0% found this document useful (0 votes)
210 views6 pages

P&F Speed Monitor

This document provides technical specifications for a rotation speed monitor model KFU8-DW-1.D. It can monitor speeds up to 40 kHz, has inputs that support 2-, 3-, 4-wire and NAMUR sensors as well as rotary encoders. It features a pre-select value with relay output and LED indicator, start-up delay, menu driven operation, and period measurement capability. The output signal can be inverted and display devices can be set between 0.1 to 2.5 seconds.

Uploaded by

mathan_ae
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
210 views6 pages

P&F Speed Monitor

This document provides technical specifications for a rotation speed monitor model KFU8-DW-1.D. It can monitor speeds up to 40 kHz, has inputs that support 2-, 3-, 4-wire and NAMUR sensors as well as rotary encoders. It features a pre-select value with relay output and LED indicator, start-up delay, menu driven operation, and period measurement capability. The output signal can be inverted and display devices can be set between 0.1 to 2.5 seconds.

Uploaded by

mathan_ae
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Rotation Speed Monitor KFU8-DW-1.

Technical data
General specifications
Signal type Digital Input
Functional safety related parameters
MTTFd 100 a
Supply
Rated voltage Ur 200 ... 230 V AC ; 100 … 130 V AC; 50/60 Hz
20 VDC ... 30 VDC
Fusing external fusing 4 A
Power consumption AC: < 5 VA
DC: < 5 W
Input
Connection side field side
Input 1
Connection terminals 8-, 9+
Connectable sensor types NAMUR sensors according to DIN EN 60947-5-6
Open loop voltage 8.2 V DC
Short-circuit current 6.5 mA
Switching point 1.2 ... 2.1 mA Switching hysteresis approx. 0.2 mA
Input frequency 0.002 ... 10000 Hz, pulse length/duration: ≥ 20µs
Impedance 1.2 kΩ
Input 2
Switching point high: 16 ... 30 V DC; max.10 mA due to integrated constant cur-
rent sink; Ri ≅ 3 kΩ
Model Number low: 0 ... 6 V DC
Input frequency 0.002 ... 40000 Hz, pulse length/duration: ≥ 12µs
KFU8-DW-1.D Connection terminals 7+, 13- sensor supply
terminals 14, 15 NPN/PNP input (galvanically isolated)
Rotation Speed Monitor Connectable sensor types Two, three, or four-wire proximity switch, incremental rotary
encoder, or externally generated pulses 16 ... 30 V
Features Sensor supply 19 ... 28 V DC non-stabilised; ≤ 30 mA short-circuit protected
Input 3
• Speed monitoring up to 40 kHz
Start-up override Triggering by external signal 16 ... 30 V or Place jumper between
• 1 pre-select value with relay output terminals 2/3 or by switching on supply voltage (terminal 2 and
terminal 3 permanently bridged)
and LED indicator
Jumpering time 0.1 ... 999.9 s (External trigger signal)
• 2-, 3-, 4-wire and NAMUR sensors as Output
well as rotary encoder connectable Connection side control side
Relay 1 changeover contact
• Start-up delay NO, NC, COM
• Menu driven operation via 4 front keys Sensor supply 24 V DC ± 10 %, 30 mA , short-circuit protected
Contact loading 250 V AC/2 A/ cos φ ≥ 0.7
• Period measurement 40 V DC/2 A
• Output signal can be inverted Delay ≤ 20 ms (incl. calculation time)
Mechanical life ≥ 30.000.000 switching cycles
• Display devices can be set between Transfer characteristics
0.1 ... 2.5 sec. Changing interval 5 ms (Internal processing time)
Time delay before availability ≤ 400 ms
Measuring error 0 ... 40000 Hz: ≤ ±0,10%
Display: ±1 digit
Timer function ON-delay, OFF-delay, one shot, pulse extension
Time 0 ... 999.9 s ; mode of operation reversible
Indicators/settings
Display elements display , 4-digit, 7-segment red display, 7 mm digit height and
LED
LED indication yellow LED : switching state
Release date: 2018-08-22 12:29 Date of issue: 2018-08-22 190149_eng.xml

