Lab Manual Electrical Power Systems PTUK
Lab Manual Electrical Power Systems PTUK
Prepared by:
2020
Palestine Technical University-Kadoorie
Faculty of Engineering and Technology | Electrical Engineering Department
Electrical Power Systems Lab || Eng. TareQ FoQha
Abstract
The electrical power systems laboratory at the Palestine Technical University Kadoorie
designed to directly apply theory learned in lectures to devices that will be studied in the
laboratory. The Lab focuses on all aspects of electrical power systems: power generation,
transmission and distribution lines, protection systems, electric power management systems
and a wide range of electrical measurement systems. Research projects carried out in this
laboratory include generation, transmission and distribution of electrical energy and all
facilities that guarantee the safe supply of electrical energy. In addition to the monitoring,
control and supervision systems that are studied and followed in this laboratory.
Objectives
List of Experiments
Chapter (1) Three Phase Synchronous Generator Experiments 1-34
Experiment (4): Parallel operation of a Synchronous Generator with public mains 31-34
Chapter 1
Three-Phase Synchronous Generator Experiments
Contents
Experiment (1) Synchronous Generator Operating Alone 02-12
Experiment (4) Parallel operation of a Synchronous Generator with public mains 31-34
Objectives:
1. Mastering the exact procedures required for generator’s starting and stop and their
exact sequence.
2. To understand how terminal voltage varies with load in a synchronous generator
operating alone.
3. To measure the voltage regulation of a synchronous generator under different loads.
4. To understand the regulation characteristic required to compensate voltage of the
synchronous generator loaded with various loads.
5. Use the Automatic Voltage Regulator (AVR) to keep the voltage across the terminals
of the synchronous generator constant at the load variation.
The stator (fixed windings in the machine casing) includes three-phase windings, shifted of
120 electrical degrees, star or delta connected. From the stator terminal you can take the
outgoing three phase power. The rotor, moved by the prime mover, at fixed speed, contains
the d.c. excitation winding. The excitation can be provided by a variable independent source
or by a d.c. (exciter) generator, coaxial to the rotor and so moved by the prime mover.
The per-phase equivalent circuit of this machine is shown in the Figure below:
The rate of rotation of the magnetic fields in the machine is related to the stator
electrical frequency by the following Equation:
nmP
fe
120
The voltage induced in a given stator phase depends on the flux Ф in the machine, the
frequency or speed of rotation, and the machine's construction by the following
Equation:
EA = K Ф ω
An understanding of how load variations effect the operation of the generator can be
obtained by considering the phasor diagram.
A variable frequency drive (VFD) is an electronic device that controls the speed of AC
induction motors. Both three phase and single phase VFDs can convert input power to
adjustable frequency and voltage source for controlling speed of AC induction motors.
The frequency of the power applied to an AC motor determines the motor speed, based
on the equation:
120f
nm
P
AC supply comes from the facility power network while the rectifier converts network
AC power to DC power. The filter and DC bus work together to smooth the rectified
DC power and to provide clean, low-ripple DC power to the inverter.
The automatic voltage regulator (AVR) is used to regulate the voltage. It takes the
fluctuate voltage and changes them into a constant voltage. The fluctuation in the
voltage mainly occurs due to the variation in load on the supply system. The variation
in voltage damages the equipment of the power system.
Necessary Material:
1. GCB-3/EV: Control board for the generating set mod.
2. MSG-3/EV: Synchronous generator-motor unit mod.
3. RL-2/EV: Variable resistive load mod.
4. IL-2/EV: Variable inductive load mod.
5. CL-2/EV: Variable capacitive load mod.
6. AVR-E/EV: Automatic Voltage Regulator mod.
Experimental Procedures:
Part I: Connection of the Motor-Generator set and the control board GCB-3/EV.
1. Connect between the machines of set MSG-3/EV and the control board GCB-3/EV as
shown in Figure 1.
Figure (1)
2. Complete the wiring including the load as shown in figure 2. Be sure that all step
switches of each load are in position of excluded load (OFF).
3. Set the rotary switch to the position 1 (ON) and the RUN / STAND-BY switch to RUN.
4. Adjust the speed to obtain 50.0 Hz in the AC motor drive.
5. Adjust the excitation of the synchronous generator to obtain a voltage equal to 400 V.
Figure (2)
Part II: Study the behavior of the synchronous generator under resistive load.
1. Set the synchronous generator under load with the insertion of the resistive load (with
different values of the resistive load) and measure the following using the power analyzer:
(a) Current drawn by the load (Iload) in mA.
(b) Terminal voltage of the synchronous generator (VT) in V.
(c) Power consumed by the load (P) in W.
3. Switch off all loads and make sure that the no-load voltage is 400V.
Part III: Study the behavior of the synchronous generator under resistive-inductive load.
1. Set the synchronous generator under load with the insertion of the resistive-inductive
load (with different values of the inductive load) and measure the following using the
power analyzer:
(a) Current drawn by the load (Iload) in mA.
(b) Terminal voltage of the synchronous generator (VT) in V.
(c) Power consumed by the load (P) in W.
Resistive-Inductive Load
Iload (mA) VT (V) P (W) VR%
R (Ω) L (mH)
No-Load 0 400.0 0 --
A A
A B
A A||B
A C
A A||C
A B||C
A A||B||C
3. Switch off all loads and set the no-load voltage at 300V.
Part IV: Study the behavior of the synchronous generator under resistive-capacitive load.
Note: Do not let the terminal voltage exceed 450V.
1. Set the synchronous generator under load with the insertion of the resistive-capacitive
load (with different values of the capacitive load) and measure the following using the
power analyzer:
(a) Current drawn by the load (Iload) in mA.
(b) Terminal voltage of the synchronous generator (VT) in V.
(c) Power consumed by the load (P) in W.
Resistive-Capacitive Load
Iload (mA) VT (V) P (W) VR%
R (Ω) C (µF)
No-Load 0 400.0 0 --
A A
A B
Sketch the terminal characteristic of this generator for different types of loads (R, R-L and
R-C) (Terminal voltage versus load current).
1. Set the synchronous generator under load with the insertion of the resistive load (with
different values of the resistive load).
2. Increase the excitation current to obtain a voltage equal to 400 V and measure the
following using the power analyzer:
(a) Current drawn by the load (Iload) in mA.
(b) Excitation current (If) in mA (Use multimeter).
(c) Power consumed by the load (P) in W.
Part VI: Output voltage regulation of a synchronous generator under resistive-inductive load.
1. Set the synchronous generator under load with the insertion of the resistive-inductive
load (with different values of the inductive load).
2. Increase the excitation current to obtain a voltage equal to 400 V and measure the
following using the power analyzer:
(a) Current drawn by the load (Iload) in mA.
(b) Excitation current (If) in mA (use multimeter).
(c) Power consumed by the load (P) in W.
Resistive-Inductive Load
Iload (mA) If (mA) P (W)
R (Ω) L (mH)
Open Circuit 0 0
A A
A B
Part VII: Output voltage regulation of a synchronous generator under resistive-capacitive load.
Resistive-Capacitive Load
Iload (mA) If (mA) P (W)
R (Ω) C (µF)
Open Circuit 0 0
A A
A B
Sketch the regulation characteristic of this generator for different types of loads (R,R-L
and R-C) (Field current versus load current).
Resistive Load
Iload (mA) If (mA) P (W)
R (Ω)
No Load 0 0
A
B
Resistive-inductive Load
Iload (mA) If (mA) P (W)
R (Ω) L (mH)
No Load 0 0
A A
A B
Resistive-capacitive Load
Iload (mA) If (mA) P (W)
R (Ω) C (µF)
No Load 0 0
A A
Figure (3)
Questions:
1. Explain the effects of increasing loads on the terminal voltage of the synchronous
generator and explain how to reduce these effects?
2. Show by drawing the effect of load changes on the phasor diagram of the
synchronous generator with Constant:
(a) Unity PF;
(b) Lagging PF;
(c) Leading PF.
Objectives:
Studying and applying a relay for:
Necessary Material:
1. GCB-3/EV: Control board for the generating set mod.
2. MSG-3/EV: Synchronous generator-motor unit mod.
3. RL-2/EV: Variable resistive load mod.
4. IL-2/EV: Variable inductive load mod.
Experimental Procedures:
Part I: Relay for phase sequence, phase failure and voltage asymmetry.
1. Insert three jumpers into the terminals set to power the relay for phase sequence, phase
lacking and voltage asymmetry as indicated in Figure 1.
2. Connect an ohmmeter to check the state of the output relay contact and complete the
wiring involving the step resistive load mod. RL-2/EV, be sure that all switches of the
steps of each phase are in position of excluded load (OFF) as shown in Figure 1.
Test 1: Disconnect one of the three phases and check the intervention of the output relay.
Test 2: Displace one of the three phases with another one and check the intervention of the
output relay.
Figure (1)
3. Set the synchronous generator under load with the insertion of the resistive load.
Test 3: Put unbalanced load and record the value of phase voltages and currents (using
power analyzer) and delay time (using chronometer), fill the following table.
1. Remove jumpers of the symmetry relay and insert four jumpers into the terminals set to
power the max/min three-phase voltage relay as indicated in Figure 2.
2. Connect an ohmmeter to check the state of the output relay contact and complete the
wiring of the GCB-3/EV panel as shown in Figure 2.
Figure (2)
Increase the voltage supplied by the synchronous generator by increasing the excitation current
and record the time between the “overvoltage” moment and the same output relay tripping one.
Reduce the voltage again to its rated value (400 V) and check the alarm suppression (the
maximum voltage output relays is reset). Consider that the relay has an hysteresis of 3% with
respect to the set point. Determine at which value of voltage will the relay reset?
Maximum
Line voltage Maximum voltage Measured delay Reset Value
voltage threshold
(V) intervention delay (Sec) (V)
%
105% 5 sec
110% 5 sec
Way 1: Decrease the voltage supplied by the synchronous generator by decreasing the excitation
current and record the time between the “undervoltage” moment and the same output relay
tripping one. Increase the voltage again to its rated value (400 V) and check the alarm suppression
(the minimum voltage output relays is reset). Consider that the relay has an hysteresis of 3% with
respect to the set point. Determine at which value of voltage will the relay reset?
Maximum
Line voltage Maximum voltage Measured delay Reset Value
voltage threshold
(V) intervention delay (Sec) (V)
%
95% 5 sec
90% 5 sec
Way 2: Complete the wiring including the step resistive load mod. RL-2/EV. Be sure that all
step switches of each phase are in position of load excluded (OFF). Set the synchronous
generator under load with the insertion of the resistive load (with different values of the
resistive load) and measure the following:
1. Remove jumpers of the max/min voltage relay and Insert two jumpers into the terminals
set to power the max/min frequency relay as indicated in Figure 3.
2. Connect an ohmmeter to check the state of the output relay contact and complete the
wiring of the GCB-3/EV panel as shown in Figure 3.
Figure (3)
Increase the test frequency using RPM potentiometer and record the time between the
overfrequency and the same output relay tripping one.
Decrease the test frequency using RPM potentiometer and record the time between the under
frequency and the same output relay tripping one.
1. Remove jumpers of the max/min frequency relay and connect the 3-Phase Overload and
the Short-Circuit relay with the proper terminals via six jumpers as indicated in
Figure 4.
2. Connect an ohmmeter to check the state of the output relay contact and complete the
wiring of the GCB-3/EV panel and complete the wiring including the step resistive load
mod. RL-2/EV to obtain the current regulation in the ammetric relay as shown in
Figure 4.
Figure (4)
3. Increase the test current by adding resistive load, measure the load current and record
the time between the “overcurrent” and the output relay tripping.
C 0.6 5 sec
Questions:
1. Describe the effect of the following on the synchrouns generator?
(a) Phase failure;
(b) Phase sequence;
(c) Voltage Asymmetry;
(d) Over and under voltage;
(e) Over and under frequency;
(f) Over load.
(b) If the load attached on the synchronous generator is (B||C = 120Ω) and the
load current measured is 889mA, Put the settings of the overload relay as:
overload current = 0.7A with intervention delay of 5 second.
1) Explain how to put the settings of the relay?
2) Explain the operation of the relay after the load attached?
3. Based on the relay for phase sequence, phase failure and voltage asymmetry
experiment answer the following questions:
(a) Sketch the connection needed to connect synchrouns generator with:
1. Relay;
2. 4-pole contactor (on-off) (to switch off the load when phase sequence or
phase failure or voltage asymmetry occur);
3. Variable three-phase resistive load.
(b) If the load attached on the synchronous generator is (C,A,A) and the
settings of the relay are:
- Asymmetry = 10%;
- Delay = 10 Second;
- Reset delay = 0.1 Sec.
Objectives:
1. To understand the conditions required to parallel two synchronous generators.
2. To understand the procedures for paralleling two synchronous generators.
3. To understand the effect of increasing the frequency of one of the generators on the system.
4. To understand the effect of increasing the field current of one of the generators on the system.
5. To understand how the real power sharing between two generators can be controlled
independently of the system frequency and vice versa.
6. To understand how the reactive power sharing between two generators can be controlled
independently of the terminal voltage and vice versa.
Figure (1)
2. Equal frequencies: This can be seen in the frequency meters of each generator.
Actually, G2 is set at a little higher speed than G1 (this because when “taking load”, the
prime mover will naturally drop the rpm).
4. Equal phase angles: the phase angles of the two a phases must be equal. It is obvious
that if the rotation speeds of both machines are exactly equal, the phases will be never
be equal.
If a generator is connected in parallel with another one of the same size, the basic constraint is
that the sum of the real and reactive powers supplied by the two generators must equal the P
and Q demanded by the load. The system frequency is not constrained to be constant, and
neither is the power of a given generator constrained to be constant. The total power P total
(which is equal to Pload) is given by:
Necessary Material:
1. PCB-3/EV: Generator parallel board mod.
2. GCB-3/EV: Control board for the generating set mod.
3. MSG-3/EV: Synchronous generator-motor unit mod.
4. RL-2/EV: Variable resistive load mod.
5. IL-2/EV: Variable inductive load mod.
Experimental Procedures:
Part I: Parallel operation of two synchronous generators.
1. Connect the circuit as shown in figure 3. Be sure that all the step switches of each phase
are in position of load excluded (OFF).
Figure (3)
2. Start the prime mover of the set 1 and adjust the speed to obtain the rated frequency
50.0 Hz, with the potentiometer RPM set to AC motor drive, and adjust the excitation of
the synchronous generator to obtain a rated voltage equal to 400 V.
3. Press the START button of the contactor K1 to connect the triad of voltages output by
the generator 1, with the main bars.
4. Start the prime mover of the set 2 and adjust the speed to obtain the rated frequency
50.0 Hz, with the potentiometer RPM set to AC motor drive, and adjust the excitation of
the synchronous generator to obtain a rated voltage equal to 400 V.
