on a PC through ATEÏS Studio.

ATEI
7
IDA8 system

IDA8C
NETWORKABLE PAVA SYSTEM CONTROLLER – MATRIX MODE

CONTROLS AND INDICATORS PARTS INCLUDED Amplifier Capacity (per zone)


Input 1000 W (MAX.)
Front Quantities Components
3.5"
ž full color touch-screen LCD display 1 IDA8Cxx Controller unit
Monitoring Loudspeaker
EVAC
ž / Zone selection buttons 1 Fireman microphone
Input 1< 50 Ohm (Display SHORT)
Fireman
ž microphone 1 Power cord (type depends on region)
50~5000 Ohm
Status
ž indicators (Power / Network / System Fault / 1 Set of mounting brackets for 19" rack
(Display Impedance value)
G.Fault / By-Pass Mode / Global Evac / By-pass 1 Set of connectors
1>5000 Ohm (Display OPEN)
Monitoring / Fireman microphone running / Zone 1 ATEÏS Studio software GUI
Fault / Zone Evac Status) 1 LAN Cable
Mechanical

INTERCONNECTIONS TECHNICAL SPECIFICATIONS Dimensions (With 19" rack mount brackets)


(H x W x D) 2RU, 88 x 486 x 313 mm
Front Electrical
(3.5" x 19" x 12-1/3")
Firemen microphone
ž Mains power supply
Weight 5.36 kg (11.8 lbs)
Rear Voltage 230/115 VAC ±15%, 50/60 Hz
Mounting 19"-rack mount
AC power socket
ž Power consumption 48 W
Color RAL7016
24VDC backup power input
ž Fuse Rating 1.6 A
Fault/EVAC/BYPASS
ž output
Environmental
9 control inputs
ž Battery power supply
Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
8 control outputs
ž Voltage 18 - 30 VDC
Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
8 analogue audio mic/line inputs/outputs (Optional)
ž Amp Consumption 1.4 A
Relative humidity 15% to 90%
Ethernet (100BASE-TX)
ž
Air pressure 600 to 1100 h Pa
Local / Global Network Card (Optional)
ž Performance
Heat Dissipation 153 BTU/hr
8 amplifier in and outputs
ž Frequency response ±1 dB @ 20 Hz and 20 kHz
2 connections for backup amplifiers
ž

4 monitored paging console inputs


ž Line inputs (Optional audio input card)
Telephone Card (Optional)
ž Connector 3-pin phoenix
Frequency response ±1 dB @ 20 Hz and 20 kHz
CERTIFICATIONS AND APPROVALS
SNR >81 dBA
THD < 0.02% @ 1 kHz
REGIONAL CERTIFICATIONS
Input sensitivity 0~66 dBu / 6dB steps
Europe Voice Alarm EN54-16 certified 2012 Input impedance 10 kohm
CE – 0359
according to EN50130 – 4 Line outputs (Optional audio output card)
Railway EN50121 – 4 Connector 3-pin phoenix
Controller SNR >81 dBA
System THD < 0.02% @ 1 kHz
USA Safety UL60065 Signal 0dB
Output impedance <100 ohm

ATEI
8
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

IDA8S
NETWORKABLE PAVA SYSTEM – SLAVE UNIT – MATRIX MODE

IDA8 is a third-generation modular system that complies with


current architectural demands requiring IP and/or fiber-optic
networking to allow for even the most complex of system designs.
IDA8S responds to Public Address and Voice Alarm requirements as
stated in EN54-16, ISO 7240-16 and BS5839/8, with specific
attributes for compliance in large installations.

CONNECTIVITY: MAIN CHARACTERISTICS


The IDA8S Slave unit houses advanced audio digital signal processing (DSP), matrix Support a maximum up to 31 slave units in ATEÏS Local-Net
Ÿ
control functions and a digital message player, along with amplifier monitoring for Up to 256 zones provision via ATEÏS Local-Net
Ÿ
hot-swap amplifiers and loudspeaker line impedance monitoring. It can support up Fully digital with 8 audio inputs and 8 audio outputs
Ÿ
to two PSS-AS monitored microphone consoles and up to eight monitored
2 dedicated and monitored PDC-ports for paging consoles
Ÿ
amplifiers plus two backup amplifiers, paging into 8 different zones per unit with
2 dedicated audio in and outputs for back-up amplifiers
Ÿ
line detection. Featuring 8 monitored zones for 25V/70V/100V outputs with
simultaneous selection, control inputs, and contact outputs. IDA8C provides the Enhanced loudspeaker line surveillance for each zone installation
Ÿ

zones and audio in & out expansion of the IDA8 systems, using a secured 48- Simultaneous control and routing of 48 audio channels over
Ÿ
channel audio and data network over CAT5 or fiber optic, which can be a network dedicated network
of one controller and a maximum up to 31 Slave units via ATEÏS local-net. Two card 24bit, 48k sampling digital A/D converter, 32bit DSP
Ÿ
slots can fitted with optional 4-channel analogue audio input/outputs cards(max
Each of the 8 zones offers 1000W (MAX.)
Ÿ
two cards per device).
25 / 70 / 100V selectable outputs
Ÿ
IDA8S Slave units provides extension of IDA8 system configuration with an Up to 100m by using CAT-5 cable with NET-C1
Ÿ
additional 8 output zones and 2 back-up amplifiers. Each input and output channel Optional Fiber-optic cards for links up to 20 km
Ÿ
is fitted with a wide range of pre- and post-processing devices such as volume
9 supervised control inputs and 8 control outputs
Ÿ
controllers, routing mixers and switches, priority and paging components, equalizers,
Modbus Protocol interface via RS485.
Ÿ
compressors, limiters and delay-lines. Digital messaging (G.711, G.722, G.726, G.727
and WAV format) can be stored for live or pre-recorded playback. Digital audio files Digital storage for up to 50 minutes in WAV format (16k 16 bit) or
Ÿ

are uploaded from a computer to the IDA8S through the user-friendly ATEÏS Studio 200 minutes in G.722 format of pre-recorded messages
GUI. Several messages can be played simultaneously into different zones: up to 4 4 message players
Ÿ
messages from a single IDA8S Slave or a total of 48 message channels across an Programmable Message Scheduler Events
Ÿ
IDA8 system (controller with slaves).
DSP functions of PEQ, GEQ, Delays, Ducker, Gate, AGC, feedback,
Ÿ

The IDA8S Slave operates on a 24VDC power supply. The power supplies is filter, inverter, local echo suppressor, mixer
monitored. The IDA8S Slave also supports redundant loop network cabling. IDA8S is Ethernet interface for TERRACOM, 3rd party devices, configuration,
Ÿ
easily configured using the PC-based ATEÏS Studio global software. Once control, diagnostics and logging
programmed, the system will operate independently (off-line) without a PC having
Incident data record with at least 800 entries (max. 1300)
Ÿ
to be connected.
Programmable of 4 user levels
Ÿ
SECURITY: 1 Fault & 1 EVAC relays outputs
Ÿ
Programmable 256 priority paging zones with priority(1~99)
Ÿ
In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system com-
ponents and peripherals are monitored. This monitoring extends from the capsule Export the incident log
Ÿ

of a paging station microphone to the end of a loudspeaker line. The external 1U standard 19" rack mounting
Ÿ
cables connected to the control inputs are monitored for short and open circuit and EN54-16 certified
Ÿ
an internal, generated pilot tone is available for monitoring impedance on the To cooperate with RU devices to do redundancy, external power is
Ÿ
loudspeaker lines. The system can handle up to 256 zones with 1~99 priorities,
requested.
satisfying even the most complex public address and voice alarm requirements. The
controller monitors the status of all the equipment in the system, reports status
changes and logs error details. The log can be accessed on the front-panel display
of IDA8C or on a PC through ATEÏS Studio.
ATEI
9
IDA8 system

IDA8S
NETWORKABLE PAVA SYSTEM – SLAVE UNIT – MATRIX MODE

CONTROLS AND INDICATORS PARTS INCLUDED

Front Quantities Components Amplifier Capacity (per zone)


Status LEDs ( Network / Bypass Monitoring /
ž 1 IDA8Sxx Slave unit Input 1000 W (MAX.)
Bypass Mode / G. EVAC / System Fault / G. Fault ) 1 110/220V AC to 24V DC power adapter
Zone LEDs (EVAC / Fault )
ž 1 Set of mounting brackets for 19" rack Monitoring Loudspeaker
Power LEDs
ž 1 Set of connectors Input 1< 50 Ohm (Display SHORT)
50~5000 Ohm
INTERCONNECTIONS TECHNICAL SPECIFICATIONS
(Display Impedance value)
Rear Electrical 1>5000 Ohm (Display OPEN)
24VDC mains power input
ž 24 VDC power supply
Fault/EVAC/BYPASS output
ž Voltage 18 - 30 VDC Mechanical
9 control inputs
ž Amp Consumption 1.4 A Dimensions (With 19" rack mount brackets)
8 control outputs
ž (H x W x D) 1RU, 44 x 486 x 285 mm
8 analogue audio mic/line inputs/outputs (Optional)
ž Performance (1-3/4" x 19" x 11-1/5")
2 Local ATEÏS Network connections
ž Frequency response ±1 dB @ 20 Hz and 20 kHz Weight 4.2 kg (9.25 lbs)
8 amplifier in and outputs
ž Mounting 19"-rack mount
2 connections for back-up amplifiers
ž Line inputs (Optional audio input card) Color RAL7016
2 monitored paging console inputs
ž Connector 3-pin phoenix
Frequency response ±1 dB @ 20 Hz and 20 kHz Environmental
CERTIFICATIONS AND APPROVALS
SNR >81 dBA Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
THD < 0.02% @ 1 kHz Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
REGIONAL CERTIFICATIONS
Input sensitivity 0~66 dBu / 6dB steps Relative humidity 15% to 90%
Europe Voice Alarm EN54-16 certified 2012 Input impedance 10 kohm Air pressure 600 to 1100 h Pa
CE – 0359 Heat Dissipation 126 BTU/hr
according to EN50130 – 4 Line outputs (Optional audio output card)
Connector 3-pin phoenix
SNR >81 dBA
THD < 0.02% @ 1 kHz
Signal 0dB
Output impedance <100 ohm

ATEI
10
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

IDA8SAB
NETWORKABLE PAVA SYSTEM – SLAVE UNIT – A/B-ZONING – MATRIX MODE

IDA8 is a third-generation modular system that complies with


current architectural demands requiring IP and/or fiber-optic
networking to allow for even the most complex of system designs.
IDA8SAB responds to Public Address and Voice Alarm requirements
as stated in EN54-16, UL60065, ISO 7240-16 and BS5839/ 8, with
specific attributes for compliance in large installations.

CONNECTIVITY: MAIN CHARACTERISTICS


The IDA8SAB Slave unit houses advanced audio digital signal processing (DSP), Support a maximum up to 31 slave units in ATEÏS Local-Net
Ÿ
matrix control functions and a digital message player, along with amplifier Up to 256 zones provision via ATEÏS Local-Net
Ÿ
monitoring with hot-swap amplifiers and loudspeaker line-impedance line Fully digital with 8 audio inputs and 8 audio outputs
Ÿ
monitoring. It can support up to two PSS-AS monitored microphone consoles, up to
2 dedicated and monitored PDC-ports for paging consoles
Ÿ
eight monitored amplifiers plus two backup amplifiers and paging into 8 different
2 dedicated audio in and outputs for back-up amplifiers
Ÿ
zones per unit with A/B line detection according to the BS 5839-part 8. Featuring 8
monitored zones for 25V/70V/100V outputs with simultaneous selection, control Enhanced loudspeaker line surveillance for AB-zoned installation
Ÿ

inputs, and contact outputs. IDA8C provides the zones and audio in & out Simultaneous control and routing of 48 audio channels over
Ÿ
expansion of the IDA8 Systems, using a secured 48-channel audio and data network dedicated network
over CAT5 or fiber optic, which can be a network of one controller and a maximum 24bit, 48k sampling digital A/D converter, 32bit DSP
Ÿ
up to 31 Slave units via ATEÏS local-net. Two rear card slots can be fitted with
Each of the 8 zones offers 1000W (MAX.)
Ÿ
optional 4-channel analogue audio in/output cards 4 channel AES/EBU cards for
25 / 70 / 100V selectable outputs
Ÿ
digital audio in/out.
Up to 100m by using CAT-5 cable with NET-C1
Ÿ
IDA8SAB Slave units provides extension of IDA8 system configuration with an Optional Fiber-optic cards for links up to 20 km
Ÿ
additional 8 output zones and 2 back-up amplifiers. Digital messaging can be stored
9 supervised control inputs and 8 control outputs
Ÿ
in the unit for live or scheduled playback. Files are uploaded in G.711, G.722, G.726,
Modbus Protocol interface via RS485.
Ÿ
G.727 and WAV format from a computer using the ATEÏS Studio system GUI. Several
messages can be played simultaneously into different zones: up to 4 from a single Digital storage for up to 50 minutes in WAV format (16k 16 bit) or
Ÿ

IDA8SAB or a total of 48 message channels across a full IDA8 system with slaves. 200 minutes in G.722 format of pre-recorded messages
4 message players
Ÿ
Each input and output channel is fitted with a wide range of pre-and post-
Programmable Message Scheduler Events
Ÿ
processing devices such as volume controllers, routing mixers and switches, priority
and paging components, equalizers, com-pressers, limiters and delay-lines. DSP functions of PEQ, GEQ, Delays, Ducker, Gate, AGC, feedback,
Ÿ
filter, inverter, local echo suppressor, mixer
IDA8SAB is easily configured with PC-based ATEÏS Studio global software. Once
Ethernet interface for TERRACOM, 3rd party devices, configuration,
Ÿ
programmed, the system will run independently without a PC connected. The
control, diagnostics and logging
IDA8SAB Slave operates either on 110VAC or 230VAC mains power or on a 24V DC
power supply for emergency back-up, with automatic switchover. Both of the power Incident data record with at least 800 entries (max. 1300)
Ÿ

supplies are monitored. Programmable of 4 user levels


Ÿ
Telephone interface via SIP protocol or telephone line services
Ÿ
SECURITY:
1 Fault & 1 EVAC relays outputs
Ÿ
In accordance with EN54-16, UL60065, ISO 7240-16 and BS5839/8, all system Programmable 256 priority paging zones with priority(1~99)
Ÿ
components and peripherals are monitored. This monitoring extends from the Export the incident log
Ÿ
capsule of a paging station microphone to the end of a loudspeaker line. The
2U standard 19" rack mounting
Ÿ
external cables connected to the control inputs are monitored for short and open
EN54-16 certified, UL listed
Ÿ
circuit and an internal, generated pilot tone is available for monitoring impedance
on the loudspeaker lines. The IDA8SAB Slave supports redundant network cabling as To cooperate with RU devices to do redundancy, external power is
Ÿ

a redundant loop. The system can handle up to 256 zones with priority(1~99), requested
satisfying even the most complex public address and voice alarm requirements.

ATEI
11
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

IDA8SAB
INSTALLATION NOTES

ATEI
12
IDA8 system

IDA8SAB
NETWORKABLE PAVA SYSTEM – SLAVE UNIT – A/B-ZONING – MATRIX MODE

CONTROLS AND INDICATORS PARTS INCLUDED

Front Quantities Components Amplifier Capacity (per zone)


Status LEDs ( Network / Bypass Monitoring /
ž 1 IDA8SABxx Slave unit Input 1000 W (MAX.)
Bypass Mode / G. EVAC / System Fault / G. Fault ) 1 Power cord (type depends on region)
Zone LEDs (EVAC / Fault )
ž 1 Set of mounting brackets for 19" rack Monitoring Loudspeaker
Power LEDs
ž 1 Set of connectors Input 1< 50 Ohm (Display SHORT)
50~5000 Ohm
INTERCONNECTIONS TECHNICAL SPECIFICATIONS
(Display Impedance value)
Rear Electrical 1>5000 Ohm (Display OPEN)
AC power socket
ž Mains power supply
24VDC backup power input
ž Voltage 230/115 VAC ±15%, 50/60 Hz Mechanical
BYPASS Mode output
ž Power consumption 48 W Dimensions (With 19" rack mount brackets)
9 control inputs
ž Fuse Rating 1.6 A (H x W x D) 2RU, 88 x 486 x 289 mm
8 control outputs
ž (3-1/2" x 19" x 11-3/8")
8 analogue audio mic/line inputs/outputs (Optional)
ž Battery power supply Weight 5 kg (11 lbs)
2 Local ATEÏS Network connections
ž Voltage 18 - 30 VDC Mounting 19"-rack mount
8 amplifier in and outputs
ž Amp Consumption 1.4 A Color RAL7016
2 connections for back-up amplifiers
ž

Telephone Card (Optional)


ž Performance Environmental
2 monitored paging console inputs
ž Frequency response ±1 dB @ 20 Hz and 20 kHz Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
CERTIFICATIONS AND APPROVALS
Line inputs (Optional audio input card) Relative humidity 15% to 90%
Connector 3-pin phoenix Air pressure 600 to 1100 h Pa
REGIONAL CERTIFICATIONS
Frequency response ±1 dB @ 20 Hz and 20 kHz Heat Dissipation 140 BTU/hr
Europe Voice Alarm EN54-16 certified 2012 SNR >81 dBA
CE – 0359 THD < 0.02% @ 1 kHz
according to EN50130 – 4 Input sensitivity 0~66 dBu / 6dB steps
Railway EN50121 – 4 Input impedance 10 kohm
Controller
System Line outputs (Optional audio output card)
USA Safety UL60065 Connector 3-pin phoenix
SNR >81 dBA
THD < 0.02% @ 1 kHz
Signal 0dB
Output impedance <100 ohm

ATEI
13
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

IDA8SL
NETWORKABLE PAVA SYSTEM LO-Z SLAVE UNIT – MATRIX MODE

IDA8 is a third-generation modular system that complies with current


architectural demands requiring IP and/or fiber-optic networking to allow
for even the most complex of system designs. IDA8SL responds to
Public Address and Voice Alarm requirements as stated in EN54-
16(Pending), UL60065, ISO 7240-16 and BS5839/8, with specific
attributes for compliance in large installations.

