Experiment 5: Single Loop Pid Level Controller: Process Control & Instrumentation Laboratory BKF3791
Experiment 5: Single Loop Pid Level Controller: Process Control & Instrumentation Laboratory BKF3791
OBJECTIVE
To study water tank level control using single loop PID level controller.
EXPERIMENT PROCEDURE
1. Switch ON the operator workstation. (Press the Acknowledge button to silence the alarm
buzzer sound if any).
2. Select Self Regulating Level Process.
3. Set LIC31 controller to PID control.
4. Call up the controller faceplate of LIC31and set control loop to Manual Mode. Enter the set
point of 400 mm.Gradually adjust the output, (MV) so that the level in the tank T-31 matches
the set point (within ±2mm). Let the process stabilize.
5. Open LIC31 Detail faceplate and enter the first trial PID tuning parameters as follows:
Gain (100/P) : 30
Reset (I) : 30 seconds
Rate (D) : 0 second
6. Put the control loop into Manual Mode.
Process Control & Instrumentation Laboratory BKF3791
7. Call up the Process History View for LIC31 from its Detail faceplate. Observe the response
for the level changes in the tank. Wait for the level to reach the set point.
8. Perform Level Load Disturbance as follows:
Switch LIC31 controller to Manual Mode and decrease its MV by 10% for 20 seconds.
Switch LIC31 controller back to Auto Mode.
9. At the LIC31 Process History View, observe the Tank T31 level response similarly.
10. Repeat procedure 4 – 9 with different PID setting as shown in Table 5.1 for Trial 2, 3 and 4.
For Trial 5, enter your own values for Gain, Reset and Rate.
11. Enclose the LIC31 level trend response in each trial and compare the response with the
different PID setting and comment in the observation column.
TABLE 5.1: Single Loop PID Level Control at Independent Operation mode
Reset Rate
PID Set point Gain
(I) (D) Observation
Trial (mm) (100/P)
sec sec
1 400 30 30 0
Remarks:
Set the recommended PID trial tuning
2 400 5 30 0 parameters value and set point. Perform the
Load Disturbance step change as described in
procedure 8.
3 400 5 3 0
Observe the level response from the Process
4 400 5 30 20 History View to see if it damp out to its set
point within 3 cycle to ±2mm of its set point
(SP) OR it continues to oscillate after 3
5 400 cycles.
DISCUSSION