Note: Do not enable the contactor K2 for any reason until reaching the stage of
synchronization.
5. Check that the two voltage triads are of approximately 400 V and almost equal between
them.
6. Check the phase sequence by using the three-lamp method. If all three bulbs get bright
and dark together, then the systems have the same phase sequence.
7. In the exact moment when the 3 lamps are actually off and the LED SYNC is lightning
in the Green Zone. Enable the contactor K2 to lead the generators to be connected in
parallel.
Part I: The effect of increasing the prime mover speed of one of the generators on the system.
1. At no-load condition measure the frequency and power of G1 and G2 then tabulate the
results in the following table.
2. Set the synchronous generator under load with the insertion of the resistive-inductive
load (R = 360 Ω - Switch B and L= 1.15 H – Switch B).
3. Increase the frequency of G1 gradually and measure the following using the power
analyzer:
No-Change
Increase f1
Increase f1
Part II: The effect of increasing the prime mover speed of G1 while decreasing it of G2 on the system.
1. Return back to the normal operation values and keep the two generators to be
synchronized with each other.
2. Set the synchronous generator under load with the insertion of the resistive-inductive
load (R = 360 Ω - Switch B and L= 1.15 H – Switch B).
3. Increase the frequency of G1 and decrease it for G2 in a small amount and measure the
following using the power analyzer:
Part III: The effect of changing the prime mover speed of both generators on the system.
1. Return back to the normal operation values and keep the two generators to be
synchronized with each other.
2. Set the synchronous generator under load with the insertion of the resistive-inductive
load (R = 360 Ω - Switch B and L= 1.15 H – Switch B).
3. Increase or decrease the frequency of both generators in a small amount and measure
the following using the power analyzer:
Part IV: The effect of increasing the excitation current of one of the generators on the system.
1. Return back to the normal operation values and keep the two generators to be
synchronized with each other.
2. Set the synchronous generator under load with the insertion of the resistive-inductive
load (R = 360 Ω - Switch B and L= 1.15 H – Switch B).
3. Increase the excitation current of G1 gradually and measure the following using the
power analyzer:
No-Load
No-Change
Increase If1
Increase If1
Part V: The effect of increasing the excitation current of G2 while decreasing it of G1 on the system.
1. Return back to the normal operation values and keep the two generators to be
synchronized with each other.
2. Set the synchronous generator under load with the insertion of the resistive-inductive
load (R = 360 Ω - Switch B and L= 1.15 H – Switch B).
3. Increase the excitation current of G1 and decrease it for G2 in a small amount and
measure the following using the power analyzer:
Part VI: The effect of increasing the excitation current of both generators on the system.
1. Return back to the normal operation values and keep the two generators to be
synchronized with each other.
2. Set the synchronous generator under load with the insertion of the resistive-inductive
load (R = 360 Ω - Switch B and L= 1.15 H – Switch B).
3. Increase or decrease the excitation current of both generators in a small amount and
measure the following using the power analyzer:
Questions:
1. Draw the corresponding house diagram at the moment G2 is paralleled with
the G1.
2. Explain with drawing (house diagram) the effect of increasing the frequency of G2
on the operation of the system.
3. Explain with drawing (house diagram) the effect of increasing the frequency of G2
and decreasing it of G1 on the operation of the system.
4. Explain with drawing (house diagram) the effect of increasing or decreasing the
frequency of both generators on the operation of the system.
5. Explain with drawing (house diagram) the effect of increasing the excitation current
of G2 on the operation of the system.
6. Explain with drawing (house diagram) the effect of increasing the excitation current
of G2 and decreasing it of G1 on the operation of the system.
7. Explain with drawing (house diagram) the effect of increasing or decreasing the
excitation current of both generators on the operation of the system.
Objectives:
1. To understand the conditions required to parallel synchronous generator with mains.
2. To understand the procedures for paralleling synchronous generator with mains.
3. To understand the effect of increasing the frequency of the generator on the system.
4. To understand the effect of increasing the field current of the generator on the system.
Figure (1)
Necessary Material:
1. PCB-3/EV: Generator parallel board mod.
2. GCB-3/EV: Control board for the generating set mod.
3. MSG-3/EV: Synchronous generator-motor unit mod.
4. AMT-3/EV: Variable three-phase power supply mod.
5. RL-2/EV: Variable resistive load mod.
6. IL-2/EV: Variable inductive load mod.
Experimental Procedures:
Part I: Parallel operation of synchronous generator and Public mains.
1. Connect the circuit as shown in figure 2. Be sure that all the step switches of each phase
are in position of load excluded (OFF).
Figure (2)
2. Enable the public mains with the variable power supply mod. AMT-3/EV adjusting the
voltage to approximately 3 x 400 V.
3. Start the prime mover of the G1 and adjust the speed to obtain the rated frequency 50.0
Hz, with the potentiometer RPM set to AC motor drive, and adjust the excitation of the
synchronous generator to obtain a rated voltage equal to 400 V.
4. Don’t press the START button of the contactor K1 to connect the triad of voltages
output by the generator 1, with the main bars.
5. Check that the two voltage triads are of approximately 400 V and almost equal between
them.
6. Check the phase sequence by using the three-lamp method. If all three bulbs get bright
and dark together, then the systems have the same phase sequence.
7. In the exact moment when the 3 lamps are actually off and the LED SYNC is lightning
in the Green Zone. Enable the contactor K1 to lead the generator to be connected in
parallel with the mains.
Part II: The effect of changing the prime mover speed of the generators on the system.
1. Set the synchronous generator under load with the insertion of the resistive-inductive
load (R = 720 Ω - Switch A and L= 2.3 H – Switch A).
2. Change the frequency of G1 (increase or decrease) gradually and measure the following
using the power analyzer:
No-Change
Increase
frequency of
Generator
Decrease
frequency of
Generator
Part III: The effect of increasing the excitation current of one of the generators on the system.
1. Return back to the normal operation values and keep the synchronous generator to be
synchronized with the public main.
2. Set the synchronous generator under load with the insertion of the resistive-inductive
load (R = 720 Ω - Switch A and L= 2.3 H – Switch A).
3. Change the excitation current of G1(increase or decrease) in a small amount and
measure the following using the power analyzer:
Increase
field current
of Generator
Decrease
field current
of Generator
Questions:
1. Why must the oncoming generator on a power system be paralleled at a higher
frequency than that of the running system?
2. Once the generator has been connected, explain with drawing (house diagram)
what happens when its frequency is increased or decreased?
3. Once the generator has been connected, explain with drawing (house diagram)
what happens when its field current is increased or decreased?
Chapter 2
Transmission lines Experiments
Contents
Experiment (2) Performance of transmission line under different load conditions. 44-53
Objectives:
1. To study the operation of a power transmission line in no-load condition. (short,
medium and long transmission lines).
2. To study the behavior in series of the no-load power transmission lines (medium and
long transmission lines).
3. To demonstrate the concept of Ferranti effect for a transmission line (medium and long
transmission lines).
Figure (1)
In this no-load condition, only charging current will flow. Hence, power that involves is called
charging power. In some cases, voltages at the end of transmission line will increases to
impermissible values because of the equivalent total capacitance.
The capacitance (and charging current) is negligible in short line but significant in medium
line and appreciable in long line. Therefore this phenomenon occurs in medium and long lines.
Consider the figure given below shows phasor diagram of Ferranti effect of transmission line.
Receiving end voltage as reference phasor;
Figure (2)
From figure it is easily observed that sending end voltage (𝑉𝑠) is less than receiving end
voltage (𝑉𝑟).