Pending

MAIN CHARACTERISTICS CONNECTIVITY:

Support a maximum up to 31 slave units in ATEÏS Local-Net


Ÿ The IDA8SL Lo-Z Slave unit houses advanced audio digital signal processing (DSP),
Up to 256 zones provision via ATEÏS Local-Net
Ÿ matrix control functions and a digital message player, along with amplifier monitoring
2 dedicated and monitored PDC-ports for paging consoles
Ÿ with hot-swap amplifiers and Lo-Z line monitoring. It can support up to two PSS-AS
monitored microphone consoles, up to four monitored amplifiers plus one backup
1 dedicated audio in/output for back-up amplifier
Ÿ
amplifier and paging into 4 different zones per unit with line detection. Each input
Enhanced loudspeaker line surveillance for each zone installation
Ÿ
and output channel is fitted with a wide range of pre-and post-processing devices
Simultaneous control and routing of 48 audio channels over
Ÿ
such as volume controllers, routing mixers and switches, priority and paging
dedicated network components, equalizers, compressors, limiters and delay-lines.
24bit, 48k sampling digital A/D converter, 32bit DSP
Ÿ
IDA8SL Slave units provides extension of IDA8 system configuration with an
Each of the 4 zones offers 1500W (MAX.)
Ÿ
additional 4 output zones and 1 back-up amplifier. Digital messaging can be stored in
25 / 70 / 100V selectable outputs
Ÿ
the unit for live or scheduled playback. Files are uploaded in G.711, G.722, G.726,
Up to 100m by using CAT-5 cable with NET-C1
Ÿ G.727 and WAV format from a computer using the ATEÏS Studio system GUI. Several
Optional Fiber-optic cards for links up to 20 km
Ÿ messages can be played simultaneously into different zones: up to 4 from a single
9 supervised control inputs and 8 control outputs
Ÿ IDA8SL or a total of 48 message channels across a full IDA8 system with slaves.
Modbus Protocol interface via RS485
Ÿ
IDA8SL is easily configured with PC-based ATEÏS Studio global software. Once
Digital storage for up to 50 minutes in WAV format (16k 16 bit) or
Ÿ programmed, the system will run independently without a PC connected. The IDA8SL-
200 minutes in G.722 format of pre-recorded messages Slave operates either on 110VAC or 230VAC mains power or on a 24V DC power
4 message players
Ÿ supply for emergency back-up, with automatic switchover. Both of the power supplies
are monitored.
Programmable Message Scheduler Events
Ÿ
DSP functions of PEQ, GEQ, Delays, Ducker, Gate, AGC, feedback,
Ÿ SECURITY:
filter, inverter, local echo suppressor, mixer
In accordance with EN54-16(Pending), UL60065, ISO 7240-16 and BS5839/8, all system
Ethernet interface for TERRACOM, 3rd party devices, configuration,
Ÿ
components and peripherals are monitored. This monitoring extends from the capsule
control, diagnostics and logging of a paging station microphone to the end of a loudspeaker line. The external cables
Incident data record with at least 800 entries (max. 1300)
Ÿ connected to the control inputs are monitored for short and open circuit and an
Programmable of 4 user levels
Ÿ internally generated pilot tone is available for monitoring impedance on the
1 Fault & 1 EVAC relays outputs
Ÿ loudspeaker lines. The IDA8SL Slave supports redundant network cabling as a
Programmable 256 priority paging zones with priority(1~99)
Ÿ
redundant loop. The system can handle up to 256 zones with 1~99 priorities,
satisfying even the most complex public address and voice alarm requirements.
Export the incident log
Ÿ
2U standard 19" rack mounting
Ÿ
UL listed
Ÿ
To cooperate with RU devices to do redundancy, external power is
Ÿ
requested

ATEI
14
IDA8 system

IDA8SL
NETWORKABLE PAVA SYSTEM LO-Z SLAVE UNIT – MATRIX MODE

CONTROLS AND INDICATORS PARTS INCLUDED

Front Quantities Components Amplifier Capacity (per zone)


Status LEDs ( Network / Bypass Monitoring /
ž 1 IDA8SLxx Slave unit Input 1500 W (MAX.)
Bypass Mode / G. EVAC / System Fault / G. Fault ) 1 Power cord (type depends on region)
Zone LEDs (EVAC / Fault )
ž 1 Set of mounting brackets for 19" rack Monitoring Loudspeaker
Power LEDs
ž 1 Set of connectors Input >0, <5000 Ohm
(Display Impedance value)
INTERCONNECTIONS TECHNICAL SPECIFICATIONS
>5000 Ohm (Display OPEN)
Rear Electrical
AC power socket
ž Mains power supply Mechanical
24VDC backup power input
ž Voltage 230/115 VAC ±15%, 50/60 Hz Dimensions (With 19" rack mount brackets)
BYPASS Mode output
ž Power consumption 48 W (H x W x D) 2RU, 88 x 486 x 300 mm
9 control inputs
ž Fuse Rating 1.6 A (3-1/2" x 19" x 11-4/5")
8 control outputs
ž Weight 4.2 kg (9.25 lbs)
2 Local ATEÏS Network connections
ž Battery power supply Mounting 19"-rack mount
4 low-impedance amplifier in and outputs
ž Voltage 18 - 30 VDC Color RAL7016
1 connection for back-up amplifiers
ž Amp Consumption 1.4 A
2 monitored paging console inputs
ž Environmental
Performance Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
CERTIFICATIONS AND APPROVALS
Frequency response ±1 dB @ 20 Hz and 20 kHz Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
Relative humidity 15% to 90%
REGIONAL CERTIFICATIONS
Line inputs (Optional audio input card) Air pressure 600 to 1100 h Pa
Europe Voice Alarm EN54-16 certified(Pending) Connector SPEAKON (electronically balanced) Heat Dissipation 140 BTU/hr
CE – 0359 Frequency response ±1 dB @ 20 Hz and 20 kHz
according to EN50130 – 4 SNR >81 dBA
USA Safety UL60065 THD < 0.02% @ 1 kHz
Input sensitivity 0~66 dBu / 6dB steps
Input impedance 10 kohm

Line outputs (Optional audio output card)


Connector XLR
SNR >81 dBA
THD < 0.02% @ 1 kHz
Signal 0dB
Output impedance <100 ohm

ATEI
15
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

IDA8C-SW
NETWORKABLE PAVA SYSTEM CONTROLLER – SWITCH MODE

Pending

IDA8C-SW supports up to 4 audio sources including Evac/ Voice/ Music/ Backup, MAIN CHARACTERISTICS
utilizing with a maximum capacity of 1000 W for each and the choice of audio
Support a maximum up to 31 slave units in ATEÏS Local-Net
Ÿ
source can be selected from one source only for the systems. Featuring 8
monitored zones for 25V/70V/100V outputs with simultaneous selection, control Up to 8192 zones provision via ATEÏS Global-Net
Ÿ

inputs, and contact outputs. IDA8C-SW provides the zones and audio in & out Fully digital with 8 audio inputs and 8 audio outputs
Ÿ
expansion of the IDA8C-SW Systems, using a secured 48-channel audio and data 4 x 1000 Watt maximum load
Ÿ
network over CAT5 or fiber optic, which can be a network of one controller and 4 channel audio distribution for EVAC, Paging, BGM & Backup
Ÿ
a maximum up to 31 Slave units via ATEÏS local-net, providing with 256 paging Combined back-up amplifier function
Ÿ
zones with priorities (1~99). Furthermore, IDA8C-SW is capable to expand up to
4 dedicated and monitored PDC-ports for paging consoles
Ÿ
8192 zones via ATEÏS global-net, satisfying with the most complex public address
and voice alarm requirements. Enhanced loudspeaker line surveillance for AB-zoned installation
Ÿ
Simultaneous control and routing of 48 audio channels over dedicated
Ÿ
The IDA8C-SW requires up to 4 channel amplifier and be capable to act as a network
backup amplifier in case other amplifiers break down. In case of evacuation, the
24bit, 48k sampling digital A/D converter, 32bit DSP
Ÿ
zones attenuators will be bypassed automatically and signal output shall be
activated when certain zone is occupied with a source that has a higher priority Up to 100m by using CAT-5 cable with NET-C1
Ÿ

than the music alarm or voice paging. Two card slots are provided for either 4- Optional Fiber-optic cards for links up to 20 km
Ÿ
channel 0dB audio input or 4-channel audio cards. Optional AES/EBU cards are Modbus Protocol interface via TCP/IP or RS485
Ÿ
also available. Digital storage for up to 100 minutes in WAV format (16k 16 bit) or 400
Ÿ

IDA8C-SW Controller unit is capable to run an impedance scan of all the minutes in G.722 format of pre-recorded messages
components, covering not only the input paging consoles but the cabling, and 4 message players
Ÿ
processing blocks such as compressors and limiters, delay lines, network and Programmable Message Scheduler Events
Ÿ
loudspeakers. Digital messaging (G.711, G.722, G.726, G.727 and WAV format) can DSP functions of PEQ, GEQ, Delays, Ducker, Gate, AGC, feedback, filter,
Ÿ
be stored for live or pre-recorded playback. It stores a reference measurement of inverter, local echo suppressor, mixer
the system as users create a given configuration. This reference will be
Ethernet interface for TERRACOM, 3rd party devices, configuration,
Ÿ
subsequently stored in the system. Any alterations of this configuration will be
reported and logged in an event log file as well. The custom setting of threshold control, diagnostics and logging
shall be applied in it, allowing users to meet each circumstances. Incident data record with at least 800 entries (max. 1300)
Ÿ
Programmable of 4 user levels
Ÿ
Password protecting to the software allows you to protect all recorded data file
Telephone interface via SIP protocol or telephone line services
Ÿ
which shall be consulted both on the front LCD display panel and in the ATEÏS-
Studio global version software (Windows compatible) via the PC. Once 1 Fault & 1 EVAC relays outputs
Ÿ

programmed, the system enables to work independently(off-line) without the Programmable 256 priority paging zones with priority(1~99)
Ÿ
need of connecting to the PC. Also, any detected fault shall be signaled by a Export the incident log
Ÿ
general fault on the front panel of IDA8C-SW Controller unit. 2U standard 19" rack mounting
Ÿ

IDA8C-SW controller unit enhances the abilities to connect with the touch panel UL listed
Ÿ

microphone consoles (PSS-AS) and programmable transfer contacts. As well as to To cooperate with RU devices to do redundancy, external power is
Ÿ
support the system operation via PC, or 3rd party control such as Crestron or requested
AMX and other control systems to meet users' demands.

ATEI
16
IDA8 system

IDA8C-SW
NETWORKABLE PAVA SYSTEM CONTROLLER – SWITCH MODE

CONTROLS AND INDICATORS PARTS INCLUDED

Front Quantities Components Amplifier Capacity (per zone)


3.5" full color touch-screen LCD display
ž 1 IDA8Cxx-SW Controller unit Input 1000 W (MAX.)
EVAC / Zone selection buttons
ž 1 Fireman microphone
Fireman microphone
ž 1 Power cord (type depends on region) Monitoring Loudspeaker
Status indicators (Power / Network / Bypass /
ž 1 Set of mounting brackets for 19" rack Input 1< 50 Ohm (Display SHORT)
Monitoring / G. EVAC / G. Fault) 1 Set of connectors 50~5000 Ohm
1 ATEÏS Studio software GUI (Display Impedance value)
INTERCONNECTIONS
1 LAN Cable 1>5000 Ohm (Display OPEN)
Front
TECHNICAL SPECIFICATIONS
Firemen microphone
ž Mechanical
Rear Electrical Dimensions (With 19" rack mount brackets)
AC power socket
ž Mains power supply (H x W x D) 2RU, 88 x 483 x 305 mm
24VDC backup power input
ž Voltage 230/115 VAC ±15%, 50/60 Hz (3-1/2" x 19" x 12")
Fault/EVAC/BYPASS output
ž Power consumption 48 W Weight 6.2 kg (13.65 lbs)
9 control inputs
ž Fuse Rating 1.6 A Mounting 19"-rack mount
8 control outputs
ž Color RAL7016
8 analogue audio mic/line inputs/outputs (Optional)
ž Battery power supply
Ethernet (100BASE-TX)
ž Voltage 18 - 30 VDC Environmental
Local / Global network in/out card
ž Amp Consumption 1.4 A Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
4 amplifier inputs and outputs
ž Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
4 monitored paging console inputs
ž Performance Relative humidity 15% to 90%
BNC (Optional with AES-EBU)
ž Frequency response ±1 dB @ 20 Hz and 20 kHz Air pressure 600 to 1100 h Pa
Telephone Card (Optional)
ž Heat Dissipation 140 BTU/hr
Line inputs (Optional audio input card)
CERTIFICATIONS AND APPROVALS
Connector 3-pin phoenix
Frequency response ±1 dB @ 20 Hz and 20 kHz
REGIONAL CERTIFICATIONS
SNR >81 dBA
Europe Voice Alarm EN54-16 certified(Pending) THD < 0,02% @ 1 kHz
CE – 0359 Input sensitivity 0~66 dBu / 6dB steps
according to EN50130 – 4 Input impedance 10 kohm
USA Safety UL60065
Line outputs (Optional audio output card)
Connector 3-pin phoenix
SNR >81 dBA
THD < 0,02% @ 1 kHz
Signal 0dB
Output impedance <100 ohm

ATEI
17
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

IDA8SAB - SW
NETWORKABLE PAVA SYSTEM – SLAVE UNIT – SWITCH MODE Pending

IDA8SAB (switch mode) supports up to 4 audio sources including Evac/ Voice/ Music/ Backup,
utilizing with a maximum capacity of 1000 W for each and the choice of audio source can be
selected from one source only for the systems. Featuring 8 monitored zones for 25V/70V/100V
outputs with simultaneous selection, control inputs, and contact outputs. IDA8SAB (switch mode)
provides the zones and audio in & out expansion of the IDA8 Systems, using a secured 48-
channel audio and data network over CAT5 or fiber optic, which can be a network of one
controller and a maximum up to 31 Slave units via ATEÏS local-net, providing with 256 paging
MAIN CHARACTERISTICS zones with priorities (1~99). Two rear card slots can be fitted with optional 4-channel analogue
Support a maximum up to 31 slave units in ATEÏS
Ÿ audio in/output cards 4 channel AES/EBU cards for digital audio in/out.
Local-Net IDA8SAB (switch mode) requires less number of amplifiers with only 4 audio inputs / outputs
Up to 8192 zones provision via ATEÏS Global-Net
Ÿ (EVAC/ Voice/ Music/ Back up) from amplifier and be capable to act as a backup amplifier in case
Fully digital with 8 audio inputs and 8 audio outputs
Ÿ other amplifiers break down. Users shall manually route the signal and digital messages into the
4 x 1000 Watt maximum load
Ÿ selected zones and adjust the audio level, switch the music (ON/OFF)...etc. In case of evacuation,
the zones attenuators will be bypassed automatically and signal output shall be activated when
4 channel audio distribution for EVAC, Paging, BGM &
Ÿ
certain zone is occupied with a source that has a higher priority than the music alarm or voice
Backup
paging.
Combined back-up amplifier function
Ÿ
2 dedicated and monitored PDC-ports for paging
Ÿ IDA8SAB (switch mode) slave unit is a user-friendly device which shall be configured via PC
based on ATEÏS Studio global version software (Windows compatible) and password protecting to
consoles
the software allows you to protect your data. Once programmed, the system enables to work
Enhanced loudspeaker line surveillance for AB-zoned
Ÿ
independently(off-line) without the need of connecting to a PC. Also, any detected fault shall be
installation signaled by a general fault. IDA8SAB (switch mode) Controller enhances the abilities to connect
Simultaneous control and routing of 48 audio channels
Ÿ with the touch panel microphone consoles (PSS-AS) and programmable transfer contacts as well
over dedicated network as support to operate the system via PC, or 3rd party control such as Crestron or AMX and other
24bit, 48k sampling digital A/D converter, 32bit DSP
Ÿ control systems to meet the users' demands. Also any detected faults and alarm status are
signaled by general fault and alarm output contacts. A local loudspeaker enables selective
Up to 100m by using CAT-5 cable with NET-C1
Ÿ
listening to all the sources and the system’s output signals.
Optional Fiber-optic cards for links up to 20 km
Ÿ
Modbus Protocol interface via RS485.
Ÿ All these features make IDA8SAB (switch mode) the ideal system for shopping malls, hotels,
Digital storage for up to 50 minutes in WAV format
Ÿ restaurants, museums and many other public places.
(16k 16 bit) or 200 minutes in G.722 format of pre-
recorded messages
Incident data record with at least 800 entries (max. 1300)
Ÿ
DSP functions of PEQ, GEQ, Delays, Ducker, Gate, AGC,
Ÿ
feedback, filter, inverter, local echo suppressor, mixer
Ethernet interface for TERRACOM, 3rd party devices,
Ÿ
configuration, control, diagnostics and logging
Programmable Message Scheduler Events
Ÿ
Programmable of 4 user levels
Ÿ
Telephone interface via SIP protocol or
Ÿ
telephone line services
1 Fault & 1 EVAC relays outputs
Ÿ
Programmable 256 priority paging zones with
Ÿ
priority(1~99)
Export the incident log
Ÿ
2U standard 19" rack mounting
Ÿ
UL listed
Ÿ
To cooperate with RU devices to do redundancy,
Ÿ
external power is requested

