On Drive Guide

PowerFlex 525 Adjustable Frequency AC Drive


Parameter Groups
Basic Display b Drive Status b006 Control Source b012 Power Saved b018 Accum kWh Sav b024
Output Freq b001 Fault 1 Code b007 Contrl In Status b013 Elapsed Run Time b019 Accum Cost Sav b025
Commanded Freq b002 Fault 2 Code b008 Dig In Status b014 Average Power b020 Accum CO2 Sav b026
Output Current b003 Fault 3 Code b009 Output RPM b015 Elapsed kWh b021 Drive Temp b027
Output Voltage b004 Process Display b010 Output Speed b016 Elapsed MWh b022 Control Temp b028
DC Bus Voltage b005 Process Fract b011 Output Power b017 Energy Saved b023 Control SW Ver b029
Basic Program P Motor NP FLA P034 Torque Perf Mode P039 Maximum Freq P044 Speed Reference2 P049
Language P030 Motor NP Poles P035 Autotune P040 Stop Mode P045 Start Source 3 P050
Motor NP Volts P031 Motor NP RPM P036 Accel Time 1 P041 Start Source 1 P046 Speed Reference3 P051
Motor NP Hertz P032 Motor NP Power P037 Decel Time 1 P042 Speed Reference1 P047 Average kWh Cost P052
Motor OL Current P033 Voltage Class P038 Minimum Freq P043 Start Source 2 P048 Reset To Defalts P053
Terminal Blocks t Opto Out1 LevelF t071 Relay Out2 Sel t081 Anlg In 0-10V Lo t091 Sleep Level t101
DigIn TermBlk 02 t062 Opto Out2 Sel t072 Relay Out2 Level t082 Anlg In 0-10V Hi t092 Sleep Time t102
DigIn TermBlk 03 t063 Opto Out2 Level t073 Relay Out2 LevelF t083 10V Bipolar Enbl t093 Wake Level t103
2-Wire Mode t064 Opto Out2 LevelF t074 Relay 2 On Time t084 Anlg In V Loss t094 Wake Time t104
DigIn TermBlk 05 t065 Opto Out Logic t075 Relay 2 Off Time t085 Anlg In4-20mA Lo t095 Safety Open En t105
DigIn TermBlk 06 t066 Relay Out1 Sel t076 EM Brk Off Delay t086 Anlg In4-20mA Hi t096 SafetyFlt RstCfg(1) t106
DigIn TermBlk 07 t067 Relay Out1 Level t077 EM Brk On Delay t087 Anlg In mA Loss t097
DigIn TermBlk 08 t068 Relay Out1 LevelF t078 Analog Out Sel t088 Anlg Loss Delay t098
Opto Out1 Sel t069 Relay 1 On Time t079 Analog Out High t089 Analog In Filter t099
Opto Out1 Level t070 Relay 1 Off Time t080 Anlg Out Setpt t090 Sleep-Wake Sel t100
Communications C EN IP Addr Cfg 3 C131 EN Comm Flt Actn C143 EN Data In 4 C156 Opt Data Out 3 C167
