Vacon Nxs NXP User Manual Dpd00910d Uk
Vacon Nxs NXP User Manual Dpd00910d Uk
Vacon Nxs NXP User Manual Dpd00910d Uk
ac drives
user manual
wall-mounted drives
standalone drives
PREFACE VACON · 3
PREFACE
Document ID: DPD00910D
Date: 20.2.2015
1. Do a check that the delivery agrees to your order, see Chapter 3 Receiving the delivery.
2. Before you start the commissioning, read carefully the safety instructions in Chapter 2
Safety.
3. Before the mechanical installation, do a check of the minimum clearances around the AC
drive (Chapter 4 Mounting) and do a check of the ambient conditions in Chapter 9.2
Vacon® NXS and NXP - technical data.
4. Do a check of the dimensions of the motor cable, mains cable, mains fuses and do a
check of the cable connections. Read Chapters 5.1 Cable connections to 5.3 Cable
dimensioning and selection.
5. Obey the installation instructions, see Chapter 5.7 Cable installation.
6. Find information on the control connections in Chapter 6.2.2 Control terminals.
7. If the Start-Up wizard is active, select the language of the keypad and the application.
Accept the selections with the Enter button. If the Start-Up wizard is not active, obey the
instructions a and b.
a) Select the language of the keypad from the Menu M6, page 6.1. For instructions on
how to use the keypad, see Chapter 7 Control panel.
b) Select the application from the Menu M6, page 6.2. For instructions on how to use
the keypad, see Chapter 7 Control panel.
8. All parameters have factory default values. To make sure that the AC drive operates
correctly, make sure that these group G2.1 parameters have the same data as the
nameplate. For more information on the parameters in the list below, see the All-in-One
Application Manual.
• nominal voltage of the motor
• nominal frequency of the motor
• nominal speed of the motor
• nominal current of the motor
• motor cos phi
9. Obey the commissioning instructions, see Chapter 8 Commissioning and additional
instructions.
10. The Vacon NXS or NXP AC drive is ready for operation.
Vacon Plc is not responsible if you use the AC drives against the instructions.
TABLE OF CONTENTS
Preface
About this manual 3
Start-up Quick Guide
1 Approvals 8
2 Safety 12
2.1 The safety symbols used in the manual 12
2.2 Warning 12
2.3 Caution 13
2.4 Grounding and earth fault protection 14
2.5 Electro-magnetic compatibility (EMC) 15
2.6 Using an RCD or an RCM device 15
3 Receiving the delivery 17
3.1 Package label 17
3.2 Type designation code 18
3.3 Storage 21
3.4 Removing the packaging and lifting the AC drive 21
3.4.1 Weight of the AC drive 21
3.5 Accessories 21
3.5.1 FR4-FR6 cable accessories 22
3.5.2 FR7-FR8 cable accessories 24
3.6 "Product modified" label 27
3.7 Disposal 27
4 Mounting 28
4.1 General information about mounting 28
4.2 Dimensions for wall mounting 29
4.2.1 Wall mounting of FR4-FR6 29
4.2.2 Wall mounting of FR7 30
4.2.3 Wall mounting of FR8 31
4.2.4 Wall mounting of FR9 32
4.3 Dimensions for flange mounting 33
4.3.1 Flange mounting of FR4 to FR6 33
4.3.2 Flange mounting of FR7 and FR8 35
4.3.3 Flange mounting of FR9 38
4.4 Dimensions for standalone 39
4.4.1 Standalone (FR10 and FR11) 39
4.5 Cooling 40
4.5.1 Cooling of FR4 to FR9 40
4.5.2 Cooling of standalone AC drives (FR10 to FR11) 43
5 Power cabling 44
5.1 Cable connections 44
5.2 UL standards on cabling 46
1 APPROVALS
Here are the approvals that have been granted to this Vacon AC drive.
1. EC Declaration of conformity
• Find the EC Declaration of Conformity on the next pages.
2. UL approval
• cULus approval file number E171278.
3. RCM approval
• RCM approval number E2204.
EC DECLARATION OF CONFORMITY
We
Manufacturer’s name: Vacon Oyj
Manufacturer’s address: P.O. Box 25
Runsorintie 7
FIN-65381 Vaasa
Finland
hereby declare that the product
Product name: Vacon NXS/P Frequency converter
Model designation: Vacon NXS/P 0003 2.... to 0300 2....
Safety: EN 61800-5-1:2007
EN 60204-1:2006+A1:2009 (as relevant)
EMC: EN 61800-3:2004+A1:2012
and conforms to the relevant safety provisions of the Low Voltage Directive
(2006/95/EC) and EMC Directive 2004/108/EC.
It is ensured through internal measures and quality control that the product
conforms at all times to the requirements of the current Directive and the
relevant standards.
EC DECLARATION OF CONFORMITY
We
Manufacturer’s name: Vacon Oyj
Manufacturer’s address: P.O. Box 25
Runsorintie 7
FIN-65381 Vaasa
Finland
hereby declare that the product
Product name: Vacon NXS/P Frequency converter
Model designation: Vacon NXS/P 0003 5.... to 1030 5....
Safety: EN 61800-5-1:2007
EN 60204-1:2006+A1:2009 (as relevant)
EMC: EN 61800-3:2004+A1:2012
and conforms to the relevant safety provisions of the Low Voltage Directive
(2006/95/EC) and EMC Directive 2004/108/EC.
It is ensured through internal measures and quality control that the product
conforms at all times to the requirements of the current Directive and the
relevant standards.
EC DECLARATION OF CONFORMITY
We
Manufacturer’s name: Vacon Oyj
Manufacturer’s address: P.O. Box 25
Runsorintie 7
FIN-65381 Vaasa
Finland
hereby declare that the product
Product name: Vacon NXS/P Frequency converter
Model designation: Vacon NXS/P 0004 6.... to 0820 6....
Safety: EN 61800-5-1:2007
EN 60204-1:2006+A1:2009 (as relevant)
EMC: EN 61800-3:2004+A1:2012
and conforms to the relevant safety provisions of the Low Voltage Directive
(2006/95/EC) and EMC Directive 2004/108/EC.
It is ensured through internal measures and quality control that the product
conforms at all times to the requirements of the current Directive and the
relevant standards.
2 SAFETY
2.1 THE SAFETY SYMBOLS USED IN THE MANUAL
This manual contains warnings and cautions, which are identified with safety symbols. The
warnings and cautions give important information on how to prevent injury and damage to
the equipment or your system.
Read the warnings and cautions carefully and obey their instructions.
WARNING!
CAUTION!
HOT SURFACE!
2.2 WARNING
WARNING!
Do not touch the components of the power unit when the drive is connected to
mains. The components are live when the drive is connected to mains. A contact
with this voltage is very dangerous.
WARNING!
Do not touch the motor cable terminals U, V, W, the brake resistor terminals or the
DC terminals when the drive is connected to mains. These terminals are live when
the drive is connected to mains, also when the motor does not operate.
WARNING!
Do not touch the control terminals. They can have a dangerous voltage also when
the drive is disconnected from mains.
WARNING!
Before you do electrical work, make sure that there is no voltage in the
components of the drive.
WARNING!
To do work on the terminal connections of the drive, disconnect the drive from
mains and make sure that the motor has stopped. Wait 5 minutes before you open
the cover of the drive. Then use a measuring device to make sure that there is no
voltage. The terminal connections and the components of the drive are live 5
minutes after it is disconnected from mains and the motor has stopped.
WARNING!
Before you connect the drive to mains, make sure that the front cover and the cable
cover of the drive are closed. The connections of the AC drive are live when the
drive is connected to mains.
WARNING!
Disconnect the motor from the drive if an accidental start can be dangerous. When
there is a power-up, a power break or a fault reset, the motor starts immediately if
the start signal is active, unless the pulse control for Start/Stop logic is selected. If
the parameters, the applications or the software change, the I/O functions
(including the start inputs) can change.
WARNING!
2.3 CAUTION
CAUTION!
Do not move the AC drive. Use a fixed installation to prevent damage to the drive.
CAUTION!
Do not make measurements when the AC drive is connected to mains. It can cause
damage to the drive.
CAUTION!
Do not use spare parts that are not from the manufacturer. Using other spare parts
can cause damage to the drive.
CAUTION!
Do not touch the components on the circuit boards. Static voltage can cause
damage to these components.
CAUTION!
Make sure that the EMC level of the AC drive is correct for your mains. See chapter
8.5 Installation in an IT system. An incorrect EMC level can cause damage to the
drive.
CAUTION!
Prevent radio interference. The AC drive can cause radio interference in a domestic
environment.
NOTE!
If you activate the autoreset function, the motor starts automatically after an
automatic fault reset. See the Application Manual.
NOTE!
If you use the AC drive as a part of a machine, the machine manufacturer must
supply a mains disconnection device (refer to EN 60204-1).
CAUTION!
Cross-sectional area of the phase conductors (S) The minimum cross-sectional area of the protective
[mm2] grounding conductor in question [mm2]
S ≤ 16 S
16 < S ≤ 35 16
35 < S S/2
The values of the table are valid only if the protective grounding conductor is made of the
same metal as the phase conductors. If this is not so, the cross-sectional area of the
protective grounding conductor must be determined in a manner that produces a
conductance equivalent to that which results from the application of this table.
The cross-sectional area of each protective grounding conductor that is not a part of the
mains cable or the cable enclosure, must be a minimum of:
NOTE!
Because there are high capacitive currents in the AC drive, it is possible that the
fault current protective switches do not operate correctly.
CAUTION!
Do not do voltage withstand tests on the AC drive. The manufacturer has already
done the tests. Doing voltage withstand tests can cause damage to the drive.
NOTE! You can download the English and French product manuals with applicable safety, warning and caution
information from www.vacon.com/downloads.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit contenant l'en-
semble des informations de sécurité, avertissements et mises en garde applicables sur le site www.vacon.com/
downloads.