ATEI
18
IDA8 system

IDA8SAB- SW
NETWORKABLE PAVA SYSTEM – SLAVE UNIT – SWITCH MODE

CONTROLS AND INDICATORS PARTS INCLUDED

Front Quantities Components Amplifier Capacity (per zone)


Status LEDs ( Network / Bypass Monitoring /
ž 1 IDA8SABxx-SW Controller unit Input 1000 W (MAX.)
Bypass Mode / G. EVAC / System Fault / G. Fault ) 1 Power cord (type depends on region)
Zone LEDs (EVAC / Fault )
ž 1 Set of mounting brackets for 19" rack Monitoring Loudspeaker
Power LEDs
ž 1 Set of connectors Input 1< 50 Ohm (Display SHORT)
50~5000 Ohm
INTERCONNECTIONS TECHNICAL SPECIFICATIONS
(Display Impedance value)
Rear Electrical 1>5000 Ohm (Display OPEN)
AC power socket
ž Mains power supply
24VDC backup power input
ž Voltage 230/115 VAC ±15%, 50/60 Hz Mechanical
BYPASS Mode output
ž Power consumption 48 W Dimensions (With 19" rack mount brackets)
9 control inputs
ž Fuse Rating 1.6 A (H x W x D) 2RU, 88 x 483 x 305 mm
8 control outputs
ž 3-1/2" x 19" x 12"
8 analogue audio mic/line inputs/outputs (Optional)
ž Battery power supply Weight 5.5 kg (12.1 lbs)
2 system LOCAL-network connections
ž Voltage 18 - 30 VDC Mounting 19"-rack mount
4 amplifier inputs and outputs
ž Amp Consumption 1.4 A Color RAL7016
BNC (Optional with AES-EBU)
ž

Telephone Card (Optional)


ž Performance Environmental
2 monitored paging console inputs
ž Frequency response ±1 dB @ 20 Hz and 20 kHz Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
CERTIFICATIONS AND APPROVALS
Line inputs (Optional audio input card) Relative humidity 15% to 90%
Connector 3-pin phoenix Air pressure 600 to 1100 h Pa
REGIONAL CERTIFICATIONS
Frequency response ±1 dB @ 20 Hz and 20 kHz Heat Dissipation 140 BTU/hr
Europe Voice Alarm EN54-16 certified(Pending) SNR >81 dBA
CE – 0359 THD < 0,02% @ 1 kHz
according to EN50130 – 4 Input sensitivity 0~66 dBu / 6dB steps
USA Safety UL60065 Input impedance 10 kohm

Line outputs (Optional audio output card)


Connector 3-pin phoenix
SNR >81 dBA
THD < 0,02% @ 1 kHz
Signal 0dB
Output impedance <100 ohm

ATEI
19
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

INSTALLATION EXAMPLES

IDA8C (Switch Mode) system requires and processes four 0 dB audio inputs into only a 4-channel amplifier (Evacuation, Voice, Music or Backup), each input is
also fitted with volume controls and equalizers. The four channels can be switched ON/OFF in each zone separately. In case of Evacuation, the three channels
can be used as a second alarm channel. There are three types of mode (Equal Mode, Unequal Mode, Backup Sharing Mode) which provide users with a
multi-functional combination for preference.

Figure 1: Equal Mode Configuration


EQUAL MODE
In this example of Equal Mode, the master unit
IDA8C (Switch Mode) is linked up with slave units
IDA8SAB(Switch Mode) by Local ATEÏS Local-Net and
contains a secured paging facility with full power
back-up. Each channel can handle up 1000 W audio
power at 100 V and be supplied not only for the
master unit but also the slave units in each zone
simultaneously. Furthermore, there are regular orders
for priority backing-up system (EVAC > Voice >
Music > Backup). For instance, when the EVAC and
Voice amplifiers break down, the Backup and Music
amplifier will automatically switch to EVAC and Voice
amplifiers in order to provide and maintain the
urgent operating paging.

UNEQUAL MODE
Figure 2: Unequal Mode Configuration
In this example of Unequal Mode, the master unit
IDA8C(Switch Mode) is linked up with slave units
IDA8SAB(Switch Mode) by Local ATEÏS Local-Net and
contains a secured paging facility with full power
back-up. It divides the four channels into two
groups and the two channels in each group can be
used for the other backup amplifier in case of
amplifier failure. With ATEÏS Studio software, pro-
viding the function of separating the two groups
with different coverage from 1~99 of priority
automatically.

Priority 1~20 sources shall be used by the EVAC and


Backup channels; Priority 21~99 sources shall be
used by the Voice and Music channels. In case you
might face the possibility when the two amplifiers
for Voice and Music sources are being occupied, the
rest amplifiers for EVAC and Backup channels shall
also be used as the Voice and Music sources
simultaneously with one condition that there are
other vacant amplifiers for EVAC and Backup.

Note: Make sure the Watt unit of each group must


be in the same power capacity.
ATEI
20
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

INSTALLATION EXAMPLES

Figure 3: Backup Sharing Mode Configuration


BACKUP SHARING MODE
In this example of Backup Sharing Mode, the master
unit IDA8C (Switch Mode) is linked up with slave
units IDA8SAB (Switch Mode) by Local ATEÏS Local-
Net and contains a secured paging facility with full
power back-up. The three amplifiers supply for each
zone with one amplifier individually and the backup
amplifier shall be a backup for the three amplifiers
once they break down and switch on the power
supply automatically.

SCENARIOS
By the ATEÏS local-Net which can be a network of one controller and a maximum up to 31 IDA8S/SL/SAB/SAB-SW Slave units in a local system, the system
connects with ATEÏS Local-Net shall be able to link up with each other in different kinds of mode(Equal, Unequal, Backup Sharing). The following pictures
below would give users a better understanding of how to combine the multiple modes together in two or more buildings.

Scenario 1: [Equal Mode + Unequal Mode]

ATEI
21
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

INSTALLATION EXAMPLES

Scenario 2: [Backup Sharing Mode + Equal Mode]

Scenario 3: [Unequal Mode + Backup Sharing Mode]

ATEI
22
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

INSTALLATION EXAMPLES

Scenario 4: [Multiple wiring with 8 amplifiers + Equal Mode]

Scenario 5: [ IDA8C ( Matrix Mode ) + IDA8C / IDA8SAB ( Switch Mode ) ]

ATEI
23
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

RU-MAIN / CTL / PDC


IDA8 FULL-REDUNDANCY SWITCHING UNIT

In place of highly sensitive and secured integration such as nuclear power centrals, underground industrial systems or places where people have to thrust on
a 100% availability of a PAVA system may requires additional full-redundancy system. Redundancy is a very widely-spread application that needs to be
further specified into a required level of redundancy. Compared to the higher levels of redundancy which requires for A/B wiring of the loudspeaker lines
where loss of the A or B line or system still ensures a minimum coverage of 50% of the venue, spare amplifiers and surveillance of essential components in
normal PAVA systems aren't capable to support emergency cases. At this high level of redundancy, not only the amplifiers have redundancy by means of
active spare amplifiers, but also the central equipment will provide a full back-up. And this is what we call: Full-Redundancy. ATEÏS RU, the thorough
switching devices ,providing the high level of redundancy and acting as a Primary / Secondary switching device for IDA8C Controller and IDA8SAB Slave unit.
Here are the three types of devices listed below,

RU-Main: Switching unit for digital audio processing with paging console interface.

RU-CTL: Switching unit for secured input and normal output contacts.

RU-PDC: Switching unit for auxiliary audio IN and OUT contacts with paging console & telephone line interface.

RU device is a device supplied with full-redundancy for audio processor. RU device is in charge of switching primary and secondary audio processor to active
one of them. If primary audio processor is active, all signal of peripherals shall be redirected to the primary audio processor by RU device. RU device is also
capable to monitor the status of audio processor. If primary audio processor breaks down, RU device will detect automatically and switch to secondary audio
processor.

ATEI
24
IDA8 system

RU-MAIN / CTL / PDC


IDA8 FULL-REDUNDANCY SWITCHING UNIT

CONTROLS AND INDICATORS

Front LED display: power, Primary IDA8 system active,


ž Mechanical
Primary Active Indicator
ž Secondary IDA8 system Active Dimensions (With 19" rack mount brackets)
Secondary Active Indicator
ž Control inputs: Primary IDA8 system watchdog,
ž (H x W x D)
Fault Indicator
ž Secondary IDA8 system watchdog RU-MAIN 2RU, 88 x 436 x 150 mm
Power Indicator
ž Control outputs: Primary IDA8 system active,
ž (3-1/2" x 17-1/5" x 5-9/10")
Secondary IDA8 system Active, Expansion RU-CTL/PDC 1RU, 44 x 436 x 150 mm
INTERCONNECTIONS
(1-3/4" x 17-1/5" x 5-9/10")
PARTS INCLUDED
RU-MAIN Weight
8 speaker lines, 8 amplifiers, 2 backup amps,
ž Quantities Components RU-MAIN 4.5 kg (10 lbs)
2 PSS inputs, 2 record Out 1 RU-xx unit RU-CTL/PDC 2.5 kg (5.5 lbs)
Switching: Electrical mechanical relays
ž 1 Power cord (type depends on region) Mounting 19"-rack mount
Switching time: 6 seconds (IDA8 watchdog period)
ž Color RAL7016
TECHNICAL SPECIFICATIONS
Connections: RJ 45, Screw terminals blocks
ž

LED display: power, Primary IDA8 system active,


ž Electrical Environmental
Secondary IDA8 system Active Power supply Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
Control inputs: Primary IDA8 system watchdog,
ž Voltage 24 VDC Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
Secondary IDA8 system watchdog Power consumption Relative humidity 15% to 90%
Control outputs: Primary IDA8 system active,
ž RU-MAIN 600mA Air pressure 600 to 1100 h Pa
Secondary IDA8 system Active, Expansion RU-CTL 200mA Heat Dissipation
RU-CTL RU-PDC 350mA RU-MAIN 50 BUT/hr
8 x Output contacts, 9 x alarm inputs
ž RU-CTL 16 BUT/hr
Switching: Electrical mechanical relays
ž RU-PDC 28 BUT/hr
Switching time: 6 seconds (IDA8 watchdog period)
ž

Connections: Screw terminals blocks


ž
RU-MAIN
LED display: power, Primary IDA8 system active,
ž

Secondary IDA8 system Active


Control inputs: Primary IDA8 system watchdog,
ž

Secondary IDA8 system watchdog


Control outputs: Primary IDA8 system active,
ž

Secondary IDA8 system Active, Expansion


RU-PDC RU-PDC
8 x 0dB inputs or outputs , 2 PSS inputs,
ž

2 Tel inputs
Switching: Electrical mechanical relays
ž

Switching time: 6 seconds (IDA8 watchdog period)


ž
RU-CTL
Connections: RJ 45, Screw terminals blocks
ž

ATEI
25
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

NET - CX
ATEÏS NET SECURED AUDIO NETWORK CARD

ATEÏS Net™ is a secured (monitored) audio network, developed and supplied for fast and low-
latency audio and data transport over a redundant copper (CAT-5) or fiber-optic network ring. ATEÏS
Net™ has an open-architecture design and interfaces with remote devices such as paging
consoles, audio break-in and break-out convertors and room controllers, providing the best solution
to medium to large-scale installations, such as shopping malls, retail stores, train stations and
airports.
ATEÏS Net™ secured audio network responds to Public Address and Voice Alarm requirements as
stated in EN54-16, UL60065, ISO 7240-16 and BS5839/8, with specific attributes for compliance in
large installations.

MAIN CHARACTERISTICS
ATEÏS Net™ audio and data secured network
Ÿ FUNCTIONS:
Local-net & Global-net
Ÿ
ATEÏS Net™ is able to simultaneously transport 48 audio channels (32 bit, 48 kHz sampling rate) with a
32 x 32 IDA8 system units in a Global network
Ÿ latency <1ms together with the necessary control data over a CAT-5 or fiber-optic dedicated network.
Low-latency <1ms
Ÿ For LOCAL and GLOBAL system networking, optional ATEÏS Net™ networking cards can be installed into
48-audio channels
Ÿ the IDA8 Controller and Slave units. Thanks to its loop architecture, the ATEÏS Net™ audio network is
fully redundant. When a fault (line open or shorted) occurs on a loop segment, it will be automatically
Redundant loop architecture
Ÿ
isolated without affecting the entire system functionality. ATEÏS global-net, can be a network of more
32 bit, 48 kHz sampling
Ÿ than one controller(Matrix Mode and Switch Mode) and a maximum up to 31 IDA8Sxx Slave units
CAT-5 for up to 100 m
Ÿ (Matrix Mode and Switch Mode) in a local system.
Fiber-optic multi-mode for up to 2 km
Ÿ
As network addresses are auto negotiated, network setup is very easy. Once programmed, the system
Fiber-optic single-mode for up to 20 km
Ÿ will operate independently without connecting to a PC having to be connected. 32 IDA8 system units
Dedicated network
Ÿ can be a network in ATEÏS Global-Net, and each system includes one control unit connecting to 31
EN54-16 certified
Ÿ
slave units in ATEÏS Local-Net.

The installation of NET-C1 cards (RJ45 to RJ45) are suitable with a maximum distance up to 100m
between Matrix and Slave unit or Slave and Slave unit. For longer installation distances, optional NET-
C2, C3 or C4 can be used to extend distances with fiber-optic, up to 2 km between units in multi-
mode or 20 km in single-mode.

Note:
Port A = network IN
Port B = network OUT

NET-C1, 2x RJ45 Port A & Port B

NET-C3, 2x fiber Port A & Port B NET-C4, 1x fiber Port B & 1x RJ45 Port A

NET-C2, 1x RJ45 Port B & 1x fiber Port A

ATEI
26
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

NET - CX
ATEÏS NET SECURED AUDIO NETWORK CARD

TECHNICAL SPECIFICATIONS SECURITY:

In accordance with EN54-16, UL60065, ISO 7240-16 and BS5839/8, all IDA8 system components and
Electrical
peripherals on the ATEÏS Net™ secured audio network are monitored and reports stored in the IDA8C
Battery power supply system controller. The controller monitors the status of all the equipment in the system, reports status
Voltage Internal multi-power socket changes and stores fault messages for recall either on the controller front-panel display or through the
Power consumption 5W ATEÏS Studio PC-based software.

Performance
Frequency response 20 Hz ~ 22 kHz
Sampling rate 32 bit / 48 kHz
Latency < 0.08 ms per node
Integrity assurance Watchdog

Center Wavelength (Fiber-optic)


Multi-mode 1300 nm
Single-mode 1310 nm

FO connector type Straight Tip


FO cable baud rate 62.5 um (Multi-mode)
9 um (Single-mode)

Indicators
LED Network active
LED Network present
ATEÏS Local Net and ATEÏS Global Net
Mechanical
(H x W x D) 18 x 100 x 150 mm
CONTROLS AND INDICATORS CERTIFICATIONS AND APPROVALS
(7/10" x 4" x 6")
Front
REGIONAL CERTIFICATIONS
Environmental Data running indicator
ž

Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF) Net-work present indicator


ž Europe Voice Alarm EN54-16 certified 2012
Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF) CE – 0359
INTERCONNECTIONS
Relative humidity 15% to 90% according to EN50130 – 4
Air pressure 600 to 1100 h Pa Front
Two system network connections either CAT5 or
ž
PARTS INCLUDED
Fiber-optic or a combination
Quantities Components
1 ATEÏS Net™ secured audio
network card
1 Set of interconnecting ribbon cables
1 Set of mounting pillars

ATEI
27
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

OPTIONAL BOARDS

Analog Audio I/O Cards: Digital Audio I/O Cards Specialty Cards

Analog audio cards are available for local inputs The digital audio I/O cards allow you to go all the How can a multi-project integrate in both PAVA
or outputs in blocks of 4 or in a 2 in/2 out way to digitize, presenting with the maximum system and conference rooms? By adding the
configuration. Highly adjustable for sensitivity and sound quality and transmission distance on IDA8 Telephone Card which successfully achieves the
output power. An outstanding design with the platform. Digital cards enhance a higher capacity teleconferencing capabilities on IDA8 platform.
maximized flexibility by providing with true 48V of input & output configuration with up to 8
phantom power for each card. channels in and 8 channels out on a single card.

