P&F Speed Monitor
P&F Speed Monitor
Technical data
General specifications
Signal type Digital Input
Functional safety related parameters
MTTFd 100 a
Supply
Rated voltage Ur 200 ... 230 V AC ; 100 … 130 V AC; 50/60 Hz
20 VDC ... 30 VDC
Fusing external fusing 4 A
Power consumption AC: < 5 VA
DC: < 5 W
Input
Connection side field side
Input 1
Connection terminals 8-, 9+
Connectable sensor types NAMUR sensors according to DIN EN 60947-5-6
Open loop voltage 8.2 V DC
Short-circuit current 6.5 mA
Switching point 1.2 ... 2.1 mA Switching hysteresis approx. 0.2 mA
Input frequency 0.002 ... 10000 Hz, pulse length/duration: ≥ 20µs
Impedance 1.2 kΩ
Input 2
Switching point high: 16 ... 30 V DC; max.10 mA due to integrated constant cur-
rent sink; Ri ≅ 3 kΩ
Model Number low: 0 ... 6 V DC
Input frequency 0.002 ... 40000 Hz, pulse length/duration: ≥ 12µs
KFU8-DW-1.D Connection terminals 7+, 13- sensor supply
terminals 14, 15 NPN/PNP input (galvanically isolated)
Rotation Speed Monitor Connectable sensor types Two, three, or four-wire proximity switch, incremental rotary
encoder, or externally generated pulses 16 ... 30 V
Features Sensor supply 19 ... 28 V DC non-stabilised; ≤ 30 mA short-circuit protected
Input 3
• Speed monitoring up to 40 kHz
Start-up override Triggering by external signal 16 ... 30 V or Place jumper between
• 1 pre-select value with relay output terminals 2/3 or by switching on supply voltage (terminal 2 and
terminal 3 permanently bridged)
and LED indicator
Jumpering time 0.1 ... 999.9 s (External trigger signal)
• 2-, 3-, 4-wire and NAMUR sensors as Output
well as rotary encoder connectable Connection side control side
Relay 1 changeover contact
• Start-up delay NO, NC, COM
• Menu driven operation via 4 front keys Sensor supply 24 V DC ± 10 %, 30 mA , short-circuit protected
Contact loading 250 V AC/2 A/ cos φ ≥ 0.7
• Period measurement 40 V DC/2 A
• Output signal can be inverted Delay ≤ 20 ms (incl. calculation time)
Mechanical life ≥ 30.000.000 switching cycles
• Display devices can be set between Transfer characteristics
0.1 ... 2.5 sec. Changing interval 5 ms (Internal processing time)
Time delay before availability ≤ 400 ms
Measuring error 0 ... 40000 Hz: ≤ ±0,10%
Display: ±1 digit
Timer function ON-delay, OFF-delay, one shot, pulse extension
Time 0 ... 999.9 s ; mode of operation reversible
Indicators/settings
Display elements display , 4-digit, 7-segment red display, 7 mm digit height and
LED
LED indication yellow LED : switching state
Release date: 2018-08-22 12:29 Date of issue: 2018-08-22 190149_eng.xml
1
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Rotation Speed Monitor KFU8-DW-1.D
2
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Rotation Speed Monitor KFU8-DW-1.D
Dimensions
40 115
Yellow LED,
Relay switch
state indication
1 2 3 4 5 6
Drehzahlwächter
Output Speed monitor
7-segment-display
Mode +
107
93
Control keys Enter –
PEPPERL+FUCHS GERMANY
7 8 9 10 11 12
13 14 15 16 17 18
Electrical connection
NAMUR NAMUR
Sensor Encoder
L+ L+ 9
9 9 NAMUR L+
8 8 8
L– L– NAMUR L-
DC-3-wire DC-3-wire
Bridge fitted:
sensor, PNP sensor, NPN start-up bypass triggered by
L+ 7 L+ 7 switching on the power supply
15 15 Sensor power
14 14
L– 13 supply 24 V DC 3
L– 13 7 Sensor power
supply 24 V DC External trigger signal
DC-2-wire DC-2-wire
sensor, PNP sensor, NPN 15 Trigger input for
L+ 7 L+ 7 Galvanically isolated start-up bypass 2
15 15 input
14
14 14 Sensor power
L– 13
L– 13 supply GND 1
13 Sensor power
Encoder, Encoder,
push-pull push-pull supply GND
L+ 7 L+ 7
15 15
14 14
13
L– 13 L–
Release date: 2018-08-22 12:29 Date of issue: 2018-08-22 190149_eng.xml
External
rectangular signal
16-30 V L+ 6
15 Not connected
14
0V L–
4
L+ COM 12
Power supply 24 V DC
