100% found this document useful (1 vote)
2K views1 page

Sf6 Gas Circuit Breaker Test Report: Characteristics

1. A test report summarizes the results of tests conducted on a 36kV, 630A SF6 gas circuit breaker with a short circuit breaking current of 16kA. 2. Key tests included mechanical operation tests, gas pressure checks, insulation resistance measurements, contact timing tests, and high voltage dielectric tests, all of which the breaker passed successfully. 3. Visual inspections and design checks were also conducted with affirmative results.

Uploaded by

Ilir R. Dalipi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
2K views1 page

Sf6 Gas Circuit Breaker Test Report: Characteristics

1. A test report summarizes the results of tests conducted on a 36kV, 630A SF6 gas circuit breaker with a short circuit breaking current of 16kA. 2. Key tests included mechanical operation tests, gas pressure checks, insulation resistance measurements, contact timing tests, and high voltage dielectric tests, all of which the breaker passed successfully. 3. Visual inspections and design checks were also conducted with affirmative results.

Uploaded by

Ilir R. Dalipi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SF6 GAS CIRCUIT BREAKER TEST REPORT

Test date ....... : 16.11.2015 Report no. .............. : 9324-10-C-1


CHARACTERISTICS
Type ............................. : EGB5 16 - 06 R Basic Insulation Level ….... : 36/70/170 kV
Serial no. ..................... : 9324-10-C-1 Short-circuit duration …….... : 3 sec
Production year .......... : 2015 S.C. Breaking current ........ : 16 kA (eff.)
Rated voltage ….......... : 36 kV Making current …….............. : 40 kA (peak)
Rated current ............. : 630 A Frequency ........................... : 50 Hz
APPLIED TESTS
1.) MECHANICAL OPERATING TEST
1.a) Charge-open-close steps are applied 40 times to the breaker at the rated voltage.
1.b) Circuit breaker is operated 5 times at minimum and maximum operating voltage.
RATED VOLTAGE MIN. VOLTAGE MAX. VOLTAGE

Charging Circuit 220 Vac 187 Vdc 242 Vdc


Closing Circuit 110 Vdc 93,5 Vdc 121 Vdc
Opening Circuit 110 Vdc 77 Vdc 121 Vdc
1.c) Charging, opening-closing circuits of breaker were operated properly.
2.) GAS PRESSURE CONTROL
Gas pressure of poles which passed the leakage tests before mounting on CB was measured.
AMBIENT REQUIRED MEASURED
PHASE SERIAL NUMBER TEMPERATURE PRESSURE RANGE PRESSURE
(°C) (kg/cm2) (kg/cm2)
L1 - 25 0,40…0,50 2,2
L2 - 25 0,40…0,50 2,2
L3 - 25 0,40…0,50 2,2
3.) TESTS ON AUXILIARY AND CONTROL CIRCUITS
3.a) Auxiliary and control circuits and their functions are controlled according to circuit sheme.
3.b) 1 kV power frequency voltage was applied to auxiliary and control circuits without any discharge.
4.) MEASUREMENT OF THE RESISTANCE OF THE MAIN CIRCUIT
STANDARD ACCEPTABLE MAX
PHASE SERIAL NUMBER MEASURED VALUE (µW)
VALUE ( µW )
L1 - 70 47
L2 - 70 51
L3 - 70 55
5.) DIELECTRIC TEST ON MAIN CIRCUIT
Power frequency voltage was applied for 1 minute.
5.a) Applied voltage for phase to phase and phase to earth = 70 kV
5.b) Applied voltage for across the isolating distance = 70 kV
6.) MEASUREMENT OF CLOSING AND OPENING TIMES OF CONTACTS
CLOSING TIMES (ms) OPENING TIMES (ms)
PHASE
REQUIRED MEASURED REQUIRED MEASURED
L1 50 ... 100 63 30 ... 70 41
L2 50 ... 100 63 30 ... 70 41
L3 50 ... 100 63 30 ... 70 41
7.) DESIGN AND VISUAL CHECKS
Desing and visual checks are done on circuit breaker.

PREPARED BY RESULT APPROVED BY STANDARD DISTRIBUTION

MURAT AYDIN Mustafa DOĞAN TS EN 62271-100 - Customer


AFFIRMATIVE
IEC 62271-100 - Quality Department
Doc.No : 5.2.F.060 Rev : 16

You might also like