Input Audio Board AES/EBU Card Telephone Card


(Mono Input / Output, Stereo
4 Channels of analog audio inputs
Ÿ Initiate outgoing calls:
Input / Output, Duplex Stereo)
3 pin Euroblock
Ÿ - DTMF tone dialing
Mono Input / Output : 4 channels audio input
Ÿ
0, 12, 24, 40, 54dB sensitivity levels
Ÿ - Speed-dialing
and 4 channels output of digital audio, Stereo
Signal, RTO, overload indicators
Ÿ - Redial
Input / Output: 2 Channels audio input (2 x 2)
+48V phantom Power
Ÿ - Flash (3-way telephone conversation)
and 2 channels output of digital audio (2 x 2),
-60 to +20dB fiber range for level
Ÿ Manual or auto answer incoming call
Ÿ
Duplex Stereo (2 CH for each channel): 4
-50 to +20dB overload threshold
Ÿ (optional N times)
Ÿ
channels audio input (1,2 CH) and 2 channels
Mute and bypass signal control
Ÿ Touch-tone decoding
Ÿ
outputs of digital audio (3,4 CH)
Volume display for each channel
Ÿ Caller ID reception
Ÿ
3 pin Euroblock
Ÿ
RoHS compliant
Ÿ Disable Hang up sound / Noise Suppression /
Ÿ
RTO / Overload / Signal Indicators
Ÿ
Line Echo Cancellation / Voice Enhance signal
-20 to + 20 dB for overload threshold
Ÿ
control
-60 to + 20 dB fiber range of level
Ÿ
Continuous Line Status and Fault Monitoring
Ÿ
Level control
Ÿ
Mute and level control for caller voice and
Ÿ
Volume display for each channel
Ÿ
ring tone
Mute and bypass control
Ÿ
Various way to control telephone module:
Ÿ
Digital transmission can be reach 100 meter
Ÿ
- Control signal from logic components
RoHS compliant
Ÿ
- External keypad remote controller
Output Audio Board
- Software control panel
4 channels of analog audio outputs
Ÿ - 3rd party command via RS232 or Ethernet
3 pin Euroblock
Ÿ Extensive customization options and
Ÿ
Signal, overload indicators
Ÿ parameters
-60 to +20dB fiber range for level
Ÿ RoHS compliant
Ÿ
-20 to +20dB overload threshold
Ÿ

Mute and bypass signal control


Ÿ

Volume display for each channel


Ÿ

RoHS compliant
Ÿ

ATEI
28
29
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

ATEÏS Studio
INTEGRATED OPERATION SOFTWARE

ATEÏS Studio is a user-friendly graphic user interface designed for intuitive system setup. The PC-
based software allows hardware updating, full system configuration and generates the user
interface for day-to-day system operation.

GRAPHICAL USER INTERFACE:

ATEÏS Studio allows complete PAVA/audio systems incorporating a range of devices to be configured,
monitored and controlled centrally from a single user interface. ATEÏS Studio supports all IP-based
products within the ATEÏS product family such as IDA8, LAP-AS and ECS. The software enables a
comprehensive overview of the system and its virtual connections and also offers control and
configuration for power amplifiers, paging consoles and remote controllers such as PSS-AS, CD16-AS
and URC-AS devices.
Configuration software
Runs on Windows
Ÿ

Assignable access levels with rights management


Ÿ

All system and unit parameters can be configured


Ÿ

Easy navigation
Ÿ

Drag & Drop features


Ÿ

Real-time monitored
Ÿ
DIAGNOSING:
Diagnostic and logging software
ATEÏS Studio monitors, controls, logs and reports a range of events. The whole system configuration
preset can be stored and reloaded at the press of a button, depending on application. Users can tailor Call, fault and general event logging
Ÿ
design elements of the graphic user interface or control panels, as well as program automatic On-line logging function
Ÿ
sequences of events and create different levels of user access for security and rights management.
Historical logging
Ÿ

BUILDING: Event display priority can be changed


Ÿ

Password-protected
Ÿ
ATEÏS Studio provides a complete set of tools and building blocks for real-time control, monitoring and
design of an audio system or Voice Evacuation system from paging console to loudspeaker. Detailed
information such as signal levels, loudspeaker impedance, pre-recorded messages, amplifier conditions
File transfer software
and other parameters can be monitored in real-time. PC-based application
Ÿ

A comprehensive library of tools, control and monitoring elements is provided along with the GUI, Supplied together with the network controller
Ÿ

including items such as volume control faders, metering, high-level EQ, compression, limiting, auto-gain, Creation of message sets
Ÿ
noise sensing, mixing, shortcut buttons and display elements. Element behavior can be fully tailored to Off-line configuration
Ÿ
suit each application. Built-in file transfer software transfers both data and audio files from the PC to
the network controller.
NOTE:
ACCESS LEVELS:
ATEÏS Studio Software Version:
Additional security can be added to the software with password-protected layers according to EN 54-
16. Multiple users can be created and assigned, each with a unique password and access to specific Version 1.X.X.XX for ATEÏS Local-Net
layers of the GUI. This creates a control surface specific which meets the need of system designers and
Version 3.X.X.XX for ATEÏS Global-Net
operators at multiple levels.
ATEÏS global-net System:

ATEÏS global-net, can be a network of more


than one controller(Matrix Mode and Switch
Mode) and a maximum up to 31 IDA8Sxx
Slave units (Matrix Mode and Switch Mode)
in a local system.

ATEI
30
IDA8 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

ATEÏS Studio
POWERFUL DIGITAL SIGNAL PROCESSING

ATEÏS designs and manufactures the leading products in the digital public address & voice alarm
systems market. A highly demanding public transportation network is installed into IDA8-series in
Europe, United States, Asia, the Middle East and global market where it is dominating the market for
high-tech audio communication solutions that combine redundant networks on CAT5, Fiber-optic and
TCP-IP.
IDA8-series of products is the ideal choice for commercial audio applications where schedule events
and background music are an integrated part of the voice-alarm, low-Z sound system. Both applications
guarantee for superb quality of sound and intelligibility. IDA8-series of products are complied with the
EN54-16, UL60065, ISO 7240-16 and BS5839/8

Drag & Drop: Matrix Mixer:

After the determination of the devices included in Breakthrough feedback cancellation -Correcting
your system, you can start configuring the internal feedback and alleviates the annoyance auto-
signal paths independently for each device with all matically. The feedback component analyzes and
the existing features that the huge component library detects the feedback source and adaptively
have offered. Simply by Drag & Drop and connects to attenuates the responsible frequency. There are 4
different audio components. types of feedback components which are
corresponded to the numbers of filters (4, 8 12 or
The all-in-one manipulating platform enhances an 16) that the feedback will use.
easy-to-use and real-time monitored tool, helping you
to concentrate on creating the cutting-edge Auto Noise Gain (A.N.G.) / DNM:
technology.
Featuring an integrated real-time frequency
analyzer and flexible per-channel, which makes a
excellent performance in a variety of operating
environments. Configuring and adjusting the
dynamic equalization bands can be easily done by
its delectated interface.

Page Control:

Some applications which are integrated in PAVA


system require a huge number of zones for
paging. It needs to be done with multiple ATEÏS
VOIP: audio processors (Matrix mode and Switch Mode)
IDA8 system, supporting VoIP based on SIP protocol connected together via ATEÏS Net. The Network
and Audio over IP applications by using PPM-IT5 Paging component provides the capabilities of
paging remote which makes an ideal and simple routing the input source signal to zones and each
solution for bridging audio and contact closures over source can specify which zone wants to page by
long distance LAN and WAN network. Efficiency and its priority value.
reliability are the unique features we have succeeded,
Telephone Card:
even dial-up users can experience the excellent sound
quality. The Telephone Card component is based as a
traditional telephone interface which manages the
telephone call for IDA8 system. The telephone
card component consists of a TC transmit
component and a TC receive component,
providing with dial, receive, detect the logic signal
response of DTMF status.

ATEI
31
Public Address - Voice Alarm
ATEI Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
DIVA8MG2
Loudspeakers
Compact PAVA system
Master Unit – Switch Mode

DIVA8G2 system is a compact


PAVA solution specifically design-
ed for small to medium-scale
installations. It has all the
essential functionality to comply
with EN-54 requirements for
DIVA8SG2
Voice Alarm, including full system
Compact PAVA system
monitoring, loudspeaker line Slave Unit – Switch Mode

impedance surveillance, micro


phone surveillance and monitored
interfacing with remote devices.
DIVA8G2 responds to Public
Address and Voice Alarm require-
ments as stated in EN54-16, ISO
7240-16 and BS5839/8, with
specific attributes for compliance
in large installations.
DIVA8G2 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

DIVA8MG2
COMPACT PAVA SYSTEM – MASTER UNIT – SWITCH MODE

DIVA8G2 system is a compact PAVA solution specifically designed for small to medium-
scale installations. It has all the essential functionality to comply with EN 54 requirements
MAIN CHARACTERISTICS for Voice Alarm, including full system monitoring, loudspeaker line impedance surveillance,
8-zone system controller with individual volume
Ÿ
microphone surveillance and monitored interfacing with remote devices.
DIVA8G2 responds to Public Address and Voice Alarm requirements as stated in EN54-16,
controls per channel
ISO 7240-16 and BS5839/8, with specific attributes for compliance in large installations.
5 audio inputs (2 x line, 1 x MIC/line, 1 x PSS or PSM,
Ÿ
1 x Fireman Mic)
CONNECTIVITY:
1000 Watts maximum load / 100V line outputs per
Ÿ
channel amplifier The DIVA8G2 Master unit provides enhanced digital audio processing (DSP), a digital message
player, a fully monitored fireman’s microphone, amplifier monitoring with switchover to
Enhanced loudspeaker line surveillance for A/B zoned
Ÿ
backups and loudspeaker line monitoring for 16 audio lines (8 lines A/B). It can process and
installations route one PSS-G2, CD8-G2 or CD16-G2 microphone console or up to ten cascaded PSM8-V3
9 monitored logic control inputs, 8 non-monitored logic
Ÿ paging microphones, along with two 0dB audio inputs and one mic/line input into two
control inputs different channels (music + voice) using configurable priorities. The DIVA8G2 system utilizes
Ethernet interface for configuration, control, diagnostics
Ÿ two external amplifier channels with a maximum capacity of 1000 W each.
and logging
PRE-PROCESSING:
Digital storage for up to 45 minutes of pre-recorded
Ÿ
messages in .WAV format All audio inputs feature contact and VOX activation and each input is fitted with volume
controls and equalizers. Up to 45 minutes of digital messaging can be stored in the unit. These
PEQ: 3 bands on inputs, 7 bands on the two outputs
Ÿ
are stored as WAV files and uploaded directly from a PC into the DIVA8MG2. Up to two
channels messages can be played simultaneously in different zones for phased evacuation.
Modbus, notifier, Vox@Net Protocol interface via RS232
Ÿ
Full monitoring of PSS and PSM paging consoles
Ÿ INTERFACING:

2 channel audio distribution for Paging and BGM


Ÿ DIVA8MG2 has nine monitored alarm inputs which can be individually programmed for specific
Incident data record with up to 2047 entries
Ÿ message/input routing to all or selected channels. Each DIVA8G2 system module has eight
Combined back-up amplifier function.
Ÿ output zones with A/B wiring and each zone can be routed manually or automatically to one
Programmable Message Scheduler Events
Ÿ
of the system’s audio channels (music or voice). The number of zones can be extended up to
128 A/B zones with the addition of DIVA8SG2 Slave units (up to a maximum of 15 slave units).
1 Fault relays & 1 EVAC relays outputs
Ÿ
The music source can be selected directly from the front panel and switched into each zone
Low and high pass filtering on inputs
Ÿ
separately, also a RS232 port on the rear panel allows third-party control and interfacing.
Programmable of 21 priority levels
Ÿ
2U standard 19” rack mounting
Ÿ
1 Fault & 1 Evac relays outputs
Ÿ
Programmable of 4 user levels
Ÿ
2'' full color TFT screen
Ÿ
Export the incident log
Ÿ
8 Logic relay contacts
Ÿ
EN54-16 certified
Ÿ

ATEI
33
DIVA8G2 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

DIVA8MG2
COMPACT PAVA SYSTEM – MASTER UNIT – SWITCH MODE

REDUNDANCY:

In case of Evacuation, the amplifier music channel can be used as a second alarm channel. Each
DIVA8G2 system requires only one 2-channel amplifier (one channel for music, one for voice).
The music amplifier will also act as a backup amplifier in case of voice amplifier failure. Each
channel can handle up to 1000W audio power (at 100V).

Users shall manually route the Fireman microphone signal, three digital messages into selected
zones, adjust the audio level and switch (ON/OFF) the music in each zones separately from the
front-panel of DIVA8MG2 (Master unit). In case of evacuation, the zone attenuator are auto-
matically bypassed. One output contact per zone can be activated each time the zone is
occupied with a source that has higher priority than the music (alarm or microphone paging).

SECURITY:

In accordance with EN54-16, ISO 7240-16 and BS5839/8, all DIVA8G2 system components and
peripherals are monitored. This monitoring extends from the capsule of a paging station
microphone to the end of a loudspeaker line. The external cables connected to the control
inputs are monitored for short and open circuit and an internally-generated pilot tone is
available for monitoring impedance on the loudspeaker lines. The master unit monitors the
status of all the equipment in the system, reports status changes and stores the last 999 fault
messages in the system. This log can be accessed on the master unit display or on a PC using
the DIVA8G2 control software.

DIVA8G2 system units operate either on 110VAC or 230VAC mains power supply or on a 24V
battery power supply for emergency back-up, with automatic switchover. Both power supplies
are monitored.

INSTALLATION NOTES:

INTERCONNECTIONS:

DIVA8MG2 Master unit and DIVA8SG2 Slave unit


with 4 amplifier channels

ATEI
34
DIVA8G2 system

DIVA8MG2
COMPACT PAVA SYSTEM – MASTER UNIT – SWITCH MODE

CONTROLS AND INDICATORS PARTS INCLUDED

Front Quantities Components Monitor loudspeaker


2" full color TFT screen
ž 1 DIVA8MG2 Master unit Frequency response -3dB @ 200 Hz and 20 kHz
Zone selection / Music control / EVAC / Reset /
ž 1 Fireman microphone SNR > 70 dB
MSG / Test buttons 1 Power cord (type depends on region) THD < 5% @ 1 kHz @8ohm
Fireman microphone
ž 1 Set of connectors Signal 16 dBu
VACIE indicators
ž 1 Set of 19" rack mount brackets
Zone attenuator knobs
ž 1 DIVA8G2-system software Amplifier Capacity (per channel)
Status indicators (Power / G. Fault / System Fault /
ž 1 LAN Cable Input 1000W
EVAC / Bypass Mode)
TECHNICAL SPECIFICATIONS
Rear Mechanical
Voltage selector
ž Electrical Dimensions (With 19" rack mount brackets)
Mains power supply (H x W x D) 2RU, 88 x 483 x 338 mm
INTERCONNECTIONS
Voltage 230/115 VAC ±15%, 50/60 Hz (3-1/2" x 19" x 13-3/10")
Front Power consumption 48 W Weight 7.5 kg (16.5lbs)
Fireman microphone
ž Fuse Rating 1.6 A Mounting 19"-rack mount
Rear Color RAL7016
AC power socket
ž Battery power supply
24VDC backup power input
ž Voltage 18 - 30 VDC Environmental
9 EVAC inputs
ž Amp Consumption 1.4 A Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
8 control inputs
ž Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
2 state inputs(open contact & close contact)
ž Performance Relative humidity 15% to 90%
8 control outputs
ž Frequency response -3dB @ 20 Hz and 20 kHz Air pressure 600 to 1100 h Pa
Evac & Fault contacts
ž Heat Dissipation 140 BTU/hr
1 remote Fireman’s mic input
ž Audio Line inputs (Optional audio input card)
Music / Line Input
ž Connector 2x2 RCA (un-balanced)
4 analogue line audio inputs
ž Frequency response -3dB @ 20 Hz and 20 kHz
Ethernet connection
ž SNR > 76 dB (Line-level)
8 zone 100 Volt outputs (A+B)
ž > 78 dB (Mic-level)
RS232 Connector
ž THD < 0.02% @ 1 kHz
1 monitored paging console input
ž Input sensitivity 770 mV (0 dBu ~ -60 dBU)
Input impedance 10 kohm
CERTIFICATIONS AND APPROVALS

Fireman microphone
REGIONAL CERTIFICATIONS
Connector 5-pin locking-DIN
Europe Voice Alarm EN54-16 certified 2012 Frequency response -3dB @ 20 Hz and 20 kHz
CE – 0359 SNR > 70 dBu
according to EN50130 – 4 THD < 1% @ 1 kHz @ 8ohm
Signal -40 to -30 dBu
Output impedance 10 kohm

ATEI
35
DIVA8G2 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

DIVA8SG2
COMPACT PAVA SYSTEM – SLAVE UNIT – SWITCH MODE

DIVA8G2 system is a compact PAVA solution specifically designed


for small to medium-scale installations. It has all the essential
functionality to comply with EN 54 requirements for Voice Alarm,
including full system monitoring, loudspeaker line impedance
surveillance, microphone surveillance and monitored interfacing
with remote devices.
DIVA8G2 responds to Public Address and Voice Alarm requirements
as stated in EN54-16, ISO 7240-16 and BS5839/8, with specific
attributes for compliance in large installations.