Necessary Material:
1. SEL-1/EV: Simulator of electric lines mod.
2. AMT-3/EV: Variable three-phase power supply mod.
3. P14A/EV: Three-phase transformer mod.
Experimental Procedures:
Part I: Short Transmission Line under no-load condition.
1. Start this experiment considering the transmission LINE 1 with the following
parameters: R= 25 Ω; C= 0.2 μF; L= 72 mH; Length = 50 km.
2. Connect with the variable three-phase power supply by inserting the three-phase insulation
transformer,
3. Connect the jumpers with the set of left capacitors, only in the LINE 1, to reproduce the
capacitance between conductors (called CL).
4. Connect the jumpers with the set of right capacitors, only in the LINE 1, to reproduce
the capacitance between the conductors and the ground (called CE).
5. Connect the circuit as shown in Figure 3.
Figure (3)
Connection 1:
1. Connect the capacitors at the sending end point of the transmission line in Δ-connection.
2. Connect the capacitors at the receiving end point of the transmission line in Y-connection.
3. Enable and adjust the voltage of the power supply at 380 V.
4. Turn the breaker at the origin and at the end of the Line 1 to ON in sequence.
5. Read the electric quantities on the measuring instruments and write them down in the
following table.
Connection 2:
1. Connect the capacitors at the sending end point of the transmission line in Δ-connection.
2. Disconnect the capacitors at the receiving end point of the transmission line.
3. Enable and adjust the voltage of the power supply at 380 V.
4. Turn the breaker at the origin and at the end of the Line 1 to ON in sequence.
5. Read the electric quantities on the measuring instruments and write them down in the
following table.
Connection 3:
1. Connect the capacitors at the sending end point of the transmission line in Δ-connection.
2. Connect the capacitors at the receiving end point of the transmission line in Δ-connection.
3. Enable and adjust the voltage of the power supply at 380 V.
4. Turn the breaker at the origin and at the end of the Line 1 to ON in sequence.
5. Read the electric quantities on the measuring instruments and write them down in the
following table.
1. Consider two lines with equal current-carrying capacity, but different length, for this
experiment, that is the Line 1 parameters are: R= 18 Ω; L= 72mH; C= 0.2µF; Length =
50 km; and Line 2 constants are: R = 18 Ω; L= 72mH; C= 0.2µF; Length = 50 km.
2. Connect the circuit as shown in Figure 4.
Figure (4)
Connection1:
1. Connect the capacitors at the sending end point of the LINE 1 in Δ-connection.
2. Connect the capacitors at the receiving end point of the LINE 1 in Y-connection.
3. Connect the capacitors at the sending end point of the LINE 2 in Δ-connection.
4. Connect the capacitors at the receiving end point of the LINE 2 in Y-connection.
5. Enable and adjust the voltage of the power supply at 360 V.
6. Turn the origin and end breakers of the LINE 1 to ON, in sequence, then turn the origin
and end breakers of the LINE 2 to ON;
7. Read the electric quantities on the measuring instruments and write them down in the
following table.
Connection2:
1. Connect the capacitors at the sending end point of the LINE 1 in Δ-connection.
2. Connect the capacitors at the receiving end point of the LINE 1 in Δ-connection.
3. Connect the capacitors at the sending end point of the LINE 2 in Δ-connection.
4. Connect the capacitors at the receiving end point of the LINE 2 in Δ-connection.
5. Enable and adjust the voltage of the power supply at 360 V.
6. Turn the origin and end breakers of the LINE 1 to ON, in sequence, then turn the origin
and end breakers of the LINE 2 to ON;
7. Read the electric quantities on the measuring instruments and write them down in the
following table.
Case 2: Long Transmission line under no load condition. (Study the Ferranti effect of a TL)
1. Consider four lines with equal current-carrying capacity, but different length, for this
experiment, that is the
Line 1 parameters are: R= 18 Ω; L= 72mH; C= 0.2µF; Length = 50 km;
Line 2 parameters are: R = 36 Ω; L= 144mH; C= 0.4µF; Length = 100 km.
Line 3 parameters are: R = 18 Ω; L= 72mH; C= 0.2µF; Length = 50 km. and
Line 4 parameters are: R = 36 Ω; L= 144mH; C= 0.4µF; Length = 100 km.
2. Connect the circuit as shown in Figure 5.
Figure (5)
3. Connect the capacitors at the sending end point of the LINES 1,2 ,3 and 4 in
Δ-connection.
4. Connect the capacitors at the receiving end point of the LINES 1,2 ,3 and 4 in
Y-connection.
5. Enable and adjust the voltage of the power supply at 360 V.
6. Turn the origin and end breakers of the LINE 1 to ON, in sequence, then turn the origin
and end breakers of the LINE 2,3 and 4 to ON, in sequence.
7. Read the electric quantities on the measuring instruments and write them down in the
following table.
Questions:
1. Calculate the reactive power generated by the capacitors and compare it with the
reactive power measured on the line:
(a) (Part I – Connection 1);
(b) (Part I – Connection 2);
(c) (Part I – Connection 3);
(d) (Part II – Case 1 – Connection 1);
(e) (Part II – Case 1 – Connection 2);
(f) (Part II – Case 2);
2. What is the cause of the increase voltage at the receiving end of the transmission
line during no-load condition?
3. Explain the relation between the increasing of the length of transmission line and
the receiving end voltage?
4. Draw the voltage profile of a medium and long TL under no-load condition and
suggest a way to decrease the receiving end voltage (Part II)?
Objectives:
1. To study the behavior of a power transmission line (short, medium and long) at different
load conditions.
2. To determine the various electrical quantities at sending and receiving end for a loaded line.
3. To observe the flow of real and reactive power in a three phase transmission line under
different load conditions.
The voltage regulation of the line is defined by the increase in voltage when full load is
removed, that is,
or
Where:
│VS│ = magnitude of sending-end phase (line-to-neutral) voltage at no load
│VR│ = magnitude of receiving-end phase (line-to-neutral) voltage at full load
│VR,NL│= magnitude of receiving-end voltage at no load
│VR,FL│ = magnitude of receiving-end voltage at full load with constant |VS|
Power
Efficiency:
Necessary Material:
1. SEL-1/EV: Simulator of electric lines mod.
2. AMT-3/EV: Variable three-phase power supply mod.
3. P14A/EV: Three-phase transformer mod.
4. RL-2/EV: Variable resistive load mod.
5. IL-2/EV: Variable inductive load mod.
6. CL-2/EV: Variable capacitive load mod.
Experimental Procedures:
Part I: Study the performance of a short-TL under different load conditions.
1. Start this experiment considering the transmission LINE 2 with the following
parameters: R= 8.9 Ω; L= 36 mH; C= 0.1 μF; Length = 25 km.
2. Connect with the variable three-phase power supply by inserting the three-phase
insulation transformer.
3. Connect the capacitors at the sending end point of the LINE 2 in Δ-connection.
4. Connect the capacitors at the receiving end point of the LINE 2 in Y-connection.
5. Connect the circuit as shown in Figure 1.
Figure (1)
Part I-1: Study the performance of the short-TL under resistive load.
No load 350
A 350
B 350
A||B 350
5. Calculate the Voltage drop, percentage voltage regulation, total power loss and the
efficiency of the Transmission line.
A||B
Part I-2: Study the performance of the short-TL under Resistive-Inductive load.
A B 350
A A||B 350
5. Calculate the Voltage drop, percentage voltage regulation, total power loss and
performance of the Transmission line.
