0% found this document useful (0 votes)
279 views

P3 Modbus-Configuration

Uploaded by

solomon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
279 views

P3 Modbus-Configuration

Uploaded by

solomon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 26

Easergy P3

Modbus configuration instructions


Application Book
P3APS18025EN
04/2019

www.schneider-electric.com
Table of Contents Modbus configuration instructions

Table of Contents
1. About this document..................................................................... 4
1.1. Purpose............................................................................................................4
1.2. Abbreviations and terms.................................................................................. 4

2. Modbus overview.......................................................................... 5

3. Modbus configuration....................................................................8
3.1. Activating Modbus RTU................................................................................... 8
3.2. Configuring Modbus RTU.................................................................................8
3.3. Configuring and activating Modbus TCP ........................................................ 9
3.4. Clock synchronization.................................................................................... 10
3.5. Events............................................................................................................ 11
3.6. Scaling........................................................................................................... 12

4. Additional information about some Modbus registers................. 15


4.1. Protection settings......................................................................................... 15
4.1.1. Modbus registers for protection settings..............................................15
4.1.2. Reading and writing protection settings...............................................15
4.2. Disturbance recordings.................................................................................. 16
4.2.1. COMTRADE files.................................................................................16
4.2.2. Modbus registers for disturbance recordings.......................................16
4.2.3. Reading disturbance records as COMTRADE files ............................ 17
4.3. Modbus fault current registers....................................................................... 19

5. Testing Modbus with Simple Tester.............................................20


5.1. Simple Tester................................................................................................. 20
5.2. Connecting the device to the PC running Simple Tester................................20
5.3. Connecting the device to Simple Tester with Modbus RTU........................... 21
5.4. Connecting the device to Simple Tester with Modbus TCP........................... 22
5.5. Reading data..................................................................................................23
5.6. Writing data....................................................................................................25
5.7. Events and clock synchronization in Simple Tester....................................... 25

P3APS18025EN 3
Modbus configuration instructions 1. About this document

1. About this document

1.1. Purpose
The purpose of this document is to describe the configuration and use of the
Modbus RTU and Modbus TCP in Easergy P3 protection devices.

1.2. Abbreviations and terms


Table 1 - Abbreviations and terms

Term Description

COMTRADE Common format for transient data exchange. File format for storing
oscillography and status data related to transient power system
disturbances.

DHCP Dynamic host configuration protocol

EF Earth fault

HR Holding register

NTP Network time protocol

OC Overcurrent

RTC Real-time clock

RTU Remote terminal unit

SNTP Simple network time protocol

TCP Transmission control protocol

4 P3APS18025EN
2. Modbus overview Modbus configuration instructions

2. Modbus overview
The Modbus protocol is a master-slave protocol typically implemented on an
RS-232 or RS-485 physical interface. There are two versions of the serial Modbus
protocol: Modbus RTU and Modbus ASCII, of which Modbus RTU is available in
Easergy P3 devices. There is also a TCP/IP implementation of the protocol,
Modbus TCP.
Modbus TCP is simply the Modbus RTU protocol with a TCP interface that runs
on Ethernet. TCP/IP refers to the transmission control protocol and Internet
Protocol which provide the transmission medium for Modbus TCP messaging. In
practice, Modbus TCP embeds a standard Modbus data frame into a TCP frame.

Modbus RTU and Modbus TCP can be used to transfer the following types of
data:

• events
• status information
• measurements
• control commands
• clock synchronization
• protection settings
• disturbance recordings

In the master-slave setup of Modbus, only the master can initiate transactions
(queries). The slaves respond by supplying the requested data to the master or
by taking the action requested in the query. The master can address individual
slaves or initiate a broadcast message to all slaves. The address space for slaves
in Modbus RTU ranges from 1-247 on one data link. Address 0 is reserved for
broadcast.

The Modbus protocol defines four different categories of data. The mapping of
data to these categories is implementation dependent. In Easergy P3 devices, all
data is mapped to the holding registers.

Table 2 - Modbus data organisation

Primary table Object type Access Comments

Discrete input Single bit Read-only This type data can be provided by an I/O
system.

Coils Single bit Read-write This type of data can be altered by an


application program.

Input registers 16-bit word Read-only This type of data can be provided by an I/O
system.

Holding 16-bit word Read-write This type of data can be altered by an


registers application program.

The actual mapping of particular data items to holding registers in Easergy P3


devices can be checked with the setting tool by selecting the items under the
Modbus main configuration setting view.

