Codigos de Falla PowerFlex 525
Codigos de Falla PowerFlex 525
Fault and Diagnostic F Fault 7 Time-min F627 Fault 1 BusVolts F651 EN Rate Act F685 Drv 1 Logic Cmd F709
Fault 4 Code F604 Fault 8 Time-min F628 Fault 2 BusVolts F652 DSI I/O Act F686 Drv 1 Reference F710
Fault 5 Code F605 Fault 9 Time-min F629 Fault 3 BusVolts F653 HW Addr 1 F687 Drv 1 Logic Sts F711
Fault 6 Code F606 Fault10 Time-min F630 Fault 4 BusVolts F654 HW Addr 2 F688 Drv 1 Feedback F712
Fault 7 Code F607 Fault 1 Freq F631 Fault 5 BusVolts F655 HW Addr 3 F689 Drv 2 Logic Cmd F713
Fault 8 Code F608 Fault 2 Freq F632 Fault 6 BusVolts F656 HW Addr 4 F690 Drv 2 Reference F714
Fault 9 Code F609 Fault 3 Freq F633 Fault 7 BusVolts F657 HW Addr 5 F691 Drv 2 Logic Sts F715
Fault10 Code F610 Fault 4 Freq F634 Fault 8 BusVolts F658 HW Addr 6 F692 Drv 2 Feedback F716
Fault 1 Time-hr F611 Fault 5 Freq F635 Fault 9 BusVolts F659 EN IP Addr Act 1 F693 Drv 3 Logic Cmd F717
Fault 2 Time-hr F612 Fault 6 Freq F636 Fault10 BusVolts F660 EN IP Addr Act 2 F694 Drv 3 Reference F718
Fault 3 Time-hr F613 Fault 7 Freq F637 Status @ Fault 1 F661 EN IP Addr Act 3 F695 Drv 3 Logic Sts F719
Fault 4 Time-hr F614 Fault 8 Freq F638 Status @ Fault 2 F662 EN IP Addr Act 4 F696 Drv 3 Feedback F720
Fault 5 Time-hr F615 Fault 9 Freq F639 Status @ Fault 3 F663 EN Subnet Act 1 F697 Drv 4 Logic Cmd F721
Fault 6 Time-hr F616 Fault10 Freq F640 Status @ Fault 4 F664 EN Subnet Act 2 F698 Drv 4 Reference F722
Fault 7 Time-hr F617 Fault 1 Current F641 Status @ Fault 5 F665 EN Subnet Act 3 F699 Drv 4 Logic Sts F723
Fault 8 Time-hr F618 Fault 2 Current F642 Status @ Fault 6 F666 EN Subnet Act 4 F700 Drv 4 Feedback F724
Fault 9 Time-hr F619 Fault 3 Current F643 Status @ Fault 7 F667 EN Gateway Act 1 F701 EN Rx Overruns F725
Fault10 Time-hr F620 Fault 4 Current F644 Status @ Fault 8 F668 EN Gateway Act 2 F702 EN Rx Packets F726
Fault 1 Time-min F621 Fault 5 Current F645 Status @ Fault 9 F669 EN Gateway Act 3 F703 EN Rx Errors F727
Fault 2 Time-min F622 Fault 6 Current F646 Status @ Fault10 F670 EN Gateway Act 4 F704 EN Tx Packets F728
Fault 3 Time-min F623 Fault 7 Current F647 Comm Sts - DSI F681 Drv 0 Logic Cmd F705 EN Tx Errors F729
Fault 4 Time-min F624 Fault 8 Current F648 Comm Sts - Opt F682 Drv 0 Reference F706 EN Missed IO Pkt F730
Fault 5 Time-min F625 Fault 9 Current F649 Com Sts-Emb Enet F683 Drv 0 Logic Sts F707 DSI Errors F731
Fault 6 Time-min F626 Fault10 Current F650 EN Addr Src F684 Drv 0 Feedback F708
(1) Parameter is available in FRN 5.xxx and later.
Fault Descriptions
No. Fault Type(1) Description Action
F000 No Fault – No fault present. –
• Check remote wiring.
F002 Auxiliary Input 1 External trip (Auxiliary) input. • Verify communications programming for intentional fault.
• Monitor the incoming AC line for low voltage or line power
interruption.
F003 Power Loss 2 Single phase operation detected with excessive load. • Check input fuses.
• Reduce load.
Monitor the incoming AC line for low voltage or line power
F004 UnderVoltage 1 DC bus voltage fell below the minimum value. interruption.