5
L- NC 11
yellow Relay output
16 10
L1 (230 V) NO
Power supply 230 V AC 18
N
Power supply 115 V AC
17
L1 (115 V)
3
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Rotation Speed Monitor KFU8-DW-1.D
Notes
Device description
The KFU8-DW-1.D Speed Monitor is a device for the indication and monitoring of periodic signals, which occur in almost all areas of
automation and process technology, i. e. of frequencies in general and rotational speeds in special cases. The input signals are evaluated in
accordance with the cycle method, i. e. by measurement of the period of oscillation and conversion into frequency or rotational speed by a very
fast µ controller.
The frequently occurring special case of rotational speed measurement has been paid particular attention in the development of the device. Thus
indication and input can be either in Hz or in rpm. It is also possible, in applications involving slow processes, in which the signal sensors
provide many pulses per revolution, to operate automatically with the actual rotational speed of the drive by specifying the number of
pulses per revolution.
The indication of the measured value is provided on a 4-digit, 7-segment LED display on the front of the device, with up to 3 places after the
decimal point.
The monitoring function is achieved on the basis of a limit value, whose upper and lower hysteresis value is freely selectable within the
respective display range.
The output signal is generated by a relay with a changeover contact, when the hysteresis limits are violated. Thanks to a high switching
capability, the relay output can be used for the direct activation of an actuating element or as an input signal for a higher level control
system.
Also, the switching status of the relay is indicated by means of a yellow LED on the front of the device.
A function block is connected in series with the relay, which 10 provides for various timer functions and thus obviates the requirement for the
subsequent addition of a timer relay. In addition to the pull-in and drop-out delay, passing make contact and and pulse extension, the
direction of operation of the relay, i. e. monitoring of speed fluctuation about a nominal value, can also be selected.
The built-in start-up override, initiated when the power supply is switched on, or by an external signal, prevents error signals during the
running up of the monitored system.
The speed monitor can be supplied with 115 V AC, 230 V AC or by a 24 V DC supply and when connected to an alternating voltage it provides
a 24 V DC source to supply the signal sensor.
All current two, three and four-wire proximity switches and incremental encoders can be accepted as the signal sensor.In addition, two
terminals are reserved for the connection of proximity switches in accordance with DIN 19234 (NAMUR).
Terminal assignment
4
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Rotation Speed Monitor KFU8-DW-1.D
tStart-up
Function No.
1
No timer function 0
0
1
ON delay 1
0
tRelay tRelay
1
OFF delay 2
0
tRelay tRelay
1
Defined ON time 3
0
tRelay tRelay
1
Pulse lengthening 4
0
tRelay tRelay
1
No timer function, inverted 5
0
1
ON delay, inverted 6
0
tRelay tRelay
1
OFF delay, inverted 7
0
tRelay tRelay
1
Defined ON time, inverted 8
0
tRelay tRelay
1
Pulse lengthening, inverted 9
0
tRelay tRelay
Release date: 2018-08-22 12:29 Date of issue: 2018-08-22 190149_eng.xml
5
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Rotation Speed Monitor KFU8-DW-1.D
Operating principle
Operating mode
Start-up bypass
0.1 s ≤ XXX.X ≤ 999.9 s
Preset at the factory: XXX.X=1.5 s
Display rate
0.01 s ≤ XX.X ≤ 2.5 s
Preset at the factory: XX.X=0.33 s
6
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]