P3APS18025EN 5
Modbus configuration instructions 2. Modbus overview

Figure 1 - Modbus main configuration setting view

NOTE:
• The data mappings are visible only when the Modbus protocol is
activated. For instructions on how to activate the protocol, see Chapter 3.
Modbus configuration.
• The values in the Address column (for example 40xxxx) consist of two
parts: “40” and “xxxx”, where the prefix “40” denotes a reference to Read/
Write Output or Holding Registers and “xxxx” denotes the address of a
particular register.
• The holding register address sent via Modbus is one less than that
indicated by a device. For example, if the Alive Indicator, holding register
address 2001, is sent over a Modbus data link, the frame indicates that
the address of the holding register is 2000.

The bit rate of Modbus RTU is typically 9600 bps and for the transmission of
frames, a parity check mode must be selected (even, odd or none parity
checking).

6 P3APS18025EN
2. Modbus overview Modbus configuration instructions

Figure 2 - Modbus data mappings

Related tasks
Activating Modbus RTU on page 8
Configuring and activating Modbus TCP on page 9

P3APS18025EN 7
Modbus configuration instructions 3. Modbus configuration

3. Modbus configuration

3.1. Activating Modbus RTU


1. In Easergy Pro, go to Communication > Protocol configuration.

2. Under Remote port, select “ModBusSlv” from the Remote port protocol
drop-down menu.

Figure 3 - Selecting the remote port protocol

• After changing the communication protocol, for the changes to take effect,
reboot the device.
• The protocol can also be enabled via the local panel of the device. You must
enter the password for the configurator access level via the local panel before
this is possible. See the manual for the device at hand for more instructions.

3.2. Configuring Modbus RTU


Before configuring Modbus, you must activate it.

Configure the Modbus protocol using Easergy Pro.

1. Go to Protocol configuration > Modbus main configuration.

2. Set the Modbus slave numer, bit rate and parity.

8 P3APS18025EN
3. Modbus configuration Modbus configuration instructions

Figure 4 - Modbus main configuration setting view

NOTE: The parity and bit rate must be set to the same value on all
devices connected to the same data link.

Related tasks
Activating Modbus RTU on page 8

3.3. Configuring and activating Modbus TCP


Configure the Ethernet port settings with Easergy Pro.

1. Go to Protocol configuration > Ethernet port.

2. Set the IP address, subnet mask (NetMask) and gateway.

Figure 5 - Ethernet port setting view

P3APS18025EN 9
Modbus configuration instructions 3. Modbus configuration

NOTE: Easergy P3 devices support dynamic host configuration protocol


(DHCP) but usually a static IP address is used. Consider this before
connecting a device to an existing network, so that no conflicts emerge.

3. Reboot the device for the changes to take effect.

4. To activate Modbus TPC, set Ethernet port protocol to “ModbusTCPs”


(Modbus TCP, slave).

Figure 6 - Ethernet protocol setting view

NOTE:
◦ There are two different Ethernet protocols, Ethernet protocol 1 and 2.
Modbus TCP can be selected to only one of them. The other protocol
can be for example IEC 61850.
◦ Two Modbus TCP masters can communicate with the device
simultaneously.
◦ Serial Modbus RTU can be used at the same time with Modbus TCP
masters.

3.4. Clock synchronization


The device’s internal clock can be synchronised via the Modbus protocol.
However, this is not a native feature of the Modbus protocol, but an Easergy-
specific system. The accuracy of the clock synchronisation is in the scale of a few
hundred milliseconds.

The clock can be synchronized either completely (all fields: seconds, minutes,
hours, days, month and year) or by synchronizing only the minutes, which in turn
sets the seconds and milliseconds to zero.

10 P3APS18025EN
3. Modbus configuration Modbus configuration instructions

An example of how minute synchronisation can be done: when the reference


clock (the clock which is assumed to be correct) is exactly seven minutes past
(any hour), a minute synchronisation is performed. The result is that the internal
clock of the device is set to HH:07:00.000
(“Hours:Minutes:Seconds.Milliseconds”) “HH” is not changed.

These two ways of synchronizing the clock are denoted “Set RTC”, where “RTC”
stands for real-time clock and “Synchronise Minutes” in the data map. The holding
register address of the minute synchronisation is 2502.

Table 3 - Description of holding registers allocated to “Set RTC”


synchronization

Holding register Content

2504 Lower byte: seconds. Milliseconds are zero.

2505 Upper byte: minutes.

Lower byte: hours.

2506 Upper byte: day.

Lower byte: month.

2507 Year

Time synchronization is recommended to be performed hourly.

For Modbus TCP, clock synchronisation can also be done by using simple
network time protocol (SNTP). This requires a NTP server, the address of which
is set in the Protocol configuration > Ethernet port setting view in Easergy Pro.

3.5. Events
The device’s event buffer can be read via the Modbus RTU protocol by reading
one event at a time, from holding registers 2101…2105. The event registers
contain the latest event, and are cleared when they are read. The registers are
then updated to contain the following event from the event buffer.

Table 4 - Description of Events in holding registers

Holding register Content

2101 Event code

2102 Event timestamp

Bits 15-6 = milliseconds

Bits 5-0 = seconds

2103 Event timestamp

Upper byte = minute

Lower byte = hour

P3APS18025EN 11
Modbus configuration instructions 3. Modbus configuration

Holding register Content

2104 Event timestamp

Upper byte = day

Lower byte = month

2105 Event timestamp, year

If an error occurs when reading an event from registers 2101…2105, the


previously read event is available in registers 2490…2494 for re-reading.

NOTE: Events can also be read from holding registers 1996…2000.

Events are coded with a numbering starting from 0. To obtain the meaning of
these event codes, run the GETSET-command “get eventcodes” in the terminal
software (for example PuTTY).

3.6. Scaling
Holding registers are 16 bits in size, so they can directly represent 216 = 65535
different values, which might not be enough to describe the values of some
physical quantity such as voltage or power. Thus, values transmitted over a
Modbus data link must be scaled to account for this.

Figure 7 - Line defined by two points in a two-dimensional space

The scaling is determined by the equation of the line connecting two points in a
two-dimensional space, (x1, y1) and (x2, y2). That is, the trajectory of the line and
the offset from origin. Note that there is no offset in the example if the point (x1,
y1) is assumed to lie at the origin.

It is common to use scaling factors with base ten (10, 100, 1000…) since, in such
cases, the original measurements only lose decimals and such values are easy to
read and re-scale to actual values on the client side after transmission. Note that
the scaled measurements get rounded.

Different settings for scaling can be used for the power, power factor, tan phi,
voltage and frequency scaling. These can be set in the Communication >
Modbus & Profibus scalings setting view item in Easergy Pro.

A short example: The frequency is internally (in the device) stored as a integer
value which also holds three decimal places, that is, 50.000 Hz is represented as

12 P3APS18025EN
3. Modbus configuration Modbus configuration instructions

50000. This is a value too large to be represented with 16 bits (signed integer),
however, frequency is by default scaled with the points: (x1, y1) = (0, 0) and (x2,
y2) = (10, 1), enabling it to be sent over Modbus.

The slope is 0.1 and there is no offset.

𝑦 2 − 𝑦1 1−0
𝑘= = = 0.1
𝑥2 −𝑥 1 10 − 0

Thus, the value on the receiving side (the Modbus value) is:

𝑣 𝑎 𝑙 𝑢 𝑒modbus = 𝑘 * 𝑣 𝑎 𝑙 𝑢 𝑒 internal = 0.1 * 50000 = 5000

Figure 8 - Default frequency scaling

To make sure that a scaling has been set as intended, you can check it in
Easergy Pro by viewing the Scaling column for each holding register in the
Modbus data mapping lists, for example in Communication > Modbus slave
401491.

For an example of scaling change, see Figure 9 - Voltage scaling changed from
default (x2 changed to 10 from 1) on page 14, Figure 10 - Result of the change
in voltage scaling on page 14 and Figure 11 - Default scaling for some holding
registers on page 14.

P3APS18025EN 13
Modbus configuration instructions 3. Modbus configuration

Figure 9 - Voltage scaling changed from default (x2 changed to 10 from 1)

Figure 10 - Result of the change in voltage scaling

Compare the scalings in Figure 10 - Result of the change in voltage scaling on


page 14 and Figure 11 - Default scaling for some holding registers on page 14.

Figure 11 - Default scaling for some holding registers

NOTE: To avoid overflow, scale values so that they are kept in the interval 0–
32768 .

14 P3APS18025EN
4. Additional information about some Modbus registers Modbus configuration instructions

4. Additional information about some Modbus


registers

4.1. Protection settings

4.1.1. Modbus registers for protection settings

The most important protection settings can be read and written using Modbus
registers starting from address 5001.