Monitor the AC line for high line voltage or transient conditions. Bus
F005 OverVoltage 1 DC bus voltage exceeded maximum value. overvoltage can also be caused by motor regeneration. Extend the
decel time or install dynamic brake option.
• Increase P041, A442, A444, A446 [Accel Time x] or reduce load so
drive output current does not exceed the current set by
F006 Motor Stalled 1 Drive is unable to accelerate or decelerate motor. parameter A484, A485 [Current Limit x] for too long.
• Check for overhauling load.
• An excessive motor load exists. Reduce load so drive output
current does not exceed the current set by parameter
F007 Motor Overload 1 Internal electronic overload trip. P033 [Motor OL Current].
• Verify A530 [Boost Select] setting.
Additional faults are listed on the next page.
• Check for blocked or dirty heat sink fins. Verify that ambient
F008 Heatsink OvrTmp 1 Heatsink/Power Module temperature exceeds a predefined value. temperature has not exceeded the rated ambient temperature.
• Check fan.
• Check product ambient temperature.
• Check for airflow obstruction.
F009 CC OvrTmp 1 Control module temperature exceeds a predefined value. • Check for dirt or debris.
• Check fan.
Check programming. Check for excess load, improper A530 [Boost
F012 HW OverCurrent 2 The drive output current has exceeded the hardware current limit. Select] setting, DC brake volts set too high or other causes of excess
current.
A current path to earth ground has been detected at one or more of Check the motor and external wiring to the drive output terminals
F013 Ground Fault 1(2) the drive output terminals. for a grounded condition.
The output torque current is below the value programmed in A490 • Verify connections between motor and load.
F015 Load Loss 2 [Load Loss Level] for a time period greater than the time • Verify level and time requirements
programmed in A491 [Load Loss Time].
Output Phase Loss (if enabled). • Verify motor wiring.
F021 Output Ph Loss 1 • Verify motor.
Configure with A557 [Output Phas Loss En].
An analog input is configured to fault on signal loss. A signal loss has • Check for broken/loose connections at inputs.
F029 Analog In Loss 1 occurred. • Check parameters.
Configure with t094 [Anlg In V Loss] or t097 [Anlg In mA Loss].
Drive unsuccessfully attempted to reset a fault and resume running
F033 Auto Rstrt Tries 2 Correct the cause of the fault and manually clear.
for the programmed number of A541 [Auto Rstrt Tries].
F038 Phase U to Gnd • Check the wiring between the drive and motor.
A phase to ground fault has been detected between the drive and • Check motor for grounded phase.
F039 Phase V to Gnd 2 motor in this phase. • Replace drive if fault cannot be cleared.
F040 Phase W to Gnd
F041 Phase UV Short Check the motor and drive output terminal wiring for a shorted
Excessive current has been detected between these two output condition.
F042 Phase UW Short 2 terminals.
F043 Phase VW Short Replace drive if fault cannot be cleared.
• Clear the fault or cycle power to the drive.
F048 Params Defaulted 1 The drive was commanded to write default values to EEPROM. • Program the drive parameters as needed.
Both of the safety inputs (Safety 1, Safety 2) are not enabled. Check safety input signals. If not using safety, verify and tighten
F059 Safety Open 1
Configure with t105 [Safety Open En]. jumper for I/O terminals S1, S2 and S+.
Programmed A486, A488 [Shear Pinx Level] has been exceeded for a • Verify connections between motor and load.
F063 SW OverCurrent 1 time period greater than the time programmed in A487, A489 [Shear • Verify level and time requirements.
Pin x Time].
F064 Drive Overload 2 Drive overload rating has been exceeded. Reduce load or extend Accel Time.
• Check maximum ambient temperature has not been exceeded.
F070 Power Unit 2 Failure has been detected in the drive power section. • Cycle power.
• Replace drive if fault cannot be cleared.
• Cycle power.
Control over the Modbus or DSI communications link has been • Check communications cabling.
F071 DSI Net Loss 2 interrupted. • Check Modbus or DSI setting.
• Check Modbus or DSI status.
• Cycle power.
Control over the network option card’s remote network has been • Check communications cabling.
F072 Opt Net Loss 2 interrupted. • Check network adapter setting.
• Check external network status.
• Cycle power.
Control through the embedded EtherNet/IP adapter has been • Check communications cabling.
F073 EN Net Loss 2 interrupted. • Check EtherNet/IP setting.
• Check external network status.
F080 Autotune Failure 2 The autotune function was either cancelled by the user or failed. Restart procedure.
Additional faults are listed on the next page.
• Cycle power.
• Check communications cabling.
• Check Modbus or DSI setting.