D
F
E
Code Description
NXS = standard
NXP = high-performance
0007 = 7 A
0022 = 22 A
0205 = 205 A, and so on
2 = 208-240 Vac
5 = 380-500 Vac
6 = 500-690 Vac
0 = IP00
2 = IP21 (UL Type 1)
5 = IP54 (UL Type 12)
T = flange mounted (through-hole mounted)
C = obeys the category C1 of standard IEC/EN 61800-3 + A1, 1st environment and nominal volt-
age less than 1000 V
H = obeys the category C2 of standard IEC/EN 61800-3 + A1, fixed installations and nominal volt-
age less than 1000 V
L = obeys the category C3 of standard IEC/EN 61800-3 + A1, 2nd environment and nominal volt-
age less than 1000 V
T = obeys the standard IEC/EN 61800-3 + A1 when used in IT networks
N = No EMC emission protection. An external EMC filter is necessary.
Code Description
1
The brake chopper:
0 = No brake chopper
1 = Internal brake chopper
2 = Internal brake chopper and resistor
NOTE!
A1A20000C3 The option boards. 2 characters for each slot. 00 = the slot is not used
NOTE!
For other possible installation combinations, speak to the distributor near you.
3.3 STORAGE
If you must keep the AC drive in storage before you use it, make sure that the ambient
conditions agree to these:
*) FR11, the product types 0460 and 0502: 400 kg (882 lb.)
3.5 ACCESSORIES
After you open the package and lift the drive out, make sure that you received all the
accessories. The content of the accessories bag is different for the different frames and
protection classes.
1 3 4 5 6 7 8
Components:
1. The grounding terminals (FR4, FR5), 2 pieces
2. The grounding clamps for control cable, 3 pieces
3. The rubber grommets (sizes vary from class to class), 3 pieces
4. The cable entry flange
5. Screws, M4x10, 5 pieces
6. Screws, M4x16, 3 pieces
7. The grounding clamps for grounding conductor (FR6), 2 pieces
8. The grounding screws M5x16 (FR6), 4 pieces
1 2 3 4
Components:
1. Screws, M4x16, 3 pieces
2. The grounding clamps for control cable, 3 pieces
3. The rubber grommets GD21 (FR7 IP54/UL Type 12), 3 pieces / (FR8), 6 pieces
4. The rubber grommets GDM36 (FR7), 3 pieces
1. FR7 standard
2. FR7 profibus
3. FR8 standard
4. FR8 profibus
Drive modified:
Option board: NXOPT......... Date:............
in slot: A B C D E Date:............
IP54 upgrade/Collar Date:............
EMC level modified: H/L to T Date:............
3.7 DISPOSAL
When the drive is at the end of its operation life, do not discard it as a part of municipal
waste. You can recycle the primary components of the drive. You must disassemble
some components before you can remove the different materials. Recycle the electrical
and electronic components as waste.
To make sure that the waste is recycled correctly, send the waste to a recycling centre.
You can also send the waste back to the manufacturer.
Obey the local and other applicable regulations.
4 MOUNTING
4.1 GENERAL INFORMATION ABOUT MOUNTING
Install the AC drive in vertical or horizontal position on the wall. If you install the drive in a
horizontal position, there is no protection against drops of water that fall vertically.
You can also install the AC drive into the cabinet wall with a flange mounting option (through-
hole mounting). With the flange mounting, the enclosure class of the power unit is IP54 (UL
Type 12) and the enclosure class of the control unit is IP21 (UL Type 1).
Attach the AC drive with the screws and other components that you received in the delivery.
Make sure that there is sufficiently free space around the AC drive for cooling, see 4.5
Cooling. Also make sure that the mounting surface is sufficiently flat.
For the dimensions of the wall-mounted and flange-mounted Vacon NX AC drives, see the
chapters below.
The sizes FR10 to FR11 are standalone AC drives. The enclosures have fixing holes. For
dimensions, see Chapter 4.4.1 Standalone (FR10 and FR11).
W2
D1
H1
H2
H3
W1
E1Ø
E2Ø*
Table 5: Dimensions in mm (in inch) of the NXS and NXP AC drive, FR4-FR6
0048 2-0061 2
195 148 558 541 519 237 9 3 x 37 -
0038 5-0061 5
(7.68) (5.83) (21.97) (21.3) (20.43) (9.33) (0.35) (3 x 1.46) (-)
0004 6-0034 6
* = FR5 only
Ø
H3
D1
H2
H1
W1
E1Ø
W2
Table 6: Dimensions in mm (in inch) of the NXS and NXP AC drive, FR7
0075 2-0114 2
237 190 630 614 591 257 9 3 x 50.3
0072 5-0105 5
(9.33) (7.48) (24.80) (24.17) (23.27) (10.12) (0.35) (3 x 1.98)
0041 6-0052 6
H1
H2
W1
E1Ø
D1
Table 7: Dimensions in mm (in inch) of the NXS and NXP AC drive, FR8
0140 2-0205 2
291 255 758 732 344 9 2 x 59
0140 5-0205 5
(11.47) (10.04) (29.88) (28.81) (13.54) (0.35) (2 x 2.32)
0062 6-0100 6
D1 D2
E1Ø H6 H4 H3
B-B+/R+R- W4
W5W5
W3
W1
W2
H2 H5
D3 H1
Table 8: Dimensions in mm (in inch) of the NXS and NXP AC drive, FR9, part 1
Drive type W1 W2 W3 W4 W5 D1 D2 D3
0261 2-0300 2
480 400 165 9 54 362 340 285
0261 5-0300 5
(18.9) (15.75) (15.74) (0.35) (2.13) (14.25) (13.39) (11.22)
0125 6-0208 6
Table 9: Dimensions in mm (in inch) of the NXS and NXP AC drive, FR9, part 2
0261 2-0300 2
1150* 1120 721 205 16 188 21 59
0261 5-0300 5
(45.28*) (44.09) (28.39) (8.07) (0.63) (7.40) (0.83) (2.32)
0125 6-0208 6
* = Brake resistor terminal box (H6) not included. For FR8 and FR9 when Brake chopper or
Additional DC connection is selected in type designation code, the total height of the AC drive
is increased by 203 mm (7.99 inch).
W2
H4
D1
D2 H5
H1
H2
H3
W1
Fig. 8: Dimensions of the NXS and NXP AC drive with flange, FR4-FR6
Table 10: Dimensions in mm (in inch) of the NXS and NXP AC drive with flange, FR4-FR6
Drive type W1 W2 H1 H2 H3 H4 H5 D1 D2 Ø
0048 2-0061 2
195 170 560 549 558 30 20 237 106 6.5
0038 5-0061 5
(7.68) (6.69) (22.05) (21.61) (22) (1.18) (0.79) (9.33) (4.17) (0.26)
0004 6-0034 6
H2
Ø
W3
W2
W1
H1
H3 H4
Fig. 9: The dimensions of the opening and drive outline with flange, FR4 to FR6
Table 11: The dimensions in mm (in inch) of the opening and drive outline with flange, FR4 to
FR6
Drive type W1 W2 W3 H1 H2 H3 H4 Ø
0048 2-0061 2
185 170 157 539 549 7 5 6.5
0038 5-0061 5
(7.28) (6.69) (6.18) (21.22) (21.61) (0.27) (0.20) (0.26)
0004 6-0034 6
D1
H4
D2
H3
H2
H1
H4
W3
W1
H5
Fig. 10: Dimensions of the NXS and NXP AC drive with flange, FR7 and FR8
Table 12: Dimensions in mm (in inch) of the NXS and NXP AC drive with flange, FR7 and FR8,
part 1
Drive type W1 W2 W3 W4 D1 D2 Ø
0075 2-0114 2
237 175 270 253 257 117 6.5
0072 5-0105 5
(9.33) (6.89) (10.63) (9.96) (10.12) (4.61) (0.26)
0041 6-0052 6
0140 2-0205 2
289 - 355 330 344 110 9
0140 5-0205 5
(11.38) (-) (13.98) (12.99) (13.54) (4.33) (0.35)
0062 6-0100 6
Table 13: Dimensions in mm (in inch) of the NXS and NXP AC drive, FR7 and FR8, part 2
Drive type H1 H2 H3 H4 H5 H6 H7
0075 2-0114 2
652 632 630 188.5 188.5 23 20
0072 5-0105 5
(25.67) (24.88) (24.80) (7.42) (7.42) (0.91) (0.79)
0041 6-0052 6
0140 2-0205 2
832* - 759 258 265 43 57
0140 5-0205 5
(32.76*) (-) (29.88) (10.16) (10.43) (1.69) (2.24)
0062 6-0100 6
* = The brake resistor terminal box (202.5 mm (7.97 in)) and conduit box (68 mm (2.68 in)) are
not included, see 5.7 Cable installation for illustrations of these.
H5 H2 H2 H3 H4
H1 H6
W1
W3
W2
Ø
Fig. 11: The dimensions of the opening and drive outline with flange, FR7
Table 14: The dimensions in mm (in inch) of the opening and drive outline with flange, FR7
Drive type W1 W2 W3 H1 H2 H3 H4 H5 H6 Ø
0075 2-0114 2
233 175 253 619 188.5 188.5 34.5 32 7 5.5
0072 5-0105 5
(9.17) (6.89) (9.96) (24.4) (7.42) (7.42) (1.36) (1.26) (0.28) (0.22)
0041 6-0052 6
H2
H1
Ø
W1
W2
H3 H4 H4 H5
Fig. 12: The dimensions of the opening and drive outline with flange, FR8
Table 15: The dimensions in mm (in inch) of the opening and drive outline with flange, FR8
Drive type W1 W2 H1 H2 H3 H4 H5 Ø
0140 2-0205 2
301 330 810 832 265 258 33 9
0140 5-0205 5
(11.85) (12.99) (31.89) (32.76) (10.43) (10.16) (1.30) (0.35)
0062 6-0100 6
D1
D2
D3
H4 H2 H4
H7
W5
W1
H5 H3 H3 H3 H5
W4
W3
A B
W2
W4
M5
H6 H1
Table 16: Dimensions in mm (in inch) of the NXS and NXP AC drive, FR9, part 1
Drive type W1 W2 W3 W4 W5 D1 D2 D3 Ø
0261 2-0300 2
530 510 485 200 5.5 362 340 109 21
0261 5-0300 5
(20.87) (20.08) (19.09) (7.87) (0.22) (14.25) (13.39) (4.29) (0.83)
0125 6-0208 6
Table 17: Dimensions in mm (in inch) of the NXS and NXP AC drive, FR9, part 2
Drive type H1 H2 H3 H4 H5 H6 H7
0261 2-0300 2
1312 1150 420 100 35 9 2
0261 5-0300 5
(51.65) (45.28) (16.54) (3.94) (1.38) (0.35) (0.08)
0125 6-0208 6
W2 W3
D1
H1
H2
W1
H3
H4
Fig. 14: Dimensions of the NXS and NXP AC drive, FR10 and FR11
Table 18: Dimensions in mm (in inch) of the NXS and NXP AC drive, FR10 and FR11
Drive type W1 W2 W3 H1 H2 H3 H4 D1
0385 5-0520 5 595 291 131 2018 1900 1435 512 602
0261 6-0416 6 (23.43) (11.46) (5.16) (79.45) (74.8) (56.5) (20.16) (23.70)
0590 5-0730 5 794 390 230 2018 1900 1435 512 602
0460 6-0590 6 (31.26) (15.35) (9.06) (79.45) (74.80) (56.5) (20.16) (23.70)
4.5 COOLING
The AC drive produces heat in operation. The fan moves air and decreases the temperature
of the drive. Make sure that there is sufficiently free space around the drive. Some free space
is also necessary for maintenance.
If many AC drives are installed above each other, the necessary free space is C + D (see Fig.
15 Installation space). You must also make sure that the outlet air from the lower drive goes
to a different direction than the air intake of the top drive.
Make sure that the temperature of the cooling air does not go above the maximum ambient
operating temperature or below the minimum ambient operating temperature of the drive.
B B
A A
A2 A2
D
A B C D A B C D
0048 2-0061 2
30 20 160 80 1.18 0.79 6.30 3.15
0038 5-0061 5
0004 6-0034 6
0075 2-0114 2
80 80 300 100 3.15 3.15 11.81 3.94
0072 5-0105 5
0041 6-0052 6
0140 2-0205 2
80 * 80 300 200 3.15 3.15 11.81 7.87
0140 5-0205 5
0062 6-0100 6
* = To change the fan with the motor cables connected, the necessary clearance on the 2
sides of the drive is 150 mm (5.91 inch).
** = The minimum clearance to change the fan.
0017 2-0031 2
190 112
0016 5-0031 5
0004 6-0013 6
0048 2-0061 2
425 250
0038 5-0061 5
0018 6-0034 6
0075 2-0114 2
425 250
0072 5-0105 5
0041 6-0052 6
0140 2-0205 2
650 383
0140 5-0205 5
0062 6-0100 6
0261 2-0300 2
1300 765
0261 5-0300 5
0125 6-0208 6
B
A
C
Fig. 16: The minimum clearances around the AC drive
A. The minimum distance to the side walls C. Free space in front of the cabinet
or adjacent components
B. The minimum distance from the top of
the cabinet
A B C A B C
Drive type The quantity of cooling air [m3/h] The quantity of cooling air [CFM]
For more information on the power losses based on the switching frequency, see Chapter 11
Appendix 1.
5 POWER CABLING
5.1 CABLE CONNECTIONS
The mains cables are connected to terminals L1, L2 and L3. The motor cables are connected
to terminals U, V and W.
To obey the EMC levels, use a cable entry gland when you install the motor cable at the two
ends. For cable selections in different EMC levels, see Table 23.
L1 U/T1
L2 V/T2
L3 W/T3
B+/R+
B-
R-
Use cables with a minimum heat resistance of +70 °C (158 °F). In the selection of the cables
and the fuses, refer to the nominal output current of the drive. You can find the nominal
output current on the nameplate.
We recommend that you select the cables and the fuses to agree with the output current
because the input current of the AC drive is almost the same as the output current.
For information on how to make the cable installation to obey the UL standards, see Chapter
5.2 UL standards on cabling.
Chapter 5.3 Cable dimensioning and selection shows the minimum dimensions of the Cu-
cables and the related fuse sizes.
If the motor temperature protection of the drive (see Vacon All in One Application Manual) is
used as an overload protection, select the cable to agree with the protection. If 3 or more
cables are used in parallel for larger AC drives, you must use a separate overload protection
for each cable.
These instructions are valid only for processes that have 1 motor and 1 cable connection
from the AC drive to the motor. In other conditions, speak to the manufacturer to get more
information.
1. A power cable for a fixed installation. A cable for the specified mains voltage. A shielded
cable is not necessary. We recommend an NKCABLES/MCMK cable.
2. A symmetrical power cable with a concentric protection wire. A cable for the specified
mains voltage. We recommend an NKCABLES/MCMK cable. See Fig. 18.
3. A symmetrical power cable with a compact low-impedance shield. A cable for the
specified mains voltage. We recommend an NKCABLES /MCCMK, SAB/ÖZCUY-J or
equivalent cable. See Fig. 18. * = For the EMC levels C1 and C2, it is necessary to have a
360º grounding of the shield with cable glands in the motor end.
4. A screened cable with a compact low-impedance shield, for example an NKCABLES/
JAMAK, or an SAB/ÖZCuY-O cable.
For the definitions of EMC protection levels, see Chapter 9.3 The compliance with the product
standard IEC/EN 61800-3 + A1.
A B
In all the frames, to obey the EMC standards, use the default values of the switching
frequencies.
If you installed a safety switch, make sure that the EMC protection continues from the start
of the cables until their ends.
The dimensions of the cables must agree with the requirements of the standard
IEC60364-5-52.
• The cables must be PVC-isolated.
• The maximum ambient temperature is +30 °C (86 °F).
• The maximum temperature of the cable surface is +70 °C (158 °F).
• Use only cables with a concentric copper shield.
• The maximum number of parallel cables is 9.
When you use parallel cables, make sure that you obey the requirements of the cross-
sectional area and the maximum number of cables.
For important information on the requirements of the grounding conductor, see chapter 2.4
Grounding and earth fault protection.
For the correction factors for each temperature, see the standard IEC60364-5-52.
5.3.1 CABLE AND FUSE SIZES FOR 208-240 V AND 380-500 V, FR4 TO FR9
Table 24: The cable and fuse sizes for Vacon® NXS and NXP
Table 24: The cable and fuse sizes for Vacon® NXS and NXP
95–185
FR8 0170 21) 168 200 3*95+50 6–95
Cu/Al
0168 51)
95–185
0205 2 205 250 3*150+70 6–95
Cu/Al
0205 5
95–185
0261 21) 261 315 3*185+95 or 6–95
Cu/Al
0261 51) 2*(3*120+70)
FR9
95–185
0300 21) 300 315 2*(3*120+70) 6–95
Cu/Al
0300 51)
1) = Use cables with a +90 °C (194 °F) heat resistance to obey the UL standards.
Table 25: The cable and fuse sizes for Vacon® NXS and NXP, North America
0003 2—0008 2 AJT10 3*16 AWG + 16 AWG 18 AWG - 4 AWG 18 AWG - 4 AWG
0003 5—0009 5
FR4
0011 2—0012 2 AJT15 3*14 AWG + 14 AWG 18 AWG - 4 AWG 18 AWG - 4 AWG
0012 5
FR5 0025 2 AJT30 3*10 AWG + 10 AWG 18 AWG - 8 AWG 18 AWG - 8 AWG
0022 5
10 AWG - 2/0
0075 2 AJT80 3*4 AWG + 6 AWG 14 AWG - 1 AWG Cu
AWG
0072 5 10 AWG - 1 AWG Al
10 AWG - 2/0
FR7 0088 2 AJT100 3*2 AWG + 6 AWG 14 AWG - 1 AWG Cu
AWG
0087 5 10 AWG - 1 AWG Al
10 AWG - 2/0
0114 2 AJT125 3*2 AWG + 4 AWG 14 AWG - 1 AWG Cu
AWG
0105 5 10 AWG - 1 AWG Al
Table 25: The cable and fuse sizes for Vacon® NXS and NXP, North America
3*350kcmil + 3/0
3/0 AWG - 350kcmil 10 AWG - 3/0
0261 21) AJT300 AWG
Cu/Al AWG
0261 51) 2*(3*250kcmil + 2/0
FR9 AWG)
1) Use cables with a +90 °C (194 °F) heat resistance to obey the UL standards.
Table 26: The cable and fuse sizes for Vacon® NXS and NXP
Table 27: The cable and fuse sizes for Vacon® NXS and NXP, North America
0004 6—0007 6 AJT10 3*14 AWG + 14 AWG 14 AWG - 1 AWG Cu 14 AWG - 2 AWG
10 AWG - 1 AWG Al
0010 6—0013 6 AJT15 3*14 AWG + 14 AWG 14 AWG - 1 AWG Cu 14 AWG - 2 AWG
10 AWG - 1 AWG Al
FR6 0018 6 AJT20 3*12 AWG + 12 AWG 14 AWG - 1 AWG Cu 14 AWG - 2 AWG
10 AWG - 1 AWG Al
0027 6—0034 6 AJT35 3*8 AWG + 8 AWG 14 AWG - 1 AWG Cu 14 AWG - 2 AWG
10 AWG - 1 AWG Al
Table 28: The cable and fuse sizes for Vacon® NXS and NXP
Number of Number of
Fuse Mains, motor and brake
Frame Type IL [A] supply motor
(gG/gL) [A] resistor cable 1) [mm2]
cables cables
Table 29: The cable and fuse sizes for Vacon® NXS and NXP, North America
Number of Number of
Mains, Motor and brake resistor
Frame Type Fuse Class(T/J) supply motor
cable Cu [AWG]
cables cables
FR10 0460 5 AJT500 (3 pcs) Cu: 2*(3*300kcmil + 2/0 AWG) Even/Odd Even/Odd
Al: 2*(3*500kcmil Al + 2/0 Cu AWG)
FR11 0650 5 AJT350 (6 pcs) Cu: 4*(3*AWG3/0 + 1/0 AWG) Even Even/Odd
Al: 4*(3*300kcmil Al + 1 AWG Cu)
Table 30: The cable and fuse sizes for Vacon® NXS and NXP
Number of Number of
Fuse Mains, motor and brake
Frame Type IL [A] supply motor
(gG/gL) [A] resistor cable 1) [mm2]
cables cables
Table 31: The cable and fuse sizes for Vacon® NXS and NXP, North America
Number of Number of
Mains, Motor and brake resistor
Frame Type Fuse Class(T/J) supply motor
cable Cu [AWG]
cables cables
0325 6 AJT400 (3 pcs) Cu: 2*(3*3/0 AWG + 1/0 AWG) Even/Odd Even/Odd
Al: 2*(3*300kcmil Al + 1 AWG Cu)
FR10
FR11 0502 6 AJT600 (3 pcs) Cu: 2*(3*350kcmil + 3/0 AWG) Even/Odd Even/Odd
Al: 2*(3*600kcmil Al + 3/0 AWG Cu)
M M
FR4-9/FR10 FR11*)
Single input Double input*)
Single output Single output
* The FR11 types 0460 6 and 0502 6 have single input terminal.