Display indication 0.002 ... 9999 Hz or


0,01 ... 9999 min-1
Control elements Control panel
Configuration via operating buttons
Labeling space for labeling at the front
Standard conformity
Electromagnetic compatibility acc. to EN 50081-2 / EN 50082-2
Ambient conditions
Ambient temperature -25 ... 40 °C (-13 ... 104 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Relative humidity max. 80 %, not condensing
Altitude 0 ... 2000 m
Operating conditions The device has only to be used in an indoor area.
Mechanical specifications
Connection assembly Caution: Please be aware that the device may only be connec-
ted to a switchable power supply. The switch or circuit breaker
must be easy to reach and identified as the separator for the
device.
Degree of protection IP20
Connection coded, removable terminals , max. core cross section 0.34 ... 2.5
mm2

1
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Rotation Speed Monitor KFU8-DW-1.D

Construction type modular terminal housing in Makrolon, System KF


For use in the switch cabinet/switch cabinet module
Mounting snap-on to 35 mm standard rail or screw fixing

Release date: 2018-08-22 12:29 Date of issue: 2018-08-22 190149_eng.xml

2
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Rotation Speed Monitor KFU8-DW-1.D

Dimensions

40 115

Yellow LED,
Relay switch
state indication

1 2 3 4 5 6
Drehzahlwächter
Output Speed monitor

7-segment-display

Mode +

107
93
Control keys Enter –

PEPPERL+FUCHS GERMANY
7 8 9 10 11 12
13 14 15 16 17 18

Electrical connection

NAMUR NAMUR
Sensor Encoder
L+ L+ 9
9 9 NAMUR L+
8 8 8
L– L– NAMUR L-
DC-3-wire DC-3-wire
Bridge fitted:
sensor, PNP sensor, NPN start-up bypass triggered by
L+ 7 L+ 7 switching on the power supply
15 15 Sensor power
14 14
L– 13 supply 24 V DC 3
L– 13 7 Sensor power
supply 24 V DC External trigger signal
DC-2-wire DC-2-wire
sensor, PNP sensor, NPN 15 Trigger input for
L+ 7 L+ 7 Galvanically isolated start-up bypass 2
15 15 input
14
14 14 Sensor power
L– 13
L– 13 supply GND 1
13 Sensor power
Encoder, Encoder,
push-pull push-pull supply GND
L+ 7 L+ 7
15 15
14 14
13
L– 13 L–
Release date: 2018-08-22 12:29 Date of issue: 2018-08-22 190149_eng.xml

External
rectangular signal
16-30 V L+ 6
15 Not connected
14
0V L–
4
L+ COM 12
Power supply 24 V DC
5
L- NC 11
yellow Relay output
16 10
L1 (230 V) NO
Power supply 230 V AC 18
N
Power supply 115 V AC
17
L1 (115 V)

3
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Rotation Speed Monitor KFU8-DW-1.D

Notes
Device description

The KFU8-DW-1.D Speed Monitor is a device for the indication and monitoring of periodic signals, which occur in almost all areas of
automation and process technology, i. e. of frequencies in general and rotational speeds in special cases. The input signals are evaluated in
accordance with the cycle method, i. e. by measurement of the period of oscillation and conversion into frequency or rotational speed by a very
fast µ controller.

The frequently occurring special case of rotational speed measurement has been paid particular attention in the development of the device. Thus
indication and input can be either in Hz or in rpm. It is also possible, in applications involving slow processes, in which the signal sensors
provide many pulses per revolution, to operate automatically with the actual rotational speed of the drive by specifying the number of
pulses per revolution.

The indication of the measured value is provided on a 4-digit, 7-segment LED display on the front of the device, with up to 3 places after the
decimal point.

The monitoring function is achieved on the basis of a limit value, whose upper and lower hysteresis value is freely selectable within the
respective display range.
The output signal is generated by a relay with a changeover contact, when the hysteresis limits are violated. Thanks to a high switching
capability, the relay output can be used for the direct activation of an actuating element or as an input signal for a higher level control
system.
Also, the switching status of the relay is indicated by means of a yellow LED on the front of the device.
A function block is connected in series with the relay, which 10 provides for various timer functions and thus obviates the requirement for the
subsequent addition of a timer relay. In addition to the pull-in and drop-out delay, passing make contact and and pulse extension, the
direction of operation of the relay, i. e. monitoring of speed fluctuation about a nominal value, can also be selected.
The built-in start-up override, initiated when the power supply is switched on, or by an external signal, prevents error signals during the
running up of the monitored system.

The speed monitor can be supplied with 115 V AC, 230 V AC or by a 24 V DC supply and when connected to an alternating voltage it provides
a 24 V DC source to supply the signal sensor.

All current two, three and four-wire proximity switches and incremental encoders can be accepted as the signal sensor.In addition, two
terminals are reserved for the connection of proximity switches in accordance with DIN 19234 (NAMUR).

Terminal assignment

T. 1: Signal sensor supply GND


T. 2: Trigger input for start-up override
T. 3: Signal sensor supply +24 V DC
T. 4: Power supply + 24 V DC
T. 5: Power supply GND
T. 6: Not connected.
T. 7: Signal sensor supply +24 V DC
T. 8: NAMUR input L-
T. 9: NAMUR input L+
T. 10: Relay make contact, NO
T. 11: Relay break contact, NC
T. 12: Relay root, COM
T. 13: Signal sensor supply GND
T. 14: Signal sensor NPN input
T. 15: Signal sensor PNP input
T. 16: Power supply L1, 230 V AC
T. 17: Power supply L1, 115 V AC
Release date: 2018-08-22 12:29 Date of issue: 2018-08-22 190149_eng.xml

T. 18: Power supply N

4
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Rotation Speed Monitor KFU8-DW-1.D

Timer functions, reversal of operating direction of the output relay

tStart-up
Function No.
1
No timer function 0
0

1
ON delay 1
0
tRelay tRelay

1
OFF delay 2
0
tRelay tRelay

1
Defined ON time 3
0
tRelay tRelay

1
Pulse lengthening 4
0
tRelay tRelay

1
No timer function, inverted 5
0

1
ON delay, inverted 6
0
tRelay tRelay

1
OFF delay, inverted 7
0
tRelay tRelay

1
Defined ON time, inverted 8
0
tRelay tRelay

1
Pulse lengthening, inverted 9
0
tRelay tRelay
Release date: 2018-08-22 12:29 Date of issue: 2018-08-22 190149_eng.xml

5
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Rotation Speed Monitor KFU8-DW-1.D

Operating principle

Operating mode

X=0: frequency measurement 0.002 Hz ... 40000 Hz


X=1: rotational speed measurement 0.01 rpm ... 9999 rpm
Preset at the factory: X=1

Number of pulses per revolution for rotational speed


measurement (will be ignored for frequency measurement)
1 ≤ XXXX ≤ 1200
Preset at the factory: XXXX=1

Measuring and display range


Frequency measurement: 0 ≤ X ≤ 3
Rotational speed measurement: 0 ≤ X £ 2
Preset at the factory: X=1

X Frequency range Rotational speed


in Hz in rpm
0000 0 ... 9999
000.1 0.0 ... 999.9
00.02 0.0 ... 99.99
0.003 0.0 ... 9.999 —

Lower hysteresis limit of switching point


0 ≤ XXXX ≤ 9998 (depending on the measuring range)
Preset at the factory: XXXX=100

Upper hysteresis limit of switching point


0.001 ≤ XXXX ≤ 9999 (depending on the measuring range)
Preset at the factory: XXXX=200

Period for the timer function of switching relay


0.1 s ≤ XXX.X ≤ 999.9 s
Preset at the factory: XXX.X=1.0 s

Timer function of switching relay


Preset at the factory: X=0
X Function
0 No timer function
1 ON delay
2 OFF delay
3 Defined ON time
4 Pulse lengthening
5 No timer function, inverted
6 ON delay, inverted
7 OFF delay, inverted
8 Defined ON time, inverted
Release date: 2018-08-22 12:29 Date of issue: 2018-08-22 190149_eng.xml

9 Pulse lengthening, inverted

Start-up bypass
0.1 s ≤ XXX.X ≤ 999.9 s
Preset at the factory: XXX.X=1.5 s

Display rate
0.01 s ≤ XX.X ≤ 2.5 s
Preset at the factory: XX.X=0.33 s

The number of the software version


can be read only.

6
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]

You might also like