Comm Write Mode C121 EN IP Addr Cfg 4 C132 EN Idle Flt Actn C144 EN Data Out 1 C157 Opt Data Out 4 C168
Cmd Stat Select C122 EN Subnet Cfg 1 C133 EN Flt Cfg Logic C145 EN Data Out 2 C158 MultiDrv Sel C169
RS485 Data Rate C123 EN Subnet Cfg 2 C134 EN Flt Cfg Ref C146 EN Data Out 3 C159 Drv 1 Addr C171
RS485 Node Addr C124 EN Subnet Cfg 3 C135 EN Flt Cfg DL 1 C147 EN Data Out 4 C160 Drv 2 Addr C172
Comm Loss Action C125 EN Subnet Cfg 4 C136 EN Flt Cfg DL 2 C148 Opt Data In 1 C161 Drv 3 Addr C173
Comm Loss Time C126 EN Gateway Cfg 1 C137 EN Flt Cfg DL 3 C149 Opt Data In 2 C162 Drv 4 Addr C174
RS485 Format C127 EN Gateway Cfg 2 C138 EN Flt Cfg DL 4 C150 Opt Data In 3 C163 DSI I/O Cfg C175
EN Addr Sel C128 EN Gateway Cfg 3 C139 EN Data In 1 C153 Opt Data In 4 C164
EN IP Addr Cfg 1 C129 EN Gateway Cfg 4 C140 EN Data In 2 C154 Opt Data Out 1 C165
EN IP Addr Cfg 2 C130 EN Rate Cfg C141 EN Data In 3 C155 Opt Data Out 2 C166
Logic L Stp Logic 6 L186 Stp Logic Time 5 L195 Step Units 2 L204 Step Units F 5 L211
Stp Logic 0 L180 Stp Logic 7 L187 Stp Logic Time 6 L196 Step Units F 2 L205 Step Units 6 L212
Stp Logic 1 L181 Stp Logic Time 0 L190 Stp Logic Time 7 L197 Step Units 3 L206 Step Units F 6 L213
Stp Logic 2 L182 Stp Logic Time 1 L191 Step Units 0 L200 Step Units F 3 L207 Step Units 7 L214
Stp Logic 3 L183 Stp Logic Time 2 L192 Step Units F 0 L201 Step Units 4 L208 Step Units F 7 L215
Stp Logic 4 L184 Stp Logic Time 3 L193 Step Units 1 L202 Step Units F 4 L209
Stp Logic 5 L185 Stp Logic Time 4 L194 Step Units F 1 L203 Step Units 5 L210
Advanced Display d Timer StatusF d366 Encoder Speed d378 PID2 Fdbk Displ d385 RdyBit Mode Act d392
Analog In 0-10V d360 Drive Type d367 Encoder Speed F d379 PID2 Setpnt Disp d386 Drive Status 2(1) d393
Analog In 4-20mA d361 Testpoint Data d368 DC Bus Ripple d380 Position Status d387 Dig Out Status(1) d394
Elapsed Time-hr d362 Motor OL Level d369 Output Powr Fctr d381 Units Traveled H d388
Elapsed Time-min d363 Slip Hz Meter d375 Torque Current d382 Units Traveled L d389
Counter Status d364 Speed Feedback d376 PID1 Fdbk Displ d383 Fiber Status d390
Timer Status d365 Speed Feedback F d377 PID1 Setpnt Disp d384 Stp Logic Status d391
2 PowerFlex 525 Adjustable Frequency AC Drive