CONNECTIVITY: MAIN CHARACTERISTICS


The DIVA8SG2 Slave unit is an extension unit for the DIVA8MG2 Master. It increases the number of 2 channel audio distribution for Paging and
Ÿ
paging zones by 8 zones for each slave unit added in the system. Up to 15 slave units can be added BGM combined back-up amplifier function
per DIVA8G2 system and must be used in conjunction with the DIVA8MG2 Master. A complete Ethernet interface for configuration, control,
Ÿ
DIVA8G2 system provides up to 128 zones (A/B). Slave units are linked to the system master via
diagnostics and logging via DIVA8MG2
shielded CAT-5 cable (max. length 100m).
9 monitored logic control inputs, 8 non-
Ÿ
The DIVA8SG2 Slave handles the same 1000 W power capacity as the master unit (at 100V) on each monitored logic control inputs
amplifier channel (music + voice). Each zone can be routed manually or automatically to either channel. 1000 Watts maximum load / 100V line outputs
Ÿ
For maximum flexibility connected amplifiers can distribute their power across multiple slaves or
per channel amplifier
additional amplifier channels can be added to the system to assist where more output power is
Enhanced loudspeaker line surveillance for
Ÿ
needed. The 100 V amplifier signal is simply linked to the slaves to create a 100 V signal bus.
A/B-zoned installations
INTERFACING: 1 Fault relays & 1 EVAC relays outputs
Ÿ

DIVA8SG2 extends the number of input and output contacts available in the system. It includes nine 1U standard 19” rack mounting
Ÿ

alarm inputs triggered either by dry contact or relay (software-selectable), eight logic contact inputs, 8 Logic relay contacts
Ÿ
two external fault contact inputs and eight contact outputs. EN54-16 certified
Ÿ

REDUNDANCY:

In case of Evacuation, the amplifier music channel can be used as a second alarm channel. Each
DIVA8G2 system requires only one 2-channel amplifier (one channel for music, one for voice). The
music amplifier will also act as a backup amplifier in case of voice amplifier failure. Each channel can
handle up to 1000 W audio power (at 100 V).

Users shall manually route the Fireman microphone signal, three digital messages into selected zones,
adjust the audio level and switch (ON/OFF) the music in each zones separately from the front-panel of
DIVA8MG2 (Master unit). In case of evacuation, the zone attenuators are automatically bypassed. One
contact output contact per zone can be activated each time once the zone is occupied with a source
that has higher priority than the music (alarm or microphone paging).

SECURITY:

In accordance with EN54-16, ISO 7240-16 and BS5839/8, all DIVA8G2 system components and
peripherals are monitored. This monitoring extends from the capsule of a paging station microphone to
the end of a loudspeaker line. The external cables connected to the control inputs are monitored for
short and open circuit and an internally-generated pilot tone is available for monitoring impedance on
the loudspeaker lines. The master unit monitors the status of all the equipment for the system, reports
status changes and stores the last 2047 incident in the system. This log can be accessed on the master
unit display or on a PC using the DIVA8G2 control software.

DIVA8G2 system units operate either on 110VAC or 230VAC mains power supply or on a 24V battery
power supply for emergency back-up, with automatic switchover. Both power supplies are monitored.

ATEI
36
DIVA8G2 system
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

DIVA8SG2
COMPACT PAVA SYSTEM – SLAVE UNIT – SWITCH MODE

INSTALLATION NOTES:
Single amplifier with single back-up Multiple amplifier with single back-up
The DIVA8MG2 Master unit and DIVA8SG2 Slave unit are designed
for entry level solutions. It provides a cost-effective system when
there's only paging requirement or paging with BGM. The DIVA8G2
System concept utilizes switched audio distribution from a single
amplifier source to up to 128 loudspeaker groups. DIVA8MG2 Master
unit and DIVA8SG2 Slave unit have 4 different system solutions.

1. Block-diagram (the upper one)

Require only 2 amplifiers DIVA8MG2 Master unit and DIVA8SG2 Slave


unit in SINGLE CHANNEL mode shows how DIVA8MG2 Master unit
and DIVA8SG2 Slave unit are connected to the amplifiers and to the
loudspeaker lines using multiple slaves.

LEFT: SINGLE-audio for Paging/Alert and Backup for small loads.


Each channel can handle up 1000 W audio power a 100 V and be
supplied not only for the master unit but also the slave units in each
zone. Note: The backup amplifier must have the same power
capacity as the Paging/Alert amplifier.

RIGHT: SINGLE-audio for Paging/Alert and Backup for higher


loads. Requires and processes 0 dB audio outputs and handle up
3000 W audio power at 100 V from the DIVA8M Master unit to the
DIVA8S slave units, feeding into the additional amplifiers. The system
needs 1 Back-up amplifier to run the multiple DIVA master and slave 1000 Watt System 3 x 1000 Watt System

units. Note: The Backup amplifier must have the same power
capacity as the Paging/Alert amplifier in the system.
Single amplifier set Multiple amplifier sets
2. Block-diagram (the lower one)

DIVA8MG2 Master unit and DIVA8SG2 Slave unit in DUAL CHANNEL


mode shows how DIVA8MG2 Master unit and DIVA8SG2 Slave unit
are connected to the amplifiers and to the loudspeaker.

LEFT: DUAL-audio for Paging/Alert/BGM and Backup for small


loads. Each channel can handle up 1000 W audio power at 100 V
and be supplied not only for the master unit but also the slave units
in each zone. Note: The BGM/Backup amplifier must have the same
power capacity as the Paging/Alert amplifier in case of amplifier
failure.

RIGHT: DUAL-audio for Paging/Alert/BGM and Backup for higher


loads. Requires and processes 0 dB audio outputs and handle up
3000 W audio power at 100 V from the DIVA8M Master unit to the
DIVA8S slave units, feeding into the additional amplifiers. In this
configuration, amplifiers provide paging and music in individual
zones simultaneously. Note: The BGM/Backup amplifier must have
the same power capacity as the Paging/Alert amplifier in the system.

1000 Watt System 3 x 1000 Watt System

ATEI
37
DIVA8G2 system

DIVA8SG2
COMPACT PAVA SYSTEM – SLAVE UNIT – SWITCH MODE

CONTROLS AND INDICATORS PARTS INCLUDED

Front Quantities Components Amplifier Capacity (per channel)


Zone selection buttons
ž 1 DIVA8SG2 Slave unit Input 1000W
Zone status / Power indicators
ž 1 Power cord (type depends on region)
VACIE indicators (EVAC / Fault / Alert / Page /
ž 1 Set of connectors Mechanical
Selected) 1 Set of 19” mounting brackets Dimensions (With 19" rack mount brackets)
(H x W x D) 1RU, 44 x 483 x 277 mm
INTERCONNECTIONS TECHNICAL SPECIFICATIONS
(1-3/4" x 19" x 10-9/10")
Rear Electrical Weight 3.9 kg (8.6 lbs)
AC power socket
ž Mains power supply Mounting 19"-rack mount
24VDC backup power input
ž Voltage 230/115 VAC ±15%, 50/60 Hz Color RAL7016
9 EVAC inputs
ž Power consumption 35 W
8 control inputs
ž Fuse Rating 1.6 A Environmental
2 state inputs(open contact & close contact)
ž Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
Master to Slave link
ž Battery power supply Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
8 zone 100 Volt outputs (A+B)
ž Voltage 18 - 30 VDC Relative humidity 15% to 90%
Terminator switch
ž Amp Consumption 1.4 A Air pressure 600 to 1100 h Pa
Heat Dissipation 120 BUT/hr
CERTIFICATIONS AND APPROVALS
Performance
Frequency response -3 dB @ 20 Hz and 20 kHz
REGIONAL CERTIFICATIONS

Europe Voice Alarm EN54-16 certified 2012


CE – 0359
according to EN50130 – 4

ATEI
38
Public Address - Voice Alarm
Audio Distribution over IP ATEI
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
DPAfour
Loudspeakers
Digital Power Amplifiers

DPAfour (Digital Power Amplifier),


SPA (Security Power Amplifier) and
BPA (Bridging Power Amplifier) are
designed for public address or
voice alarm system application.
They were specifically developed
to meet the requirements of EN54-
16 and can therefore also be used
as part of fire detection and fire
alarm systems.
Public Address - Voice Alarm
ATEI Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

SONAES

Charger and Monitoring Unit

BPA

Bridging Power Amplifiers

SPA

Security Power Amplifiers

ATEI
Amplifiers
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

DPAfour
DIGITAL POWER AMPLIFIERS

MAIN CHARACTERISTICS The DPAfour is a 2RU 19" rack mountable, 4-channel class-D power amplifier, transformer
4 audio outputs (100 V /70 V /50 V / 4 Ohm
Ÿ
isolated for 100 V, 70 V, 50 V and 4 Ohm distributed loudspeaker systems. There are two
selectable) models in the DPAfour range:
DPAfour 125 rated at 4 x 125 W
Fault reporting outputs
Ÿ
DPAfour 250 rated at 4 x 250 W
Four audio input gain control
Ÿ
And one model in 8-channel range:
Advanced audio processing for each amplifier
Ÿ
DPA8060 rated at 8 x 60 W
channel using DIVA8G2 or IDA8 systems
Each channel can deliver up to 125/250W as a separate channel or can be bridged to deliver
Supervision of the amplifiers through DIVA8G2
Ÿ
higher power. The amplifier has a dual-voltage mains supply 115/230V AC (selectable internally)
or IDA8 systems
and a 24 VDC battery back-up connection.
Back up amplifier switching through DIVA8G2
Ÿ
or IDA8 systems In combination with DIVA8G2 and IDA8 the DPAfour amplifiers have the following features:
Loudspeaker line monitoring with DIVA8G2 or
Ÿ
Ÿ Loudspeaker line monitoring for Shortcut Open line Ground leakage.
IDA8
Output bridging for higher power
Ÿ Ÿ Single spur A/B loudspeaker lines individually monitored By adding a SONAES to the system a
fully EN54-16 certified Voice Alarm system will be created, with extensive PA capabilities.

DIVA8G2 & DPA Wiring example


with DPA Ch 1&2 bridged

*If DPA channels are bridged,


gain settings should be
set at equal level for both
channel 1&2 and/ or 3&4

IDA8 & DPA


Wiring example

ATEI
41
Amplifiers

DPAfour
DIGITAL POWER AMPLIFIERS

CONTROLS AND INDICATORS TECHNICAL SPECIFICATIONS

LED VU metering
ž Electrical Loudspeakers outputs DPA4250
Status indicators for: Signal, Clip, Mains, Battery,
ž Mains power supply Rated load resistance 40 ohm (100 V)
Channel fault and General fault Voltage 230/115 VAC ±15%, 50/60 Hz Rated load capacitance 120 nF (100 V)
Power consumption** standby - idle* - Pmax (per CH.) Rated output power 250 W (cont. at 40°C)
INTERCONNECTIONS
DPA8060 5 W – 10 W – 85 W (per channel)
Rear DPA4125 1 W – 38 W – 180 W Two channels bridged 500 W (cont. at 40°C)
Rotary volume control
ž DPA4250 1 W – 44 W – 360 W
Mains switch
ž **(Total Mains-power consumption @ 230 VAC) Frequency response 40 Hz to 20 kHz(-3 dB)
AC power socket
ž *(Alarm cycle + 10 V pilot-tone @ 24 VDC) SNR >90 dB (no pilot tone)
24VDC backup power input
ž Crosstalk <70 dB at nominal load for 1 kHz
Four line inputs
ž Battery power supply Distortion <0.1% (@ 1 kHz)
100 V, 70 V, 50 V or 4 ohm outputs
ž Voltage 19-30 VDC @ -10dB of rated output power
(for each amplifier channel) Power consumption** standby - idle* - Imax (per CH.)
DPA8060 0.2 A – 0.4 A – 2.6 A Mechanical
CERTIFICATIONS AND APPROVALS
DPA4125 0.03 A – 1.45 A – 5.6 A Dimensions (19" with the fixing holes included)
DPA4250 0.03 A – 1.65 A – 11 A (H x W x D) 2RU, 88.5 x 483 x 370 mm
REGIONAL CERTIFICATIONS
**(Total Mains-power consumption @ 230 VAC) (3-1/2" x 19" x 14-3/5")
Europe Voice Alarm EN54-16 certified 2012 *(Alarm cycle + 10 V pilot-tone @ 24 VDC) Weight
CE – 0359 DPA8060 12.7 kg (27.9 lbs)
according to EN50130 – 4 Performance DPA4125 14 kg (31 lbs)
Line inputs 4 x (One per channel) DPA4250 18 kg (40 lbs)
PARTS INCLUDED
8 x for DPA8060 Mounting 19"-rack mount
Quantities Components Connector 3-pin phoenix Color RAL7016
1 DPA xxxx Digital Power Amplifier Frequency response +/-3 dB @ 50 Hz and 20 kHz
1 Power cord SNR > 90 dB Environmental
1 Set of connectors THD < 0.1% @ 1 kHz Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
Input sensitivity 770 mV Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
Input impedance 22k Ohm Relative humidity 15% to 90%
Air pressure 600 to 1100 h Pa
Loudspeakers outputs DPA8060 Heat Dissipation
Rated load resistance 167 Ohm (100 V); 82 Ohm (70 V) DPA8060 685 BTU/hr
Rated load capacitance 30 nF (100 V); 60 nF (70 V) DPA4125 750 BTU/hr
Rated output power 60 W (1 min. at 40°C) (per CH) DPA4250 1500 BTU/hr

Loudspeakers outputs DPA4125


Rated load resistance 80 ohm (100 V)
Rated load capacitance 62.5 nF (100 V)
Rated output power 125 W (cont. at 40°C)
(per channel)
Two channels bridged 250 W (cont. at 40°C)

ATEI
42
Amplifiers
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

SPA
SECURITY POWER AMPLIFIERS

MAIN CHARACTERISTICS There are two types of power amplifier units in the SPA-PAVA product range. The overall
2 audio outputs (selectable 100 / 70 / 8 Ohm
Ÿ
power rating is 2x120 or 2x240 watts. The power amplifiers can be set to 100 V, 70 V and 8
outputs) Ohm output tapings. They have short-to-ground, short-circuit detection and line-impedance
surveillance up to 5% deviation using the DIVA8G2 and IDA8 range of products for
Fault reporting outputs
Ÿ
loudspeaker-line surveillance.
Two audio inputs with gain-set
Ÿ

Supervision of the amplifiers using DIVA8G2 or


Ÿ
They support both single-spure and redundant loop cabling (A/B). The amplifiers have a
IDA8 controllers changeover facility for spare power amplifier switching. Both features are facilitated by the
DIVA8G2 and IDA8 controllers and slaves. The amplifiers have a 24 VDC back-up supply input.
Advanced audio processing for each amplifier
Ÿ
channel using DIVA8G2 or IDA8 systems FUNCTIONS:
Amplifier supervision and spare amplifier
Ÿ
The power amplifiers receive line-level input signals from the DIVA8G2 and IDA8 controllers and
switching through DIVA8G2 or IDA8 systems
slaves. The display panel will show the VU-meter is reading data when the EN54-16 default switch
Loudspeaker line and loudspeaker supervision
Ÿ is inhibited.
through DIVA8G2 or IDA8 systems