A B
A A||B
Part I-3: Study the performance of the short-TL under Resistive-Capacitive load.
A A 350
A B 350
5. Calculate the Voltage drop, percentage voltage regulation, total power loss and
performance of the transmission line.
A B
Part II: Study the performance of the medium-TL under different load conditions.
1. Start this experiment considering the transmission LINE 2 with the following
parameters: R= 36 Ω; L= 144 mH; C= 0.4 μF; Length = 100 km.
2. Connect with the variable three-phase power supply by inserting the three-phase
insulation transformer,
3. Connect the capacitors at the sending end point of the LINE 2 in Δ-connection.
4. Connect the capacitors at the receiving end point of the LINE 2 in Y-connection.
5. Connect the circuit as shown in Figure 1.
Part II-1: Study the performance of the medium-TL under Resistive-Inductive load.
4. Read the electric quantities on the instruments and write them down in the following
table.
No load 350
A A 350
A B 350
A A||B 350
5. Calculate the Voltage drop, percentage voltage regulation, total power loss and
performance of the Transmission line.
A A
A B
A A||B
Part II-2: Study the performance of the medium-TL under Resistive-Capacitive load.
A A 350
A B 350
5. Calculate the Voltage drop, percentage voltage regulation, total power loss and
performance of the transmission line.
A B
Part III: Study the performance of the Long-TL under different load conditions.
1. Consider four lines with different length, for this experiment, that is the
Line 1 parameters are: R= 18 Ω; L= 72mH; C= 0.2µF; Length = 50 km;
Line 2 parameters are: R = 36 Ω; L= 144mH; C= 0.4µF; Length = 100 km.
Line 3 parameters are: R = 18 Ω; L= 72mH; C= 0.2µF; Length = 50 km. and
Line 4 parameters are: R = 36 Ω; L= 144mH; C= 0.4µF; Length = 100 km.
2. Connect with the variable three-phase power supply by inserting the three-phase
insulation transformer,
3. Connect the capacitors at the sending end point of the LINES 1,2 ,3 and 4 in
Δ-connection.
4. Connect the capacitors at the receiving end point of the LINES 1,2 ,3 and 4 in
Y-connection.
5. Connect the circuit as shown in Figure 2.
Part III-1: Study the performance of the Long-TL under Resistive-Inductive load.
No load 350
A A 350
A B 350
A A||B 350
5. Calculate the Voltage drop, percentage voltage regulation, total power loss and
performance of the Transmission line.
A A
A B
A A||B
Figure (2)
Part III-2: Study the performance of the Long-TL under Resistive-Capacitive load.
No load 320
A A 320
A B 320
5. Calculate the Voltage drop, percentage voltage regulation, total power loss and
performance of the Transmission line.
A A
A B
Questions:
1. What does a positive/negative voltage regulation indicate?
2. For all load conditions (R, RL and RC) Explain and plot on the same graph the
relation between (short, medium and long transmission lines):
(a) Sending end voltage and sending end current (VS versus I S).
(b) Receiving end voltage and current (VR versus I R).
(c) Voltage drop and receiving end current (VD versus I R).
(d) Efficiency of transmission and receiving end current (η versus IR).
5. Draw the phasor diagram for the medium TL (Part II) under:
(a) Lagging PF Load;
(b) Leading PF Load.
7. Draw the voltage profile for the Long TL under resistive – inductive load and
suggest a way to increase the receiving end voltage under heavy load condition
(Part III-1)?
Objectives:
1. To study the parallel behavior of the power transmission lines.
2. To study the Automatic mode of DBB system;
Simulate main line failure.
Simulate overloading main line.
Necessary Material:
1. DBB-2E/EV: Simulator of electric lines mod.
2. P14A/EV: Three-phase transformer mod.
3. RL-2/EV: Variable resistive load mod.
4. RL-2K/EV: Inductive resistive load mod.
5. IL-2/EV: Variable inductive load mod.
Experimental Procedures:
Part I: Study the parallel behavior of the two power transmission lines.
1. In order to carry out the experiment, consider two equal 50-km lines having the
following parameters: R= 18 Ω, L= 72 mH, C= 0.2 μF.
2. Turn the selector operation mode to MANUAL.
3. Connect the circuit as shown in Figure 1.
Figure (1)
10. Read the electric quantities on the instruments and write them down in the following
table.
R2
R3
11. Calculate the Voltage drop, and performance of the transmission line.
R1
R2
R3
12. Disconnect one of the two lines in parallel and repeat the measurements, then
calculate the Voltage drop, and performance of the transmission line.
R-(Ω) VS IS PS VR IR PR VD η
R1
R2
R3
In this Mode the Protection Relays are fully operative, and together with the PLC, they
control the panel. Contactors Q1-Q2 (LINE 1) and Q3-Q4 (LINE 2) cannot be controlled
manually with the red/green pushbuttons.
1. Start this experiment considering the transmission LINE 1 and LINE 2 with the
following constants: R= 18 Ω, L= 72 mH, C= 0.2 μF, Length = 50 km.
2. Connect the circuit as shown in Figure 2.
Figure (2)
1. LINE 1 RELAY: should give its consensus to close Q1: there is voltage present in the
MAINS and it is within the Max/Min preset range; the voltage sequence is correct and
the Asymmetry among phases is within its limits.
2. OL RELAY: does not sense any current overload.
3. If above conditions are fulfilled, contactor Q1 closes contactor Q2.
The MAIN LINE becomes operative again, replacing LINE 2 feeding the load.
Questions:
1. For the two cases (Double TL and Single TL) (Part I) Explain and plot the relation
between:
(a) Receiving end voltage and current (VR versus I R).
(b) Sending end active power and receiving end current (PS versus IR).
(c) Voltage drop and receiving end current (VD versus I R).
(d) Efficiency of transmission and receiving end current (η versus I R).
Objectives:
1. To study the behavior of a power transmission line with insulated neutral in condition of
ground fault.
2. To study the behavior of a power transmission line with compensated neutral conductor
(Peterson coil) in condition of ground fault.
Figure (1)
Figure (2)
Necessary Material:
1. SEL-1/EV: Simulator of electric lines mod.
2. P14A/EV: Three-phase transformer mod.
3. AMT-3/EV: Variable three-phase power supply mod.
4. IL-2/EV: Variable inductive load mod.
5. RL-2K/EV: Inductive resistive load mod.
Experimental Procedures:
Part I: Study the behavior of power transmission line with insulated neutral in condition of SLG fault.
1. Consider and set the LINE 2 with the following constants: R= 18 Ω; L= 72 mH;
CES= 0.1 and CER= 0.1 μF; Length= 50 km.
2. Connect the circuit as shown in Figure 3.
Figure (3)
Sending end CES and receiving end Total Capacitance Sending end Ground fault
CER capacitors (µF) (µF) Voltage (V) current (mA)
CES (µF) CER (µF) Ctotal = CES + CER Vs IF
0.1 0.1 0.2 380
0.1 0.2 0.3 380
0.2 0.2 0.4 380
0.1 0.4 0.5 380
0.2 0.4 0.6 380
0.4 0.4 0.8 380
Part II: Studying the operation of a power transmission line with compensated neutral
conductor (Peterson coil) in condition of SLG fault.
1. Consider and set the LINE 2 with the following constants: R= 18 Ω; L= 72 mH;
CES= 0.2 and CER= 0.2 μF; Length = 50 km.