Additional parameters are listed on the previous page.


Advanced Program A Accel Time 3 A444 PID 2 Invert Err A479 PM HIFI NS Cur(1) A519 Drv Ambient Sel A554
Preset Freq 0 A410 Decel Time 3 A445 Process Disp Lo A481 PM Bus Reg Kd(1) A520 Reset Meters A555
Preset Freq 1 A411 Accel Time 4 A446 Process Disp Hi A482 Freq 1 Kp A521 Text Scroll A556
Preset Freq 2 A412 Decel Time 4 A447 Testpoint Sel A483 Freq 1 Ki A522 Out Phas Loss En A557
Preset Freq 3 A413 Skip Frequency 1 A448 Current Limit 1 A484 Freq 2 Kp A523 Positioning Mode A558
Preset Freq 4 A414 Skip Freq Band 1 A449 Current Limit 2 A485 Freq 2 Ki A524 Counts Per Unit A559
Preset Freq 5 A415 Skip Frequency 2 A450 Shear Pin1 Level A486 Freq 3 Kp A525 Enh Control Word A560
Preset Freq 6 A416 Skip Freq Band 2 A451 Shear Pin 1 Time A487 Freq 3 Ki A526 Home Save A561
Preset Freq 7 A417 Skip Frequency 3 A452 Shear Pin2 Level A488 PM FWKn 1 Kp(1) A527 Find Home Freq A562
Preset Freq 8 A418 Skip Freq Band 3 A453 Shear Pin 2 Time A489 PM FWKn 2 Kp(1) A528 Find Home Dir A563
Preset Freq 9 A419 Skip Frequency 4 A454 Load Loss Level A490 PM Control Cfg(1) A529 Encoder Pos Tol A564
Preset Freq 10 A420 Skip Freq Band 4 A455 Load Loss Time A491 Boost Select A530 Pos Reg Filter A565
Preset Freq 11 A421 PID 1 Trim Hi A456 Stall Fault Time A492 Start Boost A531 Pos Reg Gain A566
Preset Freq 12 A422 PID 1 Trim Lo A457 Motor OL Select A493 Break Voltage A532 Max Traverse A567
Preset Freq 13 A423 PID 1 Trim Sel A458 Motor OL Ret A494 Break Frequency A533 Traverse Inc A568
Preset Freq 14 A424 PID 1 Ref Sel A459 Drive OL Mode A495 Maximum Voltage A534 Traverse Dec A569
Preset Freq 15 A425 PID 1 Fdback Sel A460 IR Voltage Drop A496 Motor Fdbk Type A535 P Jump A570
Keypad Freq A426 PID 1 Prop Gain A461 Flux Current Ref A497 Encoder PPR A536 Sync Time A571
MOP Freq A427 PID 1 Integ Time A462 Motor Rr A498 Pulse In Scale A537 Speed Ratio A572
MOP Reset Sel A428 PID 1 Diff Rate A463 Motor Lm A499 Ki Speed Loop A538 Mtr Options Cfg A573
MOP Preload A429 PID 1 Setpoint A464 Motor Lx A500 Kp Speed Loop A539 RdyBit Mode Cfg A574
MOP Time A430 PID 1 Deadband A465 PM IR Voltage(1) A501 Var PWM Disable A540 Flux Braking En(1) A575
Jog Frequency A431 PID 1 Preload A466 PM IXd Voltage(1) A502 Auto Rstrt Tries A541 Phase Loss Level(1) A576
Jog Accel/Decel A432 PID 1 Invert Err A467 PM IXq Voltage(1) A503 Auto Rstrt Delay A542 Current Loop BW(1) A580
Purge Frequency A433 PID 2 Trim Hi A468 PM BEMF Voltage(1) A504 Start At PowerUp A543 PM Stable 1 Freq(1) A581
DC Brake Time A434 PID 2 Trim Lo A469 Speed Reg Sel A509 Reverse Disable A544 PM Stable 2 Freq(1) A582
DC Brake Level A435 PID 2 Trim Sel A470 Freq 1 A510 Flying Start En A545 PM Stable 1 Kp(1) A583
DC Brk Time@Strt A436 PID 2 Ref Sel A471 Freq 1 BW A511 FlyStrt CurLimit A546 PM Stable 2 Kp(1) A584
DB Resistor Sel A437 PID 2 Fdback Sel A472 Freq 2 A512 Compensation A547 PM Stable Brk Pt(1) A585
DB Threshold A438 PID 2 Prop Gain A473 Freq 2 BW A513 Power Loss Mode A548 PM Stepload Kp(1) A586
S Curve % A439 PID 2 Integ Time A474 Freq 3 A514 Half Bus Enable A549 PM 1 Efficiency(1) A587
PWM Frequency A440 PID 2 Diff Rate A475 Freq 3 BW A515 Bus Reg Enable A550 PM 2 Efficiency(1) A588
Droop Hertz@ FLA A441 PID 2 Setpoint A476 PM Initial Sel(1) A516 Fault Clear A551 PM Algor Sel(1) A589
Accel Time 2 A442 PID 2 Deadband A477 PM DC Inject Cur(1) A517 Program Lock A552
Decel Time 2 A443 PID 2 Preload A478 PM Align Time(1) A518 Program Lock Mod A553
Network N This group contains parameters for the network option card that is installed.
Modified M This group contains parameters that have their values changed from the factory default.
Additional parameters are listed on the next page.