Figure 12 - Modbus register 5001

4.1.2. Reading and writing protection settings

Modbus holding registers are 16 bits wide. However, some of the parameters
which have been mapped to these registers in the device have 32-bit values.
These parameters are mapped to two consecutive 16-bit holding registers, so that
the register with the smaller address represents the LSB 16-bit word for the
parameter and the second register represents the MSB 16-bit word for the
parameter.

In the current firmware version, all parameters (and only the parameters) which
occupy two consecutive holding registers have 32-bit values.

When the value of such parameter is updated through Modbus, the client must
perform two write operations: one for the LSB word and another for the MSB
word. Each write operation updates the value of the parameter, so that only the
word being written to is modified. The intermediate state for the parameter—
where only one word has been updated—may represent an invalid value for the
parameter. For example, the value may be out of allowed range. In such case the
first write operation gives an error message, indicating that the value of the
parameter was not updated. The client can nevertheless continue with the second
write operation. This second write operation modifies the incomplete intermediate
state of the parameter. If the intermediate state then reaches a valid 32-bit value
for the parameter, the second write operation should indicate a success.

P3APS18025EN 15
Modbus configuration instructions 4. Additional information about some Modbus registers

The client can, for example, first write the LSB 16-bit word for the parameter and
then write the MSB 16-bit word for the parameter, and the parameter should have
the new 32-bit value after the second write operation. The two 16-bit words can
be written in any order. These two write operations should occur within two
seconds of each other.

4.2. Disturbance recordings

4.2.1. COMTRADE files

COMTRADE is a standard file format for exchanging disturbance recordings.


These are (oscillographic) measurements of power system variables, such as
(instantaneous) currents and voltages, over an event like a transient fault.

One recording consists of two files: a CFG file describes what was recorded in the
recording, and a DAT file contains the recorded values.

4.2.2. Modbus registers for disturbance recordings

In P3 devices, one register is used to issue commands to the COMTRADE


reading mechanism.
Table 5 - Modbus registers for disturbance recordings

Register Content

5400 • MSB byte: Number of the recording to be downloaded, so that


value zero means the oldest record, value one means the second
(Command
oldest record, and so on.
register)
• LSB byte: A set of flags
◦ b5: Trigger to remove oldest record.
◦ b4: Trigger to request the next chunk.
◦ b3: Flag for auto-increment the chunk.
◦ b2: Flag for load DAT file.
◦ b1: Flag for load CFG file.
• (LSB) b0: Trigger start of download when value 1 is written to this
bit.

5401 • MSB byte: Number of recordings available.


• LSB byte: A set of flags.
(Status register
◦ b5: Flag for error in download.
1)
◦ b4: Flag for last chunk of data for this file.
◦ b3: Flag for chunk auto-increment in use.
◦ b2: Flag for DAT file now being loaded.
◦ b1: Flag for CFG file now being loaded.
• (LSB) b0: Flag for valid data in data registers. Implies that a
download is in progress.

16 P3APS18025EN
4. Additional information about some Modbus registers Modbus configuration instructions

Register Content

5402 • MSB byte: Number of bytes of data available in data registers.


• LSB byte: Approximate progress downloading current file in
(Status register
percentage.
2)

5403 to 5498 Content (fragment) for the file being downloaded.


(96 Data
registers)

NOTE: The maximum length of a Modbus message is 253 bytes. It is thus


possible to read the two status registers and all of the data registers in a
single command.

4.2.3. Reading disturbance records as COMTRADE files

Disturbance recordings (COMTRADE files) can be read via registers starting from
5400.
1. Open Modbus connection to the device.

2. Read status register 1 (5401), and check that there is at least one recording
available.

3. Construct a value for the command which starts the download process.

For example, value 271 (0x0x10F) starts download of the second oldest
record.

MSB byte: 0x01

Number of the recording to be downloaded

LSB byte: 0x0F

◦ b5: (0) Trigger to remove the oldest record.


◦ b4: (0) Trigger to request the next chunk.
◦ b3: (1) Flag to auto-increment the chunk.
◦ b2: (1) Flag to load the DAT file.
◦ b1: (1) Flag to load the CFG file.
◦ (LSB) b0: (1) Trigger start of download when value 1 is written to this bit.

Write this value to the command register (5400). This command indicates
which recording you want to read and whether you want to download both
CFG file and DAT file, or only either one at a time. This enables “chunk auto-
incrementing”, which means that whenever we read the value of status
register 1, the contents of the data registers are updated to contain the next
fragments of data for the file which is currently downloading.

4. Make a read request that starts from status register 1 (5401) and continues
until the end of the data registers (registers 5403...5498).
This is a total of 96 + 2 = 98 registers.