2. Connect the circuit as shown in Figure 4.
Figure (4)
Ground
Inductance of the Ground fault
Total Capacitance Sending end fault with a
compensation coil current (mA)
(µF) Voltage (V) resistor
(H) (free)
(mA)
L Ctotal = CES + CER Vs IF IFR
(C,C,C) = 1.74 0.4 380
(B,C,C) = 2.30 0.4 380
(A,C,C) = 3.46 0.4 380
(A,B,C) = 4.03 0.4 380
(A,A,C) = 5.18 0.4 380
(A,A,B) = 5.75 0.4 380
(A,A,A) = 6.90 0.4 380
7. Change the value of Ctotal to 0.8 µF (CES= 0.4, CER= 0.4) then insert the data obtained
with the measurements in the following table:
Ground
Inductance of the
Total Capacitance Sending end Ground fault fault with a
compensation coil
(µF) Voltage (V) current (mA) resistor
(H)
(mA)
L Ctotal = CES + CER Vs IF IFR
(C,C,C) = 1.74 0.8 380
(B,C,C) = 2.30 0.8 380
(A,C,C) = 3.46 0.8 380
(A,B,C) = 4.03 0.8 380
(A,A,C) = 5.18 0.8 380
(A,A,B) = 5.75 0.8 380
(A,A,A) = 6.90 0.8 380
Questions:
1. Plot a graph to show the behavior of the ground fault current according to the value
of the line to ground capacitance (IF versus Ctotal) (Part I).
2. What is the main objective for determining the ground fault current of the system
with insulated neutral conductor (Part I)?
3. Which value of the compensation coil gives the best result (Part II)?
4. Explain the effect of increasing the value of Peterson coil on the fault current
(Part II)?
5. Plot figures that show the relation between the fault current and the inductance
compensating inductor for different values of capacitance (IF versus L) (Part II).
7. Explain the effect of inserting resistor in series with the faulted line (SLG fault
through resistor)?
Objectives:
1. Protection against overcurrents in a power transmission line using overcurrent relay
SR1/EV.
2. To configure the protection device SR16/EV with the use of the DIGSI software as:
Instantaneous [50] and delayed [51] maximum current relay to protect a no-load
power transmission line against phase-phase faults.
Instantaneous [50N] and delayed [51N] maximum homopolar current relay to
protect a no-load power transmission line against phase-ground faults.
Max ground directional current relay [67N], to protect a no-load power
transmission line against phase-ground faults.
Distance relay [21], protection against phase-ground and phase-phase fault in a no-
load power transmission line.
Z of the device. The IR compares the real impedance Z of the protected device against Z0; if Z
is equal or less tan Z0, it means that a failure has occurred (could be a solid or not short-circuit).
When the measured impedance of the protected device Zmed is greater or equal to Z0, it is the
normal condition. In the opposite case, the protected device is in abnormal condition, and
the IR will trip.
Necessary Material:
1. SEL-1/EV: Simulator of electric lines mod.
2. P14A/EV: Three-phase transformer mod.
3. Contactor with On-Off control
4. AMT-3/EV: Variable three-phase power supply mod.
5. SR-1/EV: Overcurrent relay.
6. IL-2/EV: Variable inductive load mod.
7. RL-2K/EV: Inductive resistive load mod.
8. PC with DIGSI software installed.
9. SR16/EV: Distance relay mod.
10. SR20/EV: Power transmission line simulator mod.
11. SR21/EV: Isolation transformer mod.
12. UAT/EV: Fixed Power supply mod.
13. RC3-PT/EV: Rheostat mod.
Experimental Procedures:
Part I: Protection against overcurrents in a power transmission line using overcurrent relay SR1.
1. Start this experiment considering the LINE 2 with the following constants: R= 8.9 Ω;
L = 36 mH C = 0.1 µF; Length = 25 km.
2. Connect the circuit as shown in Figure 1.
Figure (1)
B 0.5 5
A || B 0.6 5
Part II: Configuration of SR16 as maximum current relay [50], [51], [50N] and [51N]
1. Perform the electrical connections following the electrical diagram of figure 2 and 3.
Figure (2)
Figure (3)
2. Set the Parameters of the protection device SR16/EV and power system data using
DIGSI software as follows:
(A) Power System Data 1:
1. Rated primary voltage [No. 203] = 1 kV
2. Rated secondary voltage [No. 204] = 100 V
3. CT Rated primary current [No. 205] = 10 A
4. CT Rated secondary current [No. 206] = 1 A
2. Back-Up O/C
(a) O/C TRIP I>> [No. 07221] Led (4) : L (latched)
(b) O/C TRIP I> [No. 07222] Led (5) : L (latched)
Figure (4)
4. Insert the data obtained with the measurements in the following table:
L2 – L3 75
L3 – L1 50
L1 – L2 25
1. Connect the T.M.C.B. between the phase and ground, as shown in figure 5.
2. Turn ON the switch to perform a phase-ground fault, respectively at 25, 50, 75 and 100 km.
3. Measure the fault current with SIGRA program.
Figure (5)
4. Insert the data obtained with the measurements in the following table:
L1 – E 100
L2 – E 75
L3 – E 50
L1 – E 25
Part III: Configuration of SR16 as maximum ground directional current relay [67N]
Figure (6)
2. Set the Parameters of the protection device SR16/EV and power system data using DIGSI
software as follows:
(A) Setting Group A – Earth Fault Overcurrent:
(a) General :
1. Earth Fault Overcurrent function [No. 3103] = ON
(b) 3I0>>>:
1. Operating mode [No. 3110] = Forward
2. Pick up current [No. 3111: 3I0>>> Pickup] = 0.07A
3. Time delay [No. 3112: T 3I0>>Time delay] = 0 Sec (Instantaneous Intervention).
(c) Direction:
1. Polarization [No. 2611]: With U0 +IY or U2
2. ALPHA, Lower angle for forward direction [No. 3612A]= 338o
3. BETA, Upper angle for forward direction [No. 3613A]= 122o
4. Min. zero seq. voltage 3U0 for polarizing [No. 3164]= 0.5 V
Figure (7)
8. Insert the data obtained with the measurements in the following table:
L2 – E 75
L3 – E 50
L1 – E 25
1. Connect a 20 Ω resistor in series to the T.M.C.B between two phases as shown in Figure. 8.
2. Turn ON the switch to perform a phase-phase fault, respectively at 25, 50, 75 and 100 km.
3. Measure the fault current with SIGRA program.
Figure (8)
4. Insert the data obtained with the measurements in the following table:
L2 – L3 75
L1 – L3 50
L1 – L2 25
1. Connect a 20 Ω resistor in series to the T.M.C.B between the phase and ground as shown
in Figure 9.
2. Turn ON the switch to perform a phase-phase fault, respectively at 25, 50, 75 and 100 km.
3. Measure the fault current with SIGRA program.
Figure (9)
4. Insert the data obtained with the measurements in the following table:
L2 – E 75
L3 – E 50
L1 – E 25
Chapter 3
Power Factor Correction Experiments
Contents
Experiment (1) Localized PF Correction of a single and three-phase user 81-88
Objectives:
1. Carry out the localized electrical power factor correction installation of a single-phase
user with low PF.
2. Carry out the localized electrical power factor correction installation of a three-phase
user with low PF.
The power factor correction of electrical user installations concerns every kind of user even
though the reactive power is charged only in average and large supplies where there are
measurement groups counting the active and the reactive power, too. The maximum
exploitation of the used power, in contractual terms as in terms of best use of the installed
conductors, can be obtained when there is no reactive power or the required one is the
minimum possible.