Communications between the drive and the Modbus or DSI master • Check Modbus or DSI status.
F081 DSI Comm Loss 2 device have been interrupted. • Modify using C125 [Comm Loss Action].
• Connecting I/O terminals C1 and C2 to ground may improve
noise immunity.
• Replace wiring, Modbus master device, or control module.
• Cycle power.
Communications between the drive and the network option card • Reinstall option card in drive.
F082 Opt Comm Loss 2 have been interrupted. • Modify using C125 [Comm Loss Action].
• Replace wiring, port expander, option card, or control module.
• Cycle power.
• Check EtherNet/IP setting.
Internal communications between the drive and the embedded
F083 EN Comm Loss 2 • Check drive’s Ethernet settings and diagnostic parameters.
EtherNet/IP adapter have been interrupted. • Modify using C125 [Comm Loss Action].
• Replace wiring, Ethernet switch, or control module.
• Check Wiring.
Requires differential encoder. • If P047, P049, P051 [Speed Referencex] = 16 “Positioning” and
F091 Encoder Loss 2 A535 [Motor Fdbk Type] = 5 “Quad Check”, swap the Encoder
One of the 2 encoder channel signals is missing. channel inputs or swap any two motor leads.
• Replace encoder.
“Freeze-Fire” (Function Loss) input is inactive, input to the
F094 Function Loss 2 Close input to the terminal and cycle power.
programmed terminal is open.
F100 Parameter 2 Drive parameter non-volatile storage is corrupted. Set P053 [Reset To Defalts] to 2 “Factory Rset”.
Chksum
F101 External Storage 2 External non-volatile storage has failed. Set P053 [Reset To Defalts] to 2 “Factory Rset”.
Clear fault and verify all parameter settings. Do not remove or
F105 C Connect Err 2 Control module was disconnected while drive was powered. install the control module while power is applied.
The PowerFlex 525 control module does not support power modules • Change to a different power module.
F106 Incompat C-P 2 with 0.25 HP power rating. • Change to a PowerFlex 523 control module.
• Change to a different power module.
The control module could not recognize the power module. Hardware
F107 Replaced C-P 2 • Replace control module if changing power module does not
failure. work.
The control module was mounted to a different drive type power
F109 Mismatch C-P 2 Set P053 [Reset To Defalts] to 3 “Power Reset”.
module.
F110 Keypad • Cycle power.
2 Keypad membrane failure / disconnected.
Membrane • Replace control module if fault cannot be cleared.
• Check safety input signals. If not using safety, verify and tighten
Safety input enable hardware malfunction. One of the safety inputs is
F111 Safety Hardware 2 jumper for I/O terminals S1, S2 and S+.
not enabled. • Replace control module if fault cannot be cleared.
• Cycle power.
F114 uC Failure 2 Microprocessor failure. • Replace control module if fault cannot be cleared.
• Cycle power.
F122 I/O Board Fail 2 Failure has been detected in the drive control and I/O section. • Replace drive or control module if fault cannot be cleared.
The firmware in the drive is corrupt, mismatched, or incompatible Perform a firmware flash update operation to attempt to load a
F125 Flash Update Req 2 with the hardware. valid set of firmware.
A non-recoverable firmware or hardware error was detected. The • Clear fault or cycle power to the drive.
F126 NonRecoverablErr 2 drive was automatically stopped and reset. • Replace drive or control module if fault cannot be cleared.
A critical problem with the firmware was detected and the drive is Perform a firmware flash update operation using DSI
F127 DSIFlashUpdatReq 2 running using backup firmware that only supports DSI communications to attempt to load a valid set of firmware.
communications.
(1) Type 1 = Auto-Reset/Run faults. Type 2 = Non-Resettable faults.
(2) This fault may be cleared by the auto-restart routine and will be attempted only once. It ignores the value set in parameter A541 [Auto Rstrt Tries].
The following publications provide specific PowerFlex 520-Series information on drive installation, features, specifications,
and service:
Title Publication
PowerFlex 520-Series Drive Adjustable Frequency AC Drive User Manual 520-UM001
PowerFlex 520-Series Drive AC Drive Specifications 520-TD001
PowerFlex Dynamic Braking Resistor Calculator PFLEX-AT001
PowerFlex AC Drives in Common Bus Configurations DRIVES-AT002
Allen-Bradley, Rockwell Automation, PowerFlex, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Publication 520-DU001D-EN-E - April 2016
Supersedes Publication 520-DU001C-EN-E - August 2014 Copyright © 2016 Rockwell Automation, Inc. All rights reserved.