DIVA8G2 & SPA


Wiring example

IDA8 & SPA


Wiring example

ATEI
43
Amplifiers
SPA
SECURITY POWER AMPLIFIERS

CONTROLS AND INDICATORS TECHNICAL SPECIFICATIONS

LED VU metering
ž Electrical Loudspeakers outputs SPA2240
Status indicators for: Overload, Over temperature,
ž Mains power supply Rated load resistance 40 Ohm (100 V); 20 Ohm (70 V)
Battery and Mains Voltage 220 VAC ±10%, 50 Hz Rated load capacitance 125 nF (100 V); 250 nF (70 V)
Power consumption** idle* - Pmax (per CH.) Rated output power 240 W (cont. at 40°C)
INTERCONNECTIONS
SPA2120 12 W – 290 W (per channel)
Rear SPA2240 12 W – 550 W
Rotary volume control
ž **(Total Mains-power consumption) Frequency response 20 Hz to 20 kHz @ -3 dB
Mains switch
ž *Idle: Measured with 10 Volt surveillance SNR > 90 dB (no pilot tone)
AC power socket
ž tone on the output. Crosstalk < 80 dB at nominal load for 1 kHz
24VDC backup power input
ž Fuse Rating Distortion < 1% (@ 1 kHz) @ -10dB
Four line inputs
ž SPA2120 5 A@110 V, 2.5 A@250 V of rated output
100 V, 70 V or 8 ohm outputs
ž SPA2240 8 A@110 V, 5 A@250 V
(for each amplifier channel) Mechanical
Battery power supply Dimensions (For 19" rack use with brackets)
CERTIFICATIONS AND APPROVALS
Voltage 19-30 VDC (H x W x D)
Power consumption** idle* - Imax (per CH.) SPA2120 2RU, 88 x 425 x 305 mm
REGIONAL CERTIFICATIONS
SPA2120 0.4 A – 8 A (3-1/2" x 16-3/4" x 12")
Europe Voice Alarm EN54-16 certified 2012 SPA2240 0.4 A – 15 A SPA2240 2RU, 88 x 425 x 402 mm
CE – 0359 **(Per ch. @ 24 VDC) (3-1/2" x 16-3/4" x 15-4/5")
according to EN50130 – 4 *(Alarm cycle + 10 V pilot-tone @ 48 VDC) Weight
SPA2120 12.3 kg (27.1 lbs)
PARTS INCLUDED
Performance SPA2240 18.5 kg (40.8 lbs)
Quantities Components Line inputs 2 x (One per channel) Mounting 19"-rack mount
1 SPA 2xxx Security Power Amplifier Connector 3-pin XLR and 3-pin phoenix Color RAL7016
1 Power cord (electronically balanced)
1 Set of mounting brackets for 19" rack Frequency response +/-3 dB @ 40 Hz and 20 kHz Environmental
1 Set of connectors SNR > 86 dB @ 1k Hz at full power Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
1 Set of feet THD <=1% @ 1k Hz Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
Input range -6 dBV to 6 dBV / 770mV Relative humidity 15% to 90%
Input impedance 22k Ohm Air pressure 600 to 1100 h Pa
Heat Dissipation
Loudspeakers outputs SPA2120 SPA2120 1160 BTU/hr
Rated load resistance 83 Ohm (100 V); 41 Ohm (70 V) SPA2240 2110 BTU/hr
Rated load capacitance 60 nF (100 V); 125 nF (70 V)
Rated output power 120 W (cont. at 40°C)
(per channel)

ATEI
44
Amplifiers
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

BPA
BRIDGING POWER AMPLIFIERS

MAIN CHARACTERISTICS The BPA is a 2RU 19" rack-mountable, 2-channel amplifier, transformer isolated for 100 V, 50 V
2 audio outputs for BPA2120, 2240 and 2480
Ÿ
and 8 Ohm distributed loudspeaker systems. There are three models in the coverage of BPA:
(100 V / 50 V / 8 ohm selectable outputs) Ÿ BPA2120: 2 x 120 W
Ÿ BPA2240: 2 x 240 W
Fault reporting outputs
Ÿ
Ÿ BPA2480: 2 x 480 W
Two audio inputs with gain-set
Ÿ
The BPA amplifier has a 230 VAC mains supply input and a 48 VDC battery back-up input which
Supervision of amplifiers through DIVA8G2 or
Ÿ
allows it to be used in combination with a battery backup system for maximum availability and
IDA8 systems
reliability in an emergency evacuation system. BPA amplifiers have short-to-ground, short-circuit
Advanced audio processing for each amplifier
Ÿ
detection and line-impedance surveillance up to 5% deviation using the DIVA8G2 or IDA8 systems
channel through DIVA8G2 or IDA8 systems for loudspeaker-line surveillance. They support both single-spure and redundant loop cabling (A/B)
Amplifier supervision and spare amplifier
Ÿ and have a switchover facility that automatically reroutes power to a backup amplifier (if present).
switching through DIVA8G2 and IDA8 systems BPA amplifiers have a rear-panel selector switch for amplifier monitoring according to EN 54-16.
Loudspeaker line and loudspeaker supervision
Ÿ
through DIVA8G2 and IDA8 systems

DIVA8G2 & BPA


Wiring example

IDA8 & BPA


Wiring example

ATEI
45
Amplifiers

BPA
BRIDGING POWER AMPLIFIERS

CONTROLS AND INDICATORS TECHNICAL SPECIFICATIONS

LED VU metering
ž Electrical Loudspeakers outputs BPA2240
Status indicators for: Overload, Over temperature,
ž Mains power supply Rated load resistance 40 ohm (100 V); 10 ohm (50 V)
Battery and Mains Voltage 230 VAC ±10%, 50/60 Hz Rated load capacitance 125 nF (100 V); 500 nF (50 V)
Power consumption** standby - idle* - Pmax (per CH.) Rated output power 240 W (1 min. at 40°C) (per CH)
INTERCONNECTIONS
BPA2120 5 W – 11 W – 295 W
Rear BPA2240 5 W – 11 W – 550 W Loudspeakers outputs BPA2480
Rotary volume control
ž BPA2480 5 W – 13 W – 1000 W Rated load resistance 20 ohm (100 V); 5 ohm (50 V)
Mains switch at the rear of the device
ž **(Total Mains-power consumption) Rated load capacitance 250 nF (100 V); 1 uF (50 V)
AC power socket
ž *Idle: Measured with 10 Volt surveillance Rated output power 480 W (1 min. at 40°C) (per CH)
48VDC backup power input
ž tone on the output.
Two line inputs
ž Fuse Rating Frequency response 20 Hz to 20 kHz @ -3 dB
100 V, 50 V or 8 ohm outputs
ž BPA2120 5 A@110 V, 2.5 A@250 V SNR > 90 dB (no pilot tone)
(for each amplifier channel) BPA2240 8 A@110 V, 5 A@250 V Crosstalk < 80 dB at nominal load for 1 kHz
BPA2480 16 A@110 V, 7 A@250 V Distortion < 1% (@ 1 kHz) @ -10dB
REGIONAL CERTIFICATIONS
of rated output
Europe Voice Alarm EN54-16 certified 2012 Battery power supply
CE – 0359 Voltage Mechanical
according to EN50130 – 4 BPA ALL TYPES 48-53 VDC Dimensions (For 19" rack use with brackets)
Power consumption** standby - idle* - Imax (per CH.) (H x W x D)
PARTS INCLUDED
BPA2120 0.09 A – 0.16 A – 4.07 A BPA2120 / BPA2240 2RU, 88 x 430 x 375 mm
Quantities Components BPA2240 0.09 A – 0.23 A – 8.13 A (3-1/2" x 17" x 14-3/4")
1 BPA 2xxx Bridging Power Amplifier BPA2480 0.09 A – 0.23 A – 13 A BPA2480 2RU, 88 x 430 x 430 mm
1 Power cord **(Per ch. @ 48 VDC ) (3-1/2" x 17" x 17")
1 Set of mounting brackets for 19" rack *(Alarm cycle + 10 V pilot-tones @ 48 VDC) Weight
1 Set of connectors BPA2120 13.7 kg (30.2 lbs)
1 Set of feet Performance BPA2240 16.2 kg (35.7 lbs)
Line inputs 2 x (One per channel) BPA2480 20.5 kg (45.1 lbs)
Connector 3-pin XLR and 3-pin phoenix Mounting 19"-rack mount
(electronically balanced) Color RAL7016
Frequency response +/-3 dB @ 50 Hz and 18 kHz
SNR > 90 dB @ 1K Hz at full power Environmental
THD < =1% @ 1 kHz Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
Input range -6 dBV to 6 dBV / 770mV Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
Input impedance 22k Ohm Relative humidity 15% to 90%
Air pressure 600 to 1100 h Pa
Loudspeakers outputs BPA2120 Heat Dissipation
Rated load resistance 83 Ohm (100 V); 20 Ohm (50 V) BPA2120 1160 BTU/hr
Rated load capacitance 60 nF (100 V); 250 nF (50 V) BPA2240 2110 BTU/hr
Rated output power 120 W (1 min. at 40°C) (per CH) BPA2480 3550 BTU/hr

ATEI
46
Battery Charger
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

SONAES
CHARGER AND MONITORING UNIT - EN 54-4

MAIN CHARACTERISTICS CHARGER AND MONITORING UNIT - EN 54-4


Soneas 6/40
The SONEAS series of battery chargers (24 VDC) are designed for Voice Alarm System. The
battery chargers are microprocessor based devices that have been designed to charge lead
2RU-rackmount charger
Ÿ
acid batteries (back-up batteries connected to the Voice Alarm System) and, simultaneously, to
3 Auxiliary outputs, max. 5 A per output
Ÿ
provide power to auxiliary devices such as the DIVA8G2 and IDA8 system controllers.
2 Main outputs, max. 20 A per output
Ÿ
The SONEAS battery chargers, 6/40 and 12/150, are EN54-4 certified. The maximum charging
Battery capacity: 24 AH to 114 AH
Ÿ
current is 6 or 12 A. The battery charger is two rack units high, and has to be installed in a 19"
Soneas 12/150 rack. Maximum battery capacity 114 or 225 AH. The SONAES comes without batteries.
2RU-rackmount charger
Ÿ
OVERVIEW:
3 Auxiliary outputs, max. 5 A per output
Ÿ

6 Main outputs, max. 40 A per output


Ÿ To meet the secured power back-up system need, determining the exact conditions and the
amount of battery back-up for a system is much complex than other applications. Public Address /
Battery capacity: 65 AH to 225 AH
Ÿ
Voice Alarm system does not draw a constant current. The standard defines a standby time and an
evacuation time. In this case, it is crucial to pick a battery back-up
that shall supply the minimum amount of power for a set amount
of time. With SONAES battery chargers, it provides you with a
battery calculator program which determines the exact capacity.

REGULAR PROCEDURE AS FOLLOWS:

1. Determine the standby / evacuation current and the amount of


battery back-up of the system.

2. Detect and enhance the standby / evacuation current


simultaneously for 24 hours.

3. 24 Hours discharge capacity of the battery.

INSTALLATION NOTES FOR SONAES 6/40

ATEI
47
Battery Charger

SONAES
CHARGER AND MONITORING UNIT - EN 54-4

REGIONAL CERTIFICATIONS

Europe Voice Alarm EN54-4 Mechanical


0333 – CPD – 075381 Dimensions (With 19" rack mount brackets)
0333 – CPD – 075382 (H x W x D) 1RU, 44 x 483 x 310 mm
(1-3/4" x 19' x 12")
PARTS INCLUDED
Weight
Quantities Components SONEAS 6/40 4.9 kg (10.8 lbs)
1 SONEAS 6/40A or SONEAS 12/150A SONEAS 12/150 6 kg (13 lbs)
1 Set of connectors Mounting 19"-rack mount
Color RAL7016
TECHNICAL SPECIFICATIONS

Electrical Environmental
Mains power supply Operating temperature -5ºC ~ 45ºC (23ºF ~ 113ºF)
Voltage 230 VAC ±15%, 50/60 Hz Storage temperature -20ºC ~ 85ºC (-4ºF ~ 185ºF)
Power consumption 380 W at Full load Relative humidity 20% to 95% (Non-Condensing)
Air pressure 600 to 1100 h Pa
Battery power supply Heat Dissipation 1300BTU/hr
Voltage 24 VDC
Maximum charging current
SONEAS 6/40 6A
SONEAS 12/150 12 A

Outputs
Main for amplifiers
SONEAS 6/40 max. 40 A for 5 outputs
SONEAS 12/150 max. 150 A for 9 outputs
Auxiliary for controllers 3 x
Maximum current 5A
Soneas 6/40

Batteries 2x12 V, 24 to 225AH


Brands Yuasa NPL Series
Power-Sonic GB Series
ABT TM Series
EnerSys VE Series Soneas 12/150
Effekta BTL Series
Long GB Series

ATEI
48
Public Address - Voice Alarm
Audio Distribution over IP ATEI
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers PSS AS /
PSS G2 /
PSS G2E

Color Touch-Screen Secured


Paging Console

PSS AS / PSS G2 : paging console, CD-


touch : wall-mounted monitored touch -
screen paging console, CD8 / CD16 :
Wall-mounted Monitored Paging Console,
PPM / PSM : Desktop Paging Consoles
for Commercial Use, DialPad / Wireless
Transceiver : Touch Dial device for IDA8
system, RAC5 / RAC8 : Wall-mounted
PPM-IT5 PPM / PSM
Level Sources Remote Selector, URC -
Color Touch-Screen Secured Desktop Paging Consoles
Programmable Remote Controller with
IP Paging Console
Display, DNM - Digital Noise Sensing
Microphone, URGP - Alarm Input Interface
for IDA8 System and DIVA8 System,
respond to Public Address and Voice
Alarm requirements with specific attri-
butes for compliance in small, medium
and large installations.
Public Address - Voice Alarm
ATEI Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

CD-touch

URC Wall-mounted Monitored


Touch -screen Paging Console
Programmable Remote
Controller with Display

URGP

Alarm Input Interface for


IDA8-System and DIVA-System
CD 8 / CD16

Wall-mounted Monitored
Paging Console
Consoles & Accessories
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

PSS AS / PSS G2 / PSS G2E / PPM-IT5


FULL COLOR TOUCH-SCREEN SECURE PAGING CONSOLE

The PSS paging console comes with a 5" TFT touch screen interface which allows call-paging,
message broadcasting and DSP matrix parameter control over a secure (monitored) bus. The
backlit full-color touch screen is designed for simple, user-friendly operation and offers a total
of 168 software keys across 14 pages for zone or group of zones selections. Each key
contains a color-changing field indicating that the zone is occupied by a different process.
Alongside the touch screen, three hardware keys are also provided for free assignment within
the software.
Several levels of operation with password protection make the PSS a versatile device that fits as
well in a commercial shopping center as in an industrial high-security environment. All paging
parameters for site operation can be pre-programmed; zones can be assigned, named, grouped to
different buttons, message triggered and level, pre-call chime set and adjusted. The message and
the chime can also be stored in the PSS console. In addition, fader control, button control and
PSS MAIN CHARACTERISTICS event control can also be pre-configured.

Secured CAT-5 link to controllers and slaves


Ÿ The PSS AS and the PSS G2 are powered by 24V DC supply.
Supervision of microphone capsule
Ÿ
Note: There are two versions of the PSS paging console with identical hardware and functionality
Monitoring loudspeaker
Ÿ but different firmware for compatibility with different systems.
5” full color touch-screen, 800 x 480 pixels
Ÿ
PSS AS: Used with IDA8 system and ECS system controllers and slaves
14-pages x 12 keys
Ÿ

Power, status and fault indicator


Ÿ PSS G2: Used with DIVA8G2 system controllers

Comprehensive system status information from


Ÿ PSS G2E: Used with DIVA8G2 system controllers and can be powered by Ethernet.
touch-screen
EN54-16 certified
Ÿ
The ATEÏS range of security systems complies with current architectural demands requiring IP
and/or fiber-optic networking to cater for any possible PAVA design, however complex. ATEÏS
responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and
BS5839/8, with specific attributes for compliance in large installations.