The power factor correction reduces the Joule losses in the transformers and the cables before
the installation point; the losses reduction, with the same transmitted power, is the more
consistent the lower was the cos ϕ before the power factor correction. The power factor
correction increases the installation performances, so transformers and cables with the same
Joule losses can transmit more power; in fact after the power factor correction, the current in
the transformers and in the cables drops, so the active power transmitted can be increased with
the same power loss.
The power factor correction reduces the voltage drop in cables and in transformers; in case of
transformers, the dispersion reactance X is higher 3 or more times in respect to the resistor in
the windings, so the voltage drop depends much on the reactive power Q the load requires from
the network crossing the transformer.
If a triad of star or delta connected (three-phase load) capacitors with the right capacity are
connected in parallel to the terminals of the resistive-inductive load, the capacitive current Ic
they absorbs, resulting in advance quadrature in respect to the voltage Vf, will oppose the
81 | Page Electrical Power Systems Lab
Palestine Technical University-Kadoorie
Faculty of Engineering and Technology | Electrical Engineering Department
Electrical Power Systems Lab || Eng. TareQ FoQha
component in delay quadrature Ig reducing it to I1 or resetting it, with consequent drop of the
current across the line which will take the value Ir; the best situation is obtained when Ic = Ig
and so I reduces to the single component in phase If ; Figure 1.
Figure (1)
Figure (2)
It follows that to obtain a total power factor correction, the inductive reactive power Q
absorbed by the users should be removed with the same capacitive reactive power Qc; actually
it is very difficult to achieve this objective, except in particular cases of constant loads with
constant cos ϕ, most of the users have active-inductive currents and powers variable in time.
Figure (3)
82 | Page Electrical Power Systems Lab
Palestine Technical University-Kadoorie
Faculty of Engineering and Technology | Electrical Engineering Department
Electrical Power Systems Lab || Eng. TareQ FoQha
The load reactive power after power factor correction is: Qr = P tgϕr
where ϕr is the angle, chosen by the user of the power corrected current.
To calculate the capacitance to be inserted at 380-400 V, three 1-μF star connected capacitors
use a reactive power of 45-50 Var while if delta connected the power becomes 135-150 Var.
Changing the voltage, the capacitors power changes proportionally to the square voltage.
Necessary Material:
1. C-PF/EV: Power Factor Correction mod.
2. AMT-3/EV: Variable three-phase power supply mod.
3. RL- 2A/EV: Variable resistive load mod.
4. IL-2/EV: Variable inductive load mod.
5. RL-2K/EV: Inductive resistive load mod.
Experimental Procedures:
Part I: Power Factor Correction of a single phase network.
Figure (4)
2. Without using power factor correction measure the following electrical quantities then
insert the data obtained with the measurements in the following table:
R L R L V I P Q S f PF /
2 1 B - 230
2 3 A - 230
3 3 - B 230
3. Calculate the capacitor value and the reactive power generated from the capacitor to be
connected in parallel to improve the PF to 0.95, then insert the data obtained with the
measurements in the following table:
You may use the following formulas:
Measutments on the single-phase user line after PF correction with tha capacitor C
R L R L V I P Q S f PF C
2 1 B - 230
2 3 A - 230
3 3 - B 230
Figure (5)
2. Without using power factor correction measure the following electrical quantities then
insert the data obtained with the measurements in the following table:
R L R L V I P Q S f PF /
1 2 A - 390
1 1 A B 390
1 2 - B 390
3. Calculate the capacitor value and the reactive power generated from the capacitor to be
connected in parallel to improve the PF to 0.98 (Δ-connected), then insert the data
obtained with the measurements in the following table:
You may use the following formulas:
Measutments on the single-phase user line after PF correction with tha capacitor C
R L R L V I P Q S f PF C
1 2 A - 390
1 1 A B 390
1 2 - B 390
Questions:
1. What are the causes of low Power Factor.
Find:
(a) The total real and reactive power , the PF at the source and the total current.
(b) The capacitance of the capacitor connected across the loads to improve the over all
PF to 0.95 lagging.
(c) Line current supplied by the source to feed these loads after connecting the
capacitor bank.
Find:
(a) The total real and reactive power , the PF at the source and the total current.
(b) The capacitance of the capacitor connected across the loads to improve the over all
PF to 0.98 lagging (Δ-connected).
(c) Line current supplied by the source to feed these loads after connecting the
capacitor bank.
Objectives:
1. Carry out an automatic centralized power factor correction installation with 3 steps of
reactive capacitive power equal between them.
2. Carry out an automatic centralized power factor correction installation with 3 steps of
reactive capacitive power one double the other.
To supply a power as near as possible to the demanded one, the connection of the capacitors is
implemented step by step with a control accuracy which will be the greater the more steps are
foreseen and the smaller the difference is between them.
Necessary Material:
1. C-PF/EV: Power Factor Correction mod.
2. AMT-3/EV: Variable three-phase power supply mod.
3. RL- 2A/EV: Variable resistive load mod.
4. IL-2/EV: Variable inductive load mod.
5. RL-2K/EV: Inductive resistive load mod.
Experimental Procedures:
Part I-1: Manual Mode of PF correction with 3-equal capacitors (4-µF).
Figure (1)
Figure (2)
1. Turn off the system and return back to the no load condition with the same connection.
2. Restart the system and set the controller to automatic mode by Long press on the
MAN/AUT pushbutton.
3. Change the Resistive-Inductive load in steps then read the electric quantities on the
measuring instruments and write them down in the following table.
Part II-1: Manual Mode of PF correction with 3 steps of reactive capacitive power one
double the other (C1= 4-µF, C2= 8-µF, C3= 16-µF).
1. Turn off the system and return back to the no load condition with the same connection.
2. Change the settings of the Controller to:
- The programmed parameters to be changed are as follows:
P.06 STEP 1 = 1 (0.5 kvar = Once P.02)
P.06 STEP 2 = 2 (0.5 kvar = Once P.02)
P.06 STEP 3 = 4 (0.5 kvar = Once P.02)
3. Insert the various steps of the Resistive and inductive loads then make the correction of
the PF using manual mode by inserting the capacitor required parallel to the load and to
check the proper value of these capacitors that match the PF of the system equal or near
to the desired PF.
4. Read the electric quantities on the measuring instruments and write them down in the
following table.
RL load R2, L5, LAB R2, L5, LABC , LB R1, L5, LABC , LABC
C1= 4µF (on/off)
C2= 4µF (on/off)
C3= 4µF (on/off)
PFold
PFnew
Pin(total)
Q2 = Qold = Qload
Q1 = Qnew
I1
I2 = Iload
Part II-2: Automatic Mode of PF correction with 3 steps of reactive capacitive power
one double the other (C1= 4-µF, C2= 8-µF, C3= 16-µF).
1. Turn off the system and return back to the no load condition with the same connection.
2. Restart the system and set the controller to automatic mode by Long press on the
MAN/AUT pushbutton.
3. Change the Resistive-Inductive load in steps then read the electric quantities on the
measuring instruments and write them down in the following table.
RL load R2, L5, LAB R2, L5, LABC , LB R1, L5, LABC , LABC
C1= 4µF (on/off)
C2= 4µF (on/off)
C3= 4µF (on/off)
PFold
PFnew
Pin(total)
Q2 = Qold = Qload
Q1 = Qnew
I1
I2 = Iload
Questions:
1. Calculate the required value of capacitance for each load and compare it with the values
selected by controller (Part I-1)
2. Calculate the required value of capacitance for each load and compare it with the values
selected by controller (Part I-2)
3. Compare between the results of manual mode with the results of the automatic mode
(Part I).