Rockwell Automation Publication 520-DU001D-EN-E - April 2016


PowerFlex 525 Adjustable Frequency AC Drive 3

Fault and Diagnostic F Fault 7 Time-min F627 Fault 1 BusVolts F651 EN Rate Act F685 Drv 1 Logic Cmd F709
Fault 4 Code F604 Fault 8 Time-min F628 Fault 2 BusVolts F652 DSI I/O Act F686 Drv 1 Reference F710
Fault 5 Code F605 Fault 9 Time-min F629 Fault 3 BusVolts F653 HW Addr 1 F687 Drv 1 Logic Sts F711
Fault 6 Code F606 Fault10 Time-min F630 Fault 4 BusVolts F654 HW Addr 2 F688 Drv 1 Feedback F712
Fault 7 Code F607 Fault 1 Freq F631 Fault 5 BusVolts F655 HW Addr 3 F689 Drv 2 Logic Cmd F713
Fault 8 Code F608 Fault 2 Freq F632 Fault 6 BusVolts F656 HW Addr 4 F690 Drv 2 Reference F714
Fault 9 Code F609 Fault 3 Freq F633 Fault 7 BusVolts F657 HW Addr 5 F691 Drv 2 Logic Sts F715
Fault10 Code F610 Fault 4 Freq F634 Fault 8 BusVolts F658 HW Addr 6 F692 Drv 2 Feedback F716
Fault 1 Time-hr F611 Fault 5 Freq F635 Fault 9 BusVolts F659 EN IP Addr Act 1 F693 Drv 3 Logic Cmd F717
Fault 2 Time-hr F612 Fault 6 Freq F636 Fault10 BusVolts F660 EN IP Addr Act 2 F694 Drv 3 Reference F718
Fault 3 Time-hr F613 Fault 7 Freq F637 Status @ Fault 1 F661 EN IP Addr Act 3 F695 Drv 3 Logic Sts F719
Fault 4 Time-hr F614 Fault 8 Freq F638 Status @ Fault 2 F662 EN IP Addr Act 4 F696 Drv 3 Feedback F720
Fault 5 Time-hr F615 Fault 9 Freq F639 Status @ Fault 3 F663 EN Subnet Act 1 F697 Drv 4 Logic Cmd F721
Fault 6 Time-hr F616 Fault10 Freq F640 Status @ Fault 4 F664 EN Subnet Act 2 F698 Drv 4 Reference F722
Fault 7 Time-hr F617 Fault 1 Current F641 Status @ Fault 5 F665 EN Subnet Act 3 F699 Drv 4 Logic Sts F723
Fault 8 Time-hr F618 Fault 2 Current F642 Status @ Fault 6 F666 EN Subnet Act 4 F700 Drv 4 Feedback F724
Fault 9 Time-hr F619 Fault 3 Current F643 Status @ Fault 7 F667 EN Gateway Act 1 F701 EN Rx Overruns F725
Fault10 Time-hr F620 Fault 4 Current F644 Status @ Fault 8 F668 EN Gateway Act 2 F702 EN Rx Packets F726
Fault 1 Time-min F621 Fault 5 Current F645 Status @ Fault 9 F669 EN Gateway Act 3 F703 EN Rx Errors F727
Fault 2 Time-min F622 Fault 6 Current F646 Status @ Fault10 F670 EN Gateway Act 4 F704 EN Tx Packets F728
Fault 3 Time-min F623 Fault 7 Current F647 Comm Sts - DSI F681 Drv 0 Logic Cmd F705 EN Tx Errors F729
Fault 4 Time-min F624 Fault 8 Current F648 Comm Sts - Opt F682 Drv 0 Reference F706 EN Missed IO Pkt F730
Fault 5 Time-min F625 Fault 9 Current F649 Com Sts-Emb Enet F683 Drv 0 Logic Sts F707 DSI Errors F731
Fault 6 Time-min F626 Fault10 Current F650 EN Addr Src F684 Drv 0 Feedback F708
(1) Parameter is available in FRN 5.xxx and later.