CAUTION!
If you use a multi-conductor cable, 1 of the conductors of the brake resistor cable
stays unconnected. Cut off the remaining conductor to prevent an accidental
contact with a conducting component.
See Chapter 9.1.5 Brake resistor ratings.
NOTE!
• Before you start, make sure that none of the components of the AC drive is live. Read
carefully the warnings in Chapter 2 Safety.
• Make sure that the motor cables are sufficiently far from other cables.
• The motor cables must go across other cables at an angle of 90°.
• If it is possible, do not put the motor cables in long parallel lines with other cables.
• If the motor cables are in parallel with other cables, obey the minimum distances (see
Table 32 The minimum distances between cables).
• The distances are also valid between the motor cables and the signal cables of other
systems.
• The maximum lengths of shielded motor cables are 300 m (984 ft) (AC drives with power
greater than 1.5 kW or 2 HP), and 100 m (328 ft) (AC drives with power from 0.75 to 1.5
kW or 1 to 2 HP). If the used motor cables are longer than these, speak to the factory to
get more information.
NOTE!
If you use long motor cables (max. 100 m or 328 ft) together with small drives
(≤1.5 kW or ≤2.01 HP), the capacitive current in the motor cable can increase
the measured motor current compared to the actual motor current. Think this
when you set up the motor stall protection functions.
• If the cable insulation checks are necessary, see Chapter 8.4 Measuring the cable and
motor insulation for instructions.
The distance between The length of the The distance between The length of the
cables [m] shielded cable [m] cables [ft] shielded cable [ft]
Table 33: The cable stripping lengths [mm]. See the figure in step 1.
Frame A1 B1 C1 D1 A2 B2 C2 D2
FR4 15 35 10 20 7 50 7 35
FR5 20 40 10 30 20 60 10 40
FR6 20 90 15 60 20 90 15 60
Table 34: The cable stripping lengths [in]. See the figure in step 1.
Frame A1 B1 C1 D1 A2 B2 C2 D2
NOTE!
C2
A1
A2
D1
D2
B1
B2
MAINS MOTOR
FR4
FR5-FR7
6 Put the cable entry plate with the cables into the
groove on the frame of the drive.
FR5
FR6
FR7
0048 2-0061 2
FR6 10 88.5
0038 5-0061 5
0004 6-0034 6
0075 2-0114 2
FR7 10 88.5
0072 5-0105 5
0041 6-0052 6
Table 36: The cable stripping lengths [mm]. See the figure in step 1.
Frame A1 B1 C1 D1 A2 B2 C2 D2
FR8
Table 37: The cable stripping lengths [in]. See the figure in step 1.
Frame A1 B1 C1 D1 A2 B2 C2 D2
FR8
NOTE!
If you want to connect an external brake resistor, see Brake Resistor Manual. See
also Chapter 7.9.7.1 Internal brake resistor connection (P6.7.1).
1 Strip the motor cable, the mains cable, and the
brake resistor cable. Grounding conductor
C1
C2
A1
A2
D1
D2
B1
B2
MAINS MOTOR
FR8
FR9
M5x8
FR8
M5x12
M5x10
FR9
B- B+
R+ R-
NOTE!
FR8
FR9
0261 2-0300 2
FR9 40 354
0261 5-0300 5
0125 6-0208 6
6 CONTROL UNIT
6.1 CONTROL UNIT COMPONENTS
The control unit of the AC drive contains the control board and additional boards (see Fig. 20
Basic and option board connections on the control board) connected to the 5 slot connectors (A
to E) of the control board. The control board is connected to the power unit through a D-
connector or fibre optic cables (FR9).
D
A
E
B
C
Fig. 20: Basic and option board connections on the control board
When you receive the AC drive, the control unit contains the standard control interface. If you
included special options in your order, the AC drive is as in your order. On the next pages,
you can find information on the terminals and general wiring examples. The type code shows
the I/O boards that are installed at the factory. For more information on the option boards,
see Vacon NX option board manual.
It is possible to use the drive with an external power source with these properties: +24 VDC
±10%, minimum 1000 mA. Connect the external power source to one of the 2 bidirectional
terminals (#6 or #12), see Chapter 6.3 Installation of option boards. This voltage is sufficient to
keep the control unit on and for you to set the parameters. The measurements of the main
circuit (for example, the DC link voltage, and the unit temperature) are not available when
the drive is not connected to mains (except with FR9 and larger).
For instructions on how to install the control unit that is not attached to the power unit, see
NXP IP00 Drives Installation Manual.
NOTE!
External
+24V
+ - + - + - + -
#6 #7 #6 #7 #6 #7 #6 #7
Nm lb-in.
Reference potentiometer,
1-10kΩ Standard I/O board
Terminal Signal Description
1 +10Vref Reference voltage Maximum current 10 mA
Selection V/mA with jumper block X1 (*)
Analogue input,
2 AI1+ 0...+10 V (Ri = 200 kΩ)
voltage or current (-10V...+10V Joystick ctrl, sel. with jumper)
0-20 mA (Ri =250 Ω)
OPTA2
OPTA3
28 TI1+
Thermistor input
29 TI1-
Fig. 23: The control terminal signals on relay boards OPTA2 and OPTA3
6.2.2.1 Digital input signal inversions
The active signal level is different when the common inputs CMA and CMB (terminals 11 and
17) are connected to +24 V or to ground (0 V). See Fig. 24.
The 24 V control voltage and the ground for the digital inputs and the common inputs (CMA,
CMB) can be internal or external.
A B
+24V GND
DIN1 DIN1
DIN2 DIN2
DIN3 DIN3
GND +24V
CMA CMA
X2
X1
X3
X3
AI1 mode: 0...20mA; Current input AI1 mode: 0...20mA; Current input
A B C D A B C D
A B C D A B C D
AI1 mode: Voltage input; 0...10V AI2 mode: Voltage input; 0...10V
differential differential
A B C D A B C D
AI1 mode: Voltage input; -0...10V AI2 mode: Voltage input; -10...10V
NOTE!
If you change the AI/AO signal contents, also change the related board parameter
in menu M7.
DO1 Digital
input
RI1/1
RO1/2
RO1/3
RO2/1
RO2/2
RO2/3 U V W
TI1+
TI1-
7 CONTROL PANEL
The control panel is the interface between the AC drive and the user. With the control panel,
you can control the speed of a motor and monitor the status of the AC drive. You can also set
the parameters of the AC drive.
You can remove the control panel from the AC drive. The control panel is isolated from the
input line potential.
A B C A B C
L
L
ready run fault ready run fault
START K
K D
D
reset reset
STOP E
E J
J
F
F
select enter select enter
I H G I H G
7.2 DISPLAY
The drive status indicators (A-G) gives you information about the status of the motor and the
AC drive.
The control place indications (H, I, J) show the selection of the control place. The control
place tells from where the START/STOP commands are given and reference values are
changed. To make this selection, go to the Keypad control menu (M3) (see Chapter 7.6 Using
the Keypad control menu (M3)).
The three text lines (K, L, M) give information about your location in the menu structure and
the operation of the drive.
A B C D E F G
L H I J
RUN READY
A
M1 Keypad
B
Monitor
C
V1V1
Fig. 30: The navigation items on the control panel
A. The location on the menu C. The number of items that are available
B. The description (name of the page) or the item value.
V1.3 Motor speed rpm 2 The actual speed of the motor in rpm
V1.8 DC link voltage V 7 The measured voltage in the DC-link of the drive
* If the AC drive only has +24V supply (for control board power-up), this value is not reliable.
See All-in-One Application Manual for more monitoring values.
Monitor
V1V14
2 To go to the Monitoring menu from the Main menu,
RUN READY
push the Menu button Right.
Keypad
Output frequency
13.95 Hz
3 To scroll through the menu, push the Browser
RUN READY
buttons Up and Down.
Keypad
FreqReference
13.95 Hz
Parameters
G1G8
2 Push the Menu button Right to move into the
READY
Parameter Group Menu (G#).
Keypad
Input signals
G1G8
Input signals
P1P18
4 Use the Browser buttons Up and Down to find the
READY
parameter (P#) you want to edit. When you are in
the last parameter of a parameter group, push the Keypad
Browser button Up to move directly to the first
parameter of that group. Min Frequency
13.95 Hz
Min Frequency
13.95 Hz
2 To go to the Edit mode, push the Menu button
READY
Right. The parameter value starts to blink.
Keypad
Min Frequency
13.95 Hz
3 Set the new value with the Browser buttons Up and
Down.
NOTE!
Min Frequency
The value does not change if you do not
push the Enter button. 14.45 Hz
Min Frequency
13.95 Hz
2 To go to the Edit mode, push the Menu button
READY
Right. The parameter value starts to blink.
Keypad
Min Frequency
13.95 Hz
3 Push the Menu button Right. You can now edit the
value digit by digit.
4 To accept the change, push the Enter button. The
READY
value stops to blink and the new value shows in the
value field. P2.1.1 Keypad
NOTE!
Min Frequency
The value does not change if you do not
push the Enter button. 14.45 Hz
When the drive is in RUN state, many parameters are locked, and you cannot edit them. If
you try to change the value of such a parameter, the text *Locked* shows on the display. You
must stop the AC drive to edit these parameters. To lock parameter values, use the function
in menu M6 (See Chapter 7.9.5.2 Parameter lock (P6.5.2)).
The basic application package "All in One+" includes 7 applications with different sets of
parameters. For more information, see All-in-one Application Manual.
display.
