Design Consideration of Cooling Load Calculation
Design Consideration of Cooling Load Calculation
Before being designed the space, the maximum time of heat which enters to
space must be known, because the selection of cooling is based on the maximum
cooling load. That time is called peak time. This time is varying on various condition
and place.
Figure 3.1. Heat Flow Diagram Showing Building Heat Gain Heat Storage and
Cooling Load
The methods for calculating cooling loads that will be used in this thesis are
essentially those recommended by carrier handbook. These calculation procedures
described are considerably accurate.
21
Items 5 and 7 are part sensible and part latent and item 6 can fall in either
category or both depending on the type of equipment. So, it is necessary to separate
the sensible and latent heat gains because the section of cooling equipment depends
on their relative values.
(4) Additional heat gain not accounted above, safety factor, etc.
(5) Supply duct leakage loss.
(6) Bypassed outside air load.
Dailyrange
to = DB – L (3.3)
where, CLTD = cooling load temperature difference (°F)
LM = correction for latitude and month
K = correction for color of surface
= 1~dack color or urban area or industrial area
= 0.5~light color roof in rural area
= 0.65~light color wall in rural
To = average difference outside design temperature
Q = U×A×TD (3.4)
where, Q = heat gain through partition, floor, or ceiling (BTU/hr)
U = overall heat transfer coefficient for partition, floor ceiling
(BTU/hr ft2 °F)
A = area of partition, floor, or ceiling (ft2)
TD =temperature difference between unconditioned a condition space (F)
(Assume temperature of unconditioned space is 5 °F less than the outdoor
temperature)
3.10. Equipment
The heat gain from equipment may sometimes be found directly from the
manufacture or the nameplate data, allowing for intermittent use. Some equipment
produces both sensible and latent heat.
The CLF factors (not shown) are applied if the system operates hours. The
heat output from motors and the equipment driven by them results from conservation
of the electrical energy to heat.
The proportion of heat generated the heat gained by the air conditioned space
depends on that whether the motor and the driven load are both in the space or only
one of them is.
Infiltration air entering a space in winter would lower than the room air
temperature and that air in summer would be higher than that of space temperature.
Sensible heat and latent heat equations can be used to find the heat gain
resulting from the infiltration air. If the lower room humidity resulting from
infiltration is acceptable then the latent heat loss effect may be neglected.
There are two methods used to estimate the CFM of infiltration air.
(1) Crack method
(2) Air change method
The crack method assumes that a reasonably accuracy of the rate of air
infiltration per foot of crack opening can be measured or established. The crack length
and area should be determined from building architectural plans or field
measurements. The following table is for the maximum allowed design infiltration
rate through exterior windows and doors.
Table 3.1. Recommended maximum allowed design infiltration rates through
exterior windows and doors.
Item Infiltration
Windows 0.75 CFM/ft crack
Doors 1.0 CFM/ft crack
The air change method assumes that the number of air changes per hour (one
air change is equal to one room volume) in a room due to infiltration air can be
determined.
Using the definition of air change, the infiltration rate in CFM is
CFM = A C × V/60
(3.9)
where, CFM = air infiltration rate to the room (CFM)
AC = number of air change per hour for room
V = room volume (ft³)
Table 3.2. Air Change per Hour Occurring Under Average Condition In
Residences, Exclusive or Air Provided For Ventilation
Kind of Room Single Glass No Weather Storm sash of Weather
strip stripped
No windows or exterior 0.5 0.3
doors
Windows or exterior doors 1.0 0.7
on one side
Windows or exterior doors 1.5 1.0
27
on two side
Windows or exterior doors 2.0 1.3
on three side
Entrance Halls 2.0 1.3
and latent heat equation can be used to find the heat gain resulting from ventilation
air.
Qs = 1.1 × CFM × TC (3.10)
Ql = 0.68 × CFM × (w´o-w´i) (3.11)
where, Qs = sensible cooling load from ventilation air (BTU/hr)
Q l = latent cooling load from ventilation air (BTU/hr)
CFM = infiltration rate to the room (CFM)
TC = temperature (t1-t2) (°F)
w´o = outdoor humidity ratio (lb.w/lb.da)
w´i = change in humidity ratio (lb.w/lb.da)
UwAw +UgAg
k = L (3.13)