DS33-CPGK-DC (Model Data Sheet (Data Center Continuous) )

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Generator set data sheet

Model: C900 D5
Frequency: 50 Hz
Fuel type: Diesel
kW rating: 820 Data Center Continuous (DCC)

Spec sheet: SS12-CPGK


Noise data sheet (open/enclosed): ND50-OSHHP/ND50-CS550
Airflow data sheet: AF50-HHP
Derate data sheet (open/closed): DD50-OSHHP/DD50-CSHHP
Transient data sheet: TD50-HHP

Fuel consumption kVA (kW)


Ratings 820 (656)
Load 1/4 1/2 3/4 Full
gph 10.1 18.7 26.6 35.4
L/hr 46.0 85.0 121.0 161.0

Engine
Engine manufacturer Cummins
Engine model QSK23-G3
Configuration Cast iron, in-line 6 cylinder
Aspiration Turbocharged and after-cooled
Gross engine power output, kWm 701
BMEP at set rated load, kPa 2441
Bore, mm 170
Stroke, mm 170
Rated speed, rpm 1500
Piston speed, m/s 8.6
Compression ratio 16:1
Lube oil capacity, L 95
Overspeed limit, rpm 1800 ±50
Regenerative power, kW 72
Governor type Electronic
Starting voltage 24 Volts DC

Fuel flow
Maximum fuel flow, L/hr 685
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 70

power.cummins.com
©2017 Cummins Inc. | DS33-CPGK-DC (08/17)
Air
Combustion air, m3/min 4.70
Maximum air cleaner restriction, kPa 6.2

Exhaust
Exhaust gas flow at set rated load, m3/min 135.6
Exhaust gas temperature, °C 532
Maximum exhaust back pressure, kPa 10.1

Standard set-mounted radiator cooling


Ambient design, °C 50
Fan load, kW m 16
Coolant capacity (with radiator), L 89
Cooling system air flow, m3/sec @ 12.7 mm H2O 11.6
Total heat rejection, Btu/min 19196
Maximum cooling air flow static restriction mm H2O 12.7

Weights* Open Enclosed


Unit dry weight, kgs 6539 N/A
Unit wet weight, kgs 6680 N/A
* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Dimensions Length Width Height


Standard open set dimensions, mm 4266 1879 2052
Enclosed set standard dimensions, mm N/A N/A N/A

Genset outline
Open set

Enclosed set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

power.cummins.com
©2017 Cummins Inc. | DS33-CPGK-DC (08/17)
Alternator data
Connection Temp rise ºC Duty Alternator Voltage
Wye, 3-phase 150/125 S/P HC6H 380-440 V

Ratings definitions
Data Center Continuous (DCC):
Applicable for supplying power continuously to a constant electrical load for unlimited hours in a data center application
where a reliable utility is present. The Data Center Continuous (DCC) power rating is in accordance with ISO8528.

Formulas for calculating full load currents:

Three phase output

kW x 1000
Voltage x 1.73 x 0.8

For more information contact your local Cummins distributor


or visit power.cummins.com

©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
DS33-CPGK-DC (08/17)

You might also like