AppView Parameter Groups


Conveyor G1 Motor NP FLA P034 Stop Mode P045 Anlg In 0-10V Hi t092 Jog Accel/Decel A432
Language P030 Motor NP Poles P035 Start Source 1 P046 Anlg In4-20mA Lo t095 S Curve % A439
Output Freq b001 Autotune P040 Speed Reference1 P047 Anlg In4-20mA Hi t096 Reverse Disable A544
Commanded Freq b002 Accel Time 1 P041 DigIn TermBlk 02 t062 Anlg In mA Loss t097
Motor NP Volts P031 Decel Time 1 P042 DigIn TermBlk 03 t063 Slip Hz Meter d375
Motor NP Hertz P032 Minimum Freq P043 Relay Out1 Sel t076 Preset Freq 0 A410
Motor OL Current P033 Maximum Freq P044 Anlg In 0-10V Lo t091 Jog Frequency A431
Mixer G2 Motor NP Hertz P032 Decel Time 1 P042 Relay Out1 Sel t076 Preset Freq 0 A410
Language P030 Motor OL Current P033 Minimum Freq P043 Anlg In 0-10V Lo t091 Stall Fault Time A492
Output Freq b001 Motor NP FLA P034 Maximum Freq P044 Anlg In 0-10V Hi t092
Commanded Freq b002 Motor NP Poles P035 Stop Mode P045 Anlg In4-20mA Lo t095
Output Current b003 Autotune P040 Start Source 1 P046 Anlg In4-20mA Hi t096
Motor NP Volts P031 Accel Time 1 P041 Speed Reference1 P047 Anlg In mA Loss t097
Compressor G3 Motor OL Current P033 Minimum Freq P043 Anlg In 0-10V Lo t091 Auto Rstrt Tries A541
Language P030 Motor NP FLA P034 Maximum Freq P044 Anlg In 0-10V Hi t092 Auto Rstrt Delay A542
Output Freq b001 Motor NP Poles P035 Stop Mode P045 Anlg In4-20mA Lo t095 Start At PowerUp A543
Commanded Freq b002 Autotune P040 Start Source 1 P046 Anlg In4-20mA Hi t096 Reverse Disable A544
Motor NP Volts P031 Accel Time 1 P041 Speed Reference1 P047 Anlg In mA Loss t097 Power Loss Mode A548
Motor NP Hertz P032 Decel Time 1 P042 Relay Out1 Sel t076 Preset Freq 0 A410 Half Bus Enable A549
Centrifugal Pump G4 Motor NP Poles P035 Speed Reference1 P047 PID 1 Trim Hi A456 PID 1 Deadband A465
Language P030 Autotune P040 Relay Out1 Sel t076 PID 1 Trim Lo A457 PID 1 Preload A466
Output Freq b001 Accel Time 1 P041 Anlg In 0-10V Lo t091 PID 1 Ref Sel A459 Auto Rstrt Tries A541
Commanded Freq b002 Decel Time 1 P042 Anlg In 0-10V Hi t092 PID 1 Fdback Sel A460 Auto Rstrt Delay A542
Motor NP Volts P031 Minimum Freq P043 Anlg In4-20mA Lo t095 PID 1 Prop Gain A461 Start At PowerUp A543
Motor NP Hertz P032 Maximum Freq P044 Anlg In4-20mA Hi t096 PID 1 Integ Time A462 Reverse Disable A544
Motor OL Current P033 Stop Mode P045 Anlg In mA Loss t097 PID 1 Diff Rate A463
Motor NP FLA P034 Start Source 1 P046 Preset Freq 0 A410 PID 1 Setpoint A464

Rockwell Automation Publication 520-DU001D-EN-E - April 2016


4 PowerFlex 525 Adjustable Frequency AC Drive

Additional groups are listed on the previous page.