5. Inspect the value of status register 1.

P3APS18025EN 17
Modbus configuration instructions 4. Additional information about some Modbus registers

Table 6 - Register 5401 (status register 1)

Byte / bit Meaning Explanation

MSB byte Number of recordings If this value changes in the


available middle of a download, a
new recording has been
made. It is recommended
that in this case the
download is aborted and
restarted, by returning to
step 3 (or to step 1).

LSB byte Set of flags

b5 Flag for error in download. If this flag is set, there was


an internal error in the
device, and the download
is automatically aborted by
the device. Contents of all
other registers are invalid.

b4 Flag for last chunk of data If this flag is set, the data
for this file registers contain the last
pieces of data for the file
which we are currently
downloading. When next
chunk is triggered, we get
the first pieces of data for
another file. (With auto-
increment, this triggering
happens when the status
register 1 is read.)

b3 Flag for chunk auto- Indicates whether auto-


increment in use increment is in use for this
download. If this is not
used, a separate write is
needed to the command
register, with correct flags,
to get the next pieces of
data in the data registers.

b2 Flag for DAT file now being If set, indicates that we are
loaded now downloading the DAT
file.

b1 Flag for CFG file now If set, indicates that we are


being loaded now downloading the CFG
file.

(LSB) b0 Flag for valid data in data If this flag is set, the data
registers registers DO contain valid
data for the files being
downloaded. Absence of
this flag indicates either an
error or that the download
is complete.

18 P3APS18025EN
4. Additional information about some Modbus registers Modbus configuration instructions

6. Assuming that you now have valid data for the download, inspect the value of
status register 2 (4602).

MSB byte Number of bytes of data available in data registers

LSB byte Approximate progress downloading current file in percentage

NOTE: The data registers hold 16-bit values (two bytes), while the amount
of data is reported in bytes. The data registers should be filled with data
(giving value 192 here), unless the last pieces of content for the file are
now in the data registers.

You can always read all data registers, and then ignore those which do not
contain valid data, or first read the two status registers, and then, with a
separate read command, read only those data registers which actually contain
data. Also, you may choose to read only at most M registers at a time, so that
M is smaller than the total number of data registers (96). These options may
be useful if the used communication link is slow or expensive.

If the link is prone to transfer errors, you can choose to read a given data
register several times, and use the value which occurs most commonly. In this
use case, it is recommended not to use the auto-increment feature.

7. Copy data from the data registers to the file which is currently being
downloaded.
Note the actual amount of (valid) data in the registers that was discovered in
step 5. If this is the last chunk of data for this file, then after the data has been
written to the file, close the file. When the next pieces of data are received,
you can open a new file. Flags on status register 1 indicate which file is then
being downloaded.

8. Start to read the next chunk by returning to step 4.

4.3. Modbus fault current registers


Here you can find explanations for some additional Modbus registers.

Table 7 - Modbus fault current registers

Register Explanation

2110 Last fault current from any dir/undir OC stage (can be cleared)

2111 Fault current from I> stage

2112 Fault current from I>> stage

2113 Fault current from I>>> stage

2130 Last fault Io current from any undirectional EF stage

2131 Fault current from Io> stage

2132 Fault current from Io>> stage

2133 Fault current from Io>>> stage

2134 Fault current from Io>>>> stage

P3APS18025EN 19
Modbus configuration instructions 5. Testing Modbus with Simple Tester

5. Testing Modbus with Simple Tester

5.1. Simple Tester


Simple Tester is a basic protocol testing tool (for PC) that supports several
different protocols, including Modbus RTU and TCP. Simple Tester can be used to
test reading data from holding registers, writing to holding registers, viewing
events and performing clock synchronization from the PC.

Figure 13 - Simple Tester user interface with Modbus selected as protocol

C
D
E

A. Communication parameters: protocol selection and device connection


configuration
B. Modbus Slave ID selector
C. Selections for data reading
D. Selections for data writing
E. Time controls
F. Event view window
G. Connection status

5.2. Connecting the device to the PC running Simple Tester


Before starting testing, connect the P3 device to the PC running Simple Tester.

You can create the connection either via RS-232 or Ethernet.


• To connect the device to the PC via RS-232 interface:

a. Connect an RS-232 cable to the device.

b. Connect an USB-to-RS-232 cable to the PC’s USB port.

