Doosan Infracore Generator Engine P222le-Ii
Doosan Infracore Generator Engine P222le-Ii
Doosan Infracore Generator Engine P222le-Ii
P222LE-II
Ratings Gross Engine Output Net Engine Output
( kWm/PS) Standby Prime Standby Prime
1500rpm(50Hz) 652/886 - 629/855 -
1800rpm(60Hz) 736/1000 - 698/948 -
Ratings Definitions
The power ratings of Emergency Standby and Prime are in accordance with ISO 8528.
Fuel Stop power in accordance with ISO 3046.
STANDBY POWER RATING is applicable for supplying emergency power for the duration of the utility power outage.
No overload capability is available for this rating. A standby rated engine should be sized for a maximum of an 70% average
load factor and 200 hours of operation per year. This includes less than 25 hours per year at the Standby Power rating.
PRIME POWER RATING is available for an unlimited number of hours per year in variable load application. Variable load
should not exceed a 70% average of the Prime Power rating during any operating period of 250 hours. The Total operating
time at 100% Prime Power shall not exceed 500 hours per year. A 10% overload capability is available for a period of 1 hour
withing a 12 hour period of operation. Total operating time at the 10% overload power shall not exceed 25 hous per year
◆ CONVERSION TABLE
in. = mm x 0.0394 lb/ft = N.m x 0.737
PS = kW x 1.3596 U.S. gal = lit. x 0.264
psi = kg/cm2 x 14.2233 kW = 0.2388 kcal/s
in3 = lit. x 61.02 lb/PS.h = g/kW.h x 0.00162
hp = PS x 0.98635 cfm = m3/min x 35.336
lb = kg x 2.20462 MPa = kPa x 1000 = bar x 10
kW = kcal/sec x 0.239