Keypad control
2 To go to the Keypad control menu from the
Main menu, push the Menu button Right. P1P4
1 = I/0 terminal
P3.1 Control place 1 3 1 125
2 = Keypad
3 = Fieldbus
0 = Limited func-
R3.4 Stop button 0 1 1 114 tion of Stop button
1 = Stop button
always enabled
Fieldbus Bus/Comm
Control Place
I/O Terminal
2 To go to the edit mode, push the Menu button Right.
STOP READY
I/O term
Control Place
I/O Remote
3 To scroll through the options, push the Browser
STOP READY
buttons Up and Down.
I/O term
Control Place
Keypad control
4 To select the control place, push the Enter button.
STOP READY
Keypad
Control Place
Keypad
For more information on how to control the motor with the keypad, see Chapters
7.1 Control keypad and 8.2 Commissioning of the drive.
If you are in other menu than M3, the special functions are not available. In other
menu than M3, when the keypad is not the active control place and you push the
start button, you get an error message Keypad Control NOT ACTIVE.
COPYING THE FREQUENCY REFERENCE SET FROM I/O OR FIELDBUS TO THE CONTROL
PANEL
1 Keep the Enter button pushed down for 3 seconds.
Active faults
F0
For more information on the fault types and how to reset faults, see Chapter 10 Fault tracing.
For the fault codes, possible causes and information on how to correct the fault, see Chapter
10.2 Fault codes.
Description Type
T.8 DC voltage V
T.11 Direction
T.12 Warnings
T.13 0-speed*
T.14 Subcode
T.15 Module
T.16 Submodule
* Tells if the drive was at zero speed (< 0.01 Hz) when the fault showed.
If real time is set on the AC drive, the data items T1 and T2 show as follows:
Description Type
11 Output phase
T1T16
2 Push the Menu button Right.
STOP FAULT
I/O term
Operation days
17
3 Scroll the data T.1-T.13 with the Browser buttons.
STOP FAULT
I/O term
Operation hours
34:21:05
Basic application
Standard application
Basic
Application selec- Local/Remote control appl.
S6.2 applica-
tion Multi-Step application
tion
PID Control application
Multi-Purpose Control appl.
Pump and Fan Control appl.
Store set 1
Load set 1
S6.3.1 Parameter sets
Store set 2
Load set 2
Load factory defaults
Parameter
P6.3.4 Yes Yes
backup
No
Compare parame-
S6.4
ters
S6.5 Security
Change
P6.5.2 Parameter lock Change Enabled
Enabled
Change Disabled
Multimonitoring
S6.5.4 Change Enabled
items
Change Disabled
Default page/
P6.6.2
Operating menu
P6.6.4 Contrast 0 31 18
Continuous
Continu-
P6.7.2 Fan control Temperature
ous
First start
Calc temp
HMI acknowledg.
P6.7.3 200 5000 ms 200
timeout
HMI number of
P6.7.4 1 10 5
retries
Connec-
P6.7.5 Sine filter Not connected
ted
Connected
System informa-
S6.8
tion
Power On day
C6.8.1.2
counte
Operating days
T6.8.2.3
trip counter
Clear operating
T6.8.2.5
time counter
System software
S6.8.3.2
version
Firmware inter-
S6.8.3.3
face
S6.8.4 Applications
Name of applica-
S6.8.4.#
tion
D6.8.4.#.
Application ID
1
Applications:
D6.8.4.#.
Firmware inter-
3
face
S6.8.5 Hardware
Language
English
2 To go to the edit mode, push the Menu button Right.
READY
The name of the language starts to blink.
I/O term
Language
English
3 To select the language for the control panel texts,
use the Menu buttons Up and Down.
4 To accept the selection, push the Enter button. The
READY
name of the languages stops to blink and all text
information on the control panel shows in the I/O term
Application
Standard
2 Push the Menu button Right.
3 To go to the edit mode, push the Menu button Right.
STOP READY
The name of the application starts to blink.
I/O term
Application
Standard
4 Scroll through the applications with the Browser
buttons and select a different application.
5 To accept the selection, push the Enter button. The
STOP READY
AC drive starts again and goes through the setup.
I/O term
Application
Multi-step
6 When the display shows the question 'Copy
parameters?', you have 2 options:
I/O term
Parameter sets
Select
3 To go to the edit mode, push the Menu button Right.
READY
The text LoadFactDef starts to blink.
I/O term
Parameter sets
LoadFactDef
4 You have 5 options to select from:
I/O term
Parameter sets
Wait...
I/O term
Parameter sets
OK
I/O term
Up to keypad
Select
3 To go to the edit mode, push the Menu button Right.
READY
All param. starts to blink.
I/O term
Up to keypad
All param.
4 To accept the selection, push the Enter button.
READY
I/O term
Up to keypad
Wait...
5 Wait until 'OK' shows on the display.
READY
I/O term
Up to keypad
OK
• All parameters
• All parameters but the motor nominal value
parameters (All. no motor)
• Application parameters
5 To accept the selection, push the Enter button.
6 Wait until 'OK' shows on the display.
NOTE!
When you change the application, the parameters in the parameter settings on
page S6.3.1 are deleted. To copy parameters from one application to a different
application, you must first upload them to the control panel.
ParamComparison
C1C3
2 Push the Menu button Right.
READY
The actual parameter values are first compared to
those of the customised parameter Set 1. If no I/O term
I/O term
Set1
P1P6
3 To compare the values to a different set, use the
Browser buttons.
4 To go to the page with the parameter values, push
READY
the Menu button Right. In the display that opens,
the value on the Description line (A) is the value of I/O term
the selected set and the value on the value line (B) A
is the actual value. P2.1.2=50.0
B 20.0 Hz
5 To go to the edit mode, push the Menu button Right.
READY
The actual value starts to blink.
I/O term
P2.1.2=50.0
20.0 Hz
6 To change the actual value, use the Browser
buttons, or change the value digit by digit with the
Menu button Right.
7.9.5 SECURITY
NOTE!
display.
Security
2 To go to the Security submenu from the
System menu, push the Menu button Right. P1P4
SETTING A PASSWORD
1 In Security submenu, push the Menu button Right.
READY
I/O term
Password
Not in use
2 To go to the edit mode, push the Menu button Right.
READY
The display shows '0' that blinks.
I/O term
Password
0
3 You have 2 options to set a password: with the
READY
Browser buttons or by digits. The password can be
a number between 1 and 65535. I/O term
Password
00
Keep the password in a safe location! You cannot change the password if you do not
first give a valid password.
ENTERING A PASSWORD
When you have set the password and try to go to a submenu that has password protection,
the display shows 'Password?'
1 When the display shows 'Password?', give the
password with the Browser buttons.
NOTE!
LOCKING A PARAMETER
1 In the Security menu (M6), find the Parameter lock
READY
(P6.5.2) with the Browser buttons.
I/O term
Parameter Lock
ChangeEnable
2 To go to the edit mode, push the Menu button Right.
READY
I/O term
Parameter Lock
ChangeEnable
3 To change the parameter lock status, use the
READY
Browser buttons.
I/O term
Parameter Lock
ChangeDisabl
4 To accept the change, push the Enter button.
7.9.5.3 Start-up wizard (P6.5.3)
The Startup wizard helps in the commissioning of the AC drive. By default, the Startup wizard
is active. In the Startup wizard, you set this information:
• the language
• the application
• the values for a set of parameters that are same to all applications
• the values for a set of application-specific parameters
Action Button
I/O term
Startup wizard
No
2 To go to the edit mode, push the Menu button Right.
READY
I/O term
Startup wizard
No
3
• To activate the Startup wizard, select Yes with READY
the Browser buttons.
• To deactivate the Startup wizard, select No with I/O term
Multimon. items
ChangeEnable
Multimon. items
ChangeEnable
3 Use Browser buttons Up and Down to select
READY
Change Enabled or Change Disabled.
I/O term
Multimon. items
ChangeDisable
4 Accept the selection with the Enter button.
Default page
0.
2 To go to the edit mode, push the Menu button Right.
READY
I/O term
Default page
0.
3 To change the number of the Main menu, use the
READY
Browser buttons.
I/O term
Default page
1.
4 To edit the number of the submenu/page, push the
Menu button Right. Change the number of the
submenu/page with the Browser buttons.
5 To edit the third level page number, push the Menu
button Right. Change the number of the third level
page with the Browser buttons.
6 To accept the new default page value, push the
Enter button.
7.9.6.2 Default page in the Operating menu (P6.6.2)
In this submenu, you can set the default page in the Operating menu. The display
automatically moves to the set page after the Timeout time (see Chapter 7.9.6.3 Timeout time
(P6.6.3)) or after you set the control panel on. For instructions, see Chapter 7.9.6.1 Default
page (P6.6.1).
NOTE!
Timeout time
90 s
2 To go to the Edit mode, push the Menu button
READY
Right.
I/O term
Timeout time
90 s.
3 To set the timeout time, use the Browser buttons.
READY
I/O term
Timeout time
60 s.
4 To accept the change, push the Enter button.
NOTE!
If the Default page value is 0, the Timeout time setting has no effect.
In the Hardware settings submenu (S6.7) in the System menu you can control these functions
of the hardware in your AC drive:
InternBrakeRes
Connected
2 To go to the edit mode, push the Menu button Right.
READY
I/O term
InternBrakeRes
Connected
InternBrakeRes
Not conn.
4 To accept the change, push the Enter button.
NOTE!
The brake resistor is available as optional equipment for all sizes. It can be
installed internally in frames FR4 to FR6.
7.9.7.2 Fan control (P6.7.2)
Use this function to control the cooling fan of the AC drive. You have 4 options to select from:
• Continuous (default setting). The fan is always on when the power is on.
• Temperature. The fan starts automatically when the heat sink temperature goes to 60 °C
(140 °F) or when the AC drive operates.
The fan stops about a minute after one of these:
• the heat sink temperature falls to 55 °C (131 °F)
• the AC drive stops
• the Fan control value is changed from Continuous to Temperature
• First start. When power is on, the fan is in the stop state. When the AC drive gets the first
start command, the fan starts.
• Calc temp. The fan function agrees to the calculated IGBT temperature:
• If the IGBT temperature is more than 40 °C (104 °F), the fan starts.
• If the IGBT temperature is below 30°C (86 °F), the fan stops.
NOTE!
As the default temperature at power-up is 25 °C (77 °F), the fan does not
start immediately.
