Model JL-17 (SIN RA1914) K16.8 (240 Metric) Early Suppression Fast Response Sprinkler

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Bulletin 019 September 2018

Model JL-17 (SIN RA1914)

Bulletin 019 September 2018


K16.8 (240 metric)
Early Suppression
Fast Response Sprinkler
Features:
1. cULus, VdS, and LPCB listed as a nominal
K16.8 (240 metric) ESFR sprinkler.
2. FM Approved as a quick-response, storage
and non-storage, sprinkler.
3. Fusible link operating element.
4. Compact design allows piping to be in-
stalled farther from the ceiling and obstruc-
tions compared with larger sprinklers.
Listings and Approvals
1. Listed by Underwriters Laboratories Inc. and UL certified
for Canada (cULus) - Category Code VNWH.
2. FM Approved as a quick-response, storage and non-
storage, sprinkler.
3. VdS Schadenverhütung GmbH (VdS).
4. Loss Prevention Certification Board (LPCB).
5. CNBOP Technical Approval. Model JL-17 ESFR Sprinkler

Product Description Application and Installation


The Reliable Model JL-17 Early Suppression Fast The Model JL-17 ESFR sprinkler is intended for instal-
Response (ESFR) Sprinkler with a nominal k-factor of lation in accordance with NFPA 13 and FM Loss Pre-
16.8 (240 metric). This sprinkler is designed to respond vention Data Sheets 2-0 and 8-9, as well as the require-
quickly to growing fires and will deliver a heavy water ments of any Authorities Having Jurisdiction. See Table
discharge to “suppress” rather than “control” fires. FM B for information on NFPA and FM Global design criteria
Global classifies the Model JL-17 as a quick-response for the Model JL-17 sprinkler.
sprinkler, storage and non-storage, when the sprinkler is Use only the Model J1 sprinkler wrench for removal
used in accordance with FM Global Property Loss Pre- and installation. Any other type of wrench may damage
vention Data Sheets. the sprinkler. A grooved wrench boss is provided on
The Model JL-17 ESFR sprinkler utilizes a levered fus- the sprinkler to limit the potential for the wrench to slip
ible alloy solder link in either a 165°F (74°C) or a 212°F during installation.
(100°C) rating. Model JL-17 sprinklers are cULus Listed When handling sprin-
for compliance with UL/ULC 1767, including the high klers, hold sprinklers
clearance test for rack storage. only on frame arms and
The Model JL-17 ESFR sprinkler was designed to be do not apply any force on
shorter and more compact than other ESFR sprinklers. the link assembly. Sprin-
The shorter sprinkler allows piping to be installed farther klers should be tight-
Model J1
from the ceiling and obstructions. The JL-17 ESFR sprin- ened between 14 - 40 ft-
Sprinkler Wrench
kler is also less susceptible to damage due to smaller lbs (19 - 54 N-m) torque.
deflector and frame design. The lighter JL-17 ESFR Sprinklers not tightened to recommended torque may
passed rough use and abuse listing tests without plastic cause leakage or impairment of the sprinkler. Damage
protectors. sprinklers must be replaced immediately.

Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Temperature Ratings and Approvals
Temperature Maximum Ambient Sprinkler
Temperature Rating Link Frame Temperature Identification
Approvals
Classification Color Color Number
°F °C °F °C
(SIN)
cULus, FM, VdS, LPCB, CNBOP
Ordinary 165 74 Black Uncolored 100 38
RA1914
cULus, FM, VdS, LPCB, CNBOP
Intermediate 212 100 White White 150 66

Installation Data
Nominal K-
Factor Maximum Finish
Sprinkler Type Thread Size
Working Pressure
US Metric