PPM-IT5 MAIN CHARACTERISTICS


5" TFT full color paging console
Ÿ

High quality gooseneck microphone and built-


Ÿ
in loudspeaker
Ethernet interface including PoE (Power Over
Ÿ
Ethernet)
Automatic gain control on microphone input
Ÿ

Echo cancellation / Noise Reduction


Ÿ

Up to 300 pages x 12 keys


Ÿ

G.711 / G.722 / G.726 / G.727 audio encoding


Ÿ
/decoding
Audio Stream using SHOUTcas t / ICEcast (AAC
Ÿ PPM-IT5: The 3 hardware keys can be freely assigned by software. The PPM-IT5 Media console is a
48K/44.1K) protocols versatile device that enhances paging over IP-networking.
Half or full duplex conversation
Ÿ
All paging parameters needed for site operating can be programmed: zones assigned to different
Memory space for prerecorded messages and
Ÿ buttons, name of zones, group of zones, messages triggering or event control. A total of 3600 keys
chime over 300 pages allow zones or groups of selection. All the settings shall be done via web pages
3 key-buttons: User-definable via ATEÏS Studio
Ÿ with your web browser.
GUI
RJ 9 for telephone headset and 2 mini-jack
Ÿ
plugs for headset (optional)

ATEI
51
Consoles & Accessories

PSS AS / PSS G2 / PSS G2E / PPM-IT5


FULL COLOR TOUCH-SCREEN SECURE PAGING CONSOLE

CONTROLS AND INDICATORS TECHNICAL SPECIFICATIONS

5" full color touch-screen, 800x480 pixels


ž Electrical Mechanical
Three LED status indicators
ž Mains power supply Dimensions(H x W x D) 80 x 250 x 140 mm
Three hardware function keys-buttons
ž Voltage 18~30 VDC PoE: 24 VDC) (3-1/5" x 9-4/5" x 5-1/2")
280 mm gooseneck microphone
ž Power consumption 250 mA Weight 1.1 kg (2.4 lbs)
Color RAL7016
INTERCONNECTIONS
Performance
Rear Frequency response Environmental
RJ45
ž for CAT-5 connection PSS AS/G2/G2E -3 dB @ 200 Hz to 8 kHz Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
3.5mm
ž mini-jack for headset PPM-IT5 -3 dB @ 100 Hz to 18 kHz Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
Additional
ž power supply connector for long-line THD < 1% @ 1 kHz Relative humidity 15% to 90%
support Output level Max 6 dBu Air pressure 600 to 1100 h Pa
Noise gate threshold -84 dBu ~ – 24 dBu Heat Dissipation 20 BTU/hr
CERTIFICATIONS AND APPROVALS
Attack time 8 ms
Release time 100 ms
REGIONAL CERTIFICATIONS
Output impedance 100 Ohm
Europe Voice Alarm EN54-16 certified 2012
CE – 0359 Monitoring speaker
according to EN50130 – 4 Impedance 4 Ohm
Output power 1 W @ 1 Khz
PARTS INCLUDED
Frequency response -3 dB @ 200 to 12 kHz
Quantities Components
PSS AS/G2/G2E Headset
1 PSS-XX Connector
1 CAT-5 cable, 1.5 m PSS AS/G2/G2E 3.5 mm mini-jack
PPM-IT5 PPM-IT5 2 x 3.5 mini-jack
1 PPM-IT5XX
1 CAT-5 cable, 1.5 m System Connection
1 AC-DC power adapter Cable type CAT-5 (FTP)
Length 100 m

ATEI
52
Consoles & Accessories
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

PPM AS / PSM
DESKTOP PAGING CONSOLES

PPM is a unidirectional addressable condenser


paging microphone compatible with IDA8 and
DIVA8 systems. PPM uses RS485 protocol over
a single CAT-5 cable connection to transport
both audio and power from the paging console
to the system units. The PPM has 8 zone
buttons with a sleek gooseneck microphone,
providing both durability and aesthetics in a
slim, stable chassis.

MAIN CHARACTERISTICS
Desktop enclosure
Ÿ

Monitored CAT-5 link to controllers and slaves


Ÿ
PPM is a unidirectional addressable condenser paging microphone compatible for IDA8 and DIVA8
Supervision of microphone capsule (not on
Ÿ
systems. In accordance with BS5839, PPM is monitored by using RS485 protocol over a single CAT-
slave units)
5 cable connection to transport both audio and power from the paging console to the system
Automatic gain control on microphone input
Ÿ units. The PPM has 8 zone buttons with a sleek gooseneck microphone, providing both durability
8-zone selection keys (Expandable with
Ÿ and aesthetics in a slim, stable chassis.
additional keypads)
The PPM enables live announcement to any pre-assigned zones (an optional SP version also allows
All-call key
Ÿ
for broadcasting the pre-recorded messages). The paging station has a gooseneck microphone, a
Power indicator
Ÿ push-to-talk button, zone selection keys and a monitor speaker. Buttons represent a single zone or
EVAC indicator
Ÿ a group of zones and be easily defined in the software using a simple matrix selection. All buttons
Status and fault indicator
Ÿ
can be programmed with drag & drop features from the software and each button can be
programmed for PTT (Push To Talk) or latching functionality.
Monitor speaker
Ÿ
In addition to the zone LEDs, “Hold” and “Busy” LED signals make PPM an extremely user-friendly
paging console. Thanks to the cardioids polar pick-up pattern, the unidirectional condenser
microphone ensures the high-quality and directive signal pick-up with minimal interference from
the surroundings.

The RS485 communication protocol allows daisy-chain wiring up to 300m on a single CAT-5 cable
(FTP/STP) and makes each station easy to connect by using standard RJ45 connectors and the
junction connection box (supplied with PPM). Also, the console can be powered locally with 24V
DC supply.

Note: There are three versions of the PPM paging console with identical hardware and
functionality but different firmware for compatibility with different systems.

PPM-AS: Used with IDA8 system controllers and slaves, ATEÏS Audio Processor, LAPG2T and UAPG2
PPM AS with keypads
PSM: Used with DIVA8 system controllers

PPM-SP, PPM G2: Used with ATEÏS Audio Processor, LAPG2T and UAPG2

ATEI
53
Consoles & Accessories

PPM AS / PSM
DESKTOP PAGING CONSOLES

CONTROLS AND INDICATORS TECHNICAL SPECIFICATIONS

Three LED status indicators


ž Electrical Mechanical
Activity indicators
ž Battery power supply Dimensions(H x W x D) 50 x 105 x 190 mm
Zone selection buttons
ž Voltage 18 - 26 VDC (2" x 4-1/5" x 7-1/2")
Gooseneck microphone
ž Power consumption 120 mA (With gooseneck) 350 x 105 x 190 mm
Monitor speaker
ž (13-3/4" x 4-1/5" x 7-1/2")
Performance Weight 0.7 kg (1.54 lbs)
INTERCONNECTIONS
Frequency response -3 dB @ 200 to 8kHz Color RAL7035
Rear THD < 0.1% @ 1 kHz
RJ45
ž for CAT-5 connection Output level Max 6 dBu Environmental
Noise gate threshold -84 dBu ~ -24 dBu Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
PARTS INCLUDED
Attack time 8 ms Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
Quantities Components Release time 100 ms Relative humidity 15% to 90%
1 PPM/PSM-XX Output impedance 100 Ohms Air pressure 600 to 1100 h Pa
1 Junction box IP rating 30
1 CAT-5 cable, 10pin, 1.5 m Monitoring speaker Heat Dissipation 10 BTU/hr
Impedance 4 Ohm
Output power 1 W @ 1 Khz
Frequency response 3 dB @ 200 to 12 kHz

System Connection
Cable type CAT-5, 10 pin (FTP)
Length 100 m

ATEI
54
Consoles & Accessories
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

PSC
DESKTOP PAGING CONSOLES

The PSC microphone console, an Unidirectional Condenser Addressable Microphone


which is compatible with all system units. By using RS485 protocol with daisy-chain
wiring can support up to 100M over a single CAT5 cable connection, PSC transmits
both audio data and power supply to system units. PSC comprises of 8 zones / 8
buttons with sleek condenser gooseneck microphone, and spring metal protection,
providing durability and excellent aesthetics as well as enhancing up to 256 zones
expansion via the additional keypad. The control buttons represent a single zone or a
group of zones and are easily defined via the GUI of the system units using a simple
Matrix selection.

Besides the original speaker, PSC also supports an external speaker to monitor the
audio source. The unit offers “Hold” and “Busy” LED signals in addition to the zone
LED’s, and these features allow an easy identification of Selection / Busy signals for
users.

All buttons can be programmed with drag & drop features from the System unit GUI
software and each button can be programmed for Push To Talk function or Latch
functionality. The unidirectional condenser microphone warrants picking up the high
quality of directive signal and less interference from the surroundings.

SPECFICATIONS

CONTROLS AND INDICATORS TECHNICAL SPECIFICATIONS

Goose-neck Microphone
ž Electrical Monitoring speaker
Fault / EVAC / Power / Talk / Hold / All Call /
ž Mains power supply Impedance 8 Ohm
Release / Busy Indicator Voltage 18~30 VDC PoE: 44~57 VDC) Output power 1 W @ 1 Khz
All Call/Release/Talk Button
ž Power consumption 150 mA Frequency response -3 dB @ 200 to 20 kHz
Microphone Connector
ž

Event Select Key


ž Performance Mechanical
Frequency response -3 dB @ 200 Hz to 20 kHz Dimensions(H x W x D) 116 x 220 x 483 mm
INTERCONNECTIONS
THD < 1% @ 1 kHz (4-3/5" x 8-3/5" x 19")

Rear Output level Max 6 dBu Weight 0.37 kg (0.8 lbs)

RS485 for CAT-5 connection


ž Noise gate threshold -84 dBu ~ – 24 dBu Color RAL7035
Release time 100 ms
PARTS INCLUDED
Output impedance 100 Ohm Environmental
Quantities Components Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
1 PSC-XX System connection Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
1 Junction Box Cable type / Length CAT-5,10 pin (FTP) / 100 m (max.) Relative humidity 15% to 90%
1 CAT-5 cable, 10pin, 1.5 m Air pressure 600 to 1100 h Pa
IP Rating 30
Heat Dissipation 12 BTU/hr

ATEI
55
Public Address - Voice Alarm
ATEI Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

CD-Touch
WALL-MOUNTED MONITORED TOUCH-SCREEN PAGING CONSOLE

The CD-TOUCH paging console is a paging interface that allows call-paging, message
broadcasting and DSP matrix parameter control. It contains a 5” full-color backlit touch-screen
for simple, user-friendly operation. The screen offers up to 168 buttons across 14 pages which
can be freely assigned in the software to any zone or group of zones. Each key contains a
color-changing field indicating if the zone is occupied by a different process. In addition, the CD-
TOUCH has 3 hardware keys that can be assigned within the system control software.

All paging parameters for site operation can be pre-programmed and stored within the console,
including message triggering, level adjustment and pre-call chime setup. Zone assignment, naming
MAIN CHARACTERISTICS and grouping can also be pre-configured.

Wall-mounted metal enclosure with lockable


Ÿ The CD-Touch-XX units connect to a monitored bus on CAT-5 FTP/STP. This connection also provides
cover Power Over Ethernet (POE). In case POE is not available, or if the cable run is greater than 100m, an
Secured CAT-5 link to controllers and slaves
Ÿ additional power connection is provided with 24 VDC supply.
Monitoring of microphone capsule
Ÿ The ATEÏS range of security systems complies with current architectural demands requiring IP and/or
Monitoring loudspeaker
Ÿ fiber-optic networking to allow for even the most complex of system designs. ATEÏS responds to
5” full colour touch-screen, 800x480 pixels
Ÿ Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and BS5839/8, with
specific attributes for compliance in large installations.
14 pages of 12 buttons
Ÿ

Power, Fault and Evac indicators


Ÿ CD-TOUCH is available in two different versions with identical hardware and functionality but different
Comprehensive system status information from
Ÿ firmware for compatibility with different systems.
touch-screen
CD-TOUCH-AS: For use with IDA8 and ECS system controllers and slaves
EN54-16 certified
Ÿ
CD-TOUCH-G2: For use with DIVA8 system controllers

SPECFICATIONS

CONTROLS AND INDICATORS TECHNICAL SPECIFICATIONS

5" full color touch-screen, 800x480 pixels


ž Electrical System connection
Three LED status indicators
ž Mains power supply Cable type / Length CAT-5 (FTP) / 100 m (max.)
Three hardware function keys-buttons
ž Voltage 18~26 VDC
Fireman's fist microphone with PTT switch
ž Power consumption 250 mA Mechanical
Dimensions(H x W x D) 397 x 206 x 127 mm
INTERCONNECTIONS
Performance (15-3/5" x 8-1/10" x 5")
Rear Frequency response -3 dB @ 200 Hz to 8 kHz Weight 4.4 kg (9.7 lbs)
RJ45
ž for CAT-5 connection THD < 1% @ 1 kHz Color RAL7016
Additional
ž power supply connector Output level Max 6 dBu
(for 24 V DC external supply in PoE not available) Noise gate threshold -84 dBu ~ – 24 dBu Environmental
Attack time 8 ms Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
PARTS INCLUDED
Release time 100 ms Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
Quantities Components Output impedance 100 Ohm Relative humidity 15% to 90%
1 CD-Touch-XX Air pressure 600 to 1100 h Pa
1 CAT-5 cable, 1m Monitoring speaker Heat Dissipation 20 BTU/hr
Impedance 4 Ohm
Output power 1 W @ 1 Khz
Frequency response -3 dB @ 200 to 20 kHz

ATEI
56
Consoles & Accessories
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

CD8 / CD16
WALL-MOUNTED MONITORED PAGING CONSOLE

CD8 CD16

MAIN CHARACTERISTICS The CD8 / CD16 paging console is a remote paging interface with Access Level 2 protection in
Wall-mounted enclosure
Ÿ
compliance with EN54-16. Compatible with DIVA8 and IDA8 PAVA systems, the unit serves up
to eight zones individually with an All-Call option. Zone selection buttons and Fireman
Secured CAT-5 link to controllers and slaves
Ÿ
microphone are encased in a heavy-duty IP30 wall-mounted metal box with a lockable door.
Monitoring of microphone capsule
Ÿ
The CD8 / CD16 console use the same architecture as the PPM paging console, a junction box
8/16 zone selection buttons
Ÿ
embedded into the enclosure multiple units by daisy-chaining wiring(only the first console in the
All-call button
Ÿ chain is under monitored). The maximum distance between units is up to 100M. The zone buttons
LED test button
Ÿ of CD8 / CD16 represent a single zone or group of zones and can be easily programmed through
Power indicator
Ÿ the system GUI using “drag and drop” functionality. The Push- To-Talk button can be programmed
for PTT or latching operation. The status indicators including Power, EVAC and Fault which show
EVAC indicator
Ÿ
the status of all the zone are also provided with.
Status and fault indicator
Ÿ

EN54-16 certified
Ÿ
The CD8 / CD16 is powered over RS485 via CAT-5 (FTP/STP), however if power is not available over
RS485 it can be locally powered by using a 24V DC supply.

Note: There are two versions of the CD8 / CD16 paging console with identical hardware and
functionality but different firmware for compatibility with different systems.

CD8-AS / CD16-AS: Used with IDA8 system and ECS system controllers and slaves (one CD8 /
CD16 connects to per PDC port with a maximum up to 10 units by daisy-chain wiring and
external power supply should be used for every third unit ).

CD8-G2 / CD16-G2: Used with DIVA8 system controllers [The maximum CD8 / CD16 units of
configuring with daisy-chain wiring is 1 units (only the first unit is under monitored). An external
power supply should be used for every third unit in the chain].

The ATEÏS range of security systems complies with current architectural demands requiring IP
and/or fiber-optic networking to cater for any possible PAVA design, however complex. ATEÏS
responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16
and BS5839/8, with specific attributes for compliance in large installations.

ATEI
57
Consoles & Accessories

CD8 / CD16
WALL-MOUNTED MONITORED PAGING CONSOLE

CONTROLS AND INDICATORS TECHNICAL SPECIFICATIONS

Three LED status indicators


ž Electrical Mechanical
Activity indicators
ž Power supply Dimensions(H x W x D)
Zone selection buttons
ž Interface RS-485 (RJ45/CAT-5) CD8 190 x 320 x 130 mm
LED test button
ž (7-1/2" x 12-3/5" x 5-1/10")
Fireman microphone with Push To Talk
ž DC/battery power requirements CD16 130 x 350 x 130 mm
Voltage 18 - 26 VDC (5-1/10" x 13-3/4" x 5-1/10")
INTERCONNECTIONS
Power consumption Weight
Rear CD8 120 mA CD8 3.6 kg (7.9 lbs)
RJ45
ž for CAT-5 connection CD16 150 mA CD16 4.7 kg (10.4 lbs)
Color RAL7016
CERTIFICATIONS AND APPROVALS
Performance
Frequency response -3 dB @ 100 Hz to 18 kHz Environmental
REGIONAL CERTIFICATIONS
THD < 1% @ 1 kHz Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
Europe Voice Alarm EN54-16 certified 2012 Output level Max 6 dBu Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
CE – 0359 Noise gate threshold -84 dBu ~ – 24 dBu Relative humidity 15% to 90%
according to EN50130 – 4 Attack time 8 ms Air pressure 600 to 1100 h Pa
Release time 100 ms IP rating 30
PARTS INCLUDED
Output impedance 100 Ohm Heat Dissipation
Quantities Components CD8 10 BTU/hr
1 CD8 / CD16 Monitoring speaker CD16 12 BTU/hr
1 CAT-5 cable, 10pin, 1.5 m Impedance 4 Ohm
Output power 1 W @ 1 Khz
Frequency response -3 dB @ 200 to 12 kHz

System Connection
Cable type CAT-5, 10pin (FTP)
Length 100 m

ATEI
58
Consoles & Accessories
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

CDPM
WALL-MOUNTED MONITORED PAGING CONSOLE

The CDPM paging console is a wall-mounted cabinet remote with Access level 2 protection in
compliance with EN 54-16. Compatible with ATEÏS audio processor, CDPM paging console
interconnects over a dedicated RS485 for power, audio and data transmit. The RS485 commu-
nication protocol with daisy-chain wiring can support up to 100 m over CAT5 cable connection.