Fan control
Continuous
Fan control
Continuous
3 To select the fan mode, use the Browser buttons.
READY
I/O term
Fan control
Temperature
4 To accept the change, push the Enter button.
7.9.7.3 HMI acknowledge timeout (P6.7.3)
Use this function to change the timeout of the HMI acknowledgement time. Use this when
there is more delay in the RS-232 transmission, for example, when modems are used for
communication over longer distances.
NOTE!
Do not change the default values of parameters 6.7.3 and 6.7.4 (200 and 5) if the AC
drive is connected to the PC with a cable. If the AC drive is connected to the PC with
a modem and the messages are transferred with a delay, set the values for
parameter 6.7.3 to agree these delays. For example, if the transfer delay between
the AC drive and the PC is 600 ms, make these settings:
Example:
• Set the value of parameter 6.7.3 to 1200 ms (2 x 600, sending delay + receiving
delay)
• Set the [Misc]-part of the file NCDrive.ini to agree with the settings:
• Retries = 5
• AckTimeOut = 1200
• TimeOut = 6000
Do not use intervals shorter than the AckTimeOut-time in the NC-Drive monitoring.
I/O term
NOTE!
The Power On time counter (days and hours) counts always, when the power is on.
Power On day counter Value on display is 1.013. The drive has operated for 1 year
C6.8.1.2.
and 13 days.
Power On hour counter Value on display is 7:05:16. The drive has operated for 7 hours
C6.8.1.3
5 minutes and 16 seconds.
NOTE!
The trip counters count only when the motor is in RUN state.
Page Counter
Trip counters
T1T5
2 To go to the Clear MWh counter page (6.8.2.2) or to
STOP READY
the Clear Operation time counter page (6.8.2.5), use
the Menu button Right. I/O term
I/O term
I/O term
I/O term
Page Content
Page Content
6.8.4.#.1 Application ID
6.8.4.#.2 Version
Applications
A1A7
Basic
D1D3
3 To select the application, use the Browser buttons.
READY
There are as many pages as there are applications
on the AC drive. I/O term
Standard
D1D3
4 To go to the Information pages, use the Menu
READY
button Right.
I/O term
Application id
ASFIFF01
5 To see the different pages, use the Browser
READY
buttons.
I/O term
Version
2.01
7.9.8.5 Hardware (S6.8.5)
The Hardware information page includes information on the AC drive hardware.
Page Content
Expander boards
E1E5
2 To go to the Expander boards page, push the Menu
READY
button Right.
I/O term
A:NXOPTA1
E1E2
3 To select the board, use the Browser buttons.
READY
If no board is connected to the slot, the display
shows 'no board'. If a board is connected to a slot I/O term
State
Run
5 To see the program version of the board, push the
READY
Browser button Up or Down.
I/O term
Software version
10001.0
For more information on the parameters of the expander boards, see Chapter 7.10 Using the
Expander board menu (M7).
7.9.8.7 Debug menu (S6.8.7)
The Debug menu is for advanced users and application designers. Speak to the factory to get
instructions, if it is necessary.
1 = 0-20 mA
2 = 4-20 mA
P7.1.1.1 AI1 mode 1 5 3
3 = 0-10 V
4 = 2-10 V
5 = –10…+10 V
1 = 0-20 mA
P7.1.1.3 AO1 mode 1 4 1 2 = 4-20 mA
3 = 0-10 V
4 = 2-10 V
Expander boards
G1G5
2 To go to the Expander board menu from the Main
READY
menu, push the Menu button Right.
I/O term
C:NXOPTC5
G1G2
3 To examine the list of connected expander boards,
READY
use the Browser buttons Up and Down.
I/O term
D:NXOPTC2
G1G2
Parameters
P1P4
C:NXOPTC5
G1G2
2 To see the information on the expander board, push
READY
the Menu button Right.
I/O term
Monitor
V1V2
3 To scroll to the Parameters use the Browser
READY
buttons Up and Down.
I/O term
Parameters
P1P4
4 To examine the list of parameters, push the Menu
READY
button Right.
I/O term
Slave address
126
Baud rate
Auto
6 To go to the edit mode, push the Menu button Right.
READY
For instructions on how to edit the parameter
values, see Chapter 7.5 Using the Parameter menu I/O term
(M2).
Slave address
126
WARNING!
Do not touch the internal components or the circuit boards of the drive when the
drive is connected to mains. These components are live. A contact with this voltage
is very dangerous. The galvanically isolated control terminals are not live.
WARNING!
Do not touch the motor cable terminals U, V, W or the brake resistor terminals
when the drive is connected to mains. These terminals are live when the drive is
connected to mains, also when the motor does not operate.
WARNING!
To do work on the connections of the drive, disconnect the drive from mains. Wait 5
minutes before you open the cover of the drive. Then use a measuring device to
make sure that there is no voltage. The connections of the drive are live 5 minutes
after it is disconnected from mains.
WARNING!
Do not touch the relay board terminals or other I/O board terminals than the
control terminals. They can have a dangerous voltage also when the drive is
disconnected from mains.
WARNING!
Before you connect the drive to mains, make sure that the front cover and the cable
cover of the drive are closed. The connections of the AC drive are live when the
drive is connected to mains.
WARNING!
Do not touch the side of the AC drive FR8 with hands when it operates. The surface
is hot.
WARNING!
Do not install the AC drive FR6 on a surface that is not fireproof. When the AC drive
FR6 operates, the rear surface of the drive is hot.
1. Turn the supply voltage off and wait until the drive stops. See Chapter 8.2 Commissioning
of the drive, step 5.
2. Connect the motor cable to the motor and to the motor cable terminals of the frequency
converter.
3. Make sure that all Start/Stop switches are in Stop positions.
4. Turn the mains switch ON.
5. Do again the Run test A or B, see Chapter 8.3.2 The Run test without the motor.
• Before you do the tests, make sure that it is safe to do each test before you do it.
• Make sure that the other workers near you know that you do the tests.
• Do the Run test A or B, see Chapter 8.3.2 The Run test without the motor.
WARNING!
Before you connect the AC drive to mains, make sure that the EMC level of the drive
is correct. An incorrect EMC level can cause damage to the drive.
FR4
FR5
FR6
Only an authorized Vacon service person can change the EMC level of FR7 back to
C2.
8.6 MAINTENANCE
In normal conditions, Vacon NX AC drives are maintenance-free. To make sure that the drive
operates correctly and has a long life, we recommend that you do regular maintenance.
Refer to the table for maintenance intervals.
Table 53: The power ratings of Vacon® NX AC drives in mains voltage 208-240V, 50/60 Hz, 3~
FR4 0003* 3.7 4.1 2.4 3.6 4.8 0.55 0.37 0.75
FR9 0261 261.0 287.0 205.0 308.0 349.0 75.0 55.0 100 75
0300 300.0 330.0 245.0 368.0 444.0 90.0 75.0 125 100
NOTE!
The currents in given ambient temperatures (in 9.2 Vacon® NXS and NXP -
technical data) are achieved only when the switching frequency is the same or
smaller than the factory default.
Table 54: The power ratings of Vacon® NX AC drive in mains voltage 380-500V, 50/60 Hz, 3~
FR4 0003 3.3 3.6 2.2 3.3 4.4 1.1 0.75 1.5 1.0 2 1
0004 4.3 4.7 3.3 5.0 6.2 1.5 1.1 2.2 1.5 3 2
0005 5.6 6.2 4.3 6.5 8.6 2.2 1.5 3.0 2.2 4 3
0007 7.6 8.4 5.6 8.4 10.8 3.0 2.2 4.0 3.0 5 4
0009 9.0 9.9 7.6 11.4 14.0 4.0 3.0 5.5 4.0 7.4 5
0012 12.0 13.2 9.0 13.5 18.0 5.5 4.0 7.5 5.5 10 7.4
FR5 0016 16.0 17.6 12.0 18.0 24.0 7.5 5.5 11.0 7.5 15 10
0023 23.0 25.3 16.0 24.0 32.0 11.0 7.5 15.0 11.0 20 15
0031 31.0 34.0 23.0 35.0 46.0 15.0 11.0 18.5 15.0 25 20
FR6 0038 38.0 42.0 31.0 47.0 62.0 18.5 15.0 22.0 18.5 29.4 25
0046 46.0 51.0 38.0 57.0 76.0 22.0 18.5 30.0 22.0 40 29.4
0061 61.0 67.0 46.0 69.0 92.0 30.0 22.0 37.0 30.0 50 40
FR7 0072 72.0 79.0 61.0 92.0 122.0 37.0 30.0 45.0 37.0 60 50
0087 87.0 96.0 72.0 108.0 144.0 45.0 37.0 55.0 45.0 74 60
0105 105.0 116.0 87.0 131.0 174.0 55.0 45.0 75.0 55.0 101 74
FR8 0140 140.0 154.0 105.0 158.0 210.0 75.0 55.0 90.0 75.0 121 101
0168 170.0 187.0 140.0 210.0 280.0 90.0 75.0 110.0 90.0 147 121
0205 205.0 226.0 170.0 255.0 336.0 110.0 90.0 132.0 110.0 177 147
FR9 0261 261.0 287.1 205.0 308.0 349.0 132.0 110.0 160.0 132.0 214 177
0300 300.0 330.0 245.0 368.0 444.0 160.0 132.0 200.0 160.0 268 214
FR10 0385 385.0 424.0 300.0 450.0 540.0 200.0 160.0 250.0 200.0 335 268
0460 460.0 506.0 385.0 578.0 693.0 250.0 200.0 315.0 250.0 422 335
0520 520.0 576.0 460.0 690.0 828.0 250.0 250.0 355.0 315.0 476 422
Table 54: The power ratings of Vacon® NX AC drive in mains voltage 380-500V, 50/60 Hz, 3~
FR11 0590 590.0 649.0 520.0 780.0 936.0 315.0 250.0 400.0 355.0 536 476
0650 650.0 715.0 590.0 885.0 1062.0 355.0 315.0 450.0 400.0 603 536
0730 730.0 803.0 650.0 975.0 1170.0 400.0 355.0 500.0 450.0 670 603
NOTE!
The currents in given ambient temperatures (in 9.2 Vacon® NXS and NXP -
technical data) are achieved only when the switching frequency is the same or
smaller than the factory default.