Pendent ¾” (R¾) 16.8 240 175 psi (12.1 bar) Bronze

Installation Criteria Model JL-17 ESFR Sprinkler Specification


See Table B on page 3 of this document. Sprinklers shall be Early Suppression Fast Response
(ESFR) pendent sprinklers specifically tested and [cULus
Maintenance Listed] [FM Approved] [VdS Approved] [LPCB Approved]
The Model JL-17 ESFR Sprinkler should be inspected
for commodity storage applications. Sprinkler frame and
and the sprinkler system maintained in accordance with
deflector to be of bronze construction. Fusible link assem-
NFPA 25. Do not clean sprinkler with soap and water,
bly shall utilize the strut and lever principle of operation with
ammonia or any other cleaning fluid. Replace any sprin-
approved fast response black-painted or white-painted
kler that has been painted (other than factory applied) or
beryllium-nickel thermal element. Water seal shall consist
damaged in any way. A stock of spare sprinklers should
of a PTFE coated Bellville spring washer and brass cap as-
be maintained to allow quick replacement of damaged or
sembly containing no plastic parts. ESFR sprinklers shall
operated sprinklers. Prior to installation, sprinklers should
have a nominal K-factor of 16.8 (240 metric) with [¾” NPT]
be maintained in the original cartons and packaging until
[ISO 7-R¾] threaded end connections. Sprinkler tempera-
used, to minimize the potential for damage to sprinklers
ture rating shall be [Ordinary 165°F (74°C)] [Intermediate
that would cause improper operation or non-operation.
212°F (100°C)]. ESFR pendent sprinklers shall be Reliable
Once operated, automatic sprinklers cannot be reassem-
Model JL-17 (Bulletin 019).
bled and reused. New sprinklers of the same size, type
and temperature rating must be installed. A cabinet of re- Ordering Information
placement sprinklers should be provided for this purpose. Specify:
1. Sprinkler: Model JL-17
2. Temperature rating: [Ordinary 165°F (74°C)]
[Intermediate 212°F (100°C)]
3. Thread type: [3/4” NPT] [ISO 7-R3/4]

2.
Model JL-17 Technical Data Table A

ITEM DESCRIPTION

Sprinkler Identification Number (SIN) RA1914

K Factor US (Metric) 16.8 (240)

Thread Size 3/4" (R3/4)


Sprinkler Orientation Pendent
Maximum Working Pressure, PSI (bar) 175 PSI (12 bar)

Model JL-17 Commodity Selection and Design Criteria Overview


Table B

Storage Type NFPA FM GLOBAL


Sprinkler Type ESFR Storage
Response Type ESFR QR
System Type Wet Wet
Temperature Rating F (C) 165F, 212 (74, 100) 165F, 212 (74, 100)
Roof Construction See NFPA 13 See FM Global 2-0
Ceiling Slope See NFPA 13 See FM Global 2-0
Maximum Coverage Area See NFPA 13 See FM Global 2-0
Minimum Coverage Area See NFPA 13 See FM Global 2-0
Maximum Spacing See NFPA 13 See FM Global 2-0
Minimum Spacing See NFPA 13 See FM Global 2-0
Minimum Clearance to Commodity See NFPA 13 See FM Global 2-0
Sprinkler Distance to Ceiling See NFPA 13 See FM Global 2-0
Open Frame, Single, Double, Multi-
ple Row, or Portable Rack Storage of See NFPA 13 See FM 2-0 & 8-9
Class I - IV, Cartoned Unexp Plastics

Solid Pile or Palletized Storage of


See NFPA 13 See FM 2-0 & 8-9
Class I - IV, Cartoned Unexp Plastics

Idle Pallet Storage See NFPA 13 See FM 2-0,8-9 & 8-24


Rubber Tire Storage See NFPA 13 See FM 2-0 & 8-3
Rolled Paper Storage See NFPA 13 See FM 8-21
Flammable Liquid Storage See NFPA 30 See FM 7-29
Aerosol Storage See NFPA 30B See FM 7-31
Auto Components in Portable Racks N/A N/A

The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years.

Manufactured by
Reliable Automatic Sprinkler Co., Inc. Recycled
(800) 431-1588 Sales Offices Paper
(800) 848-6051 Sales Fax Revision lines indicate updated or new data.
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 09/18 P/N 9999970379

You might also like