Blower/Fan G5 Motor NP Poles P035 Speed Reference1 P047 PID 1 Trim Hi A456 PID 1 Deadband A465
Language P030 Autotune P040 Relay Out1 Sel t076 PID 1 Trim Lo A457 PID 1 Preload A466
Output Freq b001 Accel Time 1 P041 Anlg In 0-10V Lo t091 PID 1 Ref Sel A459 Auto Rstrt Tries A541
Commanded Freq b002 Decel Time 1 P042 Anlg In 0-10V Hi t092 PID 1 Fdback Sel A460 Auto Rstrt Delay A542
Motor NP Volts P031 Minimum Freq P043 Anlg In4-20mA Lo t095 PID 1 Prop Gain A461 Start At PowerUp A543
Motor NP Hertz P032 Maximum Freq P044 Anlg In4-20mA Hi t096 PID 1 Integ Time A462 Reverse Disable A544
Motor OL Current P033 Stop Mode P045 Anlg In mA Loss t097 PID 1 Diff Rate A463 Flying Start En A545
Motor NP FLA P034 Start Source 1 P046 Preset Freq 0 A410 PID 1 Setpoint A464
Extruder G6 Motor OL Current P033 Maximum Freq P044 Anlg In4-20mA Lo t095 Pulse In Scale A537
Language P030 Motor NP FLA P034 Stop Mode P045 Anlg In4-20mA Hi t096 Power Loss Mode A548
Output Freq b001 Motor NP Poles P035 Start Source 1 P046 Anlg In mA Loss t097 Half Bus Enable A549
Commanded Freq b002 Autotune P040 Speed Reference1 P047 Slip Hz Meter d375
Output Current b003 Accel Time 1 P041 Relay Out1 Sel t076 Speed Feedback d376
Motor NP Volts P031 Decel Time 1 P042 Anlg In 0-10V Lo t091 Preset Freq 0 A410
Motor NP Hertz P032 Minimum Freq P043 Anlg In 0-10V Hi t092 Stall Fault Time A492
Textile/Fiber G8 Autotune P040 DigIn TermBlk 03 t063 Preset Freq 0 A410 Traverse Inc A568
Language P030 Accel Time 1 P041 Relay Out1 Sel t076 Jog Frequency A431 Traverse Dec A569
Output Freq b001 Decel Time 1 P042 Anlg In 0-10V Lo t091 Jog Accel/Decel A432 P Jump A570
Commanded Freq b002 Minimum Freq P043 Anlg In 0-10V Hi t092 S Curve % A439 Sync Time A571
Motor NP Volts P031 Maximum Freq P044 Anlg In4-20mA Lo t095 Reverse Disable A544 Speed Ratio A572
Motor NP Hertz P032 Stop Mode P045 Anlg In4-20mA Hi t096 Power Loss Mode A548
Motor OL Current P033 Start Source 1 P046 Anlg In mA Loss t097 Half Bus Enable A549
Motor NP FLA P034 Speed Reference1 P047 Slip Hz Meter d375 Bus Reg Enable A550
Motor NP Poles P035 DigIn TermBlk 02 t062 Fiber Status d390 Max Traverse A567

CustomView Parameter Group


Custom GC This group can store up to 100 of your frequently used parameters for your application.

Fault Descriptions
No. Fault Type(1) Description Action
F000 No Fault – No fault present. –
• Check remote wiring.
F002 Auxiliary Input 1 External trip (Auxiliary) input. • Verify communications programming for intentional fault.
• Monitor the incoming AC line for low voltage or line power
interruption.
F003 Power Loss 2 Single phase operation detected with excessive load. • Check input fuses.
• Reduce load.
Monitor the incoming AC line for low voltage or line power
F004 UnderVoltage 1 DC bus voltage fell below the minimum value. interruption.
Monitor the AC line for high line voltage or transient conditions. Bus
F005 OverVoltage 1 DC bus voltage exceeded maximum value. overvoltage can also be caused by motor regeneration. Extend the
decel time or install dynamic brake option.
• Increase P041, A442, A444, A446 [Accel Time x] or reduce load so
drive output current does not exceed the current set by
F006 Motor Stalled 1 Drive is unable to accelerate or decelerate motor. parameter A484, A485 [Current Limit x] for too long.
• Check for overhauling load.
• An excessive motor load exists. Reduce load so drive output
current does not exceed the current set by parameter
F007 Motor Overload 1 Internal electronic overload trip. P033 [Motor OL Current].
• Verify A530 [Boost Select] setting.
Additional faults are listed on the next page.