20 P3APS18025EN
5. Testing Modbus with Simple Tester Modbus configuration instructions

c. Connect a cable adapter between the two cables.

d. The cable adapter connects the pins 2,3, and 7 of the device’s RS-232
cable’s D-connector to pins 2,3, and 5 of the D-connector of the PC’s
cable.
• To connect the device to the PC via Ethernet interface:

– Connect an Ethernet cable or Ethernet switch between the PC and the


device.

5.3. Connecting the device to Simple Tester with Modbus RTU


Before connecting a device with Modbus RTU:
• Configure the device.
• Connect the device to the PC running Simple Tester.

1. Open Simple Tester.

2. Under Communication parameters, select ModBus from the Protocol drop-


down menu.

3. Under Communication parameters and Modbus, select the settings as


follows:

Parameter Value

Protocol Modbus

Connection type Serial line

Serial port The serial port of the PC

Modbus slave ID The slave ID configured on the device

4. Click the Go button.

P3APS18025EN 21
Modbus configuration instructions 5. Testing Modbus with Simple Tester

Figure 14 - Simple Tester when connected with Modbus RTU

A successful connection is indicated by an “OK” in the rightmost connection


status indicator furthest down in the Simple Tester window.

Related tasks
Configuring Modbus RTU on page 8
Connecting the device to the PC running Simple Tester on page 20

5.4. Connecting the device to Simple Tester with Modbus TCP


Before connecting a device with Modbus TCP:
• Configure the device Ethernet port and TCP port instances.
• Establish a physical Ethernet connection from the PC running Simple Tester
to the device.
1. Open Simple Tester.

2. Under Communication parameters, select Modbus from the Protocol drop-


down menu.

3. Under Communication parameters and Modbus, select the settings as


follows:

Parameter Value

Protocol Modbus

Connection type TCP connection

Host The IP address configured on the device

Port 502

Modbus slave ID The slave ID configured on the device

22 P3APS18025EN
5. Testing Modbus with Simple Tester Modbus configuration instructions

4. Click the Go button.

Figure 15 - Simple Tester when connected with Modbus TCP

A successful connection is indicated by an “OK” in the right-most connection


status indicator furthest down in the Simple Tester window.

Related tasks
Configuring and activating Modbus TCP on page 9
Connecting the device to the PC running Simple Tester on page 20

5.5. Reading data


Before reading data, connect the device to the PC running Simple Tester.

1. Open Simple Tester.

2. Under Communication parameters, select ModBus from the Protocol drop-


down menu.

P3APS18025EN 23
Modbus configuration instructions 5. Testing Modbus with Simple Tester

Figure 16 - Performing a cyclic read on the Alive Counter with Simple Tester

3. Set the right values for Type, Index and Count.

Parameter Description

Type Type of data: select HR (holding register).

Index Select which data item to read from the device. See the data mapping
provided by Easergy Pro.

Count Indicates how many consecutive indices are to be read. For example,
setting Index to 2001 and Count to 2 displays the values of Index 2001
and Index 2002 in the Values box.

4. Click the Read button to manually initiate a read.


Reads can also be done cyclically, by selecting the Cyclic read checkbox.
The length of one cycle can be changed by setting a value (seconds) in the
Cycles field.

Related tasks
Connecting the device to the PC running Simple Tester on page 20

24 P3APS18025EN
5. Testing Modbus with Simple Tester Modbus configuration instructions

5.6. Writing data

Figure 17 - Simple Tester after write to Virtual Input 1

1. Set the right values for Type, Index and Value.

2. Click the Write button.

If the operation is successful, the Status field indicates OK.

NOTE: The event view of Simple Tester now contains an event,


corresponding to “Virtual Input 1 ON”.

5.7. Events and clock synchronization in Simple Tester


If there are events in the event buffer when connecting to Simple Tester, they are
listed in the event view. New events triggered by writes done with Simple Tester
also show up there.

Clock synchronisation can also be performed with Simple Tester by setting the
desired behavior in the time controls settings. The two leftmost fields are used for
setting the time manually, but the time can also be taken from the PC, by
selecting the PC Time checkbox.

Clock synchronisation can also be set to be cyclic by selecting the Cyclic


timesync checkbox. The length of a cycle (minutes) is set in the rightmost field.

Related concepts
Simple Tester on page 20

P3APS18025EN 25
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison - France
Phone: +33 (0) 1 41 29 70 00
www.schneider-electric.com

As standards, specifications, and designs change from time to time,


please ask for confirmation of the information given in this publication.

© 2019 Schneider Electric All Rights Reserved.

P3APS18025EN — 04/2019

You might also like