The CDPM supports 2 channels of music input. By pressing the button for selection, the two LED
indicators shall light up and activate the music channel. The unit comprises of 24 zones / 24
buttons with Fireman microphone in a metal surface mount wall-box. It provides robust IP-30
protection. Each CDPM contains a PMM PS Master PCB with extension keypad and uses the same
architecture as for the PPM AS series of microphone consoles. Each ATEÏS audio processor is
capable to support up to 31 CDPM units per RS485 port in Master/Slave configuration.

The control buttons represent a single zone or a group of zones. All buttons can be programmed
with drag & drop features from the ATEÏS Studio software, The PTT button can be programmed for
Push To Talk function or for latching functionality.

The unit offers “Hold” and “Busy” LED signals in addition to the zone LED’s, and these features
allow an easy identification of Selection/Busy signals for users. In addition, to meet the compliance
with EN 54-16, POWER, FAULT and EVAC indicators are provided with.

Additional RCA connectors with selection buttons support local audio injection for commercial
usage. The RS485 communication protocol offers daisy chaining of up to 300 m on a simple CAT5
cable, and yet makes outlets easy to connect via a standard RJ45 connector.

SPECFICATIONS

CONTROLS AND INDICATORS TECHNICAL SPECIFICATIONS

žFireman Microphone Electrical Monitoring speaker


žPower / Music Active / Talk / All Call / Release / Mains power supply Impedance 8 Ohm
Fault / Busy / Hold / EVAC / Indicator Voltage 18~26 VDC Output power 1 W @ 1 Khz
žTalk / Music Selection / All Call / Release Button Power consumption 200 mA Frequency response -3 dB @ 200 to 20 kHz
žMonitoring Speaker
žFireman Microphone / Music Input / Connector Performance Mechanical
žEvent Select Key Frequency response -3 dB @ 200 Hz to 20 kHz Dimensions(H x W x D) 220 x 483 x 68 mm
THD < 0.1% @ 1 kHz (8-1/3" x 19" x 2-1/3")
INTERCONNECTIONS
Output level Max -6 dBu Weight 3.9 kg (8.6 lbs)
Rear Noise gate threshold -84 dBu ~ – 24 dBu Color RAL7016
RS485 for CAT-5 connection
ž Attack time 8 ms
Release time 100ms Environmental
PARTS INCLUDED
Output impedance 100 Ohm Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
Quantities Components Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
1 CDPM-XX System connection Relative humidity 15% to 90%
1 Junction Box Cable type / Length CAT-5, 10pin (FTP) / 100 m (max.) Air pressure 600 to 1100 h Pa
1 CAT-5 cable, 10pin, 1m IP Rating 30
Heat Dissipation 16 BTU/hr

ATEI
59
Public Address - Voice Alarm
ATEI Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

PCP
WALL-MOUNTED MONITORED PAGING CONSOLE

The PCP paging console is a wall-mounted heavy duty remote with Access Level 2 protection in
compliance with EN 54-16. Compatible with ATEÏS audio processor, PCP paging console
interconnects over a dedicated RS485 for power, audio and data transmit. The RS485
communication protocol with daisy-chain wiring can support up to 100 m over CAT5 cable
connection.

The unit comprises of 16 zones / 16 buttons with Fireman microphone in a metal surface mount
wall-box. It provides robust IP-30 protection. Each PCP contains a PMM PS Master PCB with
extension keypad and uses the same architecture as for the PPM AS series of microphone consoles.
Each ATEÏS audio processor is capable to support up to 31 PCP units per RS485 port in
Master/Slave configuration.

The control buttons represent a single zone or a group of zones. All buttons can be programmed
with drag & drop features from the ATEÏS Studio software, The PTT button can be programmed for
Push To Talk function or for latching functionality.

The unit offers “Hold” and “Busy” LED signals in addition to the zone LED’s, and these features
allow an easy identification of Selection/Busy signals for users. In addition, to meet the compliance
with EN 54-16, POWER, FAULT and EVAC indicators are provided with.

SPECFICATIONS

CONTROLS AND INDICATORS TECHNICAL SPECIFICATIONS

A telephone styled microphone


ž Electrical Monitoring speaker
Fault / EVAC / Power / Talk / Hold / All Call /
ž Mains power supply Impedance 8 Ohm
Release / Busy Indicator Voltage 18~26 VDC Output power 1 W @ 1 Khz
All Call/Release/Talk Button
ž Power consumption 150 mA Frequency response -3 dB @ 200 to 20 kHz
Microphone Connector
ž

Event Select Key


ž Performance Mechanical
Frequency response -3 dB @ 200 Hz to 20 kHz Dimensions(H x W x D) 220 x 346 x 128 mm
INTERCONNECTIONS
THD < 0.1% @ 1 kHz (8-3/5" x 13-3/5" x 5")

Rear Output level Max -6 dBu Weight 3 kg (6.6 lbs)

RS485 for CAT-5 connection


ž Noise gate threshold -84 dBu ~ – 24 dBu Color RAL7016(Main)
Attack time 8 ms
PARTS INCLUDED
Release time 100 ms Environmental
Quantities Components Output impedance 100 Ohm Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
1 PCP-XX Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
1 Junction Box System connection Relative humidity 15% to 90%
1 CAT-5 cable, 10pin, 1m Cable type / Length CAT-5, 10pin (FTP) / 100 m (max.) Air pressure 600 to 1100 h Pa
IP Rating 30
Heat Dissipation 12 BTU/hr

ATEI
60
Consoles & Accessories
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

URC / URC 200 / DNM


PAVA SYSTEM PERIPHERALS

URC DNM
Programmable Remote Controller Digital Noise Sensing Microphone
With built-in Electronic Condenser microphone
(omnidirectional), DNM enhances the ability to
detect the surrounding background noise. With
the 0 dB modulation through the Audio Processor,
DNM component provides the Automatic Gain
Control feature and automatically adjusts the
output level of loudspeaker under any situation.
The URC AS can be fully programmed via ATEÏS
Studio software to adjust every setting: level INTERCONNECTIONS
control, preset, components' adjustments, etc. An
elegant OLED for displaying information of Rear Connector
parameters or the status. It gives extreme simple
RJ45 for CAT-5 connection (POE)
ž Ethernet port CAT -5 Cable
design and cost-effective consideration of with
only Two buttons [EXIT], [BACK] and a knob on RS485 port for 5.08 mm EURO Block (4Pin)
ž RS485 port 5.08 mm EURO Block (4Pin)
control interface. The RS485 communication
protocol allows daisy-chain wiring up to 32 units, PARTS INCLUDED
System connection
providing with a long distance from the audio
processor. Quantities Components Cable type CAT-5 (FTP)
1 DNM-485 / DNM Ethernet Max Length 100 m
Mechanical
Dimension = 84mm (W) x 33mm (L) x 84mm (H) 1 CAT-5 cable, 100 m
3-3/10" (W) x 1-3/10" (L) x 3-3/10" (H) Mechanical
Weight = 0.08KG (0.17 lbs) TECHNICAL SPECIFICATIONS
Dimensions 100mm(Diameter) x 130mm(H)
Electrical 4"(Diameter) x 5-1/10"(H)
URC200 / Ethernet Universal Programmable Weight 0.13kg (0.28 lbs)
Power supply
Remote Controller
Voltage 18-30 VDC (if no POE available) Color RAL7035
Battery Holder 250 mA
Environmental
Performance Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
Frequency response -1 / +1 dBu 50~16 kHz@ 0 dBu, Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
Sampling rate 48 KHz Only 1 selection Relative humidity 15% to 90%
Equivalent -80 dBu 50~16 kHz @ 600 ohm Air pressure 600 to 1100 h Pa
THD+N 0.2 % 50~16 kHz @ 0 dBu IP Rating 30
Heat Dissipation 20 BTU/hr
Microphone
The URC200 is an programmable remote controller Sensitivity (60 - 120 dBA) ±5dBA
(TCP/IP) for the PAVA system and the IP-media
Frequency response 50Hz to 16kHz @ -3 dB
streamers with Terracom IP Media software. The
URC200 is powered over IP and easy to integrate THD <0.2% @ 1 kHz
with current demands for room controllers like Input -40 dBu @ 1 kHz
light, curtains, sound and video control.
EIN <-80 dB
The full color display is easy to read and has a low-
power consumption to allow for long lines and
multiple devices into one system.

Mechanical
Dimension = 140mm (W) x 108mm (H) x 34mm (L)
5-1/2" (W) x 4-1/4" (H) x 1-3/10" (L)
Weight = 0.35Kg (0.7 lb)

ATEI
61
Public Address - Voice Alarm
ATEI Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

Dialpad
TOUCH DIAL DEVICE FOR IDA8 SYSTEM

DialPad is a touch dial, cost-effective tabletop controller that connects to IDA8 or ECS audio processor.
By both on Local and SIP call, users shall connect to either external telephone set with phone line or
DialPad with Ethernet connector.

To activate each item by touch provides users with a user-friendly instruction. DialPad can be operated
by using the touch panel -dialing, mute, volume controls, 3-way calling, contact lists, etc. The OLED on
the front panel enhances a simple design, and the secured device information for users to monitor,
included the connection status and dialing information. All the items can be fully programmed with
Drag & Drop features from the system unit GUI software to adjust every custom settings and each item
Dialpad
can be operated via ATEÏS Studio Software or DialPad simultaneously.

DialPad provides a quick-access use with a long-distance calls and multi-paging. Connecting to Wireless
Transceiver device, its capabilities provide the freedom to limit the distance with you from room to
room without moving the base unit, with secure, the password protecting to each calls allows you to
confirm the callers to whom have the authority for multi-paging.

Wireless Transceiver is a handy remote which connects to IDA8 or ECS audio processor and provides the
wireless network for DialPad Device. By connecting to either two kinds of ports (RS485, RS232), the
Wireless Transceiver makes it easy to set up and operate with audio central unit and DialPad device. Its
capabilities enhance the freedom to limit the distance with you from room to room without moving the
base unit. With Wireless Transceiver

SPECFICATIONS

CONTROLS AND INDICATORS TECHNICAL SPECIFICATIONS

Dialpad Front Electrical Mechanical


Telephone Keypad / Function Keypad / Panel
ž Power supply Dimensions(H x W x D)
Display / Status LED / Buzzer Voltage Dialpad 66 x 255 x 108 mm
Dialpad Rear Dialpad 18 - 24 VDC (2-3/5" x 10" x 4-1/4")
RS485 connector / Battery Holder
ž Wireless Transceiver 24 VDC Wireless Transceiver 30 x 100 x 67 mm
Wireless Transceiver Front Battery Holder (1-1/5' x 4" x 2-5/8")
Power LED / Status LED
ž Dialpad AAA Battery x 4 Weight
Wireless Transceiver Rear Power consumption Dialpad 0.5 kg (1.1 lbs)
RS485 / RS232 / 24VDC connector
ž Wireless Transceiver 30 mA Wireless Transceiver 0.1 kg (0.22lbs)
Color RAL7016
INTERCONNECTIONS
Performance
Dialpad Rear Panel Display Environmental
RS485 for CAT-5 connection (PoE)
ž Dialpad 128*32 Pixels Monochrome (White) Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
Wireless Transceiver Rear Buzzer Sound Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
RJ45 for CAT-5 connection (POE)
ž Dialpad >85dBA @10cm Relative humidity 15% to 90%
RS232 connector
ž Air pressure 600 to 1100 h Pa
System connection IP Rating 30
PARTS INCLUDED
Cable type / Length
Quantities Components Dialpad CAT-5 (FTP) / 100 m (max.)
1 Wireless TransceiverXX / DialPadXX Wireless Transceiver CAT-5 (FTP) / RS232
1 CAT-5 cable, 500m 500 m / 12 m

ATEI
62
Consoles & Accessories
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

URGP
ALARM INPUT INTERFACE FOR IDA8-SYSTEM AND DIVA-SYSTEM

MAIN CHARACTERISTICS
Desktop enclosure
Ÿ The URGP is a contact interface extension unit to the IDA8 System.
Secured RS232/RS485 link to controllers and
Ÿ
Each URGP32in / URGP 16I16O provide 32 /16 additional alarm inputs. Each input is monitored
slaves
and can be programmed to trigger a digital audio message into a specific zone or group of zones.
32 alarm inputs
Ÿ The URGP is linked to the System units through an RS232 /RS485 monitored serial link.
Status and fault indicator
Ÿ

EN54-16 certified
Ÿ

SPECFICATIONS

CONTROLS AND INDICATORS TECHNICAL SPECIFICATIONS

Front Electrical Mechanical


EVACUATION active indicator
ž Mains power supply Dimensions(H x W x D) 44 x 140 x 75 mm
FAULT indicator
ž Voltage 18~26 VDC (1-3/4" x 5-1/2" x 3")
POWER indicator
ž Power consumption 30 mA Weight 0.5 kg (1.1 lbs)
Color RAL7016
INTERCONNECTIONS
Performance
Rear Evacuation inputs Environmental
RJ45
ž Contact mode 5 VDC Operating temperature -5ºC ~ 55ºC (23ºF ~ 131ºF)
RS232
ž Voltage mode -6 dBu Storage temperature -40ºC ~ 70ºC (-40ºF ~ 158ºF)
Monitoring resistor 4.7k Ohm Relative humidity 15% to 90%
CERTIFICATIONS AND APPROVALS
Air pressure 600 to 1100 h Pa
System connection IP Rating 30
REGIONAL CERTIFICATIONS
Cable type / Length CAT-5 (FTP) / 100 m (max.)
Europe Voice Alarm EN54-16 certified 2012
CE – 0359
according to EN50130 – 4

ATEI
63
Public Address - Voice Alarm
ATEI Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers

List Of Peripherals

Peripherals Connection Maximum number (per port) Device


PSS AS PDC port 1 IDA8
PSS G2 PSS / PSM port 1 DIVA8G2
PSS G2E Ethernet 8 DIVA8G2
PPM-IT5 Ethernet 1 (Active Over Eth.) IDA8
PPM AS PDC port 32 IDA8
PSM PSS / PSM port 10 DIVA8G2
PSC PDC port 32 IDA8
CD8 / CD16 PDC port (IDA8), PSS / PSM port (DIVA8G2) 1 IDA8/DIVA8G2
CD-Touch PDC port (IDA8), PSS / PSM port (DIVA8G2) 1 IDA8/DIVA8G2
PCP / CDPM PDC port 32 IDA8
DialPad / Wireless Transceiver PDC port 1 IDA8
URC-AS PDC port 32 IDA8
URC200AS Ethernet Eth. Limit IDA8
DNM-485 PDC port 32 IDA8
DNM-Ethernet Ethernet Eth. Limit IDA8
URGP32in / URGP 16I16O PDC port 1 IDA8

Eth. Limit: The maximum number of IP that can be assigned over the network.
Max. Number: The max. number of peripherals through per PDC port by using a Junction Box.
The devices which connected to PDC port, PSS port and PSM port are all powered over RS485 communication protocol.

ATEI
64
65
ATEI

ATEÏS Europe B.V.


Sydneystraat 42, Rotterdam,
3047 BP, Netherlands.
SWITZERLAND - F
Phone +31 (0)10 2088690 D S- RA
AN NC
Fax +31 (0)10 2088699
RL

E-
www.ateis-europe.com

E
TH

US
Email: [email protected]

NE

A-
A E - TA I WA N -

CHIN
A - SINGA
ATEÏS Suisse SA
Chemin du Dévent 7, 1024 Ecublens,
Switzerland

Y-U

POR
Phone +41 (0)21 881 25 10

N
Fax +41 (0) 21 881 25 09

MA

-I E
Email: [email protected]

ER

N
G DI
A

ATEÏS France
ZA Font Ratel - 8, rue de l'Europe
38640 Claix, France
Phone +33 (0)4 76 99 26 30
Fax +33 (0)4 76 99 26 31
Email: [email protected]

ATEÏS Germany GmbH. ATEÏS Middle East


Roggensteiner Str. 15, 82140 Olching, Light Industrial Unit 11 Dubai, Silicone Oasis,
Deutschland Dubai United Arab Emirates
Phone +49 (08142) 305070-30 Phone +971 4 3262730
Fax +49 (0)8142 305070-39 Fax +971 4 3262731
Email: [email protected] Email: [email protected]

Penton/ATEÏS USA. ATEÏS FAR EAST CORP.


21 Sabin St. Pawtucket, RI 02860, USA 2F,No.60, Xinghua 2nd Rd, Tanzi,
Phone 888-883-8383 Taichung 427, Taiwan
Fax +888-821-2121 Phone +886-4-25333820
www.penton-usa.com Fax +886-4-25333830
Email: [email protected] Email: [email protected]

ATEÏS China
Room 610, No.255 Wubao Road, Minxing district,
Shanghai, China
Phone +021-54495191/92
Fax +021-54495193
Email: [email protected]

ATEÏS SE Pte Ltd.


Blk5002 Ang Mo Kio Avenue 5,
#03-01B Techplace II, Singapore 569871
Phone +65 64811968
Fax +65 64811960
Email: [email protected]

D ELIVERING Y OUR M ESSAGE

You might also like