K Type Thermocouple Extension Cable KXYY (1-50) Pairs X 1.5 MM 300 V

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

K TypeThermocouple

K Type Thermocouple Extension


Extension Cable
Cable
KXYY (1-50) Pairs x 1.5 mm2 300 V
(Chromel-Alumel Conductor, PVC Insulated, Individual or Collective Screen, PVC Sheathed)
Standard Specification : IEC 60584, ANSI MC 96.1

Construction Data
Size Application : Chromel (Ni-Cr)
For transmission of thermoelectric voltage Alumel (Ni-Al)
No. 1.5 mm 2
from measuring junction to reference
of Collective Screen Individual Screen junction. PVC Insulation
pairs Tinned Copper -
Overall Cable Overall Cable Drain Wires
Diameter Weight Diameter Weight Special Features on Request Collective Screen
approx. approx. approx. approx. • Oil Resistance
• UV Resistance
mm kg/km mm kg/km • Flame Retardant Cat. A, B, C
PVC Sheath
1 9.9 137 - - • Flame Retardant Non Category
2 12.8 199 14.6 313 • Anti Termite
• Anti Rodent
3 14.9 243 15.5 359 • Low Smoke Zero Halogen
4 16.7 302 16.9 423 • Nylon Coated
5 18.3 386 18.5 427
6 19.7 431 21.5 529
7 21.0 474 21.5 542 Fig. 01 : Collective Screen
Note :
9 23.5 584 25.5 685
Conductor Shape
10 25.0 650 27.5 766 All construction supplied in solid (re) or circular
12 27.0 759 30.0 899 stranded (rm)
14 29.0 879 31.5 1,035
Standard Packing
15 30.0 959 33.5 1,127 All conductor supplied in wooden drum @ 1000 m
16 30.5 1,012 35.0 1,202 Length tolerance per drum ± 2%
Size of drain wire : 0.5 mm²
18 32.5 1,107 37.5 1,321
19 33.0 1,160 37.5 1,378
20 34.0 1,255 39.5 1,554
24 37.0 1,457 46.5 1,775
30 41.0 1,793 49.5 2,161
36 45.0 2,150 54.0 2,591
40 47.5 2,360 56.0 2,839
48 51.5 2,823 63.0 3,413
50 52.5 2,928 64.5 3,541

Material & Color Code


Type KX Chromel (Ni-Cr)
Material (+) Chromel Alumel (Ni-Al)
(-) Alumel PVC Insulation
Tinned Copper -
Limit of Error - IEC 60584 Class 1 ± 1.5 °C / ± 60 µV ( -25 ~ 200 °C) Drain Wires
(Temp. Range)
Class 2 ± 2.5 °C / ± 100 µV ( -25 ~ 200 °C) Individual Screen
Tinned Copper -
ANSI MC - ± 2.2 °C ( 0 ~ 200 °C )
Drain Wires
96.1

Collective Screen
Color Code Insulation (+) Yellow
(-) Red PVC Sheath

Jacket Yellow

Electrical Data
Conductor AC Fig. 02 : Individual Screen

Normal Nominal Value Voltage


Cross Loop Resistance Test
Section at 20 °C
mm2 Ω/km volt/1 min.

1.5 680 1000


KXCB33 Rev. 0.0 / 2006