The currents for FR10 to FR11 are valid at an ambient temperature of 40°C (104 °F) (except
for 0520 5: currents are valid at an ambient temperature of 35°C (95 °F)).
Table 55: The power ratings of Vacon® NX AC drive in mains voltage 500-690 V, 50/60 Hz, 3~
FR9 0125 125.0 138.0 100.0 150.0 200.0 110.0 90.0 125 100
0144 144.0 158.0 125.0 188.0 213.0 132.0 110.0 150 125
0170 170.0 187.0 144.0 216.0 245.0 160.0 132.0 150 150
0208 208.0 229.0 170.0 255.0 289.0 200.0 160.0 200 150
FR10 0261 261.0 287.0 208.0 312.0 375.0 250.0 200.0 250 200
0325 325.0 358.0 261.0 392.0 470.0 315.0 250.0 300 250
0385 385.0 424.0 325.0 488.0 585.0 355.0 315.0 400 300
0416 416.0 358.0 325.0 488.0 585.0 400.0 315.0 450 300
Table 55: The power ratings of Vacon® NX AC drive in mains voltage 500-690 V, 50/60 Hz, 3~
FR11 0460 460.0 506.0 385.0 578.0 693.0 450.0 355.0 450 400
0502 502.0 552.0 460.0 690.0 828.0 500.0 450.0 500 450
0590 590.0 649.0 502.0 753.0 904.0 560.0 500.0 600 500
NOTE!
The currents in given ambient temperatures (in 9.2 Vacon® NXS and NXP -
technical data) are achieved only when the switching frequency is the same or
smaller than the factory default.
The currents for FR10 to FR11 are valid at an ambient temperature of 40°C (104 °F) (except
for 0416 6 and 0590 6: currents are valid at an ambient temperature of 35°C (95 °F)).
IL*110% IL*110%
IL
1 min 9 min
t
Fig. 32: Low overload
The high overload means that if 150% of the continuous current (IH) is necessary for 1
minute each 10 minutes, the remaining 9 minutes must be approximately 92% of IH or less.
This is to make sure that the output current is not more than IH during the duty cycle.
I I
H*150% H*150%
I
H
1 min 9 min
Table 56: Brake resistor ratings for Vacon NX AC drives , mains voltage
208-240V
Mains voltage 208-240 V, 50/60 Hz, 3~
0003 15 30
0004 15 30
0007 15 30
0008 15 30
0011 15 30
0017 15 30
0025 15 30
0031 23 20
0048 46 10
0061 46 10
Table 57: Brake resistor ratings for Vacon NX AC drives, mains voltage
380-500V
Mains voltage 380-500 V, 50/60 Hz, 3~
0003 12 63
0004 12 63
0005 12 63
0007 12 63
0009 12 63
0012 12 63
0016 12 63
0022 12 63
0031 17 42
0038 35 21
0045 35 21
0061 51 14
Table 58: Brake resistor ratings for Vacon NX AC drives, mains voltage
500-690V
Mains voltage 500-690 V, 50/60 Hz, 3~
0004 11 100
0005 11 100
0007 11 100
0010 11 100
0013 11 100
0018 36.7 30
0022 36.7 30
0027 36.7 30
0034 36.7 30
0041 61.1 18
0052 61.1 18
0062 122.2 9
0080 122.2 9
0100 122.2 9
0125 157.1 7
0144 157.1 7
0170 157.1 7
0208 157.1 7
Table 59: The technical data of the Vacon® NXS and NXP AC drive
Mains
• Mains types: TN, TT, and IT
• Short circuit current: the maximum short circuit
current must be < 100 kA.
Table 59: The technical data of the Vacon® NXS and NXP AC drive
Table 59: The technical data of the Vacon® NXS and NXP AC drive
Altitude
100% load capacity (no derating) up to 1000 m (3281 ft)
1% derating for each 100 m (328 ft) above 1000 m
(3281 ft)
Maximum altitudes:
• 208-240 V: 3000 m (9843 ft)
• 380-400 V: 3000 m (9843 ft)(TN and IT systems)
• 415-500 V: 2000 m (6562 ft)
• 500-690 V: 2000 m (6562 ft)
Table 59: The technical data of the Vacon® NXS and NXP AC drive
Vibration 5-150 Hz
IEC/EN 60068-2-6 Displacement amplitude 1 mm (peak) at 5-15.8 Hz
IEC/EN 61800-5-1 (FR4-FR9)
Maximum acceleration amplitude 1 G at 15.8-150 Hz
(FR4-FR9)
Displacement amplitude 0.25 mm (peak) at 5-31 Hz
(FR10-FR11)
Maximum acceleration amplitude 0.25G at 31-150 Hz
(FR10-FR11)
Enclosure class
IP21 (UL Type 1) standard in entire kW/HP range
IP54 (UL Type 12) option in FR4 to FR10
NOTE!
For IP54 (UL Type 12), a keypad is necessary.
Average noise level (cool- The sound pressure depends on the cooling fan speed,
ing fan) in dB(A) which is controlled in accordance with the drive tem-
perature.
Table 59: The technical data of the Vacon® NXS and NXP AC drive
Auxiliary voltage
+24 V, ±10%, max volt. ripple < 100 mVrms; max. 250
mA
Dimensioning: max. 1000 mA/control box (power
Control connections
backup)
(apply to boards OPTA1,
OPTA2 and OPTA3)
Output reference voltage +10 V, +3%, max. load 10 mA
Relay outputs
2 programmable change-over relay outputs
Switching capacity (resistive): 24 VDC/8 A, 250 VAC/8
A, 125 VDC/0.4 A
Min.switching load: 5 V/10 mA
Table 59: The technical data of the Vacon® NXS and NXP AC drive
Earth fault protection If there is an earth fault in the motor or motor cable,
only the AC drive is protected.
Motor overload protection Yes. * The motor overload protection activates at 110%
of the full load current.
* = For the motor thermal memory and the memory retention function to obey the UL 508C
requirements, you must use the system software version NXS00001V175, NXS00002V177 or
NXP00002V186 or a newer version. If you use an older system software version, you must
install a motor overtemperature protection to obey the UL regulations.
Table 60: The equivalents of the product standard IEC/EN 61800-3 + A1 in Vacon classes
C1 C
C2 H
C3 L
CATEGORY C1
NOTE!
If the protection class of the AC drive is IP21 (UL Type 1), only the conducted
emissions are in the requirements of category C1.
CATEGORY C2
CATEGORY C3
Available for IP21 (UL Type 1) and IP54 (UL Type 12) in 380-500 V FR10 and larger, 500-690 V
FR6 and larger.
The category C3 includes AC drives that have the nominal voltage of less than 1000 V. These
AC drives are used in the 2nd environment only.
CATEGORY C4
NOTE!
If the AC drives are used with other supplies, they do not obey the EMC
requirements.
To change the EMC protection category of your Vacon NX AC drive from C2 or C3 to C4, see
the instructions in Chapter 8.5 Installation in an IT system.
In IP00.
The AC drives of this category do not give EMC emission protection. These drives are
installed in enclosures.
NOTE!
10 FAULT TRACING
When the control diagnostics of the AC drive find an unusual condition in the operation of the
drive, the drive shows this information:
• This information shows on the display (see 7.7 Using the Active faults menu (M4)):
• the location indication F1
• the fault code (see Chapter 10.2 Fault codes)
• a short description of the fault
• the fault type symbol (see )
• the FAULT or ALARM symbol
• The red LED on the keypad starts to blink (only when a fault shows).
If many faults show at the same time, you can examine the list of active faults with the
Browser buttons.
In the NX AC drives, there are 4 different types of faults.
The type A fault (Alarm) tells you about unusual operation on the drive. It does not
A (Alarm)
stop the drive. The 'A fault' stays in the display for about 30 seconds.
The type 'F fault' stops the drive. To start the drive again, you must find a solution to
F (Fault)
the problem.
The type 'AR fault' stops the drive. The fault is reset automatically and the drive tries
AR (Fault Autoreset) to start the motor again. If it cannot the start the motor again, a fault trip (FT, see
below) shows.
If the drive cannot start the motor after an AR fault, an FT fault shows. The type 'FT
FT (Fault Trip)
fault' stops the AC drive.
The fault stays active until it is reset, see Chapter 10.1 Resetting a fault. The memory of active
faults can keep the maximum of 10 faults in the order in which they were shown.
Reset the fault with the Reset button on the keypad, or through the control terminal, fieldbus
or the PC tool. The faults stay in the Fault history where you can go and examine them. See
the different fault codes in Chapter 10.2 Fault codes.
Before you ask help from the distributor or the factory because of unusual operation,
prepare some data. Write down all the texts on the display, the fault code, the source
information, the Active Faults list and the Fault History.
Fault Subcode in
Fault Possible cause How to correct the fault
code T.14
2 Overvoltage S1 = Hard- The DC-link voltage is Set the deceleration time longer.
ware trip higher than the limits. Use the brake chopper or the brake
resistor. They are available as
S2 = Over- options. Activate the overvoltage
voltage • too short a decelera- controller. Do a check of the input
control tion time voltage.
supervision • high overvoltage spikes
in the supply
• Start/Stop sequence
too fast
3* Earth fault The measurement of cur- Do a check of the motor cables and
rent tells that the sum of the the motor.
motor phase current is not
zero.
• an insulation malfunc-
tion in the cables or the
motor
5 Charging switch The charging switch is open, Reset the fault and start the drive
when the START command again. If the fault shows again, ask
is given. instructions from the distributor
near to you.
• operation malfunction
• defective component
6 Emergency stop Stop signal has been given Do a check of the emergency stop
from the option board. circuit.
Fault Subcode in
Fault Possible cause How to correct the fault
code T.14
S3 =
Reserved
S4 =
Reserved
S5 =
Reserved
S6 =
Reserved
S7 =
Charging
switch
S8 = No
power to
driver card
S9 = Power
unit com-
munication
(TX)
S10 =
Power unit
communi-
cation
(Trip)
S11 =
Power unit
comm.
(Measure-
ment)
9* Undervoltage S1 = DC- The DC-link voltage is lower If there is a temporary supply volt-
link too low than the limits. age break, reset the fault and start
during run the drive again. Do a check of the
supply voltage. If the supply voltage
S2 = No • too low a supply volt- is sufficient, there is an internal
data from age fault. Ask instructions from the dis-
power unit • AC drive internal fault tributor near to you.