Rockwell Automation Publication 520-DU001D-EN-E - April 2016


PowerFlex 525 Adjustable Frequency AC Drive 5

• Check for blocked or dirty heat sink fins. Verify that ambient
F008 Heatsink OvrTmp 1 Heatsink/Power Module temperature exceeds a predefined value. temperature has not exceeded the rated ambient temperature.
• Check fan.
• Check product ambient temperature.
• Check for airflow obstruction.
F009 CC OvrTmp 1 Control module temperature exceeds a predefined value. • Check for dirt or debris.
• Check fan.
Check programming. Check for excess load, improper A530 [Boost
F012 HW OverCurrent 2 The drive output current has exceeded the hardware current limit. Select] setting, DC brake volts set too high or other causes of excess
current.
A current path to earth ground has been detected at one or more of Check the motor and external wiring to the drive output terminals
F013 Ground Fault 1(2) the drive output terminals. for a grounded condition.
The output torque current is below the value programmed in A490 • Verify connections between motor and load.
F015 Load Loss 2 [Load Loss Level] for a time period greater than the time • Verify level and time requirements
programmed in A491 [Load Loss Time].
Output Phase Loss (if enabled). • Verify motor wiring.
F021 Output Ph Loss 1 • Verify motor.
Configure with A557 [Output Phas Loss En].
An analog input is configured to fault on signal loss. A signal loss has • Check for broken/loose connections at inputs.
F029 Analog In Loss 1 occurred. • Check parameters.
Configure with t094 [Anlg In V Loss] or t097 [Anlg In mA Loss].
Drive unsuccessfully attempted to reset a fault and resume running
F033 Auto Rstrt Tries 2 Correct the cause of the fault and manually clear.
for the programmed number of A541 [Auto Rstrt Tries].
F038 Phase U to Gnd • Check the wiring between the drive and motor.
A phase to ground fault has been detected between the drive and • Check motor for grounded phase.
F039 Phase V to Gnd 2 motor in this phase. • Replace drive if fault cannot be cleared.
F040 Phase W to Gnd
F041 Phase UV Short Check the motor and drive output terminal wiring for a shorted
Excessive current has been detected between these two output condition.
F042 Phase UW Short 2 terminals.
F043 Phase VW Short Replace drive if fault cannot be cleared.
• Clear the fault or cycle power to the drive.
F048 Params Defaulted 1 The drive was commanded to write default values to EEPROM. • Program the drive parameters as needed.
Both of the safety inputs (Safety 1, Safety 2) are not enabled. Check safety input signals. If not using safety, verify and tighten
F059 Safety Open 1
Configure with t105 [Safety Open En]. jumper for I/O terminals S1, S2 and S+.
Programmed A486, A488 [Shear Pinx Level] has been exceeded for a • Verify connections between motor and load.
F063 SW OverCurrent 1 time period greater than the time programmed in A487, A489 [Shear • Verify level and time requirements.
Pin x Time].
F064 Drive Overload 2 Drive overload rating has been exceeded. Reduce load or extend Accel Time.
• Check maximum ambient temperature has not been exceeded.
F070 Power Unit 2 Failure has been detected in the drive power section. • Cycle power.
• Replace drive if fault cannot be cleared.
• Cycle power.
Control over the Modbus or DSI communications link has been • Check communications cabling.
F071 DSI Net Loss 2 interrupted. • Check Modbus or DSI setting.
• Check Modbus or DSI status.
• Cycle power.
Control over the network option card’s remote network has been • Check communications cabling.
F072 Opt Net Loss 2 interrupted. • Check network adapter setting.
• Check external network status.
• Cycle power.
Control through the embedded EtherNet/IP adapter has been • Check communications cabling.
F073 EN Net Loss 2 interrupted. • Check EtherNet/IP setting.
• Check external network status.
F080 Autotune Failure 2 The autotune function was either cancelled by the user or failed. Restart procedure.
Additional faults are listed on the next page.

