BEV20703 Power System Analysis

The document discusses balanced three-phase fault analysis in power systems. It introduces balanced three-phase faults and their importance for protective relay setting and selecting equipment ratings. The chapter then describes calculating fault currents, voltages, and line currents during a balanced three-phase fault using the bus impedance matrix method. It also covers determining the short-circuit capacity of buses for dimensioning bus bars and circuit breaker ratings.

Uploaded by

Ahmad Blaze
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views13 pages

BEV20703 Power System Analysis

The document discusses balanced three-phase fault analysis in power systems. It introduces balanced three-phase faults and their importance for protective relay setting and selecting equipment ratings. The chapter then describes calculating fault currents, voltages, and line currents during a balanced three-phase fault using the bus impedance matrix method. It also covers determining the short-circuit capacity of buses for dimensioning bus bars and circuit breaker ratings.

Uploaded by

Ahmad Blaze
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

BEV20703

POWER SYSTEM ANALYSIS


BALANCED FAULT ANALYSIS
CHAPTER 5
Contents
5.1 Introduction
5.2 Balanced three-phase fault
5.3 Short-circuit capacity
5.1 Introduction
• Important part of power system analysis.
• Determining of bus voltages and line currents during various
types of faults.
• The fault types are segregated as follows:
❑ Balanced three-phase fault.
❑ Unbalanced faults:
• Single line to ground fault,
• Line-to-line fault,
• Double line to ground fault.
5.1 Introduction
• It is used for proper relay setting and coordination.
• The three-phase balanced fault information is used to select
and set phase relays.
• The line-to-ground fault is used for ground relays.
• It is also used to obtain the rating of the protective
switchgears.
• The magnitude of the fault currents depends on:
❑ The internal impedance of the generators,
❑ The impedance of the intervening circuit.
5.1 Introduction
• The generator behavior can be divided into three periods:
❑ The sub-transient period
• Represented by sub-transient reactances 𝑋′′𝑑 .
• Lasting only for the first few cycles.
❑ The transient period
• Represented by transient reactances 𝑋′𝑑 .
• Covering a relatively longer time.
❑ The steady state period
• Represented by synchronous reactance 𝑋𝑑 .
• For steady state condition.
5.2 Balanced Three-phase Fault
• The duration of the short circuit current depends on the time of
operation of the protective system.
• Generally, the subtransient reactance is used for determining
the interrupting capacity of the circuit breakers.
• For relay setting and coordination, fault studies required
transient reactance.
• Also, transient reactance is used in transient stability.
5.2 Balanced Three-phase Fault
Example 5.1
The one-line diagram of a simple three-bus power system is
shown in Figure 1. Each generator is represented by an emf
behind the transient reactance. All impedances are expressed in
per unit on a common 100 MVA base, and for simplicity,
resistances are neglected. The following assumptions are made.
i. Shunt capacitances are neglected and the system is
considered on no-load.
ii. All generators are running at their rated voltage and rated
frequency with their emfs in phase.
5.2 Balanced Three-phase Fault
Example 5.1 Determine the fault current, the
bus voltages, and the line
currents during the fault when a
balanced three-phase fault with a
fault impedance 𝑍𝑓 = 𝑗0.16 per
unit occurs on:
a) Bus 3 [-j2.0 pu, -j0.1 pu, -j1.1 pu, -
j0.9 pu],
b) Bus 2 [-j2.5 pu, -j0.5 pu, -j0.5 pu, -
j0.5 pu],
c) Bus 1 [j3.125 pu, j3.125 pu, -j3.125
pu, -j3.125 pu].
Figure 1
5.2 Balanced Three-phase Fault
Tutorial 5.1
A three-phase fault with a fault impedance 𝑍𝑓 = 0.16 per unit
occurs at bus 3 in the network of Example 5.1. Using the bus
impedance matrix method, compute the fault current, the bus
voltages, and the line currents during the fault.
5.2 Balanced Three-phase Fault
• The load currents were neglected and all prefault bus voltages
were assumed to be equal to 1.0 per unit.
• For more accurate calculation, the prefault bus voltages can
be obtained from the power flow solution.
• In a power system, loads are specified and the currents are
unknown.
• Express the loads by a constant impedance evaluated at the
prefault bus voltages.
• This is a very good approximation which results in linear nodal
equations.
5.3 Short-circuit Capacity
• It is a common measure of the strength of a bus.
• Definition: The product of the magnitudes of the rated bus
voltage and the fault current.
• It is used to determine the dimension of a bus bar, and the
interrupting capacity of a circuit breaker.
• The short -circuit capacity at bus k is given by:

• The line-to-line voltage 𝑉𝐿𝑘 is expressed in kilovolts and 𝐼𝑘 (𝐹)


is expressed in amperes .
5.3 Short-circuit Capacity
• The symmetrical three-phase fault current in per unit is given
by:

• 𝑉𝑘 (0) is the per unit prefault bus voltage, and 𝑋𝑘𝑘 is the per
unit reactance to the point of fault.
• System resistance is neglected.
• The base current is given by:
5.3 Short-circuit Capacity
• 𝑆𝐵 is the base MVA and 𝑉𝐵 is the line-to-line base voltage in
kilovolts.
• The fault current in amperes is:

• Therefore, SCC is rewritten as follows: