Termostato Analogico Siemens Raa31 Xa
Termostato Analogico Siemens Raa31 Xa
Termostato Analogico Siemens Raa31 Xa
Use
The RAA31.. room thermostat is used in heating only or cooling only systems to main-
tain the selected room temperature.
Typical use:
· Residential buildings
· Light industrial buildings
In conjunction with
- zone valves, thermal valves
- gas or oil burners
- fans
- pumps
CE1N3563en
2015-01-13 Building Technologies
Functions
Type summary
Equipment combinations
Accessories
Technical desig
2/6
The required temperature is selected by a setpoint adjuster on the front of the thermo-
stat.
The setpoint setting range can be mechanically limited by means of setpoint limiter
under the cover.
Notes
Mounting, installation The room thermostat should be located where the air temperature can be sensed as
and commissioning accurately as possible, without getting adversely affected by direct solar radiation or
other heat or refrigeration sources.
Mounting height is about 1.5 m above the floor.
The unit can be fitted to most commercially available recessed conduit boxes or directly
on the wall.
Only authorised personnel may open the unit to perform service.
Warning:
The unit must be isolated from the mains supply before opening.
AC 24…250 V!
When installing the unit, fix the base plate first then hook on the thermostat body and
make the electrical connections. Then fit the cover and secure it (also refer to separate
mounting instructions).
The thermostat must be mounted on a flat wall.
The local electrical regulations must be complied with.
If there are thermostatic radiator valves in the reference room, set them to their fully
open position.
Warning!
No internal line protection for supply lines to external consumers (Y1, Y2)
Risk of fire and injury due to short-circuits!
· Adapt the line diameters as per local regulations to the rated value of the installed
overcurrent protection device.
Ordering
3/6
The devices are considered electronics devices for disposal in term of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
· Dispose of the device via the channels provided for this purpose
· Comply with all local and currently applicable laws and regulations.
Technical Data
Switching capacity
Power Voltage
· RAA31... AC 24...250 V / 50 or 60 Hz
· RAA31.16 and 31.26 AC 230 V +/-10 %
Power consumption of each LED 0.5 VA (Only RAA31.16 and RAA31.26)
Current 0.2…6 (2.5) A
Frequency 50 or 60 Hz
No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line required under all
circumstances
2 2
Screw terminals for 2 x 1.5 mm (min. 0.5 mm )
Operational data Switching differential SD £1 K
Setpoint setting range 8…30 °C
Environmental conditions Operation to IEC 60721-3-3
Climatic conditions Class 3K5
Temperature 0…50 °C
Humidity <95 % r.h.
Pollution degree Normal, to EN 60730-1
Transport / storage to IEC 60721-3-2
Climatic conditions Class 2K3/1K3
Temperature -20…50 °C
Humidity <95 % r.h.
Mechanical conditions Class 2M2
*)
Industry standards EU Conformity (CE) CE1T3561xx
*)
RCM Conformity CE1T3561en_C1
Safety standard II to EN 60730-1
Degree of protection of housing IP30 to EN 60529
*)
Environmental The product environmental declarations CE1E3015, CE1E3561 contain data on envi-
ronmentally compatible product design and assessments (RoHS compliance, materials
compatibility composition, packaging, environmental benefit, disposal).
Mechanical design Weight 0.14 kg
Colour of top cover white, NCS 50502-G (RAL 9003)
*)
The documents can be downloaded from http://siemens.com/bt/download.
4/6
3210A03
3210A04
Y1 Control output "Heating",
AC 24…250 V (RAA31 only)
RAA31 – Heating mode RAA31 – Cooling mode AC 230 V
(RAA31.16 / 26 only)
Y2 Control output "Cooling",
AC 24…250 V (RAA31 only)
AC 230 V
(RAA31.16 / 26 only)
N Neutral
T Thermostat element
(gas-filled diaphragm)
5/6
Remarks
Heating:
Because of the unavoidable self heating effects of the electrical current, any loads of
more than 3 Amperes connected to the unit can influence the control behavior and
temperature accuracy in a negative way.
Cooling:
Because of the unavoidable self heating effects of the electrical current, any loads of
more than 1 Amperes connected to the unit can influence the control behavior and
temperature accuracy in a negative way.