Rockwell Automation Publication 520-DU001D-EN-E - April 2016


6 PowerFlex 525 Adjustable Frequency AC Drive

• Cycle power.
• Check communications cabling.
• Check Modbus or DSI setting.
Communications between the drive and the Modbus or DSI master • Check Modbus or DSI status.
F081 DSI Comm Loss 2 device have been interrupted. • Modify using C125 [Comm Loss Action].
• Connecting I/O terminals C1 and C2 to ground may improve
noise immunity.
• Replace wiring, Modbus master device, or control module.
• Cycle power.
Communications between the drive and the network option card • Reinstall option card in drive.
F082 Opt Comm Loss 2 have been interrupted. • Modify using C125 [Comm Loss Action].
• Replace wiring, port expander, option card, or control module.
• Cycle power.
• Check EtherNet/IP setting.
Internal communications between the drive and the embedded
F083 EN Comm Loss 2 • Check drive’s Ethernet settings and diagnostic parameters.
EtherNet/IP adapter have been interrupted. • Modify using C125 [Comm Loss Action].
• Replace wiring, Ethernet switch, or control module.
• Check Wiring.
Requires differential encoder. • If P047, P049, P051 [Speed Referencex] = 16 “Positioning” and
F091 Encoder Loss 2 A535 [Motor Fdbk Type] = 5 “Quad Check”, swap the Encoder
One of the 2 encoder channel signals is missing. channel inputs or swap any two motor leads.
• Replace encoder.
“Freeze-Fire” (Function Loss) input is inactive, input to the
F094 Function Loss 2 Close input to the terminal and cycle power.
programmed terminal is open.
F100 Parameter 2 Drive parameter non-volatile storage is corrupted. Set P053 [Reset To Defalts] to 2 “Factory Rset”.
Chksum
F101 External Storage 2 External non-volatile storage has failed. Set P053 [Reset To Defalts] to 2 “Factory Rset”.
Clear fault and verify all parameter settings. Do not remove or
F105 C Connect Err 2 Control module was disconnected while drive was powered. install the control module while power is applied.
The PowerFlex 525 control module does not support power modules • Change to a different power module.
F106 Incompat C-P 2 with 0.25 HP power rating. • Change to a PowerFlex 523 control module.
• Change to a different power module.
The control module could not recognize the power module. Hardware
F107 Replaced C-P 2 • Replace control module if changing power module does not
failure. work.
The control module was mounted to a different drive type power
F109 Mismatch C-P 2 Set P053 [Reset To Defalts] to 3 “Power Reset”.
module.
F110 Keypad • Cycle power.
2 Keypad membrane failure / disconnected.
Membrane • Replace control module if fault cannot be cleared.
• Check safety input signals. If not using safety, verify and tighten
Safety input enable hardware malfunction. One of the safety inputs is
F111 Safety Hardware 2 jumper for I/O terminals S1, S2 and S+.
not enabled. • Replace control module if fault cannot be cleared.
• Cycle power.
F114 uC Failure 2 Microprocessor failure. • Replace control module if fault cannot be cleared.
• Cycle power.
F122 I/O Board Fail 2 Failure has been detected in the drive control and I/O section. • Replace drive or control module if fault cannot be cleared.
The firmware in the drive is corrupt, mismatched, or incompatible Perform a firmware flash update operation to attempt to load a
F125 Flash Update Req 2 with the hardware. valid set of firmware.
A non-recoverable firmware or hardware error was detected. The • Clear fault or cycle power to the drive.
F126 NonRecoverablErr 2 drive was automatically stopped and reset. • Replace drive or control module if fault cannot be cleared.
A critical problem with the firmware was detected and the drive is Perform a firmware flash update operation using DSI
F127 DSIFlashUpdatReq 2 running using backup firmware that only supports DSI communications to attempt to load a valid set of firmware.
communications.
(1) Type 1 = Auto-Reset/Run faults. Type 2 = Non-Resettable faults.
(2) This fault may be cleared by the auto-restart routine and will be attempted only once. It ignores the value set in parameter A541 [Auto Rstrt Tries].

Rockwell Automation Publication 520-DU001D-EN-E - April 2016


All the recommended documentation listed in this section is available online at
http://www.rockwellautomation.com/literature.

The following publications provide general drive information:


Title Publication
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives DRIVES-IN001
Preventive Maintenance of Industrial Control and Drive System Equipment DRIVES-TD001
Safety Guidelines for the Application, Installation and Maintenance of Solid State Control SGI-1.1
A Global Reference Guide for Reading Schematic Diagrams 100-2.10
Guarding Against Electrostatic Damage 8000-4.5.2

The following publications provide specific PowerFlex 520-Series information on drive installation, features, specifications,
and service:
Title Publication
PowerFlex 520-Series Drive Adjustable Frequency AC Drive User Manual 520-UM001
PowerFlex 520-Series Drive AC Drive Specifications 520-TD001
PowerFlex Dynamic Braking Resistor Calculator PFLEX-AT001
PowerFlex AC Drives in Common Bus Configurations DRIVES-AT002

The following publications provide specific Network Communications information:


Title Publication
PowerFlex 525 Embedded EtherNet/IP Adapter 520COM-UM001
PowerFlex 25-COMM-D DeviceNet Adapter 520COM-UM002
PowerFlex 25-COMM-E2P Dual-Port EtherNet/IP Adapter 520COM-UM003
PowerFlex 25-COMM-P PROFIBUS DPV1 Adapter 520COM-UM004

Allen-Bradley, Rockwell Automation, PowerFlex, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Publication 520-DU001D-EN-E - April 2016
Supersedes Publication 520-DU001C-EN-E - August 2014 Copyright © 2016 Rockwell Automation, Inc. All rights reserved.