• a defective input fuse
S3 = • the external charge
Undervolt- switch is not closed
age control
supervision
Fault Subcode in
Fault Possible cause How to correct the fault
code T.14
10 * Input line supervi- The input line phase is Do a check of the supply voltage,
sion missing. the fuses and supply cable.
11 * Output phase The measurement of cur- Do a check of the motor cable and
supervision rent tells that there is no the motor.
current in 1 motor phase.
15 * Motor stalled The motor stalled. Do a check of the motor and the
load.
16 * Motor overtemper- There is too heavy a load on Decrease the motor load. If there is
ature the motor. no motor overload, do a check of
the temperature model parame-
ters.
18 ** Unbalance S1 = Cur- Unbalance between power If the fault occurs again, ask
rent unbal- modules in parallelled instructions from the distributor
ance power units. near to you.
S2 = DC
voltage
unbalance
22 EEPROM check- Parameter save fault. If the fault occurs again, ask
sum fault instructions from the distributor
near to you.
• operation malfunction
• defective component
Fault Subcode in
Fault Possible cause How to correct the fault
code T.14
26 Start-up prevented Start-up of the drive has Cancel prevention of start-up if this
been prevented. Run can be done safely. Remove Run
request in ON when new request
application is downloaded to
the drive.
30 Safe disable The input on OPTAF board Cancel Safe Disable if this can be
has opened, done safely.
32 Fan cooling Cooling fan of the AC drive Ask instructions from the distribu-
does not start, when ON tor near to you.
command is give.
34 CAN bus commu- Sent message not acknowl- Make sure that there is another
nication edged. device on the bus with the same
configuration.
36 Control unit NXS Control Unit can not Change the control unit.
control NXP Power Unit and
vice versa
37 ** Device changed The option board was Reset the fault. The device is ready
(same type) replaced by a new one that for use. The drive starts to use the
you have used before in the old parameter settings.
same slot. The parameters
are available in the drive.
38 ** Device added The option board was added. Reset the fault. The device is ready
(same type) You have used the same for use. The drive starts to use the
option board before in the old parameter settings.
same slot. The parameters
are available in the drive.
39 ** Device removed An option board was The device is not available. Reset
removed from the slot. the fault.
Fault Subcode in
Fault Possible cause How to correct the fault
code T.14
40 Device unknown S1 = An unknown device was Ask instructions from the distribu-
Unknown connected (the power unit/ tor near to you.
device option board)
S2 =
Power1not
same type
as Power2
42 Brake resistor Brake resistor overtemper- Set the deceleration time longer.
overtemperature ature protection has detec- Use external brake resistor.
ted too heavy braking.
2=
Encoder 1
channel B
is missing
3 = Both
encoder 1
channels
are miss-
ing
4=
Encoder
reversed
5=
Encoder
board
missing
44 ** Device changed Option board or power unit Reset. Set the option board param-
(different type) changed. New device of dif- eters again if option board was
ferent type or different changed. Set converter parameters
power rating. again if power unit was changed.
45 ** Device added (dif- Option board of different Reset. Set the power unit parame-
ferent type) type added. ters again.
Fault Subcode in
Fault Possible cause How to correct the fault
code T.14
49 Division by zero in Division by zero has occur- If the fault shows again while the
application red in application program. AC drive is in run state, ask
instructions from the distributor
near to you. If you are an applica-
tion programmer, do a check of the
application program.
50 * Analogue input Iin Current at the analogue Do a check of the current loop cir-
< 4mA (sel. signal input is < 4mA. control cable cuitry.
range 4 to 20 mA) is broken or loose signal
source has failed.
52 Keypad communi- The connection between the Do a check of the control panel
cation fault control panel (or NCDrive) connection and the control panel
and the drive is defective. cable.
54 Slot fault Defective option board or Do a check of the board and slot.
slot Ask instructions from the distribu-
tor near to you.
56 Over Temp. Temperature exceeded set Find the cause of temperature rise.
limit. Sensor disconnected.
Short circuit.
57 ** Identification Identification run has failed. Run command was removed before
completion of identification run.
The motor is not connected to the
AC drive. There is load on motor
shaft.
62 Run disable Run enable signal is low. Do a check of the reason for the
Run enable signal.
Fault Subcode in
Fault Possible cause How to correct the fault
code T.14
64 ** Input switch open Drive input switch is open. Do a check of the main power
switch of the drive.
65 Over Temp. Temperature exceeded set Find the cause of temperature rise.
limit. Sensor disconnected.
Short circuit.
* = You can set different responses in the application for these faults. See parameter group
Protections.
** = A faults (alarms) only.
11 APPENDIX 1
11.1 POWER LOSSES FOR 380-500 V
If you want to increase the switching frequency of the drive (for example, to decrease the
level of the motor noise), the power losses and cooling requirements change as the figures
below show.
0.40
0.35
0.30
Power loss (kW)
0.25
0.20
0.15
0.10
0.05
0.00
0 2 4 6 8 10 12 14 16 18
Switching frequency (kHz)
NX0003 500V NX0003 400V
NX0004 500V NX0004 400V
NX0005 500V NX0005 400V
NX0007 500V NX0007 400V
NX0009 500V NX0009 400V
NX0012 500V NX0012 400V
Fig. 34: Power loss as function of switching frequency; NXS or NXP 0003-0012
1.00
0.90
0.80
0.70
Power loss (kW)
0.60
0.50
0.40
0.30
0.20
0.10
0.00
0 2 4 6 8 10 12 14 16 18
Switching frequency (kHz)
NX0016 500V NX0016 400V
NX0023 500V NX0023 400V
NX0031 500V NX0031 400V
Fig. 35: Power loss as function of switching frequency; NXS or NXP 0016-0031
2.00
1.80
1.60
1.40
Power loss (kW)
1.20
1.00
0.80
0.60
0.40
0.20
0.00
0 2 4 6 8 10 12 14 16 18
Switching frequency (kHz)
NX0038 500V NX0038 400V
NX0045 500V NX0045 400V
NX0061 500V NX0061 400V
Fig. 36: Power loss as function of switching frequency; NXS or NXP 0038-0061
2.50
2.00
Power loss (kW)
1.50
1.00
0.50
0.00
0 1 2 3 4 5 6 7
Switching frequency (kHz)
NX0072 500V NX0072 400V
NX0087 500V NX0087 400V
NX0105 500V NX0105 400V
Fig. 37: Power loss as function of switching frequency; NXS or NXP 0072-0105
4.00
3.50
3.00
Power loss (kW)
2.50
2.00
1.50
1.00
0.50
0.00
0 1 2 3 4 5 6 7
Switching frequency (kHz)
NX0140 500V NX0140 400V
NX0170 500V NX0170 400V
NX0205 500V NX0205 400V
Fig. 38: Power loss as function of switching frequency; NXS or NXP 0140-0205
7.00
6.00
5.00
Power loss (kW)
4.00
3.00
2.00
1.00
0.00
0 1 2 3 4 5 6 7
Switching frequency (kHz)
NX0261 500V NX0261 400V
NX0300 500V NX0300 400V
Fig. 39: Power loss as function of switching frequency; NXS or NXP 0261-0300
10.00
9.00
8.00
7.00
Power loss (kW)
6.00
5.00
4.00
3.00
2.00
1.00
0.00
0 1 2 3 4 5 6 7
Switching frequency (kHz)
NX0385 500V NX0385 400V
NX0460 500V NX0460 400V
NX0520 500V NX0520 400V
Fig. 40: Power loss as function of switching frequency; NXS or NXP 0385-0520
16.00
14.00
12.00
Power loss (kW)
10.00
8.00
6.00
4.00
2.00
0.00
0 1 2 3 4 5 6 7
Switching frequency (kHz)
NX0590 500V NX0590 400V
NX0650 500V NX0650 400V
NX0730 500V NX0730 400V
Fig. 41: Power loss as function of switching frequency; NXS or NXP 0590-0730
1.20
1.00
Power loss (kW)
0.80
0.60
0.40
0.20
0.00
0 1 2 3 4 5 6 7
Switching frequency (kHz)
NX0004 690V NX0018 690V
NX0007 690V NX0022 690V
NX00010 690V NX0027 690V
NX0013 690V NX0034 690V
Fig. 42: Power loss as function of switching frequency; NXS or NXP 0004-0034
1.40
1.20
1.00
Power loss (kW)
0.80
0.60
0.40
0.20
0.00
0 1 2 3 4 5 6 7
Switching frequency (kHz)
NX0041 690V NX0052 690V
Fig. 43: Power loss as function of switching frequency; NXS or NXP 0041-0052
3.00
2.50
Power loss (kW)
2.00
1.50
1.00
0.50
0.00
0 1 2 3 4 5 6 7
Switching frequency (kHz)
NX0062 690V NX0100 690V
NX0080 690V
Fig. 44: Power loss as function of switching frequency; NXS or NXP 0062-0100
5.00
4.50
4.00
3.50
Power loss (kW)
3.00
2.50
2.00
1.50
1.00
0.50
0.00
0 1 2 3 4 5 6 7
Switching frequency (kHz)
NX0125 690V NX0170 690V
NX0144 690V NX0208 690V
Fig. 45: Power loss as function of switching frequency; NXS or NXP 0125-0208
12.00
10.00
Power loss (kW)
8.00
6.00
4.00
2.00
0.00
0 1 2 3 4 5 6 7
Switching frequency (kHz)
NX0261 690V NX0385 690V
NX0325 690V NX0416 690V
Fig. 46: Power loss as function of switching frequency; NXS or NXP 0261-0416
16.00
14.00
12.00
Power loss (kW)
10.00
8.00
6.00
4.00
2.00
0.00
0 1 2 3 4 5 6 7
Switching frequency (kHz)
NX0460 690V NX0590 690V
NX0502 690V
Fig. 47: Power loss as function of switching frequency; NXS or NXP 0460-0590
www.vacon.com
Vacon Plc.
Runsorintie 7
65380 Vaasa
Finland
Rev. D
Subject to change without prior notice
© 2015 Vacon Plc. Sales code: DOC-INSNXS/NXP+DLUK