4. Calculate the required value of capacitance for each load and compare it with the values
selected by controller (Part II-1)
5. Calculate the required value of capacitance for each load and compare it with the values
selected by controller (Part II-2)
6. Compare between the results of manual mode with the results of the automatic mode
(Part II).
Objectives:
1. Carry out the connections and the sequence of operations to enable the synchronous
compensator.
2. Carry out the using of synchronous compensator to correct the power factor of a system.
The synchronous motor receives excitation in the rotor from an external dc adjustable source.
The excitation voltage determines the kind of power the motor absorbs from the network:
Reactive inductive power in under-excitation conditions;
Reactive capacitive power in over-excitation conditions.
On the right of these values, the motor operates in overexcitation condition (synchronous phase
advancer), showing a Capacitive load to the mains. On the left of these values, the motor
operates in under-excitation conditions, showing an inductive load to the mains.
Necessary Material:
1. PCB-3/EV: Generator parallel board mod.
2. GCB-3/EV: Control board for the generating set mod.
3. MSG-3/EV: Synchronous generator-motor unit mod.
4. AMT-3/EV: Variable three-phase power supply mod.
5. RL-2/EV: Variable resistive load mod.
6. IL-2/EV: Variable inductive load mod.
Experimental Procedures:
Part I: Enabling the Synchronous Machine used as Synchronous Compensator.
6. Adjust the excitation current to get a PF equal to unity then measure the values of
active and reactive power of the main supply and synchrnous motor.
7. Insert the inductive load (L= switch B), change the value of excitation current of the
synchronous motor in steps to get the PF of the system equal to 0.96 Lagging.
8. Read the electric quantities on the instruments and write them down in the following
tables.
Figure (2)
Measutments / (Load)
Questions:
1. What is a synchronous capacitor? Why would one be used?
2. Explain what happen to the system PF and synchronous motor as its field current is
varied?
3. Compare between using capacitor bank and using synchronous compensator for power
factor correction.
Chapter 4
Overall Power System Experiments
Contents
Experiment (1) Simulator of Production, Transmission and Use of Electric Power 100-104
Objectives:
1. Describing the different sections of a complete System of production, distribution and
use of electric energy, and their operation.
2. Enabling an easy and intuitive learning by an interaction with the same System via
control and display devices available in both Panel and Software.
As consumption is not constant during a day, when there is a high energy demand, the power
distribution agency must set some power plants at work to produce the power demanded and
avoid catastrophic black-outs.
The plants enabling to satisfy the energy peaks during the day are generally of medium power
and are arranged in the territory near the users with considerable consumptions, when possible;
they must reach their full operation in short times (some tens of minutes).
The great thermoelectric or nuclear power plants are distributed and connected in parallel on
the territory, so that they can meet the normal demand of electric power, whereas peak
demands can be satisfied (where possible) by medium power plants of thermoelectric,
hydroelectric type or using renewable energies (wind power, solar energy, etc…), managed by
personnel, or wholly automated.
Great power plants satisfy the normal daily demand; during the peaks of demand they are
‘helped’ or ‘relieved’ by the plants of medium power. During the night, consumptions of
production activities are reduced, and power availability is used in hydroelectric plants to pump
water back into the upper basin (even water is not available forever), as reserve for future
needs.
Necessary Material:
1. SEE-1/EV: Simulator of the cycle of Electric Energy mod as shown in Figure 1.
2. PC with SEE01 software installed.
Figure (1)
Experimental Procedures:
Part I: National Electrical Power Net
This part concerns the automatic control of the distribution of electric power according to the
daily demand of users.
1. Switch ON the computer.
2. Switch ON the simulator main switch.
3. Connect with USB cable the Simulator to PC.
4. Follow these commands:
- Start → Programs → Simulator SEE → SEE
Figure 2 shows how this automatic control goes on in 24 hours (Daily load curve).
Figure (2)
This program enables to use all the controls of digital instruments and the potentiometers P and
Q of the simulator so that the various electric quantities can be displayed and the values of
active power (W) and of reactive power (Var) can be set.
Question: Describe the effect of resistance and inductance on losses, voltage drop along lines
and power output by the generators, and discuss the way that used to decrease the inductive
effect.
………………………………………………………………………………………………..……
………………………………………………………………………………………………..……
………………………………………………………………………………………………..……
………………………………………………………………………………………………..……
………………………………………………………………………………………………..……
………………………………………………………………………………………………..……
………………………………………………………………………………………………..……
Objectives:
1. To study the behavior and the operation of a power system with SCADA system.
2. Using the instrument to measure the electrical quantities like voltage, current, active
power, reactive power, apparent power, power factor and frequency.
3. Showing and implementing a connection in wireless network for the supervision of the
data coming from 2 multifunction instruments by PC.
4. Use of the supervision and energy management software for the monitoring and
management of electrical parameters and energy consumptions of an electrical
installation.
Necessary Material:
1. SEL-1/EV: Simulator of electric lines mod.
2. PRMCE-1/EV: Panel of Supervision Networks of Electrical Parameters.
3. P14A/EV: Three-phase transformer mod.
4. AMT-3/EV: Variable three-phase power supply mod.
5. RL-2/EV: Variable resistive load mod.
6. IL-2/EV: Variable inductive load mod.
7. Contactor with On-Off control
Experimental Procedures:
1. Consider and set the LINE 2 with the following constants: R= 18Ω; L= 72mH;
CES= 0.1 and CER= 0.1μF; Length= 50km.
2. Connect with the variable three-phase power supply by inserting the three-phase
insulation transformer.
3. Connect the capacitors at the sending end point of the LINE 2 in Δ-connection.
4. Connect the capacitors at the receiving end point of the LINE 2 in Y-connection.
5. Connect the instruments with the Switch/Access Point via 2 cables (of the equipment)
with RJ45 connectors as shown in Figure 1.
6. Connect the circuit as shown in Figure 2.
Figure (1)
Figure (2)
7. Set the parameters of the first instrument (Left) as follows using DMK remote control
software:
- LIM 1:
Max voltage = 400; Delay = 5 sec;
Min Voltage = 250; Delay = 5 sec.
- LIM 2, 3 and 4 (Line current 1, 2 and 3):
Max current = 0.7A; Delay = 5 sec;
Min current = 0.7A; Delay = 5 sec.
- Configure Boolean function to Combines the 4 Limits (OR operator).
- Set the Output OUT1 used to energize the relay (ALARM 1) (This relay will
depend on BOO1 which includes the OR operator of the LIM1 and LIM2, 3 and 4).
8. Set the parameters of the Second instrument (Centre) as follows using DMK remote
control software:
- LIM 1:
Max voltage = 400; Delay = 2 sec;
Min Voltage = 250; Delay = 2 sec.
- LIM 2, 3 and 4 (Line current 1, 2 and 3):
Max current = 0.7A; Delay = 2 sec;
Min current = 0.7A; Delay = 2 sec.
- Configure Boolean function to Combines the 4 Limits (OR operator).
- Set the Output OUT1 used to energize the relay (ALARM 1) (This relay will
depend on BOO1 which includes the OR operator of the LIM1 and LIM2, 3 and 4).
9. Enable and adjust the voltage of the power supply at 350 V.
10. Turn the breaker at the origin and at the end of the Line 2 to ON in sequence.
11. Set the transmission line under load with the insertion of resistive-inductive load.
12. Read the electric quantities on the measuring instruments and write them down in the
following table.
A A 350
A B 350
13. Change the load to (R= A, L= A || B), Explain the operation of the system?
14. Change the settings of the limits and describe the operation of the system.